Вы находитесь на странице: 1из 46

VOLTAGE DROP & POWER CABLE SIZING CALCULATION

ION EXCHANGE ( INDIA) LIMITED


PROJECT : NTECL POWER PROJECT

CLIENT

NTPC , VALLURE

NTPC DOC. NO. : 0260-189-00-PVE-W-013


PLANT

: DESALINAION PLANT

TITLE

Revised as
response to Tr
No - 13514

23.8.10

Revised as
08.04.10 response to Tr
No - 9453

Revised as per
NTPC
23.11.09 comments &
as per revised
load

02.06.09

SJ

DATE

RY

PR./
MECH

SR. NO.

: Voltage Drop & Power Cable Sizing Calculation

AMENDMENT

ELEC/
INST

CIVIL

PREPARED BY

PR./
MECH

ELEC/
INST

REV

CIVIL

CHECKED BY

APPD. BY

IEI DOC. NO. : A4-10053 -12-09-VI

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

VOLTAGE DROP & POWER CABLE SIZING CALCULATION


FOR
DESALINATION PLANT PACKAGE
OF
3X500 MW NTPC VALLURE THERMAL POWER PROJECT

TABLE OF CONTENTS
CLAUSE

DESCRIPTION

PAGE NO.

1.00.00

PREAMBLE

2.00.00

BASIS DESIGN DATA

3.00.00

SIZING CALCULATION

4.00.00

REFERENCE DOCUMENTS

ATTACHMENTS :
1.0 ANNEXURE - I

CABLE SIZING CALCULATION FOR MOTOR OPERATED VALVE (MOV)

2.0 ANNEXURE - II

CABLE SIZING CALCULATION FOR LT DRIVE & OTHERS LOAD

3.0 ANNEXURE - III

CABLE DATA AS PER POLYCAB CABLE CATALOGUE

4.0 ANNEXURE - IV

LT MOTOR EFFICIENCY LIST (AS PER IS12615)

5.0 ANNEXURE - V

SIZE & DESCRIPTION OF MOTOR SPACE HEATER CABLE &


220V DC CABLE.

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 2 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

1.00.00

PREAMBLE
This document presents the sizing calculations of LT power cable based on Voltage drop , Ampacity
& Short circuit current withstand capacity (for ACB operated feeder only) for the area of Desalination
plant package under the scope of Ion Exchange (India) Ltd. under an EPC package of Desalination
plant for 3X500 MW Thermal Power Project of NTPC-Tamilnadu Energy Company Ltd. (NTECL).

2.00.00

BASIS DESIGN DATA

2.01.00

Design Ambient Air Temperature

2.02.00

Type of Cables & Limiting Temperature:

2.02.01

1100 V Power Cables

50C

[Ref. - 1 ]

XLPE insulated, PVC Inner sheathed,


armoured and FRLS PVC outer sheathed.

2.02.02

Limiting /Permissible (maximum


conductor temperature under rated
current carrying capacity conditions)

90C

(for XLPE)

[Ref. - 1 ]

2.02.03

Limiting /Permissible (maximum


conductor temperature under short
circuit conditions)

250C

(for XLPE)

[Ref. - 1 ]

2.02.04

Conductor Material
Copper conductor up to

2.5 mm2

Alluminium conductor

4 mm2 & above

2.03.00

Allowable Voltage Drop of cable

2.03.01

during normal running condition

3%

2.03.02

during the starting condition

10 %

2.04.00

Motor starting current:

2.05.00

Cable lengths are assumed based on Equipment layout for Desalination

720

% of full load current


[Ref. - 5 ]

Plant Pacakge drawing.


2.06.00

For the current ratings of the cables and applicable derating factors are taken from the
technical data's catalogues of POLYCAB.

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 3 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

2.07.00

Selection of Derating factor


For cable trays laid in air
a) Deating factor for variation in ambient air temperature at 50C (Fa )

0.88

0.68

b) Deating factor for cable spacing:


9 cables, touching in 1 tray and arranged in 3 racks (Fs)
Therefore, overall derating factor

d1

= 0.88 x 0.68
=

3.00.00

SIZING CALCULATION

3.01.00

Based on Voltage drop & Ampacity


For motor operated valve feeders
For LT motor & other feeders

3.02.00

:
:

0.598

Refer Annexure-I
Refer Annexure-II

Based on Short Circuit withstand capacity (for ACB operated feeders only)
The minimum cross section of the cable from short circuit considerations, is given by the formula,
S

Ish t
k

where,

Conductor cross section in mm2

Fault clearance time in secs

A constant depending upon


i) Material of conductor, insulation and other parts.
ii) Initial and final temparature.

The value of K for


For XLPE insulated aluminium conductor

94

Ish1

45.0

kA

Value of 't' is based on the fault clearance time (Breaker tripping time + relay operation time + tolerance).
However, due to numerical relays being used in the system and the fast acting breakers, the fault
withstand time has been taken for ACB feeders as:
t
Minimum conductor size required ( S )

0.12

secs.

= 45000 X 0.12

mm2

94
S
Minimum selected size

which corresponds to

50.3

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

185
kA for

165.835

mm2

mm2
0.12

secs
Cable sizing
Page 4 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

4.00.00

REFERENCE DOCUMENTS
1

Technical Requirements - LT Power Cables


[ Doc. no- PART-B, SUB-SECTION-III B-04 ]

Technical Requirements - Motors.


[ Doc. no- PART-B, SUB-SECTION-III B-01 ]

Technical Requirements - LT Switchgear & Busduct.


[ Doc. no- PART-B, SUB-SECTION-III B-06 ]

Cable parameters and derating factors are from Manufacturer's (POLYCAB) catalogue.

EQUIPMENT LAYOUT FOR DESALINATION PLANT PACKAGE


[ NTPC Dwg. No. : 0260-189-00-PVM-F-001, Rev.-1 ]

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 5 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 6 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 7 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 8 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 9 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 10 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Cable sizing
Page 11 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

ANNEXURE-I
CABLE SIZING CALCULATION FOR MOTOR OPERATED VALVE (MOV)

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

IN-V01

SEA WATER INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

184

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.92

P1A-V02

MOV AT THE DISCHARGE OF P1-A

0.75

kW

415

82.5

0.85

1.49

2.49

163

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.82

P1B-V02

MOV AT THE DISCHARGE OF P1-B

0.75

kW

415

82.5

0.85

1.49

2.49

163

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.82

P1C-V02

MOV AT THE DISCHARGE OF P1-C

0.75

kW

415

82.5

0.85

1.49

2.49

163

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.82

P1D-V02

MOV AT THE DISCHARGE OF P1-D

0.75

kW

415

82.5

0.85

1.49

2.49

163

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.82

SC-V06

MOV AT THE DISCHARGE OF PE


DOSING PUMP NEAR PARSHALL
FLUME

0.75

kW

415

82.5

0.85

1.49

2.49

95

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.48

SC-V07

MOV AT THE DISCHARGE OF FeCL3


DOSING PUMP NEAR PARSHALL
FLUME

0.75

kW

415

82.5

0.85

1.49

2.49

95

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.48

SC-V01

STILLING CHAMBER INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

131

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.66

SC-V04

BI-PASS VALVE FOR SC-V01

0.75

kW

415

82.5

0.85

1.49

2.49

131

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.66

10

SC-V05

CHLORINATION INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

131

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.66

11

CWST-V01

FILTER FEED PUMP


RECIRCULATION VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

126

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.63

12

P3A-V02

MOV AT THE DISCHARGE OF P3-A

0.75

kW

415

82.5

0.85

1.49

2.49

158

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.79

13

P3B-V02

MOV AT THE DISCHARGE OF P3-B

0.75

kW

415

82.5

0.85

1.49

2.49

158

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.79

14

P3C-V02

MOV AT THE DISCHARGE OF P3-C

0.75

kW

415

82.5

0.85

1.49

2.49

158

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.79

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 12 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

P3D-V02

MOV AT THE DISCHARGE OF P3-D

0.75

kW

415

82.5

0.85

1.49

2.49

158

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.79

16

P2A-V02

MOV AT THE DISCHARGE OF P2-A

0.75

kW

415

82.5

0.85

1.49

2.49

163

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.82

17

P2B-V02

MOV AT THE DISCHARGE OF P2-B

0.75

kW

415

82.5

0.85

1.49

2.49

163

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.82

18

B1A-V01

MOV AT THE DISCHARGE OF HDMF


BLOWER B1-A

0.75

kW

415

82.5

0.85

1.49

2.49

123

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.62

19

B1B-V01

MOV AT THE DISCHARGE OF HDMF


BLOWER B1-B

0.75

kW

415

82.5

0.85

1.49

2.49

123

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.62

20

CF1A-V01

MOV AT CF1-A INLET

0.75

kW

415

82.5

0.85

1.49

2.49

86

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.43

21

CF1A-V02

MOV AT CF1-A OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

86

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.43

22

CF1B-V01

MOV AT CF1-B INLET

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

23

CF1B-V02

MOV AT CF1-B OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

24

CF1C-V01

MOV AT CF1-C INLET

0.75

kW

415

82.5

0.85

1.49

2.49

92

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.46

25

CF1C-V02

MOV AT CF1-C OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

92

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.46

26

CF1D-V01

MOV AT CF1-D INLET

0.75

kW

415

82.5

0.85

1.49

2.49

94

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.47

27

CF1D-V02

MOV AT CF1-D OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

94

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.47

28

CF1E-V01

MOV AT CF1-E INLET

0.75

kW

415

82.5

0.85

1.49

2.49

97

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.49

29

CF1E-V02

MOV AT CF1-E OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

97

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.49

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

15

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 13 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

CF1F-V01

MOV AT CF1-F INLET

0.75

kW

415

82.5

0.85

1.49

2.49

100

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.50

31

CF1F-V02

MOV AT CF1-F OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

100

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.50

32

CF1G-V01

MOV AT CF1-G INLET

0.75

kW

415

82.5

0.85

1.49

2.49

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.51

33

CF1G-V02

MOV AT CF1-G OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.51

34

CF1H-V01

MOV AT CF1-H INLET

0.75

kW

415

82.5

0.85

1.49

2.49

104

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.52

35

CF1H-V02

MOV AT CF1-H OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

104

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.52

36

CF1I-V01

MOV AT CF1-I INLET

0.75

kW

415

82.5

0.85

1.49

2.49

107

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.54

37

CF1I-V02

MOV AT CF1-I OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

107

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.54

38

V411

DUMP VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.55

39

P5A-V01

MOV AT SUCTION OF HP PUMP

1.1

kW

415

83.8

0.85

2.15

3.59

87

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.63

40

RO-IA-V01

MOV FOR PRESSURE RELIEF AT


INLET OF RO-1A

0.75

kW

415

82.5

0.85

1.49

2.49

93

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.47

41

RO-IA-V02

MOV FOR PRESSURE RELIEF AT


REJECT OF RO-1A

0.75

kW

415

82.5

0.85

1.49

2.49

98

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.49

42

P5B-V01

MOV AT SUCTION OF HP PUMP

1.1

kW

415

83.8

0.85

2.15

3.59

96

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.69

43

RO-IB-V01

MOV FOR PRESSURE RELIEF AT


INLET OF RO-1B

0.75

kW

415

82.5

0.85

1.49

2.49

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.51

44

RO-IB-V02

MOV FOR PRESSURE RELIEF AT


REJECT OF RO-1B

0.75

kW

415

82.5

0.85

1.49

2.49

106

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

30

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 14 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

P5C-V01

MOV AT SUCTION OF HP PUMP

1.1

kW

415

83.8

0.85

2.15

3.59

104

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.75

46

RO-IC-V01

MOV FOR PRESSURE RELIEF AT


INLET OF RO-1C

0.75

kW

415

82.5

0.85

1.49

2.49

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.55

47

RO-IC-V02

MOV FOR PRESSURE RELIEF AT


REJECT OF RO-1C

0.75

kW

415

82.5

0.85

1.49

2.49

114

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.57

48

P7-V04

MOV AT SUCTION OF P7-A/B

0.75

kW

415

82.5

0.85

1.49

2.49

116

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.58

49

P8A-V02

MOV AT THE DISCHARGE OF P8-A

0.75

kW

415

82.5

0.85

1.49

2.49

115

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.58

50

P8B-V02

MOV AT THE DISCHARGE OF P8-B

0.75

kW

415

82.5

0.85

1.49

2.49

115

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.58

51

P8-V04

P8-A/B RECIRCULATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

115

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.58

52

P9A-V02

MOV AT THE DISCHARGE OF P9-A

0.75

kW

415

82.5

0.85

1.49

2.49

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

53

P9B-V02

MOV AT THE DISCHARGE OF P9-B

0.75

kW

415

82.5

0.85

1.49

2.49

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

54

P9C-V02

MOV AT THE DISCHARGE OF P9-C

0.75

kW

415

82.5

0.85

1.49

2.49

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

55

P9-V04

P9-A/B/C RECIRCULATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

56

P9-V07

MOV FOR P9-A/B/C HEADER TO


CHLORINE BOOSTER PUMP

0.75

kW

415

82.5

0.85

1.49

2.49

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

57

P10A-V02

MOV AT THE DISCHARGE OF P10-A

0.75

kW

415

82.5

0.85

1.49

2.49

112

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.56

58

P10B-V02

MOV AT THE DISCHARGE OF P10-B

0.75

kW

415

82.5

0.85

1.49

2.49

112

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.56

59

P10-V04

P10-A/B RECIRCULATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

112

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.56

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

45

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 15 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

P10-V07

ISOLATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

112

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.56

61

P11A-V02

MOV AT THE DISCHARGE OF P11-A

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

62

P11B-V02

MOV AT THE DISCHARGE OF P11-B

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

63

P11C-V02

MOV AT THE DISCHARGE OF P11-C

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

64

P11-V04

P11-A/B/C RECIRCULATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

65

P11-V08

MOV FOR ALKALI DOSING HEADER

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

66

P11-V07

MOV FOR DOSING TANK HEADER

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

67

P11-V06

MOV FOR OVERHEAD TANK


HEADER

0.75

kW

415

82.5

0.85

1.49

2.49

90

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.45

68

CF3A-V01

MOV AT CF3-A INLET

0.75

kW

415

82.5

0.85

1.49

2.49

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.36

69

CF3A-V02

MOV AT CF3-A OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.36

70

CF3B-V01

MOV AT CF3-B INLET

0.75

kW

415

82.5

0.85

1.49

2.49

76

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.38

71

CF3B-V02

MOV AT CF3-B OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

76

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.38

72

CF3C-V01

MOV AT CF3-C INLET

0.75

kW

415

82.5

0.85

1.49

2.49

78

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.39

73

CF3C-V02

MOV AT CF3-C OUTLET

0.75

kW

415

82.5

0.85

1.49

2.49

78

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.39

74

V411

DUMP VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

79

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

60

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 16 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

P12A-V01

MOV AT SUCTION OF HP PUMP

1.1

kW

415

83.8

0.85

2.15

3.59

79

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.57

76

P12B-V01

MOV AT SUCTION OF HP PUMP

1.1

kW

415

83.8

0.85

2.15

3.59

79

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.57

77

P12C-V01

MOV AT SUCTION OF HP PUMP

1.1

kW

415

83.8

0.85

2.15

3.59

79

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.57

78

ROIIC-V05

MOV AT REJECT WATER HEADER

0.75

kW

415

82.5

0.85

1.49

2.49

95

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.48

79

ROIIC-V06

MOV AT SEA WATER TANK HEADER

0.75

kW

415

82.5

0.85

1.49

2.49

95

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.48

80

P16A-V02

MOV AT THE DISCHARGE OF P16-A

0.75

kW

415

82.5

0.85

1.49

2.49

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.32

81

P16B-V02

MOV AT THE DISCHARGE OF P16-B

0.75

kW

415

82.5

0.85

1.49

2.49

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.32

82

P16C-V02

MOV AT THE DISCHARGE OF P16-C

0.75

kW

415

82.5

0.85

1.49

2.49

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.32

83

P16D-V02

MOV AT THE DISCHARGE OF P16-D

0.75

kW

415

82.5

0.85

1.49

2.49

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.32

84

P16A-V05

RECIRCULATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.32

85

P14A-V02

MOV AT THE DISCHARGE OF P14-A

0.75

kW

415

82.5

0.85

1.49

2.49

68

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.34

86

P14B-V02

MOV AT THE DISCHARGE OF P14-B

0.75

kW

415

82.5

0.85

1.49

2.49

68

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.34

87

P15A-V02

MOV AT THE DISCHARGE OF P15-A

0.75

kW

415

82.5

0.85

1.49

2.49

66

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.33

88

P15B-V02

MOV AT THE DISCHARGE OF P15-B

0.75

kW

415

82.5

0.85

1.49

2.49

66

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.33

89

DMWTA-V01

DMWT INLET MOV

0.75

kW

415

82.5

0.85

1.49

2.49

320

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.60

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

75

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 17 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

DMWTB-V01

DMWT INLET MOV

0.75

kW

415

82.5

0.85

1.49

2.49

346

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.73

91

P17A-V02

MOV AT THE DISCHARGE OF P17-A

0.75

kW

415

82.5

0.85

1.49

2.49

341

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.71

92

P17B-V02

MOV AT THE DISCHARGE OF P17-B

0.75

kW

415

82.5

0.85

1.49

2.49

341

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.71

93

P17-V01

RECIRCULATION MOV

0.75

kW

415

82.5

0.85

1.49

2.49

341

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.71

94

DP6B-V05

P6-A/B COMMON OUTLET HEADER


MOV

0.75

kW

415

82.5

0.85

1.49

2.49

84

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.42

95

P22A-V02

P22-A DISCHARGE VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

181

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.91

96

P22B-V02

P22-B DISCHARGE VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

181

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.91

97

P22A-V04

WASTE DISPOSAL PUMP


RECIRCULATION VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

181

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.91

98

P22B-V04

WASTE DISPOSAL PUMP OUTLET


VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

181

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.91

99

P22-V05

WASTE DISPOSAL PUMP


RECIRCULATION MOV TO RST

0.75

kW

415

82.5

0.85

1.49

2.49

183

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.92

100 P22-V06

WASTE DISPOSAL PUMP


RECIRCULATION MOV TO ECT

0.75

kW

415

82.5

0.85

1.49

2.49

183

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.92

101 P4A-V02

P4-A DISCHARGE VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

178

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.89

102 P4B-V02

P4-B DISCHARGE VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

178

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.89

103 P4C-V02

P4-C DISCHARGE VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

178

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.89

104 P4C-V04

P4-A/B/C RECIRCULATION VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

178

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.89

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

90

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 18 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

kW

415

82.5

0.85

1.49

2.49

178

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.89

106 POWSTA-V01 POWST-A INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

368

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.84

107 POWSTB-V01 POWST-B INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

381

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.91

108 POWSTA-V05 BLENDING PUMP MOV2 POWST-A

0.75

kW

415

82.5

0.85

1.49

2.49

368

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.84

109 POWSTB-V05 BLENDING PUMP MOV2 POWST-B

0.75

kW

415

82.5

0.85

1.49

2.49

381

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.91

110 PWSTA-V01

PWST-A INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

340

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.70

111 PWSTB-V01

PWST-B INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

310

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.55

112 PWSTC-V01

PWST-C INLET VALVE

0.75

kW

415

82.5

0.85

1.49

2.49

282

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.41

113 LBVA-V05

LIME BED VESSEL-A

0.75

kW

415

82.5

0.85

1.49

2.49

95

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.48

114 LBVB-V05

LIME BED VESSEL-B

0.75

kW

415

82.5

0.85

1.49

2.49

95

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.48

115 xxx

MoV on P15-A/B Header

0.75

kW

415

82.5

0.85

1.49

2.49

100

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.50

105 P4C-V05

P4-A/B/C OUTLET VALVE

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description
Rating

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

0.75

Sl
no.

Unit (KW / A)

During running

% Voltage drop

Efficiency (%)

Power factor
(Cos)

System voltage (V)

Motor/ Feeder
Rating

Annex.-I
Page 19 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

ANNEXURE-II
CABLE SIZING CALCULATION FOR LT DRIVE & OTHERS LOAD

During starting

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

180

KW

415

95.8

0.91

0.20

287.26 480.04

7.2

161

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

594

2.13

7.81

117 P3-B

FILTER FEED PUMP-B

180

KW

415

95.8

0.91

0.20

287.26 480.04

7.2

161

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

594

2.13

7.81

118 P3-C

FILTER FEED PUMP-C

180

KW

415

95.8

0.91

0.20

287.26 480.04

7.2

161

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

594

2.13

7.81

119 P3-D

FILTER FEED PUMP-D

180

KW

415

95.8

0.91

0.20

287.26 480.04

7.2

161

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

594

2.13

7.81

120 P4-A

FILTER BACKWASH PUMP

132

KW

415

95.5

0.85

0.20

226.23 378.06

7.2

165

120.0

3.0

AL

1100

226

0.253

0.3244 0.0712

452

2.44

7.55

121 P4-B

FILTER BACKWASH PUMP

132

KW

415

95.5

0.85

0.20

226.23 378.06

7.2

165

120.0

3.0

AL

1100

226

0.253

0.3244 0.0712

452

2.44

7.55

122 P4-C

FILTER BACKWASH PUMP

132

KW

415

95.5

0.85

0.20

226.23 378.06

7.2

165

120.0

3.0

AL

1100

226

0.253

0.3244 0.0712

452

2.44

7.55

123 P6-A

RO BOOSTER PUMP - VFD PANEL

90

KW

415

95.0

0.85

0.20

155.06 259.13

7.2

120

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

297

1.68

6.28

124 P6-B

RO BOOSTER PUMP - VFD PANEL

90

KW

415

95.0

0.85

0.20

155.06 259.13

7.2

120

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

297

1.68

6.28

125 P6-C

RO BOOSTER PUMP - VFD PANEL

90

KW

415

95.0

0.85

0.20

155.06 259.13

7.2

120

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

297

1.68

6.28

126 P7-A

RO CLEANING PUMP

132

KW

415

95.5

0.85

0.20

226.23 378.06

7.2

120

120.0

3.0

AL

1100

226

0.253

0.3244 0.0712

452

1.77

5.49

127 P7-B

RO CLEANING PUMP

132

KW

415

95.5

0.85

0.20

226.23 378.06

7.2

120

120.0

3.0

AL

1100

226

0.253

0.3244 0.0712

452

1.77

5.49

128 P8-A

RO FLUSHING PUMP

55

KW

415

94.2

0.85

0.20

95.56

7.2

123

95.0

3.0

AL

1100

194

0.32

0.4103 0.0724

194

1.90

5.40

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

159.70

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During running

FILTER FEED PUMP-A

Tag no.

Current considering
derating factor
(AMP)

Efficiency (%)

116 P3-A

Sl
no.

Full load current


(AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 20 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

129 P8-B

RO FLUSHING PUMP

55

KW

415

94.2

0.85

0.20

95.56

159.70

7.2

123

95.0

3.0

AL

1100

194

0.32

0.4103 0.0724

194

1.90

5.40

130 P9-A

DEGASSED WATER TRANSFER


PUMP

75

KW

415

94.7

0.85

0.20

129.63 216.62

7.2

112

150.0

3.0

AL

1100

257

0.206

0.2641 0.0716

257

1.59

5.36

131 P9-B

DEGASSED WATER TRANSFER


PUMP

75

KW

415

94.7

0.85

0.20

129.63 216.62

7.2

112

150.0

3.0

AL

1100

257

0.206

0.2641 0.0716

257

1.59

5.36

132 P9-C

DEGASSED WATER TRANSFER


PUMP

75

KW

415

94.7

0.85

0.20

129.63 216.62

7.2

112

150.0

3.0

AL

1100

257

0.206

0.2641 0.0716

257

1.59

5.36

133 P12-A

RO HIGH PRESSURE PUMP

55

KW

415

94.2

0.85

0.20

95.56

159.70

7.2

87

95.0

3.0

AL

1100

194

0.32

0.4103 0.0724

194

1.34

3.82

134 P12-B

RO HIGH PRESSURE PUMP

55

KW

415

94.2

0.85

0.20

95.56

159.70

7.2

87

95.0

3.0

AL

1100

194

0.32

0.4103 0.0724

194

1.34

3.82

135 P12-C

RO HIGH PRESSURE PUMP

55

KW

415

94.2

0.85

0.20

95.56

159.70

7.2

87

95.0

3.0

AL

1100

194

0.32

0.4103 0.0724

194

1.34

3.82

136 P22-A

WASTE DISPOSAL PUMP

200

KW

415

95.0

0.85

0.20

344.58 575.84

7.2

190

240.0

3.0

AL

1100

351

0.125

0.1603 0.0710

702

2.37

10.00

137 P22-B

WASTE DISPOSAL PUMP

200

KW

415

95.0

0.85

0.20

344.58 575.84

7.2

190

240.0

3.0

AL

1100

351

0.125

0.1603 0.0710

702

2.37

10.00

138 P1-A

CLARIFIED WATER FEED PUMP-A

37

KW

415

93.6

0.85

0.20

64.70

108.12

7.2

171

70.0

3.0

AL

1100

150

0.443

0.5680 0.0740

150

2.41

6.19

139 P1-B

CLARIFIED WATER FEED PUMP-B

37

KW

415

93.6

0.85

0.20

64.70

108.12

7.2

171

70.0

3.0

AL

1100

150

0.443

0.5680 0.0740

150

2.41

6.19

140 P1-C

CLARIFIED WATER FEED PUMP-C

37

KW

415

93.6

0.85

0.20

64.70

108.12

7.2

171

70.0

3.0

AL

1100

150

0.443

0.5680 0.0740

150

2.41

6.19

141 P1-D

CLARIFIED WATER FEED PUMP-D

37

KW

415

93.6

0.85

0.20

64.70

108.12

7.2

171

70.0

3.0

AL

1100

150

0.443

0.5680 0.0740

150

2.41

6.19

142 FM1-AG1

AGITATOR OF FLASH MIXER -1

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

128

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.80

3.18

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 21 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

143 FM2-AG1

AGITATOR OF FLASH MIXER -2

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

128

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.80

3.18

144 FM3-AG1

AGITATOR OF FLASH MIXER -3

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

128

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.80

3.18

145 FT1-AG1

AGITATOR-1 OF FLOCULATION
TANK -1

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

146 FT1-AG2

AGITATOR-2 OF FLOCULATION
TANK -1

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

147 FT1-AG3

AGITATOR-3 OF FLOCULATION
TANK -1

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

148 FT1-AG4

AGITATOR-4 OF FLOCULATION
TANK -1

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

149 FT2-AG1

AGITATOR-1 OF FLOCULATION
TANK -2

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

150 FT2-AG2

AGITATOR-2 OF FLOCULATION
TANK -2

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

151 FT2-AG3

AGITATOR-3 OF FLOCULATION
TANK -2

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

152 FT2-AG4

AGITATOR-4 OF FLOCULATION
TANK -2

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

153 FT3-AG1

AGITATOR-1 OF FLOCULATION
TANK -3

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

154 FT3-AG2

AGITATOR-2 OF FLOCULATION
TANK -3

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

155 FT3-AG3

AGITATOR-3 OF FLOCULATION
TANK -3

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

156 FT3-AG4

AGITATOR-4 OF FLOCULATION
TANK -3

0.55

KW

415

78.0

0.85

0.20

1.15

1.93

7.2

137

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.53

0.94

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 22 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

157 P2-A

SLUDGE DISPOSAL PUMP-A

11

KW

415

91.0

0.85

0.20

19.79

33.06

7.2

167

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.93

5.65

158 P2-B

SLUDGE DISPOSAL PUMP-B

11

KW

415

91.0

0.85

0.20

19.79

33.06

7.2

167

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.93

5.65

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 23 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

159 DT1A-AG

AGITATOR FOR PE DOSING TANK


DT1-A

1.5

KW

415

85.0

0.85

0.20

2.89

4.83

7.2

99

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.96

1.71

160 DT1B-AG

AGITATOR FOR PE DOSING TANK


DT1-B

1.5

KW

415

85.0

0.85

0.20

2.89

4.83

7.2

99

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.96

1.71

161 DP1-A

PE DOSING PUMP-A

1.5

KW

415

85.0

0.85

0.20

2.89

4.83

7.2

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.99

1.76

162 DP1-B

PE DOSING PUMP-B

1.5

KW

415

85.0

0.85

0.20

2.89

4.83

7.2

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.99

1.76

163 DT2A-AG

AGITATOR FOR FeCL3 DOSING


TANK DT2-A

1.1

KW

415

83.8

0.85

0.20

2.15

3.59

7.2

91

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.66

1.17

164 DT2B-AG

AGITATOR FOR FeCL3 DOSING


TANK DT2-B

1.1

KW

415

83.8

0.85

0.20

2.15

3.59

7.2

91

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.66

1.17

165 DP2-A

FeCL3 DOSING PUMP-A

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

91

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.46

0.81

166 DP2-B

FeCL3 DOSING PUMP-B

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

91

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.46

0.81

167 B1-A

HDMF BLOWER-A

30

KW

415

93.2

0.85

0.20

52.69

88.04

7.2

130

35.0

3.0

AL

1100

103

0.868

1.1129

0.0783

103

2.82

6.16

168 B1-B

HDMF BLOWER-B

30

KW

415

93.2

0.85

0.20

52.69

88.04

7.2

130

35.0

3.0

AL

1100

103

0.868

1.1129

0.0783

103

2.82

6.16

169 B1-C

HDMF BLOWER-C

30

KW

415

93.2

0.85

0.20

52.69

88.04

7.2

130

35.0

3.0

AL

1100

103

0.868

1.1129

0.0783

103

2.82

6.16

170 DP3-A

ACID DOSING PUMP-A (FOR RO


PASS-I)

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.31

0.54

171 DP3-B

ACID DOSING PUMP-B (FOR RO


PASS-I)

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.31

0.54

172 DP4-A

SBS DOSING PUMP-A (FOR RO


PASS-I)

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

107

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.30

0.53

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 24 of 46

Sl
no.
Tag no.

173 DP4-B

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Efficiency (%)

SBS DOSING PUMP-B (FOR RO


PASS-I)

System voltage (V)

Equipment Description
Unit (KW / A)

Motor/ Feeder
Rating

Rating

0.37
KW
415
73.0

Full load current


(AMP)
Current considering
derating factor
(AMP)
Max permissible
starting current in
times

Cable length (M)


No of parallal
run

Cable size
in SQ. MM
No of core
Conductor
Voltage grade
in Volts
Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

0.85
0.20
0.83
1.39
7.2
107
1
2.5
3.0
CU
1100
24
7.41

Details of Cables (XLPE insulation)

9.4485 0.0985

During starting

24

During running

Total Current
carrying capacity on
air at 90C (AMP)

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

During starting

Power factor
(Cos)
During running

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

% Voltage drop

0.30
0.53

Annex.-II
Page 25 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

174 DT4A-AG

AGITATOR FOR SBS DOSING TANK


DT4-A

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

112

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.56

0.99

175 DT4B-AG

AGITATOR FOR SBS DOSING TANK


DT4-B

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

112

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.56

0.99

176 DP5-A

ANTISCALENT DOSING PUMP-A


(FOR RO PASS-I)

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

97

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.27

0.48

177 DP5-B

ANTISCALENT DOSING PUMP-B


(FOR RO PASS-I)

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

97

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.27

0.48

178 DT5A-AG

AGITATOR FOR ANTISCALENT


DOSING TANK DT5-A

1.1

KW

415

83.8

0.85

0.20

2.15

3.59

7.2

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.74

1.31

179 DT5B-AG

AGITATOR FOR ANTISCALENT


DOSING TANK DT5-B

1.1

KW

415

83.8

0.85

0.20

2.15

3.59

7.2

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.74

1.31

180 CST1A-AG

AGITATOR FOR CST-1A

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

115

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.62

2.86

181 CST1B-AG

AGITATOR FOR CST-1B

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.55

2.74

182 B3-A

DEGASSER AIR BLOWER-A FOR


RO PASS-I

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

152

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

2.14

3.78

183 B3-B

DEGASSER AIR BLOWER-B FOR


RO PASS-I

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

152

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

2.14

3.78

184 B3-C

DEGASSER AIR BLOWER-C FOR


RO PASS-I

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

140

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.97

3.48

185 B3-D

DEGASSER AIR BLOWER-D FOR


RO PASS-I

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

140

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.97

3.48

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 26 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

186 B3-E

DEGASSER AIR BLOWER-E FOR


RO PASS-I

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

130

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.83

3.23

187 B3-F

DEGASSER AIR BLOWER-F FOR


RO PASS-I

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

130

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.83

3.23

188 P10-A

POTABLE WATER TRANSFER PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

120

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.85

5.50

189 P10-B

POTABLE WATER TRANSFER PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

120

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.85

5.50

190 P11-A

RO PASS-II FEED PUMP

18.5

KW

415

92.2

0.85

0.20

32.84

54.88

7.2

118

25.0

3.0

AL

1100

84

1.2

1.5385 0.0805

84

2.18

4.50

191 P11-B

RO PASS-II FEED PUMP

18.5

KW

415

92.2

0.85

0.20

32.84

54.88

7.2

118

25.0

3.0

AL

1100

84

1.2

1.5385 0.0805

84

2.18

4.50

192 P11-C

RO PASS-II FEED PUMP

18.5

KW

415

92.2

0.85

0.20

32.84

54.88

7.2

118

25.0

3.0

AL

1100

84

1.2

1.5385 0.0805

84

2.18

4.50

193 P14-A

RO-II FLUSHING PUMP

9.3

KW

415

91.5

0.85

0.20

16.64

27.80

7.2

76

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.68

4.82

194 P14-B

RO-II FLUSHING PUMP

9.3

KW

415

91.5

0.85

0.20

16.64

27.80

7.2

76

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.68

4.82

195 B4-A

DEGASSER AIR BLOWER-A FOR


RO PASS-II

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.25

0.44

196 B4-B

DEGASSER AIR BLOWER-B FOR


RO PASS-II

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.25

0.44

197 B4-C

DEGASSER AIR BLOWER-C FOR


RO PASS-II

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

55

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.28

0.49

198 B4-D

DEGASSER AIR BLOWER-D FOR


RO PASS-II

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

55

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.28

0.49

199 B4-E

DEGASSER AIR BLOWER-E FOR


RO PASS-II

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

60

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.30

0.53

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 27 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

200 B4-F

DEGASSER AIR BLOWER-F FOR


RO PASS-II

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

60

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.30

0.53

201 CSTIIA-AG

CST-IIA AGITATOR

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

104

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.52

0.92

202 CSTIIB-AG

CST-IIB AGITATOR

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

104

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.52

0.92

203 P13-A

RO-II CLEANING PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

92

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.19

4.22

204 P13-B

RO-II CLEANING PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

92

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.19

4.22

205 P15-A

BLENDING PUMP-A

9.3

KW

415

91.5

0.85

0.20

16.64

27.80

7.2

74

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.61

4.69

206 P15-B

BLENDING PUMP-B

9.3

KW

415

91.5

0.85

0.20

16.64

27.80

7.2

74

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.61

4.69

207 P16-A

MB FEED PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

70

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.67

4.92

208 P16-B

MB FEED PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

70

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.67

4.92

209 P16-C

MB FEED PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

70

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.67

4.92

210 P16-D

MB FEED PUMP

15

KW

415

91.5

0.85

0.20

26.83

44.84

7.2

70

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.67

4.92

211 B5-A

MIXED BED BLOWER

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

30

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

0.86

1.56

212 B5-B

MIXED BED BLOWER

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

35

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

1.01

1.82

213 P17-A

MB REGENERATION PUMP

5.5

KW

415

89.2

0.85

0.20

10.09

16.87

7.2

320

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.86

5.52

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 28 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

214 P17-B

MB REGENERATION PUMP

5.5

KW

415

89.2

0.85

0.20

10.09

16.87

7.2

320

16.0

3.0

AL

1100

62

1.91

2.4488 0.0808

62

2.86

5.52

215 P18-A

BULK ACID UNLOADING CUM


TRANSFER PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

216 P18-B

BULK ACID UNLOADING CUM


TRANSFER PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

217 DP7-A

ACID DOSING PUMPFOR MB

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.70

1.24

218 DP7-B

ACID DOSING PUMPFOR MB

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.70

1.24

219 P19-A

COAGULANT UNLOADING CUM


TRANSFER PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

2.36

4.18

220 P19-B

COAGULANT UNLOADING CUM


TRANSFER PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

102

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

2.36

4.18

221 CMT1A-AG

CMT1A AGITATOR FOR Ph


CORRECTION (DWHT-A )

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

45

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.13

0.22

222 CMT2A-AG

CMT2A AGITATOR FOR Ph


CORRECTION (DWHT-B )

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

45

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.13

0.22

223 DP6-A

CAUSTIC DOSING PUPM FOR Ph


CORRECTION

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

92

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.26

0.46

224 DP6-B

CAUSTIC DOSING PUPM FOR Ph


CORRECTION

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

92

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.26

0.46

225 CMT2A-AG

CMT2-A AGITATOR FOR MB

0.18

KW

415

70.0

0.85

0.20

0.42

0.70

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.07

0.13

226 CMT2B-AG

CMT2-B AGITATOR FOR MB

0.18

KW

415

70.0

0.85

0.20

0.42

0.70

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.07

0.13

227 DP8-A

CAUSTIC DOSING PUPM FOR MB

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.70

1.24

Equipment Description

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 29 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

228 DP8-B

CAUSTIC DOSING PUMP FOR MB

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

50

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.70

1.24

229 CPTA-AG

CPT (ALKALI PREPARATION TANK


FOR Ph CORRECTION) AGITATOR

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

48

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.13

0.24

230 CPTB-AG

CPT (ALKALI PREPARATION TANK


FOR Ph CORRECTION) AGITATOR

0.37

kW

415

73.0

0.85

0.20

0.83

1.39

7.2

48

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.13

0.24

231 P21-A

ALKALI TRANSFER CUM


RECIRCULATION PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

60

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.39

2.46

232 P21-B

ALKALI TRANSFER CUM


RECIRCULATION PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

60

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.39

2.46

233 P20-A

BULK ALKALI UNLOADING CUM


TRANSFER PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.46

2.58

234 P20-B

BULK ALKALI UNLOADING CUM


TRANSFER PUMP

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

63

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.46

2.58

235

ELECTRICAL HEATER FOR


CHLORINATION

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

85

6.0

3.0

AL

1101

44

4.61

5.9105 0.0883

44

2.45

4.41

Equipment Description

Reactance per
Ohm/Km

Tag no.

Resistance at
90C Ohm/Km

Sl
no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

236

DRAINAGE PUMP-A

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

130

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.51

4.64

237

DRAINAGE PUMP-B

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

145

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.80

5.18

238

DRAINAGE PUMP-C

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

130

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.51

4.64

239

DRAINAGE PUMP-D

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

60

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

1.16

2.14

240

DRAINAGE PUMP-E

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

95

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

1.84

3.39

241

DRAINAGE PUMP-F

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

40

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

0.77

1.43

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Annex.-II
Page 30 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

MONORAIL ALONG RO HIGH


PRESSURE PUMP AT RO SHED

32

415

100.0

0.85

32.00

53.48

65

10.0

4.0

AL

1100

59

3.08

3.9489 0.0837

59

2.95

243

MONORAIL ALONG RO PASS-II


FEED PUMP AT RO SHED

32

415

100.0

0.85

32.00

53.48

116

25.0

4.0

AL

1100

84

1.2

1.5385 0.0805

84

2.09

244

MONORAIL AT P1-A/B/C/D PUMP


SHED

32

415

100.0

0.85

32.00

53.48

160

25.0

4.0

AL

1100

84

1.2

1.5385 0.0805

84

2.89

245

MONORAIL AT P3-A/B/C/D PUMP


SHED

32

415

100.0

0.85

32.00

53.48

152

25.0

4.0

AL

1100

84

1.2

1.5385 0.0805

84

2.74

246

MONORAIL AT P4-A/B/C PUMP


SHED

32

415

100.0

0.85

32.00

53.48

160

25.0

4.0

AL

1100

84

1.2

1.5385 0.0805

84

2.89

247

MONORAIL AT P22-A/B PUMP SHED

32

415

100.0

0.85

32.00

53.48

190

35.0

3.5

AL

1100

103

0.868

1.1129

0.0783

103

2.50

248

MONORAIL AT P14, P15 & P16


PUMP SHED

32

415

100.0

0.85

32.00

53.48

40

6.0

4.0

AL

1100

44

4.61

5.9105 0.0883

88

1.35

249

HOIST IN CHLORINATION SYSTEM,


WEIGHING SCALE POINT

16

415

100.0

0.85

16.00

26.74

86

6.0

4.0

AL

1100

44

4.61

5.9105 0.0883

44

2.91

250

HOIST IN CHEMICAL HOUSE (1ST


FLOOR)

16

415

100.0

0.85

16.00

26.74

100

10.0

4.0

AL

1100

59

3.08

3.9489 0.0837

59

2.27

251

DP4-C

SBS DOSING PUMP-C (FOR RO


PASS-II)

0.37

kW

415

73.0

0.85

0.20

0.83

1.39

7.2

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.31

0.54

252

DP4-D

SBS DOSING PUMP-D (FOR RO


PASS-II)

0.37

kW

415

73.0

0.85

0.20

0.83

1.39

7.2

110

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.31

0.54

253

DP5-C

ANTISCALENT DOSING PUMP-C


(FOR RO PASS-II)

0.37

kW

415

73.0

0.85

0.20

0.83

1.39

7.2

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.29

0.52

254

DP5-D

ANTISCALENT DOSING PUMP-D


(FOR RO PASS-II)

0.37

kW

415

73.0

0.85

0.20

0.83

1.39

7.2

105

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.29

0.52

255

MB REGENERATION WASTE TO
ECT

7.5

kW

415

90.1

0.85

0.20

13.62

22.77

7.2

107

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.07

3.82

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

During starting

Efficiency (%)

242

Equipment Description

During running

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

Sl
no.

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 31 of 46

257

FEEDER FOR AIR CONDITIONED


SYSTEM

200

415

100.0

0.85

258

FEEDER FOR VENTILATION


SYSTEM

16

415

100.0

0.85

259

FEEDER TO ACFB

63

415

100.0

260

MLDB LIGHTING TRANSFORMER-1

163

415

261

MLDB LIGHTING TRANSFORMER-2

163

262

FEEDER TO WELDING
TRANSFORMER OF WDB

80

263

FEEDER-1 TO UPS SYSTEM

264

265

7.2

107

10.0

3.0

AL

1100

59

3.08

3.9489 0.0837

59

2.07

3.82

200.00 334.22

40

95.0

3.5

AL

1100

194

0.32

0.4103 0.0724

388

0.65

16.00

26.74

20

10.0

4.0

AL

1100

59

3.08

3.9489 0.0837

59

0.45

0.85

63.00

105.28

20

35.0

3.5

AL

1100

103

0.868

1.1129

0.0783

206

0.26

100.0

0.85

163.00 272.39

30

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

297

0.44

415

100.0

0.85

163.00 272.39

30

185.0

3.0

AL

1100

297

0.164

0.2103 0.0718

297

0.44

415

100.0

0.85

80.00

133.69

25

50.0

3.0

AL

1100

125

0.641

0.8218 0.0750

250

0.31

32

415

100.0

0.85

32.00

53.48

35

16.0

4.0

AL

1100

62

1.91

2.4488 0.0808

62

0.99

FEEDER-2 TO UPS SYSTEM

32

415

100.0

0.85

32.00

53.48

35

16.0

4.0

AL

1100

62

1.91

2.4488 0.0808

62

0.99

FEEDER-3 TO UPS SYSTEM

32

415

100.0

0.85

32.00

53.48

35

16.0

4.0

AL

1100

62

1.91

2.4488 0.0808

62

0.99

266

ELECTRICAL HEATER FOR HWT-1

30

KW

415

93.2

0.85

49.10

82.05

7.2

95

35.0

3.0

AL

1100

103

0.868

1.1129

0.0783

103

1.92

267

ELECTRIC HEATER

30

KW

415

93.2

0.85

52.69

88.04

7.2

95

35.0

3.0

AL

1100

103

0.868

1.1129

0.0783

103

2.06

268

RO SHED WASTE DRAINAGE PUMP

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

85

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.45

4.41

269

RO SHED WASTE DRAINAGE PUMP

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

85

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.45

4.41

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

22.77

Equipment Description

Resistance at
90C Ohm/Km

During starting

13.62

During running

0.20

Resistance at
20C Ohm/Km

0.85

Current carrying
capacity on air
at 90C (AMP)

90.1

Voltage grade
in Volts

415

Conductor

Full load current


(AMP)

kW

No of core

During starting

7.5

Cable size
in SQ. MM

During running

MB REGENERATION WASTE TO
ECT

No of parallal
run

Efficiency (%)

Cable length (M)

System voltage (V)

256

% Voltage drop

Max permissible
starting current in
times

Tag no.

Details of Cables (XLPE insulation)

Current considering
derating factor
(AMP)

Sl
no.

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Total Current
carrying capacity on
air at 90C (AMP)

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Annex.-II
Page 32 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Tag no.

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

270

FILTER SHED DRAINAGE PUMP

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

90

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.59

4.67

271

FILTER SHED DRAINAGE PUMP

7.5

KW

415

90.1

0.85

0.20

13.62

22.77

7.2

90

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.59

4.67

272

CHEMICAL HOUSE DRAINAGE


PUMP

5.5

KW

415

89.2

0.85

0.20

10.09

16.87

7.2

40

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

0.85

1.54

273

CHEMICAL HOUSE DRAINAGE


PUMP

5.5

KW

415

89.2

0.85

0.20

10.09

16.87

7.2

40

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

0.85

1.54

274

PR-EV-01

PRE-SYSTEM - EVAPORATOR 50KG/HR

5.5

KW

415

89.2

0.85

0.20

10.09

16.87

7.2

85

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

1.82

3.27

275

PR-EV-02

PRE-SYSTEM - EVAPORATOR 50KG/HR

5.5

KW

415

89.2

0.85

0.20

10.09

16.87

7.2

85

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

1.82

3.27

276

PR-BP-01

PRE BOOSTER PUMP - 50 KG/HR

9.3

KW

415

91.5

0.85

0.20

16.64

27.80

7.2

78

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.75

4.95

277

PR-BP-02

PRE BOOSTER PUMP - 50 KG/HR

9.3

KW

415

91.5

0.85

0.20

16.64

27.80

7.2

78

6.0

3.0

AL

1100

44

4.61

5.9105 0.0883

44

2.75

4.95

278

PR-BW-01

COMMEN LEAK ABSORBTION


BLOWER

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

81

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.14

2.01

279

PR-BW-02

COMMEN LEAK ABSORBTION


BLOWER

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

81

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.14

2.01

280

PR-CP-01

COMMEN CAUSTIC RECIRCULATION PUMP

1.5

KW

415

85.0

0.85

0.20

2.89

4.83

7.2

81

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.79

1.40

281

PR-CP-02

COMMEN CAUSTIC RECIRCULATION PUMP

1.5

KW

415

85.0

0.85

0.20

2.89

4.83

7.2

81

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.79

1.40

282

PO-BP-01

POST BOOSTER PUMP - 4 KG/HR

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

78

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.10

1.94

283

PO-BP-02

POST BOOSTER PUMP - 4 KG/HR

2.2

KW

415

86.4

0.85

0.20

4.17

6.96

7.2

78

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.10

1.94

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

Sl
no.

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 33 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

PR-DA-03

DAMPER

20

415

100.0

0.85

20.00

33.42

85

2.5

4.0

CU

1100

24

7.41

9.4485 0.0985

48

2.87

285

PR-DA-04

DAMPER

20

415

100.0

0.85

0.20

20.00

33.42

85

2.5

4.0

CU

1100

24

7.41

9.4485 0.0985

48

2.87

286

PR-MBFV-01

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 01

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

287

PR-MBFV-02

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 02

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

288

PR-MBFV-03

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 03

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

289

PR-MBFV-04

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 04

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

290

PR-MBFV-05

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 05

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

291

PR-BV-17

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 06

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

292

PR-BV-18

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 07

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

ELECTRIC ACTUATOR FOR VALVE


(PRE) - 08

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

293

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

During starting

Efficiency (%)

284

Equipment Description

During running

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

Sl
no.

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

294

PO-MBFV-01

ELECTRIC ACTUATOR FOR VALVE


(POST) - 01

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

295

PO-MBFV-02

ELECTRIC ACTUATOR FOR VALVE


(POST) - 02

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

296

PO-MBFV-03

ELECTRIC ACTUATOR FOR VALVE


(POST) - 03

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

297

PO-MBFV-04

ELECTRIC ACTUATOR FOR VALVE


(POST) - 04

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Annex.-II
Page 34 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

ELECTRIC ACTUATOR FOR VALVE


(POST) - 05

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

ELECTRIC ACTUATOR FOR VALVE


(POST) - 06

0.75

KW

415

82.5

0.85

0.20

1.49

2.49

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.40

0.71

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

During starting

299

During running

PO-MBFV-05

Efficiency (%)

298

System voltage (V)

Tag no.

% Voltage drop

Unit (KW / A)

Sl
no.

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

300

Feeder For oil Skimmer - 1

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

301

Feeder For oil Skimmer - 2

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

302

Feeder For CO2 Absorbtion System 1

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

303

Feeder For CO2 Absorbtion System 2

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

304

Feeder For CO2 Absorbtion System 3

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

305

Feeder For CO2 Absorbtion System 4

3.7

KW

415

88.3

0.85

0.20

6.86

11.46

7.2

72

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

1.67

2.95

306

Exhaust Fan - 1

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

307

Exhaust Fan - 2

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

308

Exhaust Fan - 3

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

309

Exhaust Fan - 4

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

310

Exhaust Fan - 5

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

311

Exhaust Fan - 6

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Annex.-II
Page 35 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

Tag no.

Efficiency (%)

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

During running

During starting

312

Exhaust Fan - 7

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

313

Exhaust Fan - 8

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

80

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.22

0.40

314

FEEDER FOR INST. Supply DB - 1

63

415

100.0

0.85

63.00

105.28

25

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.49

315

FEEDER FOR INST. Supply DB - 2

63

415

100.0

0.85

63.00

105.28

25

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.49

316

WELDING RECEPTACLE AT
HDMF/HPSF SHED-1

63

415

100.0

0.85

63.00

105.28

125

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.43

317

WELDING RECEPTACLE AT
HDMF/HPSF SHED-2

63

415

100.0

0.85

63.00

105.28

145

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.81

318

WELDING RECEPTACLE AT RO
SHED-3

63

415

100.0

0.85

63.00

105.28

100

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

1.94

319

WELDING RECEPTACLE AT RO
SHED-4

63

415

100.0

0.85

63.00

105.28

50

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.97

320

WELDING RECEPTACLE AT FILTER


FEED PUMP SHED-5

63

415

100.0

0.85

63.00

105.28

135

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.62

321

WELDING RECEPTACLE AT
CLARIFIED WATER FEED PUMP
SHED-6

63

415

100.0

0.85

63.00

105.28

145

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.81

322

WELDING RECEPTACLE AT
CHEMICAL BUILDING-7

63

415

100.0

0.85

63.00

105.28

80

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

1.55

323

WELDING RECEPTACLE AT
CMT/AMT AREA-8

63

415

100.0

0.85

63.00

105.28

35

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.68

324

WELDING RECEPTACLE AT
SWITCHGEAR ROOM-9

63

415

100.0

0.85

63.00

105.28

20

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.39

325

WELDING RECEPTACLE AT
CONTROL ROOM-10

63

415

100.0

0.85

63.00

105.28

45

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.87

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

Equipment Description

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

Sl
no.

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 36 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

WELDING RECEPTACLE AT DMWT


AREA-11

63

415

100.0

0.85

63.00

105.28

250

95.0

3.5

AL

1100

194

0.32

0.4103 0.0724

194

2.54

327

WELDING RECEPTACLE AT DMWT


AREA-12

63

415

100.0

0.85

63.00

105.28

290

95.0

3.5

AL

1100

194

0.32

0.4103 0.0724

194

2.95

328

SWITCHGEAR ROOM VENTILATION


PANEL TO FAN-01

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

33

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.09

0.16

329

SWITCHGEAR ROOM VENTILATION


PANEL TO FAN-02

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

37

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.10

0.18

330

SWITCHGEAR ROOM VENTILATION


PANEL TO FAN-03

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

25

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.07

0.12

331

SWITCHGEAR ROOM VENTILATION


PANEL TO FAN-04

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

30

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.08

0.15

332

SWITCHGEAR ROOM VENTILATION


PANEL TO FAN-05

0.37

KW

415

73.0

0.85

0.20

0.83

1.39

7.2

35

2.5

3.0

CU

1100

24

7.41

9.4485 0.0985

24

0.10

0.17

333

LP-1

LIGHTING PANEL FOR


SWITCHGEAR ROOM

63

415

100.0

0.85

63.00

105.28

20

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.39

334

LP-2

LIGHTING PANEL FOR CONTROL


ROOM

63

415

100.0

0.85

63.00

105.28

35

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.68

335

LP-3

LIGHTING PANEL FOR BAT/BCT &


MB AREA

63

415

100.0

0.85

63.00

105.28

25

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.49

336

LP-4

LIGHTING PANEL FOR CHEMICAL


BUILDING

63

415

100.0

0.85

63.00

105.28

65

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

1.26

337

LP-5

LIGHTING PANEL FOR SWST, SC,


FT & LC AREA

63

415

100.0

0.85

63.00

105.28

140

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.72

338

LP-6

LIGHTING PANEL FOR CWST & SP


AREA

63

415

100.0

0.85

63.00

105.28

125

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.43

339

LP-7

LIGHTING PANEL FOR HDMF/HPSF


SHED

63

415

100.0

0.85

63.00

105.28

110

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.13

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

During starting

Efficiency (%)

326

Equipment Description

During running

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

Sl
no.

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

Annex.-II
Page 37 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

During running

During starting

Full load current


(AMP)

Current considering
derating factor
(AMP)

Max permissible
starting current in
times

Cable length (M)

No of parallal
run

Cable size
in SQ. MM

No of core

Conductor

Voltage grade
in Volts

Current carrying
capacity on air
at 90C (AMP)

Resistance at
20C Ohm/Km

LP-8

LIGHTING PANEL FOR ECT/RST


AREA

63

415

100.0

0.85

63.00

105.28

145

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

2.81

341

LP-9

LIGHTING PANEL FOR RO SHED

63

415

100.0

0.85

63.00

105.28

40

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.78

342

LP-10

LIGHTING PANEL FOR DGT-I AREA

63

415

100.0

0.85

63.00

105.28

80

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

1.55

343

LP-11

LIGHTING PANEL FOR DGT-2 AREA

63

415

100.0

0.85

63.00

105.28

40

50.0

3.5

AL

1100

125

0.641

0.8218 0.0750

125

0.78

344

LP-12

LIGHTING PANEL FOR DMWT,


PWST & POWST AREA

63

415

100.0

0.85

63.00

105.28

200

70.0

3.5

AL

1100

150

0.443

0.5680 0.0740

150

2.74

CU =

0.00393

AL =

0.00403

Temperature co-efficient of resistance:

Formula used to calculate percentage voltage drop

Allowable voltage drop for Motor feeders :

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Reactance per
Ohm/Km

Resistance at
90C Ohm/Km

During starting

Efficiency (%)

340

Equipment Description

During running

Tag no.

Details of Cables (XLPE insulation)

Total Current
carrying capacity on
air at 90C (AMP)

Sl
no.

System voltage (V)

% Voltage drop

Unit (KW / A)

Power factor
(Cos)

Rating

Motor/ Feeder
Rating

3 x Full load current x (Resistance x Cos + Reactance x Sin ) x Length of cable in Metre
Supply voltage x 10
3 % during normal running
10 % during starting

Annex.-II
Page 38 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

ANNEXURE-III

Nominal Cross
Sectional area
Sq. MM

Max DC Resistance at Reactance


20C OHMS/KM
OHM/KM at
50Hz
Plain CU

AL

Multi Core

Current Rating(amp.)- XLPE insulated(Power, max


condct temp-90C)

In air (3/3.5 or 4 Core)

Laid in Ground(3/3.5 or 4
Core)

1.1 kV

CU

AL

CU

AL

1.5

12.1

18.1

0.107

17

13

21

16

2.5

7.41

12.1

0.0985

24

18

27

21

4.61

7.41

0.0927

36

31

43

34

3.08

4.61

0.0883

47

44

54

43

10

1.83

3.08

0.0837

62

59

72

57

16

1.15

1.91

0.0808

79

62

92

73

25

0.727

1.2

0.0805

108

84

119

94

35

0.524

0.868

0.0783

132

103

144

113

50

0.387

0.641

0.075

162

125

174

133

70

0.268

0.443

0.074

198

150

210

164

95

0.193

0.32

0.0724

240

194

252

196

120

0.153

0.253

0.0712

276

226

288

223

150

0.124

0.206

0.0716

318

257

324

249

185

0.0991

0.164

0.0718

366

297

360

282

240

0.0754

0.125

0.071

426

351

414

326

300

0.061

0.1

0.0705

480

455

462

367

400

0.047

0.0778

0.0704

546

530

510

418

500

0.0366

0.0605

0.0702

612

470

630

0.0283

0.0469

0.0698

707

529

800

0.0221

0.0367

1000

0.0176

0.0291

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Page 39 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

ANNEXURE-IV
LT MOTOR EFFICIENCY LIST (AS PER IS12615)
Rated Output

Nominal Efficiency

No of Pole

No of Pole 4
For eff 2

For eff 1

kW

Percent

Percent

0.37
0.55
0.75
1.10
1.50
2.20
3.70
5.50
7.50
9.30
11.00
15.00
18.50
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
125.00
132.00
160.00
180.00
200.00

66.0
70.0
73.0
76.2
78.5
81.0
84.0
85.7
87.0
87.7
88.4
89.4
90.0
90.5
91.4
92.0
92.5
93.0
93.6
93.9
94.4
94.7
94.7
95.0
95.0
95.0

73.0
78.0
82.5
83.8
85.0
86.4
88.3
89.2
90.1
91.5
91.0
91.5
92.2
92.5
93.2
93.6
93.9
94.2
94.7
95.0
95.2
95.5
95.5
95.8
95.8
95

Contractor Doc. No. : A4-10053 -12-04-VI


NTPC Doc. No. : 0260-189-00-PVE-W-013

Annex.-IV_Motor Eff.
Page 40 of 46

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

ANNEXURE-V
A. SPACE HEATER CABLE FOR DRIVE OF 30 KW & ABOVE

Sl
No.

Space Heater For Drive


Tag No.

Description

Drive Rating
(KW)

Space Heater Cable Size &


Desription

Cable Length
(m)

B1-A

HDMF BLOWER - A

30

1 X 2 Core, 2.5 sq. mm. CU


cable

130

B1-B

HDMF BLOWER - B

30

1 X 2 Core, 2.5 sq. mm. CU


cable

130

B1-C

HDMF BLOWER - C

30

1 X 2 Core, 2.5 sq. mm. CU


cable

130

P1-A

CLARIFIED WATER FEED PUMPA

37

1 X 2 Core, 2.5 sq. mm. CU


cable

171

P1-B

CLARIFIED WATER FEED PUMPB

37

1 X 2 Core, 2.5 sq. mm. CU


cable

171

P1-C

CLARIFIED WATER FEED PUMPC

37

1 X 2 Core, 2.5 sq. mm. CU


cable

171

P1-D

CLARIFIED WATER FEED PUMPD

37

1 X 2 Core, 2.5 sq. mm. CU


cable

171

P8-A

RO FLUSHING PUMP

55

1 X 2 Core, 2.5 sq. mm. CU


cable

123

P8-B

RO FLUSHING PUMP

55

1 X 2 Core, 2.5 sq. mm. CU


cable

123

10

P9-A

DEGASSED WATER TRANSFER


PUMP

75

1 X 2 Core, 2.5 sq. mm. CU


cable

112

11

P9-B

DEGASSED WATER TRANSFER


PUMP

75

1 X 2 Core, 2.5 sq. mm. CU


cable

112

12

P9-C

DEGASSED WATER TRANSFER


PUMP

75

1 X 2 Core, 2.5 sq. mm. CU


cable

112

13

P12-A

RO HIGH PRESSURE PUMP

55

1 X 2 Core, 2.5 sq. mm. CU


cable

87

14

P12-B

RO HIGH PRESSURE PUMP

55

1 X 2 Core, 2.5 sq. mm. CU


cable

87

15

P12-C

RO HIGH PRESSURE PUMP

55

1 X 2 Core, 2.5 sq. mm. CU


cable

87

16

P4-A

FILTER BACKWASH PUMP

132

1 X 2 Core, 2.5 sq. mm. CU


cable

185

17

P4-B

FILTER BACKWASH PUMP

132

1 X 2 Core, 2.5 sq. mm. CU


cable

185

18

P4-C

FILTER BACKWASH PUMP

132

1 X 2 Core, 2.5 sq. mm. CU


cable

185

19

P7-A

RO-I CLEANING PUMP

132

1 X 2 Core, 2.5 sq. mm. CU


cable

120

20

P7-B

RO-I CLEANING PUMP

132

1 X 2 Core, 2.5 sq. mm. CU


cable

120

21

P3-A

FILTER FEED PUMP-A

180

1 X 2 Core, 2.5 sq. mm. CU


cable

161

Contractor Doc. No. : A4-10053 -12-13-VI


NTPC Doc. No. : 0260-189-00-PVE-U-001

Annex.-V

CONTRACTOR'S NAME : ION EXCHANGE ( INDIA) LIMITED


PROJECT / PACKAGE : NTECL POWER PROJECT / DESALINATION PLANT PACKAGE

22

P3-B

FILTER FEED PUMP-B

180

1 X 2 Core, 2.5 sq. mm. CU


cable

161

23

P3-C

FILTER FEED PUMP-C

180

1 X 2 Core, 2.5 sq. mm. CU


cable

161

24

P3-D

FILTER FEED PUMP-D

180

1 X 2 Core, 2.5 sq. mm. CU


cable

161

25

P22-A

WASTE DISPOSAL PUMP

200

1 X 2 Core, 2.5 sq. mm. CU


cable

188

26

P22-B

WASTE DISPOSAL PUMP

200

1 X 2 Core, 2.5 sq. mm. CU


cable

188

27

P6-A

RO-I BOOSTER PUMP

90

1 X 2 Core, 2.5 sq. mm. CU


cable

95

28

P6-B

RO-I BOOSTER PUMP

90

1 X 2 Core, 2.5 sq. mm. CU


cable

104

29

P6-C

RO-I BOOSTER PUMP

90

1 X 2 Core, 2.5 sq. mm. CU


cable

112

30

P5-A

RO HIGH PRESSURE PUMP-A

730

1 X 2 Core, 2.5 sq. mm. CU


cable

110

31

P5-B

RO HIGH PRESSURE PUMP-B

730

1 X 2 Core, 2.5 sq. mm. CU


cable

110

32

P5-C

RO HIGH PRESSURE PUMP-C

730

1 X 2 Core, 2.5 sq. mm. CU


cable

110

R3

B. CABLE FOR 220V DC SUPPLY FROM DCFB

Sl
No.

DC Control Cable

DC Cable Size & Desription

Cable Length
(m)

FOR 415V LT SWITCHGEAR

2 Core, 2.5 sq. mm. CU cable

25

FOR 415V MOTORISED VALVE BOARD MCC

2 Core, 2.5 sq. mm. CU cable

25

Contractor Doc. No. : A4-10053 -12-13-VI


NTPC Doc. No. : 0260-189-00-PVE-U-001

Annex.-V

SAMPLE CALCULATION FOR THE FILTER FEED PUMP P3-A


DESCRIPTION
SYSTEM VOLTAGE
RATING OF MOTOR
FULL LOAD POWER FACTOR

UNIT

VALUES

VOLTS

415

KW

180

As per Load List - Filter Feed Pump P3

COS

0.91

As per Motor Datasheet Approved

SIN

0.41
95.8%

As per Motor Datasheet Approved

AMPER

287.26

KW * 1000
1.732 * VOLTAGE*PF*EFFICIENCY

EFFICIENCY OF MOTOR
RATED FULL LOAD CURRENT OF
MOTOR
DERATING FACTOR FOR LYING

0.598

NOMINAL CURRENT FOR SELECTION


OF CABLE
SELECTED CABLE SIZE
RATED CURRENT CAPACITY FOR
CABLE
NO OF PARALLEL RUN FROM MCC TO
MOTOR
LENGTH OF CABLE FROM MCC
RESISTANCE AT 20 DEG CEL OF
CABLE
REACTANCE AT 20 DEG CEL OF
CABLE
TEMPRETURE CO-EFFICIENT OF
RESISTANCE

480.36

AMPER

297

No.

Meters

161

Ohms/KM

0.164

AS PER Annx-3

Ohms/KM

0.0718

AS PER Annx-3

Ohms/KM

0.2110

ACTUAL RESISTANCE CABLE AT 90


DEG CEL

Ohms

0.0170

ACTUAL REACTANCE CABLE AT 70


DEG CEL

Ohms

0.0718

2.14

COS

0.20

SIN

0.98

7.82

VOLTAGE DROP DURING STARTING

RATED FULL LOAD CURRENT


DERATING FACTOR

3C X 185

RESISTANCE CABLE AT 70 DEG CEL

MOTOR STARTING POWER FACTOR

AS PER SPECIFICATION

Sq. MM

0.00409

VOLTAGE DROP DURING RUNNING

FORMULA USED / REFERANCE

AS PER Annx-3

For Aluminium Cables


Resis at 20

* ( 1 + (90-20) * Temp co-eff of conductor))

Length of Cable * Resis at 90 Deg Cel


1000 * No. of Runs
Length of Cable * Reactance of Cable
1000 * No. of Runs
Formula - A

Formula - B

During Running
Voltage drop in % =

Sqrt (3) x IFL x L x ( R COS + X SIN )


KV x 10000 x N.R

Formula A

Sqrt (3) x IST x L x ( R COS + X SIN )


KV x 10000 x N.R

Formula B

During Starting
Voltage drop in % =

where
IFL =
L=
R=
X=
N.R =

Full load current in amperes under steady state condition.


Length of cable in meters
Resistance of cable at 90oC in ohm/ KM
Reactance of cable at 50 Hz in ohm/KM.
Number of Runs

COS = Power Factor during running & Starting


IST = Starting current, which is 7.2 times the full load Current.

o-eff of conductor))