where
L = air volume (m3/s)
Q = heat loss from the building (kW)
cp = specific heat capacity air - 1.005 (kJ/kgoC)
= density of air - 1.2 (kg/m3)
th = heating air temperature (oC)
tr = room temperature (oC)
As a rule of thumb the heating supply temperature should be in the range 40-50oC. The air flow
should be in the range 1-3 times the room volume.
Equation (1) expressed in imperial units:
L = Q / (1.08 (th - tr))
where
Q = heat (btu/hr)
(2)