Converting amperage between single phase (120, 240 and 480 Voltage) and
three phase (240 and 480 Voltage)
With single-phase AC power there is only one single sinusoidal voltage. Most AC power today is produced and distributed as three-phase power where
three sinusoidal voltages are generated out of phase with each other.
Sometimes it is necessary to turn between power (VA), voltage (V) and amperage (A). The diagram and table below can be used to convert amperage
between single phase and three phase equipment and vice versa.
Amperage (A)
Power
(VA)
Volts 3 Phase
Balanced Load
240
480
240
480
100
150
200
250
300
0.83
1.25
1.67
2.08
2.50
0.42
0.63
0.83
1.04
1.25
0.21
0.31
0.42
0.52
0.63
0.24
0.36
0.49
0.61
0.73
0.13
0.18
0.25
0.30
0.37
350
400
450
500
600
2.92
3.33
3.75
4.17
5.00
1.46
1.67
1.88
2.08
2.50
0.73
0.84
0.93
1.04
1.25
0.85
0.97
1.10
1.20
1.45
0.43
0.49
0.55
0.60
0.73
700
750
800
900
1,000
5.83
6.25
6.67
7.50
8.33
2.92
3.13
3.33
3.75
4.17
1.46
1.56
1.67
1.87
2.10
1.70
1.81
1.93
2.17
2.41
0.85
0.91
0.97
1.09
1.21
1,100
1,200
1,250
1,300
1,400
9.17
10.0
10.4
10.8
11.7
4.58
5.00
5.21
5.42
5.83
2.30
2.51
2.61
2.71
2.91
2.65
2.90
3.10
3.13
3.38
1.33
1.45
1.55
1.57
1.69
1,500
1,600
1,700
1,750
1,800
12.5
13.3
14.2
14.6
15.0
6.25
6.67
7.08
7.29
7.50
3.12
3.34
3.54
3.65
3.75
3.62
3.86
4.10
4.22
4.34
1.82
1.93
2.05
2.10
2.17
1,900
2,000
2,200
2,500
2,750
15.8
16.7
18.3
20.8
23.0
7.92
8.33
9.17
10.4
11.5
3.96
4.17
4.59
5.21
5.73
4.58
4.82
5.30
6.10
6.63
2.29
2.41
2.65
3.05
3.32
3,000
3,500
4,000
4,500
5,000
25.0
29.2
33.3
37.5
41.7
12.5
14.6
16.7
18.8
20.8
6.25
7.30
8.33
9.38
10.42
7.23
8.45
9.64
10.84
12.1
3.62
4.23
4.82
5.42
6.1
6,000
7,000
8,000
9,000
10,000
50.0
58.3
66.7
75.0
83.3
25.0
29.2
33.3
37.5
41.7
12.50
14.59
16.67
18.75
20.85
14.50
16.9
19.3
21.7
24.1
7.25
8.5
9.65
10.85
12.1