OPERATION MANUAL FOR 11kV

REMOTE CONTROL PANEL


Hospital Teluk Intan
Teluk Intan, Perak.

Supplied by:
WARNA RS SDN. BHD.
No. 5 Bangunan Perniagaan
Taman Desa Meranti Indah
Padang Temusu
08000 Sungai Petani, Kedah
Tel: 019-4473264, 012-4823264
Fax: 04-4319640
warnarssb@gmail.com

OPERATIO
ONMANUAL:11kVREMO
OTECONTROLLPANEL,HOSSPITALTELUK
KINTAN

Op
peratio
onMan
nualforr
11kVRemotteConttrolPa
anel

Revision:1.0

W
WARNA
RSSDN..BHD.
No.5BanggunanPerniaagaan,
Taman
nDesaMerantiIndah,PaadangTemussu,
08000Sun
ngaiPetani,K
Kedah.
+60443
319640,+60194473264
4,+6012482
23264
warnarrssb@gmail.ccom

Page2of12
Rev.01.2

WaarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

CONTENTS:
1. Introduction

2. Features

3. RemoteControlPanelSwitches&Indicators

4. LcdDisplayDetails

5. CircuitBreakerOperation

6. SiteTestResults

7. Gallery

10

Page3of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

INTRODUCTION

Operationofhighvoltageswitchgearsposeshighsafetyrisktotheoperator.Incidents
involvinghighvoltageswitchgearduringoperationandarcflashproducedduringfault
always end with serious injuries and fatalities. Operation of high voltage switchgear
remotelyisoneofthebestoptionsinordertoensuresafetyoftheoperators.

ARemoteControlPanelallowsausertooperate(open&close)circuitbreakerswithout
being in front of the switchgear. Installed at a distance away from the switchgear, it
helpstoimprovepersonnelsafetybyputtingoperatorsoutsidethearcflashboundary.

FEATURES

o Lockablewhetherprooftypepanelsuitableforoutdoorinstallation.
o EquippedwithLCDdisplay240x128pixelshowingsitesinglelinediagramwith
circuitbreakersandRemoteSwitchStatus.
o RedandGreenIndicationLightsforeverycircuitbreaker.
o CBcontrolbyathreepositionspringreturncamswitchforeverycircuitbreaker.
o ARemoteSwitchwithlockingfacility

Page4of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

REMOTECONTROLPANELSWITCHES&INDICATORS

LCDDisplay

RemoteSwitch

CBIndicatorLights

CBControlSwitch

a) LCDDisplay
Atalltime,thedisplaywillshowsubstationsinglelinediagramwithrealtimecircuit
breakerstatus(open/closed)andRemoteSwitchposition.Thesinglelinediagram
reflectsactualpanelarrangement.Abacklightisprovidedandwillbeturnedonwhen
RemoteSwitchisatONposition.

Page5of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

b) RemoteSwitch
PutRemoteSwitchtoONpositiontoenableremoteoperationofcircuitbreakers.
OperationofcircuitbreakersatRemoteControlPanelisdisablediftheRemoteSwitchis
puttoOFF.Lockingfacilityisalsoprovidedtoavoidunauthorizedoperation.
c) CBIndicatorLights.
EachCircuitBreakersrealtimestatus(ON,OFF)canbeseenfromtheredandgreen
indicationlights.

d) CBControlSwitch
Eachcircuitbreakeroperationcanbecontrolledbythisswitch.Turnanticlockwiseto
openandclockwisetoclosecircuitbreaker.OperationisonlysuccessfuliftheRemote
SwitchisatONposition.

Page6of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIO
ONMANUAL:11kVREMO
OTECONTROLLPANEL,HOSSPITALTELUK
KINTAN

LC
CDDISPLAY

CBStatussforTNB

Incom
ming

InstallationLoccation

RemoteSSwitchStatuss

CBStatussforS/S1
CBStatusforS
C
S/S2

a)CBStatuss
i.Circuitb
breakerwith
hOpenstattus. ii.Circuit breakerwith
hClosedsttatus.

us
b) RemoteSSwitchStatu
i.Remote
eSwitchOFFF ii.RemoteeSwitchON

Page7of12
Rev.01.2

WaarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

CBOPERATION

a) Close
i.
Ensurecircuitbreakerhasbeenrackinandlockedatconnectedposition.
ii.

InsertkeyandputRemoteSwitchtoON.

iii.

SelectdesignatedCBControlSwitch.Turnclockwiseandreleasebackto
neutral(o).Circuitbreakerwillbeclosedremotely.

iv.

CheckandconfirmcorrectcircuitbreakerstatusfromLCDdisplayandCB
IndicationLightsatRemoteControlPanel.

v.

PutRemoteSwitchtoOFFandremovekey.

b) Open
i.

CheckandconfirmcorrectcircuitbreakerstatusfromLCDdisplayandCB
IndicationLightsatRemoteControlPanel.

ii.

InsertkeyandputRemoteSwitchtoON.

iii.

SelectdesignatedCBControlSwitch.Turnanticlockwiseandreleasebackto
neutral(o).Circuitbreakerwillbeopenremotely.

iv.

CheckandconfirmcorrectcircuitbreakerstatusfromLCDdisplayandCB
IndicationLightsatRemoteControlPanel.

v.

PutRemoteSwitchtoOFFandremovekey.

vi.

Ensureproperandsafeisolationmethodisfollowedaccordingtolocal
regulations.NonstandardlockmaybeappliedtodesignatedCBControl
SwitchtoprohibitunauthorizedoperationofcircuitbreakerfromRemote
ControlPanel.

Page8of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

SITETESTRESULTS

REMOTECONTROLPANELTESTRESULTS

ReferenceNo:
WRS/RCP/14001
Contractor:
WarnaRSSdn.Bhd.
Consumer:
HospitalTelukIntan,Perak.
Site:
11kVSubstation

a) LCDDISPLAY
Correctsinglelinediagramandpanelarrangementaccordingtositeinstallation:PASS

b) STATUSINPUTCHECK
ConfirmcorrectLCDandIndicationlightsaccordingtoactualCBstatus.
No

Panel

ActualCB
LCD
IndicationLight
Status
Status
1 TNBIncoming
Open
OFF
Green
2 TNBIncoming
Closed
ON
Red
3 S/S2
Open
OFF
Green
4 S/S2
Closed
ON
Red
5 S/S1
Open
OFF
Green
6 S/S1
Closed
ON
Red
Remarks:RemoteControlPanelshowscorrectCBstatusforallpanels.

Pass/Fail
Pass
Pass
Pass
Pass
Pass
Pass

c) REMOTECONTROLCHECK
EnsureRemoteSwitchisON.OperateCBfromRemoteControlPanelforeachpanel.
No

Panel

Remote Pass/Fail
Remarks
Operation
1 TNBIncoming
Open
Pass
CBopensuccessfullyfromRCP
2 TNBIncoming
Close
Pass
CBclosedsuccessfullyfromRCP
3 S/S2
Open
Pass
CBopensuccessfullyfromRCP
4 S/S2
Close
Pass
CBclosedsuccessfullyfromRCP
5 S/S1
Open
Pass
CBopensuccessfullyfromRCP
6 S/S1
Close
Pass
CBclosedsuccessfullyfromRCP
Remarks:SuccessfuloperationofCBfromRemoteControlPanelforallpanels.
Testedby:HjAhmadRadziyanBan
Date :25/1/2014

Page9of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

GALLERY

OutdoortypeRemoteControlPanel.

RemoteControlPanelinstalledoutsideswitchroom.

RemoteControlPanelinstalledoutsideswitchroom.

LCDDisplay,IndicationLights&CBControlSwitches.

Page10of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

LCDshowsswitchgearsinglelinediagramandCBsstatus.

IndicationLightsandCBControlSwitchesforeverypanel.

Page11of12
Rev.01.2

WarnaRSSdn.Bhd.

OPERATIONMANUAL:11kVREMOTECONTROLPANEL,HOSPITALTELUKINTAN

NOTES

__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________

Page12of12