Вы находитесь на странице: 1из 292

PLANTA DE RESERVA FRA

DE GENERACIN DE ETEN S.A

PROYECTO
PROJECT

RESERVA FRA ETEN


CONTRATISTA
CONTRACTOR

TTULO
TITLE

COORDINACIN PROTECCIONES
N DE DOCUMENTO PROYECTO
PROJECT DOCUMENT N

RFE-1-YE_-EEC-IDO-001

REV
FECHA
DATE

20-11-2014

EDITADO PARA
ISSUED FOR

PARA DISEO

JMM

PRV

JSA

REALIZADO
DONE BY

REVISADO
CHECKED BY

APROBADO
APPROVED BY

ESTE DOCUMENTO CONTIENE INFORMACIN PROPIETARIA Y NO PUEDE SER DUPLICADO, PROCESADO O CEDIDO A TERCEROS PARA UN USO DISTINTO AL DE
ESTE PROYECTO Y EL OBJETO PARA EL QUE HA SIDO PREVISTO SIN LA AUTORIZACIN ESCRITA DE COBRA.
THIS DOCUMENT CONTAINS PROPIETARY INFORMATION AND CAN NOT BE DUPLICATED, PROCESSED OR DISCLOSED TO THIRD PARTIES FOR ANY USE OTHER
THAN THIS PROJECT AND THE PURPOSE FOR WHICH IT IS INTENDED FOR WITHOUT THE WRITTEN CONSENT OF COBRA.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 2 de/of 288

CONTROL DE MODIFICACIONES/CHANGE LOG


Revisin

Fecha

Modificaciones

Revision

Date

Modifications

20/11/14

EDICIN INICIAL

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 3 de/of 288

NDICE
1.

OBJETO ............................................................................................................................. 5

2.

REFERENCIAS ................................................................................................................... 6

3.

DATOS DE PARTIDA ......................................................................................................... 8


3.1.

CARACTERSTICAS DE LOS EQUIPOS .............................................................. 8

3.1.1.

RED DE 220 KV .................................................................................................... 8

3.1.2.

TRANSFORMADOR PRINCIPAL .......................................................................... 8

3.1.3.

TRANSFORMADOR AUXILIAR ............................................................................. 9

3.1.4.

GENERADORES ................................................................................................... 9

3.1.5.

TRANSFORMADORES M.T./M.T. ....................................................................... 10

3.1.6.

TRANSFORMADORES M.T./B.T......................................................................... 10

3.1.7.

MOTORES DE M.T.............................................................................................. 11

3.1.8.

CARGAS DE B.T. ................................................................................................ 12

3.1.9.

GENERADOR DIESEL DE EMERGENCIA.......................................................... 12

3.1.10. LNEA DE TRANSMISIN ................................................................................... 12


3.1.11. CABLES DE MEDIA Y BAJA TENSIN............................................................... 12
4.

5.

SETTINGS RELS DE PROTECCIN ............................................................................. 14


4.1.

GE MULTILIN T60 ............................................................................................... 14

4.2.

GE MULTILIN F650 ............................................................................................. 16

4.3.

50GE MULTILIN 339 ........................................................................................... 21

4.4.

GE MULTILIN 350 ............................................................................................... 23

CRITERIOS PARA AJUSTE Y COORDINACIN DE PROTECCIONES. SISTEMA DE


MEDIA TENSIN. ............................................................................................................. 26
5.1.

ACOMETIDA DESDE TRANSFORMADOR AUXILIAR ........................................ 26

5.2.

ACOMETIDA DESDE GENERADOR AUXILIAR ................................................. 28

5.3.

MEDIDA DE BARRA ............................................................................................ 29

5.4.

TRANSFORMADOR DE AISLAMIENTO (LCI) .................................................... 29

5.5.

TRANSFORMADOR DE EXCITACIN ............................................................... 30

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

6.

7.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 4 de/of 288

5.6.

TRANSFORMADORES DE DISTRIBUCIN DE MT/BT...................................... 31

5.7.

TRANSFORMADORES DE MT/MT MOTORES DE MT ................................... 32

CRITERIOS PARA AJUSTE Y COORDINACIN DE PROTECCIONES. SISTEMA DE


BAJA TENSIN. ............................................................................................................... 35
6.1.

ACOMETIDAS ..................................................................................................... 35

6.2.

ACOPLAMIENTO DE BARRAS ........................................................................... 36

6.3.

ACOMETIDA GRUPO DIESEL DE EMERGENCIA ............................................. 37

6.4.

MEDIDA DE BARRAS ......................................................................................... 38

6.5.

ALIMENTACIONES FEEDER .............................................................................. 38

6.6.

MOTORES CON MEDIDA DIRECTA................................................................... 39

ANEXOS ........................................................................................................................... 41

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

1.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 5 de/of 288

OBJETO

El objeto del presente documento es establecer los criterios para el ajuste y la coordinacin de
las protecciones elctricas del sistema elctrico de la Planta de Reserva Fra de Eten (Per), a
fin de establecer las caractersticas que debern tener los equipos.

El estudio se ha realizado con el programa de diseo, anlisis y simulacin de sistemas


elctricos ETAP Powerstation, de Operation Technology, Inc., versin 12.0.0C.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

2.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 6 de/of 288

REFERENCIAS

[1] ISA-REP: PE-REQU-ANTE-2011-D230 Anteproyecto de Ingeniera Subestacin Reque


220 kV y obras conexas
[2] Email

RFE-CPI-GE-EML-0070. de 2012-12-13 con datos de la red 220 kV.

[3] Doc. 401A6263 GE LOAD SUMMARY


[4] Diagram

105T6742 ONE LINE DIAGRAM GAS TURBINE

[5] RFE-1-YTU-EDU-IDO-300 Diagrama Unifilar General


[6] RFE-1-YTU-EDU-IDO-310 Diagrama Unifilar Cabinas 6,6 kV 1BBA51
[7] RFE-1-YTU-EDU-IDO-311 Diagrama Unifilar Cabinas 480V 1BFA51/53-BMA52
[8] RFE-1-YTU-EDU-IDO-303 Esquema unifilar simplificado baja tensin
[9] RFE-1-YTU-EDU-IDO-302 Unifilar de proteccion y medida
[10] RFE-1-BAT-EHP-IDO-001 HOJA DE DATOS TRANSFORMADOR PRINCIPAL
[11] RFE-1-BBT-EDA-SIE-003 Placa de caractersticas de Transformador Auxiliar
[12] RFE-1-BFT-EHP-CON-001 Hojas de datos Transformadores MT-BT
[13] RFE-1-YE_-ELC-IDO-001 Lista de Consumidores Electricos
[14] RFE-1-YE_-ECE-IDO-001 Clculos Elctricos
[15] RFE-1-MKA-ESO-WRT-002 Principal Protection scheme
[16] RFE-1-MKA-EEC-WRT-001 Protection Relay Settings, MV System
[17] RFE-1-MKA-EEC-WRT-002 LV Breaker Settings
[18] 106T0023 Generator Electrical Data

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 7 de/of 288

[19] C184 Protection Report_Planta de Etan_R0


[20]

PE-AM14-ETEN-D066

60-ETEN-PRB-2256-PE-A

Estudio

de

Coordinacin

de

Protecciones de Lnea 220 kV y Subestacin Reque 220 kV


[21] 726191_607M_MDS_- Atomizing Air, Motor Information
[22] 726191_607M_SST_- Atomizing Air, Motor Safe Stall Time Curve
[23] 726191_607M_TSC_- Atomizing Air, Motor Speed-Torque Curve
[24] 726191_A35A_MDS_- Water Injection Pump, Motor Information
[25] IEEE C37.91-2008: IEEE Guide for Protecting Power Transformers.
[26] IEEE C37. 96-2000: IEEE Guide for AC Motor Protection.
[27] IEC 60255 Electrical relays.
[28] IEEE C37.102-2006: IEEE Guide por AC Generator Protection.
[29] IEEE 242-2001: IEEE Recommended Practice for Protection and Coordination of Industrial
and Commercial Power Systems.
[30] Manuales rels de proteccin

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

3.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 8 de/of 288

DATOS DE PARTIDA

3.1. CARACTERSTICAS DE LOS EQUIPOS

3.1.1.

Red de 220 kV

De acuerdo a lo establecido en la referencia [2], se considera la red de 220 kV definida por los
siguientes valores:

Tensin nominal ............................................................................................................ 220 kV

Puesta a tierra del neutro del sistema ................................................................. Rgido a tierra

Frecuencia nominal ......................................................................................................... 60 Hz

Intensidad de cortocircuito trifsica ................................................................................. 9,3 kA

Intensidad de cortocircuito monofsica ......................................................................... 10,5 kA

3.1.2.

Transformador principal

Los parmetros principales del transformador principal son los siguientes (ver [10] de la seccin
2):

Potencia nominal ............................................................................................... 225 / 300 MVA

Refrigeracin ..................................................................................................... ONAN / ONAF

Relacin de transformacin .................................................................................... 220 / 18 kV

Regulacin: ............................................................................................. en carga, 10 x 1,5%

Tensin de cortocircuito ................................................................................... 10% (225 MVA)

Grupo de conexin .......................................................................................................... YNd1

Neutro a tierra .................................................................................................. Conexin slida

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

3.1.3.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 9 de/of 288

Transformador auxiliar

Los parmetros principales del transformador auxiliar son los siguientes (ver [11] de la seccin
2):

Potencia nominal ............................................................................................... 8,5 / 11,5 MVA

Refrigeracin ..................................................................................................... ONAN / ONAF

Relacin de transformacin ..................................................................................... 18 / 6,9 kV

Regulacin: .............................................................................................. en vaco, 2 x 2,5%

Tensin de cortocircuito .................................................................................... 10% (8,5 MVA)

Grupo de conexin ......................................................................................................... Dyn11

Neutro a tierra ...................................................................... Mediante resist. De 796,74 (5A)

3.1.4.

Generadores

Los datos y curvas considerados para el generador de la turbina principal son los siguientes:

Generador Principal (ver [18] de la seccin 2)

Tensin nominal .............................................................................................................. 18 kV

Potencia aparente nominal ...................................................................................... 279,5 MVA

Potencia activa nominal ............................................................................................ 223,6 MW

Factor de potencia ........................................................................................................ 0,8 p.u.

Capacidad de potencia reactiva con cos =0,80 inductivo ....................................... 167 MVAr

Capacidad de potencia reactiva con cos =0,95 capacitivo ...................................... -86 MVAr

Reactancia subtransitoria saturada ............................................................................. 0,17 p.u.

Neutro a tierra ..........................................................................Mediante trafo-resist. (10Aprim)

Los datos del generador auxiliar se muestran a continuacin:


Generador Auxiliar (ver [20] de la seccin 2)

Tensin nominal ........................................................................................................... 6.600 V

Potencia aparente nominal .................................................................................... 10,549 MVA

Potencia activa nominal .............................................................................................. 8,44 MW

Factor de potencia ...................................................................................................... 0,80 p.u.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 10 de/of 288

Capacidad de potencia reactiva con cos =0,80 inductivo .......................................6,33 MVAr

Capacidad de potencia reactiva con cos =0,95 capacitivo ................................... -3,29 MVAr

Reactancia subtransitoria saturada ............................................................................. 0,16 p.u.

Neutro a tierra ........................................................................... Mediante resist. De 762 (5A)

3.1.5.

Transformadores M.T./M.T.

Se han empleado las siguientes caractersticas de los transformadores de los motores de MT


(ver [21] de la seccin 2):

Potencia nominal ......................................................................................................... 600 kVA

Refrigeracin ....................................................................................................................... AN

Relacin de transformacin ................................................................................ 6,6 / 0,505 kV

Regulacin de tensin ............................................................................................... En vaco

Regulacin en el primario .......................................................................................... 2x2,5%

Tensin de cortocircuito ...................................................................................................... 6 %

Grupo de conexin ............................................................................................................. Yd1

Neutro ............................................................................................................................ Aislado

Se han empleado las siguientes caractersticas del Transformador de Aislamiento del LCI:

Potencia nominal ..................................................................................... 5450-2725/2725 kVA

Configuracin........................................................................................................ 3 devanados

Refrigeracin ....................................................................................................................... AN

Relacin de transformacin .......................................................................... 6,6 / 2,08-2.08 kV

Tensin de cortocircuito ...................................................................................................... 6 %

Grupo de conexin ......................................................................................................... Dy1d1

Neutro ............................................................................................................................ Aislado

3.1.6.

Transformadores M.T./B.T.

Se han empleado las siguientes caractersticas de los transformadores de servicio de MT/BT (ver
[12] de la seccin 2):

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 11 de/of 288

Potencia nominal ....................................................................................................... 3500 kVA

Refrigeracin ....................................................................................................................... AN

Relacin de transformacin ................................................................................ 6,6 / 0,505 kV

Regulacin de tensin ............................................................................................... En vaco

Regulacin en el primario .......................................................................................... 2x2,5%

Tensin de cortocircuito .................................................................................................... 12 %

Grupo de conexin ......................................................................................................... Dyn11

Neutro a tierra .................................................................................................. Conexin slida

Se han empleado las siguientes caractersticas del transformador de excitacin:

Potencia nominal ....................................................................................................... 1500 kVA

Refrigeracin .................................................................................................................. ONAN

Relacin de transformacin .................................................................................. 6,6 / 0,45 kV

Tensin de cortocircuito ...................................................................................................... 6 %

Grupo de conexin ............................................................................................................. Yd1

Neutro ............................................................................................................................ Aislado

3.1.7.

Motores de M.T.

De acuerdo a la lista de consumidores de la planta, ver [13] de la seccin 2, se describen a


continuacin los motores de MT:
Pn

Un

Cos

Rend.

Utilizac.

[kW]

[V]

[%]

[%]

[%]

375

4000

92

93,22

85

375

4000

92

93,22

85

WATER INJECTION PUMP MOTOR 88WN-1

224

4000

92

93

55

WATER INJECTION PUMP MOTOR 88WN-2

224

4000

92

93

55

Motor
ATOMIZING AIR SYSTEM COMPRESSOR
DRIVE MOTOR 1
ATOMIZING AIR SYSTEM COMPRESSOR
DRIVE MOTOR 2

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 12 de/of 288

Estos motores irn alimentados, cada uno, a travs de un transformador reductor de M.T./M.T.
(ver seccin 3.1.5).

3.1.8.

Cargas de B.T.

Las cargas de BT vienen descritas en el documento [13] indicado en la seccin 2.

3.1.9.

Generador Diesel de Emergencia

La potencia neta en bornas del grupo motor-generador viene determinada por el grupo motor y
es la siguiente:

Potencia en emergencia-standby (ESP) ................................................... 2123 kW / 2654 kVA

Potencia continua (PRP) ........................................................................... 1873 kW / 2342 kVA

Los datos principales del generador de emergencia son:

Tensin nominal .............................................................................................................. 480 V

Potencia aparente nominal (calentamienteo 105C continuo) .................................... 2736 kVA

Factor de potencia ...................................................................................................... 0,80 p.u.

Reactancia subtransitoria saturada Xd ...................................................................... 0,11 p.u.

Velocidad giro del motor ............................................................................................ 1800 rpm

3.1.10. Lnea de Transmisin


Se considera la lnea de transmisin area desde la planta Reserva Fra Eten hasta S.E.
Reque, situada a 2.92 km mediante cable Narcissus (1272 MCM).

3.1.11. Cables de Media y Baja Tensin


Los cables de Media Tensin considerados son:
Carga
Acometida Tablero M.T.
Trafo Excitacin

Configuracin Cable

Material

Aislamiento

Longitud [m]

3x(4x(1x240mm2))

Cu

XLPE (6/10 kV)

40

3x(1x150mm2)

Cu

XLPE (6/10 kV)

40

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Carga

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 13 de/of 288

Configuracin Cable

Material

Aislamiento

Longitud [m]

Trafo LCI

3x(3x(1x240mm2))

Cu

XLPE (6/10 kV)

40

Tablero MT Black Start

3x(3x(1x300mm2))

Cu

XLPE (6/10 kV)

120

Generador Auxiliar (BS)

3x(3x(1x300mm2))

Cu

XLPE (6/10 kV)

20

3x(1x300mm2)

Cu

XLPE (6/10 kV)

20

Trafo M.T./B.T. (1BFT51)

3x(2x(1x185mm2))

Cu

XLPE (6/10 kV)

40

Trafo M.T./B.T. (1BFT53)

3x(2x(1x185mm2))

Cu

XLPE (6/10 kV)

40

Trafo Atomizing Air 1

3x70mm2

Cu

XLPE (6/10 kV)

100

Motor Atomizing Air 1

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Atomizing Air 2

3x70mm2

Cu

XLPE (6/10 kV)

100

Motor Atomizing Air 2

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Water Injection 1

3x70mm2

Cu

XLPE (6/10 kV)

70

Motor Water Injection 1

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Water Injection 2

3x70mm2

Cu

XLPE (6/10 kV)

70

Motor Water Injection 2

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Black Start

Adems, se han considerado los siguientes cables de Baja Tensin:


Carga

Configuracin Cable

Material

Aislamiento

Longitud [m]

Generador Diesel Emerg.

3x(6x(1x300mm2))

Cu

XLPE (0,6/1kV)

50

Cu

XLPE (0,6/1kV)

115

Sistema PCI

3x(2x(1x240mm2))+2x(
1x120mm2)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

4.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 14 de/of 288

SETTINGS RELS DE PROTECCIN

4.1. GE Multilin T60


Los settings de las funciones de proteccin del rel GE Multilin T60 son los siguientes:
Sobreintensidad temporizada (51PV)
Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.00 : 30.00] pu

0.001 pu

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C/ short-time inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t
Definite Time

N/A

Time dial

[0.00 : 600.00]

0.01

Reset type

[INSTANTANEOUS TIMED]

N/A

Voltage restraint

[DISABLED ENABLED]

N/A

Sobreintensidad instantnea (50P)


Descripcin

Rango

Step

Input type

[SRC 1 SRC 2 SRC 3 SRC 4]

N/A

Pickup level

[0.00 : 30.00] pu

0.001 pu

Trip time

[0.00 : 600.00]

0.01

Reset time

[0.00 : 600.00]

0.01

Sobreintensidad temporizada de tierra (51G)


Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.00 : 300.00] pu

0.001 pu

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C/ short-time inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t
Definite Time

N/A

Time dial

[0.00 : 600.00]

0.01

Reset type

[INSTANTANEOUS TIMED]

N/A

Sobreintensidad instantnea de tierra (50G)


Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 15 de/of 288

Descripcin

Rango

Step

Input type

[SRC 1 SRC 2 SRC 3 SRC 4]

N/A

Pickup level

[0.05 : 30.00] pu

0.001 pu

Trip time

[0.00 : 600.00]

0.01

Reset time

[0.00 : 600.00]

0.01

Sobrecorriente temporizada de neutro (51N)


Descripcin

Rango

Step

Input type

[SRC 1 SRC 2 SRC 3 SRC 4]

N/A

Pickup level

[0.000 : 30.000] pu

0.001 pu

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C/ short-time inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t
Definite Time

N/A

Trip dial

[0.00 : 600.00]

0.01

Reset type

[INSTANTANEOUS TIMED]

N/A

Proteccin diferencial porcentual (87)


Descripcin

Rango

Step

Differential pickup

[0.050 : 1.00]

0.001

Differential slope 1

[15% : 100%]

1%

Differential break 1
(Kneepoint 1)

[1.0 : 2.0]

0.001

Differential break 2
(Kneepoint 2)

[2.000 : 30.000]

0.001

Differential slope 2

[50% : 100%]

1%

Inrush inhibit function

[DISABLED ADAPT. TRAD. 2ND]

N/A

Inrush inhibit mode

[PER PHASE 2 OUT OF 3 AVERAGE]

N/A

Inrush inhibit level

[1.0% : 40.0%]

0.1%

Overexcitation inhibit
function

[DISABLED 5th]

N/A

Overexcitation inhibit
level

[1.0% : 40.0%]

0.1%

Proteccin diferencial instantnea (87)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 16 de/of 288

Descripcin

Rango

Step

Differential pickup

[2 : 30.00]

0.001

Descripcin

Rango

Step

Input type

[SRC 1 SRC 2 SRC 3 SRC 4]

N/A

Pickup Level

[0.80 : 4.00] pu

0.01 pu

Curves

[Definite Time Inverse A/B/C FlexCurve


A/B/C/D]

N/A

Multiplier

[0.05 : 600.00]

0.01

Time Reset

[0.0 : 1000.0] s

0.1 s

Descripcin

Rango

Step

Max voltage difference

[0 : 400000] V

1V

Max angle difference

[0 : 100] Deg

1 Deg

Max frequency diff.

[0.00 : 2.00] Hz

0.01 Hz

Max frequency
hysteresis

[0.00 : 0.10] Hz

0.01 Hz

Dead source selection

None
LV1 and DV2
DV1 and LV2
DV1 or DV2
DV1 Xor DV2
DV1 and DV2

N/A

Dead V1 max voltage

[0.00 : 1.25] pu

0.01 pu

Dead V2 max voltage

[0.00 : 1.25] pu

0.01 pu

Live V1 min voltage

[0.00 : 1.25] pu

0.01 pu

Live V2 min voltage

[0.00 : 1.25] pu

0.01 pu

Voltios por Hertz (24)

Sincronismo (25)

4.2. GE Multilin F650


Los settings para las funciones de proteccin del rel GE Multilin F650 son los siguientes:
Sobreintensidad temporizada (51PV)
Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 17 de/of 288

Descripcin

Rango

Step

Pickup level

[0.05 : 160.00]

0.01 A

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C/ long-time inverse / short-time
inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t
Definite Time
ANSI Extremely Inverse/ Moderately Inverse /
Normally Inverse / Very Inverse
Rectifier Curve

N/A

Time dial

[0.00 : 900.00]

0.01 s

Reset type

[INSTANTANEOUS TIME DELAYED]

N/A

Voltage restraint

[DISABLED ENABLED]

N/A

Sobreintensidad instantnea (50P)


Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.05 : 160.00]

0.01 A

Trip time

[0.00 : 900.00]

0.01 s

Reset time

[0.00 : 900.00]

0.01 s

Sobreintensidad instantnea de tierra (50G)


Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.05 : 160.00]

0.01 A

Trip time

[0.00 : 900.00]

0.01 s

Reset time

[0.00 : 900.00]

0.01 s

Sobreintensidad temporizada de neutro (51N)


Descripcin

Rango

Step

Input type

[PHASOR]

N/A

Pickup level

[0.05 : 160.00]

0.01 A

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C long-time inverse / short-time
inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t

N/A

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Descripcin

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 18 de/of 288

Rango

Step

Definite Time
Rectifier Curve
Time dial

[0.00 : 900.00]

0.01 s

Reset type

[INSTANTANEOUS TIME DELAYED]

N/A

Sobreintensidad instantnea de neutro (50N)


Descripcin

Rango

Step

Input type

[PHASOR]

N/A

Pickup level

[0.05 : 160.00]

0.01 A

Trip time

[0.00 : 900.00]

0.01 s

Reset time

[0.00 : 900.00]

0.01 s

Sobreintensidad temporizada de tierra (51G)


Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.05 : 160.00]

0.01 A

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C/ long-time inverse / short-time
inverse curve
IAC Inverse / Extremely Inverse / Very Inverse
I2t
Definite Time
Rectifier curve

N/A

Time dial

[0.00 : 900.00]

0.01 s

Reset type

[INSTANTANEOUS TIME DELAYED]

N/A

Sobreintensidad temporizada para sistemas de tierra sensible (51SG)


Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.005 : 16.000]

0.001 A

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C / long-time inverse / short-time
inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t

N/A

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Descripcin

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 19 de/of 288

Rango

Step

Definite Time
Rectifier curve
Time dial

[0.00 : 900.00]

0.01 s

Reset type

[INSTANTANEOUS TIME DELAYED]

N/A

Sobreintensidad instantnea para sistemas de tierra sensible (50SG)


Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Pickup level

[0.005 : 16.000]

0.001 A

Trip time

[0.00 : 900.00]

0.01 s

Reset time

[0.00 : 900.00]

0.01 s

Mnima tensin de fase(27P)


Descripcin

Rango

Step

Input mode

[PHASE-PHASE, PHASE-GROUND]

N/A

Pickup level

[3 : 300]

1V

Curve shape

[DEFINITE TIME INVERSE TIME]

N/A

Time dial

[0.00 : 900.00]

0.01 s

Minimum voltage

[0 : 300]

1V

Operation logic

[ANY PHASE, TWO PHASES, ALL PHASES]

N/A

Supervision by breaker

[DISABLED ENABLED]

N/A

Sobretensin de fase (59P)


Descripcin

Rango

Step

Pickup level

[3 : 300]

1V

Trip time

[0.00 : 900.00]

0.01 s

Reset time

[0.00 : 900.00]

0.01 s

Operation logic

[ANY PHASE, TWO PHASES, ALL PHASES]

N/A

Descripcin

Rango

Step

Dead bus voltage level

[0.00 : 300.00]

0.01 V

Live bus voltage level

[0.00 : 300.00]

0.01 V

Dead line voltage level

[0.00 : 300.00]

0.01 V

Live line voltage level

[0.00 : 300.00]

0.01 V

Max voltage difference

[2.00 : 300.00]

0.01 V

Max angle difference

[2.0 : 80.00]

0.1 Deg

Sincronismo (25)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 20 de/of 288

Descripcin

Rango

Step

Max frequency slip

[10 : 5000]

10 mHz

Breaker closing time

[0.01 : 600.00]

0.01 s

DL-DB function

[DISABLED ENABLED]

N/A

LL-DB function

[DISABLED ENABLED]

N/A

DL-LB function

[DISABLED ENABLED]

N/A

Descripcin

Rango

Step

Heating constant

[3.0 : 600.0]

0.1 min

Cooling constant

[1.00 : 6.00]

0.01 times Hc

Pickup level

[0.05 : 160.00]

0.01 A

Alarm level

[1.0 : 110.0]

0.1 %

Descripcin

Rango

Step

Pickup level

[0.05 : 160.00]

0.01 A

Curve shape

IEEE Inverse / Extremely Inverse / Very Inverse


IEC Curve A / B / C / long-time inverse / short-time
inverse
IAC Inverse / Extremely Inverse / Very Inverse
I2t
Definite Time
Rectifier curve

N/A

Time dial

[0.00 : 900.00]

0.01 s

Reset type

[INSTANTANEOUS TIME DELAYED]

N/A

Descripcin

Rango

Step

Input type

[PHASOR RMS]

N/A

Full load current

[0.10 : 10.00]

0.01 kA

Pickup level

[1.01 : 109.00]

0.01 x FLC

Trip time

[0.00 : 900.00]

0.01 s

Reset time

[0.00 : 900.00]

0.01 s

Imagen trmica (49)

Secuencia Negativa (46)

Rotor Bloqueado (48)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 21 de/of 288

Mximo nmero de arranques (66)


Descripcin

Rango

Step

Full load current

[0.5 : 10.0]

0.1 A

Supervision by breaker

[DISABLED ENABLED]

N/A

Minimum stop time

[0.0 : 900.0]

0.01 s

Number of start-ups

[0 : 10]

Restart time

[0 : 100]

1 min

Reset counter

[DISABLED ENABLED]

N/A

4.3. 50GE Multilin 339


Los settings para las funciones de proteccin del rel GE Multilin 339 son los siguientes:
Sobreintensidad temporizada (51P Mechanical Jam)
Descripcin

Rango

Step

MECH JAM PKP

[1.01 : 4.50] x FLA

0.01 x FLA

MECH JAM DELAY

[0.00 : 30.00] s

0.01 s

Sobreintensidad instantnea (50P Short Circuit)


Descripcin

Rango

Step

S/C PKP

[1.00 : 20.00] x FLA

0.01 x FLA

S/C Delay

[0.00 : 60.00]

0.01 s

Sobreintensidad instantnea de tierra (50G Ground Fault)


Descripcin

Rango

Step

GND ALARM PKP (para


CT con secundarios a 1A
5 A)

[0.03 : 1.00] x FLA

0.01 x FLA

GND ALARM PKP (para


CT con ratio 50:0.025)

[0.50 : 15.00] x FLA

0.01 x FLA

GND ALARM ON RUN

[0.00 : 60.00] s

0.01 s

GND ALARM ON START

[0.00 : 60.00] s

0.01 s

GND TRIP PKP (para CT


con secundarios a 1A
5 A)

[0.03 : 1.00] x FLA

0.01 x FLA

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 22 de/of 288

Descripcin

Rango

Step

GND TRIP PKP (para CT


con ratio 50:0.025)

[0.50 : 15.00] x FLA

0.01 x FLA

GND TRIP ON RUN

[0.00 : 5.00] s

0.01 s

GND TRIP ON START

[0.00 : 10.00] s

0.01 s

Imagen trmica (49 Thermal Protection)


Descripcin

Rango

Step

START PROTECTION

[Off On Contact Input 1 to 10 Virtual Input


1 to 32 Remote Input 1 to 32 Logic Element 1
to 16]

N/A

LOCKED ROTOR
CURRENT

[2.0 : 11.0] x FLA

0.1 x FLA

SAFE STALL T COLD

[1.0 : 600.0]

0.1 s

THERMAL O/L CURVE

[Standard FlexCurve]

N/A

CURVE MULTIPLIER

[1 : 15]

THERMAL O/L PKP

[1.01 : 1.25] x FLA

0.01 x FLA

UNBALANCE K FACTOR

[0 : 19]

COOL TIME RUNNING

[1 : 1000] min

1 min

COOL TIME STOPPED

[1 : 1000] min

1 min

HOT / COLD RATIO

[0.01 : 1.00]

0.01

RTD BIAS FUNC

[Disabled Enabled]

N/A

RTD BIAS MINIMUM

[0 : 130] C

1C

RTD BIAS CENTER

[40 : 155] C

1C

RTD BIAS MAXIMUM

[130 : 250] C

1C

THERMAL ALARM FUNC

[Disabled Enabled]

N/A

THERMAL ALARM PKP

[10 : 100] %

1%

AUTORESET TCU15%

[Auto Manual]

N/A

Secuencia Negativa (46 Current Unbalance)


Descripcin

Rango

Step

UNBAL ALARM PKP

[4% : 40%]

1%

UNBAL ALARM DELAY

[1.00 : 60.00] s

0.01 s

UNBAL TRIP PKP

[4% : 40%]

1%

UNBAL TRIP DELAY

[1.00 : 60.00] s

0.01 s

Rotor Bloqueado (48 Acceleration Time Trip)


Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 23 de/of 288

Descripcin

Rango

Step

ACCELERATION TIMER

[1.0 : 250.0] s

0.1 s

ACCEL T ON STOPPED

[1.0 : 250.0] s

0.1 s

ACCEL T ON LOW SPD

[1.0 : 250.0] s

0.1 s

(2 speed motor application)

Mximo nmero de arranques (66 Start Inhibit)


Descripcin

Rango

Step

THERMAL INHIBIT

[0 : 25] %

1%

START/HOUR LIMIT

[1 : 5]

TIME BETWEEN STARTS

[1 : 3600] s

1s

RESTART INHIBIT

[1 : 50000] s

1s

4.4. GE Multilin 350


Los settings para las funciones de proteccin del rel GE Multilin 350 son los siguientes:
Sobreintensidad temporizada (51P Phase Timed Overcurrent)
Descripcin

Rango

Step

PH TOC PKP

[0.04 : 20.00] x FLA

0.01 x FLA

PH TOC CURVE

ANSI Extremely Inverse/ Moderately Inverse /


Normally Inverse / Very Inverse
Definite Time
IEC Curve A / B / C/ long-time inverse / shorttime inverse
IAC Inverse / Extremely Inverse / Very Inverse /
Short
User Curve
FlexCurve A / FlexCurve B

N/A

PH TOC TDM

[0.50 : 20.00]

0.01

PH TOC RESET

[INSTANTANEOUS LINEAR]

N/A

Sobreintensidad instantnea (50P Phase Instanteneous Overcurrent)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 24 de/of 288

Descripcin

Rango

Step

PH IOC1/2 PKP

[0.05 : 20.00] x FLA

0.01 x FLA

PH IOC1/2 DELAY

[0.00 : 300.00] s

0.01 s

Sobreintensidad temporizada de tierra (51G Ground Timed Overcurrent)


Descripcin

Rango

Step

GND TOC PKP

[0.04 : 20.00] x FLA

0.01 x FLA

SENS GND TOC PKP

[0.005 : 3.000] x FLA

0.001 x FLA

GND TOC CURVE

ANSI Extremely Inverse/ Moderately Inverse /


Normally Inverse / Very Inverse
Definite Time
IEC Curve A / B / C/ long-time inverse / shorttime inverse
IAC Inverse / Extremely Inverse / Very Inverse /
Short
User Curve
FlexCurve A / FlexCurve B

N/A

GND TOC TDM

[0.50 : 20.00]

0.01

PH TOC RESET

[INSTANTANEOUS LINEAR]

N/A

Sobreintensidad instantnea de tierra (50G Ground Instantaneous Overcurrent)


Descripcin

Rango

Step

GND IOC PKP

[0.05 : 20.00] x FLA

0.01 x FLA

SENS GND IOC PKP

[0.005 : 3.000] x FLA

0.001 x FLA

GND IOC DELAY

[0.00 : 300.00] s

0.01 s

Sobreintensidad temporizada de neutro (51N Neutral Timed Overcurrent)


Descripcin

Rango

Step

NTRL TOC PKP

[0.05 : 20.00] x FLA

0.01 x FLA

NTRL TOC CURVE

ANSI Extremely Inverse/ Moderately Inverse /


Normally Inverse / Very Inverse
Definite Time
IEC Curve A / B / C/ long-time inverse / shorttime inverse
IAC Inverse / Extremely Inverse / Very Inverse /
Short
User Curve
FlexCurve A / FlexCurve B

N/A

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 25 de/of 288

Descripcin

Rango

Step

NTRL TOC TDM

[0.50 : 20.00]

0.01

NTRL TOC RESET

[INSTANTANEOUS LINEAR]

N/A

NTRL TOC DIRECTION

[Disabled Forward Reverse]

N/A

Sobreintensidad instantnea de neutro (50N Neutral Instantaneous Overcurrent)


Descripcin

Rango

Step

NTRL IOC PKP

[0.05 : 20.00] x FLA

0.01 x FLA

NTRL IOC DELAY

[0.00 : 300.00]

0.01 s

NTRL IOC DIRECTION

[Disabled Forward Reverse]

N/A

Mnima tensin de fase (27P Phase Undervoltage)


Descripcin

Rango

Step

PH UV PKP

[0.00 : 1.25] x VT

0.01 x VT

PH UV CURVE

[Definite Time Inverse Time]

N/A

PH UV DELAY

[0.1 : 600.0] s

0.1 s

PH UV PHASES

[Any One Any Two All Three]

N/A

PH UV MIN VOLTAGE

[0.00 : 1.25] x VT

0.01 x VT

Sobretensin de fase (59P)


Descripcin

Rango

Step

PH OV PKP

[0.00 : 1.25] x VT

0.01 x VT

PH OV DELAY

[0.1 : 600.0] s

0.1 s

PH OV PHASES

[Any One Any Two All Three]

N/A

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

5.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 26 de/of 288

CRITERIOS PARA AJUSTE Y COORDINACIN DE PROTECCIONES. SISTEMA


DE MEDIA TENSIN.

En general, el ajuste de protecciones est determinado por la capacidad y comportamiento de


los equipos:
El margen de tiempo ser de ~ 200 ms para la mxima corriente de falta.
Las curvas Tiempo-corriente no se superpondrn.

A continuacin se establecen los valores para la parametrizacin de las protecciones segn la


aplicacin de cada cabina. En el Anexo IV se incluyen las parametrizaciones de los rels de
proteccin para los equipos del sistema de MT. En el Anexo V se incluyen las curvas de
selectividad tiempo-corriente correspondiente a equipos de MT.

5.1. Acometida desde Transformador Auxiliar


Sobreintensidad temporizada de fases con frenado por tensin (51P)
Pickup level: ajustado al aproximadamente 130% (479,5 Alado_18kV y 1250 Alado_6.9kV) de
la corriente nominal del Transformador Auxiliar.
Time dial: 0,23 (requerido para una correcta proteccin del transformador y para una
coordinacin selectiva con las protecciones de aguas abajo)
Curve shape: IEC curve C.
Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado a unas 10 veces el valor de la corriente nominal del
Transformador Auxiliar para permitir su energizacin.
Trip time: 0,2 s para permitir selectividad con los protecciones del sistema de MT.
Sobreintensidad instantnea de tierra (50G)
Pickup level: ajustado a 5 Aprimario del transformador de corriente instalado en el neutro
del Transformador Auxiliar.
Time delay: 5 s

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 27 de/of 288

Sobreintensidad instantnea de tierra (51G)


Pickup level: ajustado a 3 Aprimario del transformador de corriente instalado en el neutro
del Transformador Auxiliar.
Time dial: 1
Curve Shape: IEC Curve B
Diferencial de transformador (87T)
Pickup: ajustado al 10% de la corriente nominal del transformador de corriente del
lado de AT.
Slope 1: 30 %
Break 1: Ajustado a 2 pu.
Break 2: Ajustado a 3,7 pu.
Slope 2: 85 %
Inrush Inhibit Function: Adapt.
Inrush Inhibit Mode: 2 out of 3
Inrush Inhibit Level: 20 %
Overexcitation Inhibit Function: 5th
Overexcitation Inhibit Level: 20 %
Proteccin de Voltios por Hercios (24)
Pickup level: ajustado al aproximadamente 110% de la relacin V/Hz nominal del
Transformador Auxiliar.
Time dial: 0,8
Curve shape: Inverse A
Time reset: 600 s.
Proteccin de sincronismo (25)
Fuente de tensin V1: Lado 18 kV
Fuente de tensin V2: Lado 6,6 kV
Mx Diferencia de Tensin: 8% de la tensin nominal
Mx Diferencia de ngulo: 12 Deg
Mx Diferencia de Frecuencia: 0,20 Hz

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 28 de/of 288

Mx Histresis de Frecuencia: 0,03 Hz


Seleccin de fuente de barra muerta: LV1 and DV2
Mx Tensin barra V1 muerta: 30% de la tensin nominal
Mx Tensin barra V2 muerta: 30% de la tensin nominal
Mn Tensin barra V1 viva: 70% de la tensin nominal
Mn Tensin barra V2 viva: 70% de la tensin nominal
Esta proteccin actuar como una verificacin de sincronismo, o synchrocheck, para
realizar una sincronizacin segura en el interruptor de servicios auxiliares desde el
sistema de sincronizacin ubicado en el Black Start.

5.2. Acometida desde Generador Auxiliar


Sobreintensidad temporizada de fases con frenado por tensin (51P)
Pickup level: ajustado al mismo nivel (aproximadamente) que la proteccin
parametrizada en el interruptor de salida del Black Start. 1050 Aprimario.
Time dial: 0,25 de forma que permita una selectividad con la acometida desde el
Transformador Auxiliar y permita la energizacin del Transformador de Aislamiento
(LCI).
Curve shape: IEC curve C.
Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado a 7500 Aprimario para permitir la energizacin del Transformador
de Aislamiento (LCI).
Trip time: 0,17 s de forma que permita la energizacin del Transformador de
Aislamiento (LCI).
Sobreintensidad instantnea de tierra (50SG)
Pickup level: ajustado al mismo nivel que la proteccin parametrizada en el interruptor
de salida del Black Start. 3 Aprimario.
Time delay: ajustado al mismo nivel que la proteccin parametrizada en el interruptor
de salida del Black Start. 0,1 s

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 29 de/of 288

Sobreintensidad temporizada de tierra (51SG)


Pickup level: ajustado al mismo nivel que la proteccin parametrizada en el interruptor
de salida del Black Start. 2 Aprimario.
Time dial: ajustado al mismo nivel que la proteccin parametrizada en el interruptor de
salida del Black Start. 0,8 s
Curve shape: Tiempo Definido.

5.3. Medida de Barra


Mnima tensin de fase(27P)
Pickup level: ajustado al 90% Un del sistema de MT (para disparar los motores del
sistema de MT).
Time dial: 0,5 s.
Sobretensin de fase (59P)
Pickup level: ajustado al 110% Un del sistema de MT.
Trip time: 2 s.

Esta funcin de proteccin, nicamente generar una ALARMA.

5.4. Transformador de Aislamiento (LCI)


Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado a unas 10 veces el valor de la corriente nominal del
transformador de corriente para permitir la energizacin del Transformador de
Aislamiento (LCI).
Trip time: 0,12 s
Sobreintensidad temporizada de fases con frenado por tensin (51P)
Pickup level: ajustado al 100 % de la corriente nominal del Transformador de
Aislamiento de forma que permita la operacin de ste y a su vez lo protega frente a
la curva de daos del transformador.
Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 30 de/of 288

Time dial: el valor requerido para tener selectividad con la energizacin del
transformador (valor de referencia: 0,8 s).
Curve shape: IEC Curve C.
Sobreintensidad instantnea de tierra (50G)
Pickup level: ajustado al 3

Aprimario

para mantener selectividad con las protecciones de

la acometida del Transformador Auxiliar y la acometida del Black Start.


Trip time: 0,08 s
Sobreintensidad temporizada de tierra (51G)
Pickup level: ajustado al 2

Aprimario

para mantener selectividad con las protecciones de

la acometida del Transformador Auxiliar y la acometida del Black Start.


Time dial: 0,7 s

Curve shape: Tiempo Definido

5.5. Transformador de Excitacin


Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado a unas 22 veces el valor de la corriente nominal del
transformador de corriente para permitir la energizacin del Transformador de
Excitacin.
Trip time: 0,12 s
Sobreintensidad temporizada de fases con frenado por tension (51P)
Pickup level: ajustado al 114 % de la corriente nominal del Transformador de
Aislamiento de forma que permita la operacin de ste y a su vez lo protega frente a
la curva de daos del transformador.
Time dial: el valor requerido para tener selectividad con la energizacin del
transformador (valor de referencia: 1,2 s).
Curve shape: IEC Curve C.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 31 de/of 288

Sobreintensidad instantnea de tierra (50G)


Pickup level: ajustado al 3

Aprimario

para mantener selectividad con las protecciones de

la acometida del Transformador Auxiliar y la acometida del Black Start.


Trip time: 0,08 s
Sobreintensidad temporizada de tierra (51G)
Pickup level: ajustado al 2

Aprimario

para mantener selectividad con las protecciones de

la acometida del Transformador Auxiliar y la acometida del Black Start.


Time dial: 0,7 s

Curve shape: Tiempo Definido

5.6. Transformadores de Distribucin de MT/BT


Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado a unas 18 veces el valor de la corriente nominal del
transformador de corriente para permitir la energizacin del Transformador de
Distribucin.
Trip time: 0,15 s
Sobreintensidad temporizada de fases con frenado por tension (51P)
Pickup level: ajustado al 122 % de la corriente nominal del Transformador de
Distribucin de forma que permita la operacin de ste y a su vez lo protega frente a
la curva de daos del transformador.
Time dial: el valor requerido para tener selectividad con la energizacin del
transformador (valor de referencia: 0,5 s).
Curve shape: IEC Curve C.
Sobreintensidad instantnea de tierra (50G)
Pickup level: ajustado al 3

Aprimario

para mantener selectividad con las protecciones de

la acometida del Transformador Auxiliar y la acometida del Black Start.


Trip time: 0,08 s

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 32 de/of 288

Sobreintensidad temporizada de tierra (51G)


Pickup level: ajustado al 2

Aprimario

para mantener selectividad con las protecciones de

la acometida del Transformador Auxiliar y la acometida del Black Start.


Time dial: 0,7 s

Curve shape: Tiempo Definido

5.7. Transformadores de MT/MT Motores de MT

El ajuste de las proteccin para este tipo de salidas se ha realizado de acuerdo a la


documentacin facilitada por GE ([21] al [24]) indicada en la seccin 2 y a experiencias previas
en motores similares. Debido a la falta de informacin facilitada por GE, los ajustes se han
parametrizado de manera conservadora pudindose, de esta manera, producirse disparos
intempestivos. A pesar de haberse diseado de manera conservadora, estos ajustes de debern
verificar durante la Puesta En Marcha de los Motores de Media Tensin.
Sobreintensidad instantnea de fase (50P Short Circuit)
Pickup level: ajustado a 7 veces la corriente nominal en el primario de los
transformadores de corriente de fase de manera que permita la energizacin del
transformador de MT/MT junto con el motor.
Trip time: 0,03 s -valor de referencia- para permitir la energizacin del transformador y
proteger los cables de Media Tensin.
Proteccin de atasco mecnico (Mechanical Jam)
Pickup level: ajustado al mnimo.
Delay: ajustado a 0,5 ms (Water Injection Pump Motor) o 1 s (Atomizing Air Motor).
Sobreintensidad instantnea de tierra (50G Ground Fault)
Alarm: Deshabilitado.
Trip Pickup level: ajustado al 3 Aprimario para mantener selectividad con las protecciones
de la acometida del Transformador Auxiliar y la acometida del Black Start.
Trip time on run: 0,08 s
Trip time on start: 0,5 s

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 33 de/of 288

Imagen Trmica (49 Thermal Protection)


Start Thermal Protection: OFF
Locked Rotor Current: 6,5 veces la corriente nominal del motor
Safe Stall T cold: Acorde a la documentacin facilitada por GE.
Thermal O/L curve: Standard
Curve Multiplier: 3 (Water Injection Pump Motor) & 8 (Atomizing Air Motor)
Thermal O/L Pickup: 1,10
Unbalance Factor: 5
Cool Time Running: 15 minutos
Cool Time Stopped: 30 minutos
Hot/Cold Ratio: 0,85 (Water Injection Pump Motor) & 0,65 (Atomizing Air Motor)
RTD Bias Func: Habilitado
RTD Minimum: 25 C
RTD Center: 90 C
RTD Maximum: 130 C
Thermal Alarm: Habilitado
Thermal Pickup: 90 %
Autoreset: Manual
Proteccin LR rotor bloqueado (48 Acceleration Time)
Trip time: Ajustado por debajo del Safe Hot Stall Time facilitado por el fabricante.
Secuencia Negativa (46 Current Unbalance)
Alarm Pickup level: ajustado al 15% del FLA del motor.
AlarmTime dial: 5 s.
Trip Pickup level: ajustado al 20% del FLA del motor.
Trip Time dial: 10 s.
Mximo nmero de arranques (66 Start Inhibit)
Thermal Inhibit: deshabilitado
Start/hour Limit: 2 arranques por hora.
Time Between Starts: 600 s.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 34 de/of 288

Restart Inhibit: 120 s.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

6.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 35 de/of 288

CRITERIOS PARA AJUSTE Y COORDINACIN DE PROTECCIONES. SISTEMA


DE BAJA TENSIN.

En general, se aplicarn los siguientes criterios para la coordinacin:


El margen de tiempo ser de ~ 200 ms para la mxima corriente de falta.
Las curvas Tiempo-corriente no se superpondrn.

Para el ajuste de las protecciones es necesario conocer los valores de cortocircuito mnimo con
el fin de conocer el valor mnimo de corriente suficiente para operar los relevadores, segn se
observa en el Anexo VIII.-Clculo de cortocircuito mnimo, los valores de cortocircuito mnimo
estn por encima de los valores parametrizados en los correspondientes relevadores por lo
tanto, se garantiza la actuacin de las protecciones.

A continuacin se establecen los valores para la parametrizacin de las protecciones segn la


aplicacin de cada cabina. En el Anexo VI se incluyen las parametrizaciones de los rels de
proteccin para los equipos del sistema de BT.

En el Anexo VII se incluyen las curvas de selectividad tiempo-corriente correspondiente a


equipos de BT.

6.1. Acometidas

Las acometidas poseen rels indirectos modelo Multilin F650 de GE


Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado a unas 5,5 el valor de la corriente nominal del Transformador
de Distribucin.
Trip time: 0,25 s
Sobreintensidad temporizada de fases con frenado por tension (51P)
Pickup level: ajustado al 120 % de la corriente nominal del Transformador de

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 36 de/of 288

Distribucin de forma que permita la operacin de ste con una sobrecarga del 20% y
a su vez lo protega frente a la curva de daos del transformador. Las sondas de
temperatura darn una proteccin directa contra sobrecargas
Time dial: el valor requerido para tener selectividad con la energizacin del
transformador (valor de referencia: 0,5 s).
Curve shape: IEC Curve C, que es la misma que en MT y similar a la de los
interruptores de Baja Tensin de Schneider.
Sobreintensidad instantnea de tierra (50N)
Pickup level: ajustado a 10.000 Aprimario para mantener selectividad con las
protecciones aguas abajo.
Trip time: 2 s
Sobreintensidad temporizada de tierra (51N)

Fuera de servicio
Sobreintensidad instantnea de Neutro (50G)

Fuera de servicio
Sobreintensidad temporizada de Neutro (51G)
Pickup level: ajustado a 3750 A, por debajo del 50N
Curva IEEE Extremadamente Inversa
Time dial: el valor requerido para tener selectividad con la funcin 50N (15 s).

6.2. Acoplamiento de barras


Sobreintensidad temporizada de fases con frenado por tensin (51PV)
Pickup level: ajustado a un 80% nominal del transformador (In2).
Time dial: el requerido para tener selectividad cronomtrica con la cabina de
acometida.
Curve shape: IEC Curve C.
Sobreintensidad instantnea de fase (50P)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 37 de/of 288

Pickup level: ajustado a 3,5 veces el valor de la corriente nominal del transformador
(In2).

Trip time: 0,15 s -valor de referencia-.


Sobreintensidad instantnea de tierra (50N)
Pickup level: ajustado a 2000 Aprimario para mantener selectividad con las protecciones
aguas abajo.
Trip time: 1 s
Sobreintensidad temporizada de tierra (51N)

Fuera de servicio

6.3. Acometida Grupo Diesel de Emergencia


Sobreintensidad instantnea de fase (50P)
Pickup level: ajustado al 75% de la corriente de cortocircuito del grupo. Deber ser
selectivo con el interruptor del generador
Trip time: 0,3 s.
Sobreintensidad temporizada de fases con frenado por tensin (51PV)
Pickup level: ajustada al 120 % de la corriente nominal del grupo.
Time dial: Valor requerido para selectividad cronomtrica (valor referencia 0,5 s).
Curve shape: IEC Curve C.
Sobreintensidad temporizada de neutro (51N)
Pickup level: ajustado al 20 % de la corriente nominal del GDE.
Time dial: 0,33 s, valor requerido para selectividad cronomtrica.
Curve shape: IEC Curve C.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 38 de/of 288

6.4. Medida de Barras


Mnima tensin de fase (27P)
Pickup level: ajustado al 70% Un para que active el sistema automatico de
transferencia.
Time dial: 2 s.
Logic: Any Phase.
Sobretensin de fase (59P3)
Pickup P3: ajustado al 110% Un.
Delay P3: 2 s.
Logic P3: All Phases.
Esta function de proteccin, nicamente generar una Alarma.

6.5. Alimentaciones Feeder

Para los interruptores marca Schneider y modelos de reveladores electrnicos.


Proteccin sobrecargas (L)
Long Time Pickup: ajustado de tal forma que sea selectiva con la proteccin de la
acometida y permitiendo el consumo nominal de la carga.
Trip time: 2 s @ 6x Ir -valor de referencia- que se corresponde con 8 s @ 3x Ir para
otras marcas de interruptores. En todo caso tiene que permitir el arranque del mayor
motor con el resto de las cargas conectadas.
Curve shape: Es fija en los interruptores de Schneider
Proteccin selectiva de cortocircuito (S)
ST Pickup: ajustado de tal forma que sea selectiva con la proteccin de la acometida.
ST Band time: el valor requerido para asegurar una selectividad cronomtrica (valor
de referencia: 0,3 s). En todo caso tiene que permitir el arranque del mayor motor con
el resto de las cargas conectadas.
Proteccin instantnea de cortocircuito (I)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 39 de/of 288

Inst. Pickup: ajustado de tal forma que sea selectiva con la proteccin de la
acometida. En todo caso tiene que permitir el arranque del mayor motor con el resto
de las cargas conectadas.
Proteccin de defectos de tierra (G)
Deshabilitado si no es posible la coordinacin con las protecciones de fase aguas
abajo
Ground Pickup: ajustado a 1 veces la intensidad nominal.

Ground band: 0,5 s para subcuadros valor de referencia-

6.6. Motores con medida directa


Proteccin sobrecargas (L)
LT Pickup: ajustado al valor 105% del Full Load Current (FLC) del motor.
Trip time: ajustado para permitir el arranque del motor al 80% y a su vez proteger el
motor segn su curva trmica.
Curve shape: IEC Curve B (Compresores) IEC Curve C (Ventiladores torres).
Proteccin selectiva de cortocircuito (S)
ST Pickup: ajustado de tal forma que sea selectiva con la proteccin de la acometida.
ST Band time: el valor requerido para asegurar una selectividad cronomtrica (valor
de referencia: 0,36 s).
Proteccin instantnea de cortocircuito (I)
Inst. Pickup: ajustado a 12 veces la intensidad.
Proteccin de defectos de tierra (G)
Ground Pickup: ajustado a 0,2 veces la intensidad nominal.
Ground band: 0,1 s valor de referencia-

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 40 de/of 288

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

7.

COORDINACIN PROTECCIONES

Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 41 de/of 288

ANEXOS

Anexo I: C184 Protection Report_Planta de Etan_R0

Anexo II: PE-AM14-ETEN-D066 - 60-ETEN-PRB-2256-PE-A Estudio de Coordinacin de


Protecciones de Lnea 220 kV y Subestacin Reque 220 kV

Anexo III: RFE-1-MKA-EEC-WRT-001-REV0 Protection Relay Settings, MV System

Anexo IV: Listado ajuste de protecciones elctricas sistema de MT

Anexo V: Curvas de selectividad tiempo-corriente sistema de MT

Anexo VI: Listado ajustes de protecciones elctricas sistema de BT

Anexo VII: Curvas de selectividad tiempo-corriente sistema de BT

Anexo VIII: Clculo Mnima Corriente Cortocircuito

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

ANEXO I

COORDINACIN PROTECCIONES
Rev. A

RFE-1-YE_-EEC-IDO-001

Pg/Page 42 de/of
288

ANEXO I:

ESTUDIO PROTECCIONES BLOQUE DE POTENCIA

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

C184 Protective Relaying Setting Report to:


GE Energy Global Projects Organization for
PLANTA DE ETEN

ETAN
IPS 726191
Chiclayo, Peru

Generators : 761X201
Prepared by:
Mike Reichard, P.E.
GE - ENERGY CONSULTING
Revision 0
26 August 2013

GE Energy

Foreword
This document was prepared by General Electric International, Inc. through its Energy
Consulting (EC) department in Schenectady, NY. It is submitted to GE Power Plant
Systems Department (GE PPSD). Technical and commercial questions and any
correspondence concerning this document should be referred to:

Mike Reichard
Energy Consulting
General Electric International, Inc.
Building 53, Room 302G
Schenectady, New York 12345
Phone: (518) 385-2299
Fax: (518) 385-5703
E-mail: michael.reichard@ge.com

Revision List
Revision
0

Date
26AUG13

Change
New Document

Effected Pages
all

Author
M.L. Reichard

GE Energy

Legal Notice
This report was prepared by General Electric International, Inc.s Energy Consulting (EC)
department as an account of work sponsored by GE GPO for the PP12 Project. Neither
GE GPO nor EC, nor any person acting on behalf of either:
1. Makes any warranty or representation, expressed or implied, with respect to the
use of any information contained in this report, or that the use of any information,
apparatus, method, or process disclosed in the report may not infringe privately
owned rights.
2. Assumes any liabilities with respect to the use of or for damage resulting from the
use of any information, apparatus, method, or process disclosed in this report.

Data Sources
1
2
3
4
5
5

Name
GTG One-line Diagram
GTG Elementary Diagram
GTG Generator Electrical Datasheet
GTG Excitation System Model Constants
Eten 18kV-SC Complete Report.pdf
Metering and protection SLD

Source
GE
GE
GE
GE
cobra
cobra

Drawing Number
105T6742
106T3974
106T0023
106T4923
RFE-1-YTU-EDUIDO-302-REVD

Rev
C
D

GE Energy

Section Title

Relay

Primary/ Backup Generator Protection

GE G60A/B

Overall Differential Protection

GE T60U

Step-Up Transformer Protection

GE T60T

Generator Bus Protection

GE C60

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Phase Distance and Power Swing Detect Functions (ANSI Devices 21, 78)
A) System Data
281.25 MVAG

Generator:

18 kVG

220 kVS

System:

0.8 pf

26.5% X'dv

7,931 Amps minimum 3f fault @ angle

GSU Transformer: 225/300 MVA

kVpri = 220.0

YNd1

kVsec = 18
ZT =

ONAN/ONAF

-82.6

10.0% @ 225 MVAT,

X/R = 50

B) 21 Function Data
21 Function Ranges:

78 Function Ranges:

0.02 - 250.00 W PHS DIST REACH in steps of 0.01

0.050 - 30.000 pu V POWER SWING SUPV in steps of 0.001

30 to 90 PHS DIST RCA in steps of 1

0.10 - 500.00 W POWER SWING FWD REACH in steps of 0.01

30 to 90 PHS DIST COMP LIMIT in steps of 1

0.10 - 500.00 W POWER SWING QUAD FWD REACH MID/OUT

30 to 90 PHS DIST DIR RCA in steps of 1

40 to 90 POWER SWING FWD RCA in steps of 1

30 to 90 PHS DIST DIR COMP LIMIT in steps of 1

0.10 - 500.00 W POWER SWING REV REACH in steps of 0.01

0.02 - 250.00 W PHS DIST QUAD RGT BLD in steps of 0.01

0.10 - 500.00 W POWER SWING QUAD REV REACH MID/OUT

30 to 90 PHS DIST QUAD RGT BLD RCA in steps of 1

40 to 90 POWER SWING REV RCA in steps of 1

0.02 - 250.00 W PHS DIST QUAD LFT BLD in steps of 0.01

40 to 140 POWER SWING OUTER/MIDDLE/INNER LIMIT ANGLE

30 to 90 PHS DIST QUAD LFT BLD RCA in steps of 1

0.10 - 500.00 W POWER SWING OUTER/INNER RGT/LFT BLD

0.050 - 30.000 pu PHS DIST Z SUPV in steps of 0.001

0.000 - 65.535 s POWER SWING PICKUP/RESET DELAY (1/4)

0.000 - 5.000 pu PHS DIST Z VOLT LEVEL in steps of 0.001


0.000 - 65.535 s PHS DIST Z DELAY in steps of 0.001

CT Ratio (CTR):

12,000 / 5

PT Ratio (PTR):

18,000 / 120 =

2,400 :1

CTR/PTR=

150.00 :1, Vsec =

16.00

120.0 V

delta VTs

C) Settings Calculations
1. Calculate impedances in relay ohms on generator base with the CT and VT at the generator terminals:
Transformer:

Zt = Z x (MVA G /MVA T )(kVsec/kV G ) 2 (kV G 2 /MVA G ) =


Zt secondary = Zt primary * (CTR/PTR) =

Generator:

kVG 2

Xg X ' dv Zbase X ' dv


MVA G

X'dv secondary = Zg primary * (CTR/PTR) = j


System:

kV sec
kVs

Zs

Ifault 3 kVpri

0.1440 ohms primary


2.30 W
@

88.9

0.3053 ohms primary


4.88 ohms secondary

Zs secondary = Zs primary * (CTR/PTR) =

0.1072 ohms primary


1.715 W

82.6

2. Backup distance relay (21) setting philosophy: Relay reach and time delay should be set to allow maximum generator
loading and coordinate with system line protection. The protection will be set for 200% of machine MVA rating at rated
power factor, with a 90 degree MTA. This will be a second zone function.
Zone 2 = 200% Generator MVA rating @ MTA =
15.36 W relay @
90 MTA
Zone 2 time delay =
0.8 sec
Generator load impedance @ rated (kVG2/MVAG) =
1.15 W primary
@
36.9
=
18.43 W relay
@
36.9

Section 1

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Backup Distance Protection, 21G60 (relay ohms)


X
25

20

15

10

0
-10

-5

10

15

20

-5

= F RCA

-10

21 G60

Section 1

Generator Capabilty Curve

G60_R0

Zt

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

3. Out-of-Step (78) Relay Setting Philosophy - the application follows the approach outlined in GE technical reference
GER-3179, Out-of-Step Protection for Generators. This approach utilizes two impedance relays (OUTER unit and INNER
unit) to track the impedance locus of the generator during an out-of-step swing. The objective is to detect that the
generator is going out of step and initiate separation from the system during the first swing. Traditionally, a 120
separation has been considered the criterion to define an out-of-step condition. The INNER unit is set at the points at
which the generator and system are 120 and 240 apart. The OUTER unit is set to avoid tripping on stable swings, and to
initiate separation when the generator voltage approaches 300 with respect to the system. This assures that the
maximum voltage angle across the breaker at the time that it opens will be 60 or less.
The impedance locus of most out-of-step swings passes through the generator step-up (GSU) transformer, or the
generator itself (relatively closer to the line-side terminals). For this reason, GER-3179 suggests that with the relay applied
at the generator terminals and polarized to look toward the system, the reverse reach into the machine should be two to
three times the generator transient reactance (X'dv). The forward reach into the system should extend well past the highvoltage terminals of the GSU, and forward reach settings typically fall in the range of one to two times the GSU leakage
impedance.
a. Zt+Zs =
4.01 W sec @
1.5Zt =
3.46 W sec @
b. Forward Reach (ZF) =

86 = F RCA
89
4.01 ohms sec.

c. Reverse Reach (ZR) = 2X'dv =

-9.77 ohms sec.


90 = R RCA

forward

O
Z

reverse

The line OC is the lateral reach of the relay. For


Figure A
B
the settings to be secure, the apparent impedance associated with an output equal to the rating
of the machine must be greater than OC.
ZAB / 2
ZAB = Zs + Zt + X'dv =

8.89 W

OC

tan( Z / 2)

d. Outer Right Blinder Reach (Z = 60) = OC[1+cos(RCA)] =

8.21 ohms secondary

e. Inner Right Blinder Reach (Z = 120) = OC[1+cos(RCA)] =

2.74 ohms secondary

f. Outer Left Blinder Reach (Z = 60) = OC[1+cos(RCA)] =

8.21 ohms secondary

g. Inner Left Blinder Reach (Z = 120) = OC[1+cos(RCA)] =

2.74 ohms secondary

h. Calculate the apparent impedance associated with rated load operation:


Impedance of rated load = kV2/MVAG =
1.152 W pri =

78 Settings are acceptable


18.43 W sec

I. 78 times(s) : 60 = 0.14
120 = 0.28
240 = 0.6
300 = 0.67
Delay 1 time interval between outer and inner characteristics (between 60 and 120) =
Delay 2 is not applicable for Two Step applications.
Delay 3 time interval of the inner characteristic (between 120 and 240) =
Delay 4 time interval between inner and outer characteristics (between 240 and 300) =
Es
1.0
1.0
1.0
1.0
1.0

puV @ 0
puV @ 0
puV @ 0
puV @ 0
puV @ 0

Eg
1.0
1.0
1.0
1.0
1.0

puV@60
puV@120
puV@180
puV@240
puV@300

0.14 s
0.32 s
0.07 s

delta V (voltage across breaker contacts)


1.0
puV @
-60
deg
1.73
puV @
-30
deg
2.0
puV @
0
deg
1.73
puV @
30
deg
1.0
puV @
60
deg

Both 21 and 78 functions are disabled during startup and blocked for VTFF.

Section 1

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

78 Protection (relay ohms)


X
6

0
-10

-8

-6

-4

-2

10

-2

-4

-6

-8

-10

-12
Zf

Section 1

Zr

Outer

Inner

60

120

G60_R0

X'dv

Zt

Zs

Swing Locus

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Critical clearing time is defined as the maximal fault duration for which the generator remains transiently stable during
power swings. Two dynamic simulations were conducted for a HV 3-Phase fault; one at the critical clearing time and one
quarter cycle later. Time intervals at 60, 120, 240 and 300 degrees between generator and system are calculated to insure
a loss-of-synchronism condition exists. Simulation assumes all units on line, all line in service. Note the Y-axis is the rotor
angle.

Section 1

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Differential Function (ANSI Device 87G)
A) Generator Data
Generator Data:
281.25 MVAG,
Generator Base Current:
9,021
B) Relay Data
87G Relay Ranges:
Pickup:
Slope:
Break 1:
Break 2:
CT Ratio (CTR):

12,000 / 5

18.00 kV,

0.8 pf

A
0.050 - 1.000 pu in steps of 0.001
1 - 100% in steps of 1%
1.00 - 1.50 pu in steps of 0.01
1.50 - 30.00 pu in steps of 0.01
2,400 :1

C) Settings Calculations
Relay Setting Philosophy: The 87G function provides primary phase fault
protection for the generator and should be set as sensitive as possible, yet
not trip for CT errors that can occur during an external fault. Slope 1 and
pickup of 10% and 0.1 per unit respectively are recommended for this
application. Break 1 should be set marginally above the machine rating.
Break 2 should be set lower than the saturation curve kneepoint and coordinate
with the maximum generator fault current contribution.
Slope 2 should be set at 80%.

Set 87G pickup:


Set 87G Slope 1:
Set 87G Break 1:
Set 87G Slope 2:
Set 87G Break 2:

0.1
10
1.15
80
4.00

pu
%
pu
%
pu

Generator fault current =


1/X"dv * generator base current
1/X"dv =
Gen fault current =
=

5.88 pu
53,064 A primary
4.42 pu CT rating

Figure 5-51 in G60 Instruction Manual


87G

Section 1

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Overload Protection (ANSI Device 51P)
A) Generator Data
Generator Data:
281.25 MVAG,
18.00 kV,
Generator Base kW Rating:
225 MW
IFG =
X"dv = 0.17
T"d = 0.026

2011 A, FL Field

IF =

567 A, NL Field

X'dv = 0.265

T'd = 0.77

Xdv = 2.39

Ta = 0.42

ZGSU =
B) Relay Data
51 Relay Ranges:

10.0%

0.8 pf

IFG / IF =
225

3.5

MVA

CT Ratio (CTR):

0.000 to 30.000 pu pickup range


0.00 to 600 TD multiplier range
12,000 / 5 =
2,400 :1

PT Ratio (PTR):

18,000 / 120 =

150.00 :1

C) Settings Calculations
Relay Setting Philosophy: This function is stator overload protection and is set to
pickup at 115% of rated current with an IEC Type B curve characteristic at the.TDM
to coordinate with C50.13-2005 Stator Winding Short-Time Thermal Limits.

Recommended 51P pickup (IPU) = IFL * 1.15 =


Curve Type:
Recommended Time Dial Multiplier =
Generator fault current @ 1.0 second (I) =
(per generator decrement curve)

10374
0.864
IEC
0.53
22732
9.47

Amperes
pu CT rating
B
Curve
Amperes
secondary amps

51P

Section 1

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Generator Stator Overload Protection


1000

100

T (seconds)

10

0.1

0.01
100

1,000

10,000

100,000

1,000,000

I (amperes)
Gen. Decrement

Section 1

51P

C50.13-2005 Stator Winding Short-Time Thermal Limits

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Generator Unbalance Functions (ANSI Devices 46A & 46T)
A) Generator Data
Generator Data:

281.25 MVAG,

18.00 kV,

Relay Full Load Current (IFL):

0.8 pf

9,021 Amperes
0.752 pu CT rating

Continuous Unbalanced Current (I2C) Capability: 8.0%


I22t Capability (KC): 10
B) Relay Data
46A Relay Ranges:

Pickup: 0.00 - 100.00% in steps of 0.01


Delay: 0.0 to 1000.0 seconds in steps of 0.1

46T Relay Ranges:

Pickup: 0.00 - 100.0% in steps of 0.01


K-value: 0.00 - 100.00 in steps of 0.01
TMIN/TMAX/K-Reset: 0.0 - 1000.0 seconds in steps of 0.1

CT Ratio (CTR):

12,000 / 5

2,400 :1

C) Settings Calculations
Relay Setting Philosophy:The 46A settings are calculated slightly below (70%)
the machines I22t capability. The 46T settings are calculated to operate
when the machine is operating at its full negative sequence current capability
to ensure tripping before damage to the stator occurs due to overheating.
Recommended 46A [STG2] Pickup Setting: 0.7 * I2C =
5.6%
Recommended 46A [STG2] Delay:
1 second
Recommended 46T [STG1] Pickup Setting: I2C =
8.0%
Recommended 46T [STG1] K-Value:
8.0
Recommended 46T [STG1] Min Operate Time:
0.001 seconds
Recommended 46T [STG1] Max Operate Time:
1000 seconds
Recommended 46T [STG1] K-Reset:
227 seconds

46A & 46T

Section 1

G60_R0

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Generator I22t Capacity vs Protection

1000.000

100.000

T (seconds)

10.000

1.000

0.100

0.010

0.001
0.01

0.1

10

100

I2 per unit

Generator

Section 1

46T

46A

Open-Phase I2

G60_R0

Rated Continuous I2

HV Gnd Fault I2

HV P-P Fault I2

10

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

D) Open Phase Calculations


EG

Simplified System :

TG

GE Energy

ES

Sequence Network - Open Phase :

Z1G

Z1S

EG= 1.0 0

ES
Z2G

Z2S

Z0G

Z0S

Sequence Network - Open Phase (reduced) :

Z1G
1.0 pu 0

kVSYSTEM =

220

MVAbase =

100

Ibase =

Z2G

Z2S

Z0G

Z0S

262.4 A

1. Generator impedance at rated output converted to base values:


281.25 MVA
0.8 pf
Z1GEN = 0.3556
pu @
36.87 =
pu * (MVAbase/MVAT) =
Z2GEN =
X2v =
0.170
Z0GEN =

X0v =

0.115

Z1S

0.2844

pu * (MVAbase/MVAT) =

+j

0.2133 pu

+j

0.0604 pu

+j

0.0409 pu

2. GSU transformer impedance at rated capacity converted to base values:


2
Z1GSU H-L=
0.1000 pu * (MVAbase/MVAT) * (kVpri/kVSYSTEM) = j
225 MVAT

Z2GSU H-L=
Z0GSU H-L=

0.0444 pu

0.1000 pu * (MVAbase/MVAT) * (kVpri/kVSYSTEM) = j


2
0.1000 pu * (MVAbase/MVAT) * (kVpri/kVSYSTEM) = j

0.0444 pu
0.0444 pu

3. Generator/GSU side equivalent [(GTG + GSUH-L) at base values:

4. System side equivalent at base values:

Z1G = Z1GEN + Z1GSU =

0.2844

+j

0.2578 pu

Z2G = Z2GEN + Z2GSU =

+j

0.1049 pu

Z0G = Z0GSU =

+j

0.0444 pu

Z1S =
Z2S =
Z0S =

0.00427
0.00427
-0.00513

+j
+j
+j

0.03281 pu
0.03281 pu
-0.03432 pu

46A & 46T

Section 1

G60_R0

11

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

-0.03432
+j
0.03931
0.0522
pu @
-48.9
6. Z2EQ = Z2S + Z2G =
0.03281
+j
0.10916
=
0.1140
pu @
73.3
7. ZEQ = Z0EQ // Z2EQ =
0.74788247
+j
0.02890
=
0.7484
pu @
2.2
8. ZTOTAL = Z1S + ZEQ + Z1P =
1.0651
+j
=
1.1042 pu @
9. I1 = +Vpu / ZTOTAL; where +Vpu = kVsystem/kVpri
I1 = +Vpu / ZTOTAL =
0.874
+j
-0.239
=
0.906
pu @
-15.3
10. I2 = -I1 [Z0EQ/(Z0EQ+Z2EQ)] =
-0.288
+j
=
0.318
pu @
205.3
11. I0 = -I1 [Z2EQ/(Z0EQ+Z2EQ)] =
0.5857807
+j
=
0.695
pu @
327.4
12. IA = I1 + I2 + I0 =
1.1716
+j
13. IB = a2I1 + aI2 + I0 =
0.204
+j
-1.1932
=
1.210
pu @
-80.3
14. IC = aI1 + a2I2 + I0 =
0.382
+j
0.819
=
0.903
pu @
65.0
15. IN = IA + IB + IC =
1.7573
+j
-1.1234
=
2.086
pu @
-32.6
16. Open Phase I2 =
84 A I2 @ kVSYSTEM =

GE Energy

5. Z0EQ = Z0S + Z0G =

0.2909
15.3

=
-0.136

=
-0.374

=
-0.7489

238 A

220 kV

84 A

220 kV

182 A
@
OPEN PHASE

220 kV

318 A

220 kV

237 A

220 kV

547 A
A @ kVG =
A Full Load

1021
9021

46 function time to operate for open phase = K / (I2/Inom)2 =

624.5 seconds

Summary: An open-phase condition at full load will result in


causing the 46T function to trip in

0.113 pu I2
624.5 seconds

@
0.113 pu I2

220 kV

E) HV Phase-to-Ground Fault Calculations (GSU terminal fault)


1. Calculations on generator base. Z1 = X'd + Z1t, Z2 = X2g + Z2t, Z0 = Z0t
I0 = 1Vpu / (Z1+Z2+Z0) = I1 = I2=
1.23 pu I2 =
11137 A
46 function time to operate for a phase-to-ground fault = K / (I2/Inom)2 =

5.2 seconds

Summary: A HV phase-to-ground fault condition will result in


causing the 46T function to trip in

1.23 pu I2
5.2 seconds

F) HV Phase-to-Phase Fault Calculations (GSU terminal fault)


1. Calculations on generator base. Z1 = X'd + Z1t, Z2 = X2g + Z2t
I2 = 1Vpu / (Z1+Z2) = -I1 =
1.46 pu I2 =

13169 A

46 function time to operate for a phase-to-phase fault = K / (I2/Inom)2 =

3.8 seconds

Summary: A HV phase-to-phase fault condition will result in


causing the 46T function to trip in

1.46 pu I2
3.8 seconds

46A & 46T

Section 1

G60_R0

12

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

G) 2% Phase HV Phase Unbalance Calculations


The analysis assumes the system 2% phase HV unbalance is significantly stronger than the generator,
thus the system is an infinite source.
1. 2% Phase HV Unbalance:
Va =
1.00 pu A =
0
=
1.0000
+j
0.0000
Vb =
1.02 pu B =
-120
=
-0.5100
+j
-0.8833
Vc =
1.00 pu C =
120
=
-0.5000
+j
0.8660
Vn =
0.02 pu N =
60
=
-0.0100
+j
-0.0173
HVs Line to Neutral Voltage =
Va =
Vb =
Vc =
V0 =
V1 =
V2 =

127.0 kV A =
129.6 kV B =
127.0 kV C =
0.847
127.9
0.847

kV 0 =
kV 1 =
kV 2 =

127.01345 kV
0 =
-120 =
120 =

127.0135
-64.7769
-63.5067

+j
+j
+j

0.0000
-112.1968
109.9969

=
=
=

-0.4234
127.8602
-0.4234

+j
+j
+j

-0.7333
0.0000
0.7333

240.00
0.00
120.00

2. GSU Zt at Generator MVA base:


Zt = 0.1000 pu
@
225 MVA
220
Zt @ MVAG = Zt * (MVAG/MVAT) =
0.1250 pu = Z2t
3. Generator Negative Sequence Impedance (unsaturated) at Generator MVA base:
X2i @ MVAG =
0.22
pu
4. I2 calcaulation:
V2 pu = V2actual / (kVs/3) =
0.0067 pu
Z2 total = Z2t + X2i =
0.3450 pu
I2 = V2 / Z2 =
0.0193 pu
=
Continuous Unbalanced Current (I2C) Capability:

1.93%
8%

46A & 46T

Section 1

G60_R0

13

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Undervoltage Function (ANSI Device 27)
A) Generator Data
Generator Data:
B) Relay Data
27 Relay Ranges:

PT Ratio (PTR):

281.25 MVAG,

18.00 kV,

0.8 pf

0 - 3.0 per unit Volts pickup range


0.00 - 600.00 second delay time range
Inverse Time Characteristic or Definite Time
18,000 / 120 =

150.00 :1

C) Settings Calculations
Relay Setting Philosophy: The 27 function is set to alarm for an undervoltage
condition. Set 27 function alarm for 80% nominal voltage in 10 seconds.
This function will be blocked for VTFF and startup.

Recommended Mode = Ph-to-Ph voltage measurement


Recommended 27 pickup =
Recommended time delay =
Recommended curve characteristic =
Recommended Minimum Voltage =

0.8 pu
10.00 seconds
definite time
0.0 pu

27

Section 1

G60_R0

14

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Overvoltage Function (ANSI Device 59)
A) Generator Data
Generator Data:
B) Relay Data
59 Relay Ranges:

PT Ratio (PTR):

281.25 MVAG,

18.00 kV,

0.8 pf

0.000 to 3.000 pu pickup range


0.00 to 600.00 second pickup/reset time delay range

18,000 / 120 =

150.00 :1

C) Settings Calculations
Relay Setting Philosophy: The 59 function should be set with a safe margin
below the overvoltage capability of the generator. Set time delay to coordinate
with the 24T function. This function will be blocked for VTFF and startup.
Nominal voltage =

120.0 volts

Recommended 59 pickup =
=

1.2 pu nominal volts


144.0 volts

Recommended 59 Time Delay =


Recommended 59 Reset Delay =

3.00 seconds
0 seconds

59

Section 1

G60_R0

15

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Overvoltage Protection - 59

1000

T (seconds)

100

59G
24T

10

1
100%

110%

120%

130%

140%

150%

160%

% V Nominal

Section 1

G60_R0

16

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Ground Fault Functions (ANSI Device 59N)
A) Generator Data
Generator Data:

281.25 MVAG,

18.00 kV,

Neutral Grounding Transformer Ratio (NGTR):

0.8 pf

12,000 / 240 =

Neutral Grounding Transformer Resistor Impedance (ZRES):

B) Relay Data
Auxiliary OV1 Relay Ranges:

50.00 :1
0.509 W

0.000 to 3.000 pu in steps of 0.001


0.00 to 600.00 seconds in steps of 0.01

C) Settings Calculations
Relay Setting Philosophy: Set 59N pickup as sensitive as possible to provide
maximum stator ground fault coverage. Set tripping time delay for 5 second
definite time operation. The auxiliary OV1 function within the G60 is assigned
to the 59N digital element of the relay. 59N is disabled during startup.

IGMAX = VL-N / (ZRES * NGTR2) =

8 amps

Neutral Grounding Transformer Secondary Voltage at IGMAX:


VMAX SEC = IGMAX * NGTR * ZRES =

208 Volts

Recommended 59N Pickup Setting (VSET) :

5 Volts =

Stator Ground Fault Coverage = (1 -VSET/VMAX SEC) * 100 =


Recommended 59N Time Delay Setting:

0.021 pu
97.6%

5 seconds

59N

Section 1

G60_R0

17

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Overexcitation Function (ANSI Device 24)
A) Generator Data
Generator Data:
B) Relay Data
24T Relay Ranges:

PT Ratio (PTR):

281.25 MVAG,

18.00 kV,

0.8 pf

DT, Inverse A-C, Flexcurve A,B curve settings


0.80 to 4.00 per unit Volts/Hertz pickup range
0.05 to 600.00 TD multiplier range
0 to 1000.0 second T-Reset settings range
18,000 / 120 =

150.00 :1

C) Settings Calculations
Relay Setting Philosophy: The generator is capable of continuous operation
at 1.05 per unit V/Hz. Corrective action should be taken for operation of the
machine above 105% V/Hz, which is not sanctioned by GE. The 24T setting
follows the recommendations of GEs generator technical reference GEK75512F,
trip for >118% V/Hz at 2 sec., and trip for <118% V/Hz according to the overexcitation capability of the GSU transformer while coordinating with the
exciter's limiter. Transformer V/Hz curve based on C37.91-2000, Figure 14.
Reset time should be 600 seconds per GE recommendation.

Inverse Time Curve Element


Set 24T1 curve type : Inverse A
Set 24T1 inverse pickup :
1.10 per unit V/Hz
Set 24T1 time dial multiplier :
7.0
Set 24T1 T-Reset:
600 seconds
Instantaneous Element
Set 24T2 curve type : Definite Time
Set 24T2 instantaneous pickup :
1.18 per unit V/Hz
Set 24T2 time dial multiplier :
2 seconds
Set 24T2 T-reset :
600 seconds
Alarm Element (via Flexlogic)
Set 24A pickup :
1.06 per unit V/Hz
Set 24A1 definite time delay :
10.0 seconds

24

Section 1

G60_R0

18

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

V/Hz Protection

1.4

1.35

1.3

V/Hz per unit

1.25

1.2

1.15

1.1

1.05

1
1

10

100

1000

10000

T (seconds)
Transformer

Section 1

24T

G60_R0

Exciter Limiter

24A

19

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Loss of Field Functions (ANSI Devices 40-1 & 40-2)
A) Generator Data
Generator Data:

281.25 MVAG,

18.00 kV,

XDV =

2.39 per unit

XDV =

0.265 per unit

B) Relay Data
40-1,2 Relay Ranges:
CT Ratio (CTR):

0.10 - 300.00 W Center & Radius


0.00 - 65.535 seconds Time Delay
12,000 / 5 =
2,400 :1

PT Ratio (PTR):

18,000 / 120 =

CTR/PTR:

0.8 pf

150 :1

16.00

C) Settings Calculations
Relay Setting Philosophy: During loss of excitation, these relay functions will
detect vars. from the system into the generator. The offset of XDV / 2 is to
avoid misoperations during system faults. The 40-1 circle is set at 1.0 per unit
ohms (on generator base) in order to detect short circuited fields at full and
moderate load, while not tripping for stable swings or regulator undershoot.
The 40-2 circle is set at XDV with a time delayof 0.6 seconds to provide tripping
for short circuited fields at no load or open circuit field, while not tripping for
stable swings. This function should be blocked for VTFF.
Convert XDV and XDV from per unit on gen. MVA and kV bases to relay ohms:
ZBASE (Generator Relay Base Impedance) = (kV2/MVAG)*(CTR/PTR) =
XDV-RELAY = (XDV) * ZBASE) =

4.88 W

1.0 PU-RELAY = (1.0 pu W) * ZBASE) =

18.43 W

XDV-RELAY = (XDV) * ZBASE) =

44.05 W

Set 40-STG1 Center = (XDV-RELAY + 1.0 PU-RELAY) / 2 =

11.66 W

Set 40-1 Radius = (1.0 PU-RELAY / 2) =


Set 40-STG1 Delay =
Set 40-STG2 Center = (XDV-RELAY + XDV-RELAY) / 2 =

9.22 W
0.06 seconds
24.47 W

Set 40-2 Radius = (XDV-RELAY / 2) =


Set 40-STG2 Delay =
Set 40-STG1 & 40-STG2 UV Supervision =

22.03 W
0.6 seconds
0.9 per unit

18.43

40-1 & 40-2

Section 1

G60_R0

20

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Loss of Excitation Protection (relay ohms)


X
40

20

0
-30

-20

-10

10

20

30

40

-20

-40

-60

-80

-100

40-1

Section 1

40-2

Capability Curve @ 40C Cold Gas

G60_R0

SSSL

UEL

21

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Loss of Excitation Protection


300

250

200

150

100

MVAR

50

0
0

50

100

150

200

250

300

350

400

-50

-100

-150

-200

-250

-300

-350

-400

MW
Capability Curve @ 40C Cold Gas

Section 1

UEL

G60_R0

40-1

40-2

SSSL

22

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

Setting Calculation Sheet


Inadvertant Energization Function (ANSI 50/27)
A) Generator Data
Generator Data:
281.25 MVAG,
18.00 kV,
B) Relay Data
50/27 Function Ranges:

GE Energy

0.8 pf

0.0 - 3.00 pu, 50 Function pickup range


0.0 - 3.00 pu, 27 pickup range

CT Ratio (CTR):

12,000 / 5

2,400 :1

PT Ratio (PTR):

18,000 / 120 =

150 :1

C) Settings Calculations
Relay Setting Philosophy: The 50 function should be set at 0.20pu A.
27 should be set well below nominal, 50%.

Recommended 50 arming mode: UV and Offline


Recommended 50 pickup:
0.20 pu A =
Recommended 27 pickup:
0.50 pu V =

2400 A
9,000 V

50/27

Section 1

G60_R0

23

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Anti-Motoring Function (ANSI Device 32-1)
A) Generator Data
Generator Data:
281.25 MVAG,
Generator Base kW Rating:
B) Relay Data
32-STG1,32-STG2 Relay Ranges:
CT Ratio (CTR):

12,000 / 5

PT Ratio (PTR):

18,000 / 120 =

18.00 kV,
225.0 MW

0.8 pf

-1.200 to 1.200 pu in steps of 0.001


0 to 600.00 seconds in steps of 0.01
2,400 :1
150.00 :1

C) Settings Calculations
Relay Setting Philosophy: Gas turbines require 10 - 50% of rated power
to motor depending on design. 32-STG1 pickup settings should be 7% of
rating. 32-STG2 will be disabled. This function should be blocked for VTFF.
This function is blocked during startup.
32-STG1 pickup set for

7.0%

of machine rating

32-STG1 base quantity = 3 x VT pu base x CT pu base =

15.75 MW
648.0 MW

Sensitive Directional Power Element

Set Dir. Power 1 Relay


Characteristic Angle for:

180

Set Directional Power 1


Calibration for:

Set Directional Power 1 STG1


SMIN for:
Figure 5-85 (a) in G60 Instruction Manual

Set Directional Power 1 STG1


Delay for:

0.024 pu

10 seconds

32-1

Section 1

G60_R0

24

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Under/Overfrequency Functions (ANSI Devices 81-U/O)
A) Generator Data
Generator Data:
B) Relay Data
81 Relay Ranges:

PT Ratio (PTR):

281.25 MVAG,
Nominal Frequency:

18.00 kV,
60 Hz

0.8 pf

35 - 99% Undervoltage Cutoff


20.0 - 65.0 Hz Set Points (81U, 81O)
0.000 - 65.535 second delay time range
18,000 / 120 =

150.00 :1

C) Settings Calculations
Relay Setting Philosophy: GE heavy-duty single shaft gas turbines are designed
to operate over a 95% to 105% speed range.
Settings will back up the MARK VI under and over speed protection of GE "F" line
gas turbines set for instantaneous breaker trip at 94% speed and alarm at 108%
speed. Function blocked for VTFF and startup.

Recommended 81-U/O Settings:


Recommended Undervoltage Cutoff = 85%
81U-1 pickup =
56.4
Hz
81U-1 delay =
20.0
sec
81U-1 reset =
0.0
sec
81U-1 output = TRIP 52G

81O-1 pickup =
81O-1 delay =
81O-1 reset =
81O-1 output =

64.8
1.0
0.0
ALARM

Hz
sec
sec

81-U/O

Section 1

G60_R0

25

PLANTA DE ETAN
Generator 761X201
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Ground Fault 3RD Harmonic Undervoltage Function (ANSI Device 27TN)
A) Generator Data
Generator Data:
B) Relay Data
27TN Relay Ranges:

281.25 MVAG,

18.00 kV,

0.8 pf

0.0000 - 3.0000 per unit Volts pickup range


0.00 - 600.00 second delay time range

C) Settings Calculations
Relay Setting Philosophy: The 27TN function is set during commissioning to cover the last
several percent of the stator closest to the neutral. The 27TN pickup setting must be based
upon the minimum measured 3RD harmonic voltage appearing across the resistor (NGR)
in the neutral grounding transformer. This voltage can be internally monitored using the data
accumulated in the DATA LOGGER. DATA LOGGER has been programmed to capture this
data and the 27TN function has temporary settings for 3rd harmonic voltage measurement.
The following procedure should be used to set the the 27TN function:
1 Enable the 3RD HARM NTRL UV function.
2 Obtain the minimum 3rd harmonic voltage across the NGR by methods described above
during generator load testing.
3 Program the 3RD HARM NTRL UV PICKUP setting to be one half of the minimum
observed 3rd harmonic voltage across the NGR in per unit on 240V base.
This setting may be entered in steps of 0.0001 puV.
4 Program the 3RD HARM NTRL UV DELAY setting to 5 seconds.
5 Program the 3RD HARM NTRL UV MAX POWER pickup setting for a margin above the
per-unit power level in which the 3RD HARM NTRL UV PICKUP setting is determined.
6 Program the 3RD HARM NTRL UV MIN POWER pickup setting for a margin below the
per-unit power level in which the measured 3RD harmonic voltage falls below the pickup
setting. Set for 0 if minimum does not fall below the setting.
This function will be blocked during startup.

27TN

Section 1

G60_R0

26

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function
GOOSEOut 1 ID
GOOSEOut 1 Destination MAC
GOOSEOut 1 VLAN Priority
GOOSEOut 1 VLAN ID
GOOSEOut 1 ETYPE APPID
GOOSEOut 1 ConfRev
GOOSEOut 1 Retransmission Curve
GOOSEOut 2 Function
GOOSEOut 2 ID
GOOSEOut 2 Destination MAC
GOOSEOut 2 VLAN Priority
GOOSEOut 2 VLAN ID
GOOSEOut 2 ETYPE APPID
GOOSEOut 2 ConfRev
GOOSEOut 2 Retransmission Curve
GOOSEOut 3 Function

Enabled
GOOSEOut_1
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_2
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
TX CONFIGURABLE GOOSE (continued from last page)
GOOSEOut 3 ID
GOOSEOut 3 Destination MAC
GOOSEOut 3 VLAN Priority
GOOSEOut 3 VLAN ID
GOOSEOut 3 ETYPE APPID
GOOSEOut 3 ConfRev
GOOSEOut 3 Retransmission Curve
GOOSEOut 4 Function
GOOSEOut 4 ID
GOOSEOut 4 Destination MAC
GOOSEOut 4 VLAN Priority
GOOSEOut 4 VLAN ID
GOOSEOut 4 ETYPE APPID
GOOSEOut 4 ConfRev
GOOSEOut 4 Retransmission Curve
GOOSEOut 5 Function
GOOSEOut 5 ID
GOOSEOut 5 Destination MAC
GOOSEOut 5 VLAN Priority
GOOSEOut 5 VLAN ID
GOOSEOut 5 ETYPE APPID
GOOSEOut 5 ConfRev
GOOSEOut 5 Retransmission Curve
GOOSEOut 6 Function
GOOSEOut 6 ID
GOOSEOut 6 Destination MAC
GOOSEOut 6 VLAN Priority
GOOSEOut 6 VLAN ID
GOOSEOut 6 ETYPE APPID
GOOSEOut 6 ConfRev
GOOSEOut 6 Retransmission Curve
GOOSEOut 7 Function
GOOSEOut 7 ID
GOOSEOut 7 Destination MAC
GOOSEOut 7 VLAN Priority
GOOSEOut 7 VLAN ID
GOOSEOut 7 ETYPE APPID
GOOSEOut 7 ConfRev
GOOSEOut 7 Retransmission Curve
GOOSEOut 8 Function
GOOSEOut 8 ID
GOOSEOut 8 Destination MAC
GOOSEOut 8 VLAN Priority
GOOSEOut 8 VLAN ID
GOOSEOut 8 ETYPE APPID
GOOSEOut 8 ConfRev
GOOSEOut 8 Retransmission Curve

GOOSEOut_3
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_4
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_5
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_6
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_7
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_8
00 00 00 00 00 00
4
0
0
1
Relaxed

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband
MMXU1: A phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband
MMXU3: PF phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel
SPCSO 33 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max
IEC61850 GGIO4 Analog 9 Value

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min
IEC61850 GGIO4 Analog 25 max

100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt
Clear XSWI16 OpCnt

No
No
No
No
No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 15
Digital Channel 16
Digital Channel 17
Digital Channel 18
Digital Channel 19
Digital Channel 20
Digital Channel 21
Digital Channel 22
Digital Channel 23
Digital Channel 24
Digital Channel 25
Digital Channel 26
Digital Channel 27
Digital Channel 28
Digital Channel 29
Digital Channel 30
Digital Channel 31
Digital Channel 32
Digital Channel 33
Digital Channel 34
Digital Channel 35
Digital Channel 36
Digital Channel 37
Digital Channel 38
Digital Channel 39
Digital Channel 40
Digital Channel 41

3
Automatic Overwrite
25 %
OSC TRIG On (VO6)
64 samples/cycle
86G-1A TRIP On (VO1)
STATOR DIFF OP A
STATOR DIFF OP B
STATOR DIFF OP C
3RD HARM NTRL UV PKP
3RD HARM NTRL UV OP
3RD HARM NTRL UV DPO
AUX OV 1 PKP
AUX OV 1 OP
AUX OV 1 DPO
86G-2A TRIP On (VO2)
VOLTS PER HERTZ 1 PKP
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 1 DPO
VOLTS PER HERTZ 2 PKP
VOLTS PER HERTZ 2 OP
VOLTS PER HERTZ 2 DPO
LOSS EXCIT PKP
LOSS EXCIT OP
LOSS EXCIT DPO
GEN UNBAL PKP
GEN UNBAL OP
GEN UNBAL DPO
52G TRIP On (VO3)
PH DIST Z2 OP AB
PH DIST Z2 OP BC
PH DIST Z2 OP CA
DIR POWER 1 OP
DIR POWER 2 OP
POWER SWING TRIP
UNDERFREQ 1 PKP
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
24A (FE 1) DPO
GEN UNBAL STG2 OP
ACCDNT ENRG OP
SRC2 VT FUSE FAIL OP
PHASE UV1 OP
PHASE OV1 OP
PHASE TOC1 PKP
PHASE TOC1 OP

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
OSCILLOGRAPHY (continued from last page)
Digital Channel 42
Digital Channel 43
Digital Channel 44
Digital Channel 45
Digital Channel 47
Digital Channel 48
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

PHASE TOC1 DPO


OVERFREQ 1 PKP
OVERFREQ 1 OP
OVERFREQ 1 DPO
86G1A On(P7A)
86G2A On(P7C)
Stator Diff Iad
Stator Rest Iar
Stator Diff Ibd
Stator Rest Ibr
Stator Diff Icd
Stator Rest Icr
Stator Gnd Vn 3rd
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ia RMS
SRC2
Ib RMS
SRC2
Ic RMS
SRC1
Ia RMS
SRC1
Ib RMS
SRC1
Ic RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5

Continuous
OFF
10000 msec
Stator Gnd Vn 3rd
SRC2
P
SRC2
PF
SRC1
Vx RMS
SRC1
Vx Mag

USER-PROGRAMMABLE LEDS
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input
USER PROGRAMMABLE LEDS
LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE

ANY TRIP On (VO4)


Alarm On (VO8)
3RD HARM NTRL UV OP
Latched
59N(DE1) OP
Latched
STATOR DIFF OP A
Latched
STATOR DIFF OP B
Latched
STATOR DIFF OP C
Latched
VOLTS PER HERTZ 1 OP
Latched
VOLTS PER HERTZ 2 OP
Latched
LOSS EXCIT STG1 OP
Latched
LOSS EXCIT STG2 OP
Latched
PH DIST Z2 OP AB
Latched
PH DIST Z2 OP BC
Latched
PH DIST Z2 OP CA
Latched
POWER SWING TRIP
Latched
DIR POWER 1 OP
Latched

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
USER PROGRAMMABLE LEDS (continued from last page)
LED 15: OPERAND
LED 15: TYPE
LED 16: OPERAND
LED 16: TYPE
LED 17: OPERAND
LED 17: TYPE
LED 18: OPERAND
LED 18: TYPE
LED 19: OPERAND
LED 19: TYPE
LED 20: OPERAND
LED 20: TYPE
LED 21: OPERAND
LED 21: TYPE
LED 22: OPERAND
LED 22: TYPE
LED 24: OPERAND
LED 24: TYPE
LED 25: OPERAND
LED 25: TYPE

UNDERFREQ 1 OP
Latched
SRC2 VT FUSE FAIL OP
Latched
GEN UNBAL OP
Latched
OVERFREQ 1 OP
Latched
PHASE UV1 OP
Latched
PHASE OV1 OP
Latched
ACCDNT ENRG OP
Latched
PHASE TOC1 OP
Latched
86G1A Off(P7A)
Self-Reset
86G2A On(P7C)
Self-Reset

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG G60A

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary

12000 A
5A
1A
1A
12000 A
5A
1A
1A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio
VT M5: Phase VT Connection
VT M5: Phase VT Secondary
VT M5: Phase VT Ratio
VT M5: Auxiliary VT Connection
VT M5: Auxiliary VT Secondary
VT M5: Auxiliary VT Ratio

Delta
120.0 V
150.00 :1
Vn
240.0 V
50.00 :1
Delta
25.0 V
1.00 :1
Vag
25.0 V
1.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Reverse Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

60 Hz
ABC
OFF
LINE (SRC 2)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT

NEUTRL
F1
None

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
SIGNAL SOURCES (continued from last page)
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT

F5
F5
LINE
M1
None
F5
None

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19
FlexLogic Entry 20
FlexLogic Entry 21
FlexLogic Entry 22
FlexLogic Entry 23
FlexLogic Entry 24
FlexLogic Entry 25
FlexLogic Entry 26
FlexLogic Entry 27
FlexLogic Entry 28
FlexLogic Entry 29
FlexLogic Entry 30
FlexLogic Entry 31
FlexLogic Entry 32
FlexLogic Entry 33
FlexLogic Entry 34
FlexLogic Entry 35
FlexLogic Entry 36
FlexLogic Entry 37
FlexLogic Entry 38
FlexLogic Entry 39
FlexLogic Entry 40
FlexLogic Entry 41
FlexLogic Entry 42
FlexLogic Entry 43
FlexLogic Entry 44

3RD HARM NTRL UV OP


59N(DE1) OP
STATOR DIFF OP
OR(3)
= 86G-1A TRIP (VO1)
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 2 OP
LOSS EXCIT STG1 OP
LOSS EXCIT STG2 OP
GEN UNBAL STG1 OP
OR(5)
= 86G-2A TRIP (VO2)
PH DIST Z2 OP
DIR POWER 1 OP
PHASE TOC1 OP
ACCDNT ENRG OP
POWER SWING TRIP
UNDERFREQ 1 OP
OR(6)
= 52G TRIP (VO3)
86G-1A TRIP On (VO1)
86G-2A TRIP On (VO2)
52G TRIP On (VO3)
OR(3)
= ANY TRIP (VO4)
52G/b On(H7A)
SRC2 VT FUSE FAIL OP
OR(2)
= BLOCK (VO5)
ANY TRIP On (VO4)
POSITIVE ONE SHOT
TRIG OSC On(U7A)
POSITIVE ONE SHOT
OR(2)
= OSC TRIG (VO6)
24A (FE 1) OP
GEN UNBAL STG2 OP
OVERFREQ 1 OP
PHASE OV1 OP
PHASE UV1 OP
SRC2 VT FUSE FAIL OP
OR(6)
= Alarm (VO8)
END

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
FLEXELEMENTS
FLEXELEMENTS 1: Function
FLEXELEMENTS 1: Name
FLEXELEMENTS 1: InputPlus
FLEXELEMENTS 1: InputMinus
FLEXELEMENTS 1: InputMode
FLEXELEMENTS 1: Compare Mode
FLEXELEMENTS 1: Direction Type
FLEXELEMENTS 1: Pickup
FLEXELEMENTS 1: Hysteresis
FLEXELEMENTS 1: DeltaTUnits
FLEXELEMENTS 1: DeltaT
FLEXELEMENTS 1: Pickup Delay
FLEXELEMENTS 1: Reset Delay
FLEXELEMENTS 1: Block
FLEXELEMENTS 1: Target
FLEXELEMENTS 1: Events
GROUPED ELEMENTS
GROUP 1
DISTANCE
DISTANCE [GROUP 1]
Source
Memory Duration
Force Self-Polar
Force Mem-Polar

Enabled
24A
Volts Per Hertz 1
OFF
ABSOLUTE
LEVEL
OVER
1.060 pu
3.0 %
Milliseconds
20
10.000 s
60.000 s
OFF
Self-reset
Enabled

LINE (SRC 2)
10 cycles
OFF
OFF

PHASE DISTANCE [GROUP 1]


PHASE DISTANCE Z2: Function
PHASE DISTANCE Z2: Direction
PHASE DISTANCE Z2: Shape
PHASE DISTANCE Z2: Xfmr Vol Connection
PHASE DISTANCE Z2: Xfmr Curr Connection
PHASE DISTANCE Z2: Reach
PHASE DISTANCE Z2: RCA
PHASE DISTANCE Z2: Rev Reach
PHASE DISTANCE Z2: Rev Reach RCA
PHASE DISTANCE Z2: Comp Limit
PHASE DISTANCE Z2: DIR RCA
PHASE DISTANCE Z2: DIR Comp Limit
PHASE DISTANCE Z2: Quad Right Blinder
PHASE DISTANCE Z2: Quad Right Blinder RCA
PHASE DISTANCE Z2: Quad Left Blinder
PHASE DISTANCE Z2: Quad Left Blinder RCA
PHASE DISTANCE Z2: Supervision
PHASE DISTANCE Z2: Volt Level
PHASE DISTANCE Z2: Delay
PHASE DISTANCE Z2: Block
PHASE DISTANCE Z2: Target
PHASE DISTANCE Z2: Events

Enabled
Forward
Mho
Dy11
Dy11
15.36 ohms
90 deg
0.02 ohms
85 deg
90 deg
90 deg
90 deg
10.00 ohms
85 deg
10.00 ohms
85 deg
0.200 pu
0.000 pu
0.800 s
BLOCK On (VO5)
Latched
Enabled

POWER SWING DETECT [GROUP 1]


Function
Source
Shape
Mode
Supv
Fwd Reach
Quad Fwd Mid
Quad Fwd Out
Fwd Rca
Rev Reach
Quad Rev Mid
Quad Rev Out
Rev Rca
Outer Limit Angle
Middle Limit Angle

Enabled
LINE (SRC 2)
Quad Shape
Two Step
0.600 pu
4.01 ohms
4.01 ohms
4.01 ohms
89 deg
8.89 ohms
8.89 ohms
8.89 ohms
90 deg
120 deg
90 deg

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
POWER SWING DETECT [GROUP 1] (continued from last page)
Inner Limit Angle
Outer Rgt Bld
Outer Lft Bld
Midle Rgt Bld
Midle Lft Bld
Inner Rgt Bld
Inner Lft Bld
Delay 1 Pickup
Delay 1 Reset
Delay 2 Pickup
Delay 3 Pickup
Delay 4 Pickup
Seal-In Delay
Trip Mode
Block
Target
Event

60 deg
8.21 ohms
8.21 ohms
8.21 ohms
8.21 ohms
2.74 ohms
2.74 ohms
0.140 s
0.050 s
0.017 s
0.320 s
0.070 s
0.400 s
Delayed
BLOCK On (VO5)
Latched
Enabled

STATOR DIFFERENTIAL [GROUP 1]


Function
Line End Source
Neutral End Source
Pickup
Slope 1
Break 1
Slope 2
Break 2
Block
Targets
Events

Enabled
LINE (SRC 2)
NEUTRL (SRC 1)
0.100 pu
10 %
1.15 pu
80 %
4.00 pu
OFF
Latched
Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events
GENERATOR UNBALANCE [GROUP 1]
Function
Source
Inom
Stage 1 Pickup
Stage 1 K-Value
Stage 1 Tmin
Stage 1 Tmax
Stage 1 K-Reset
Stage 2 Pickup
Stage 2 Pickup Delay
Block
Target
Events
VOLTAGE ELEMENTS
PHASE UV [GROUP 1]
PHASE UV1: Function
PHASE UV1: Signal Source
PHASE UV1: Mode

Enabled
LINE (SRC 2)
Phasor
0.864 pu
IEC Curve B
0.53
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled
Enabled
LINE (SRC 2)
0.752 pu
8.00 %
8.00
0.001 s
1000.0 s
227.0 s
5.60 %
1.0 s
OFF
Latched
Enabled

Enabled
LINE (SRC 2)
Phase to Phase

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
PHASE UV [GROUP 1] (continued from last page)
PHASE UV1: Pickup
PHASE UV1: Curve
PHASE UV1: Delay
PHASE UV1: Minimum Voltage
PHASE UV1: Block
PHASE UV1: Target
PHASE UV1: Events

0.800 pu
Definite Time
10.00 s
0.000 pu
BLOCK On (VO5)
Latched
Enabled

PHASE OV [GROUP 1]
PHASE OV1: Function
PHASE OV1: Source
PHASE OV1: Pickup
PHASE OV1: Delay
PHASE OV1: Reset Delay
PHASE OV1: Block
PHASE OV1: Target
PHASE OV1: Events

Enabled
LINE (SRC 2)
1.200 pu
3.00 s
0.00 s
BLOCK On (VO5)
Latched
Enabled

AUXILIARY OV [GROUP 1]
AUXILIARY OV 1: Function
AUXILIARY OV 1: Source
AUXILIARY OV 1: Pickup
AUXILIARY OV 1: Pickup Delay
AUXILIARY OV 1: Reset Delay
AUXILIARY OV 1: Block
AUXILIARY OV 1: Target
AUXILIARY OV 1: Events

Enabled
NEUTRL (SRC 1)
0.021 pu
5.00 s
0.00 s
OFF
Latched
Enabled

VOLTS PER HERTZ [GROUP 1]


VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: VHZ Voltage Mode
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
VOLTS PER HERTZ 2: Function
VOLTS PER HERTZ 2: Source
VOLTS PER HERTZ 2: VHZ Voltage Mode
VOLTS PER HERTZ 2: Pickup
VOLTS PER HERTZ 2: Curves
VOLTS PER HERTZ 2: TD Multiplier
VOLTS PER HERTZ 2: T Reset
VOLTS PER HERTZ 2: Block
VOLTS PER HERTZ 2: Target
VOLTS PER HERTZ 2: Events

Enabled
LINE (SRC 2)
Phase to Ground
1.10 pu
Inverse A
7.00
600.0 s
SRC2 VT FUSE FAIL OP
Latched
Enabled
Enabled
LINE (SRC 2)
Phase to Ground
1.18 pu
Definite Time
2.00
600.0 s
SRC2 VT FUSE FAIL OP
Latched
Enabled

LOSS OF EXCITATION [GROUP 1]


Function
Source
Center 1
Radius 1
UV Supervision Enable 1
Pickup Delay 1
Center 2
Radius 2
UV Supervision Enable 2
Pickup Delay 2
UV Supervision
Block
Target
Events

Enabled
LINE (SRC 2)
11.66 ohm
9.22 ohm
Enabled
0.060 s
24.47 ohm
22.03 ohm
Enabled
0.600 s
0.900 pu
SRC2 VT FUSE FAIL OP
Latched
Enabled

ACCIDENTAL ENERGIZATION [GROUP 1]

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
ACCIDENTAL ENERGIZATION [GROUP 1] (continued from last page)
Function
Source
Accidental Energization Arming Mode
Accidental Energization OC Pickup
Accidental Energization UV Pickup
Accidental Energization Offline
Block
Target
Events
STATOR GROUND
STATOR GROUND SOURCE [GROUP 1]
Source
3RD HARMONIC NTRL UV [GROUP 1]
Function
Pickup
Delay
Max Power
Min Power
Volt Supervision
Block
Target
Events
POWER
SENSITIVE DIRECTIONAL POWER
SENSITIVE DIRECTIONAL POWER [GROUP 1]
SENS DIR POWER1: Function
SENS DIR POWER1: Signal Source
SENS DIR POWER1: Sensitive Directional Power RCA
SENS DIR POWER1: Sensitive Directional Power Calibration
SENS DIR POWER1: Stage 1 SMIN
SENS DIR POWER1: Stage 1 Delay
SENS DIR POWER1: Stage 2 SMIN
SENS DIR POWER1: Stage 2 Delay
SENS DIR POWER1: Block
SENS DIR POWER1: Target
SENS DIR POWER1: Events
CONTROL ELEMENTS
UNDERFREQUENCY
UNDERFREQUENCY 1: Function
UNDERFREQUENCY 1: Block
UNDERFREQUENCY 1: Source
UNDERFREQUENCY 1: Min Volt/Amp
UNDERFREQUENCY 1: Pickup
UNDERFREQUENCY 1: Pickup Delay
UNDERFREQUENCY 1: Reset Delay
UNDERFREQUENCY 1: Target
UNDERFREQUENCY 1: Events

Enabled
LINE (SRC 2)
UV AND OFFLINE
0.200
0.500
52G/b On(H7A)
OFF
Latched
Enabled

NEUTRL (SRC 1)
Enabled
0.3000 pu
0.00 s
3.000 pu
0.000 pu
0.500 pu
OFF
Self-reset
Enabled

Enabled
LINE (SRC 2)
180 deg
0.00 deg
0.024 pu
10.00 s
0.024 pu
10.00 s
BLOCK On (VO5)
Latched
Enabled

Enabled
BLOCK On (VO5)
LINE (SRC 2)
0.85 pu
56.40 Hz
20.000 s
0.000 s
Latched
Enabled

OVERFREQUENCY
OVERFREQUENCY 1: Function
OVERFREQUENCY 1: Block
OVERFREQUENCY 1: Source
OVERFREQUENCY 1: Pickup
OVERFREQUENCY 1: Pickup Delay
OVERFREQUENCY 1: Reset Delay
OVERFREQUENCY 1: Target
OVERFREQUENCY 1: Events

Enabled
BLOCK On (VO5)
LINE (SRC 2)
64.80 Hz
1.000 s
0.000 s
Latched
Enabled

DIGITAL ELEMENTS
Digital Element 1 Function
Digital Element 1 Name
Digital Element 1 Input
Digital Element 1 Pickup Delay

Enabled
59N
AUX OV 1 OP
0.000 s

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
DIGITAL ELEMENTS (continued from last page)
Digital Element 1 Reset Delay
Digital Element 1 Pickup Led
Digital Element 1 Block
Digital Element 1 Target
Digital Element 1 Events
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function
VT FUSE FAILURE 1: Neutral Wire Open Detection
VT FUSE FAILURE 1: 3rd Harmonic Pickup
VT FUSE FAILURE 2: Function
VT FUSE FAILURE 2: Neutral Wire Open Detection
VT FUSE FAILURE 2: 3rd Harmonic Pickup
VT FUSE FAILURE 3: Function
VT FUSE FAILURE 3: Neutral Wire Open Detection
VT FUSE FAILURE 3: 3rd Harmonic Pickup
VT FUSE FAILURE 4: Function
VT FUSE FAILURE 4: Neutral Wire Open Detection
VT FUSE FAILURE 4: 3rd Harmonic Pickup
FREQUENCY OOB ACCUMULATION
Freq OOB Accumulator Source
Freq OOB Accumulator Min V A
Freq OOB Accumulator Block
Freq OOB Accumulator Target
Freq OOB Accumulator Events
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events

0.000 s
Enabled
OFF
Latched
Enabled

Disabled
Disabled
0.100 pu
Enabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
NEUTRL (SRC 1)
0.10 pu
OFF
Self-reset
Disabled

52G/b
2.0 ms
Enabled
Cont Ip 2
2.0 ms
Disabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
86G1A
2.0 ms
Enabled
86G2A
2.0 ms
Enabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
TRIG OSC
2.0 ms
Enabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
CONTACT INPUT THRESHOLDS
52G/b, Cont Ip 2, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
86G1A, 86G2A, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
TRIG OSC, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

84 Vdc
84 Vdc
84 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P2] Contact Output 8 ID
[P2] Contact Output 8 Operate
[P2] Contact Output 8 Seal-In
[P2] Contact Output 8 Events
[P3] Contact Output 9 ID
[P3] Contact Output 9 Operate
[P3] Contact Output 9 Seal-In
[P3] Contact Output 9 Events
[P4] Contact Output 10 ID
[P4] Contact Output 10 Operate
[P4] Contact Output 10 Seal-In
[P4] Contact Output 10 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[U1] Contact Output 13 ID
[U1] Contact Output 13 Operate
[U1] Contact Output 13 Seal-In
[U1] Contact Output 13 Events
[U2] Contact Output 14 ID
[U2] Contact Output 14 Operate
[U2] Contact Output 14 Seal-In
[U2] Contact Output 14 Events
[U3] Contact Output 15 ID
[U3] Contact Output 15 Operate
[U3] Contact Output 15 Seal-In
[U3] Contact Output 15 Events
[U5] Contact Output 17 ID
[U5] Contact Output 17 Operate
[U5] Contact Output 17 Seal-In
[U5] Contact Output 17 Events
[U6] Contact Output 18 ID
[U6] Contact Output 18 Operate
[U6] Contact Output 18 Seal-In
[U6] Contact Output 18 Events

TRIP 86G-1A
86G-1A TRIP On (VO1)
OFF
Enabled
TRIP 86G-2A
86G-2A TRIP On (VO2)
OFF
Enabled
TRIP 52G TC1
52G TRIP On (VO3)
OFF
Enabled
TRIP 52G TC2
52G TRIP On (VO3)
OFF
Enabled
ANY TRIP (A)
ANY TRIP On (VO4)
OFF
Enabled
24(A)
24A (FE 1) OP
OFF
Enabled
46(A)
GEN UNBAL STG2 OP
OFF
Enabled
81O(A)
OVERFREQ 1 OP
OFF
Enabled
VTFF
SRC2 VT FUSE FAIL OP
OFF
Enabled
27P(A)
PHASE UV1 OP
OFF
Enabled
59P(A)
PHASE OV1 OP
OFF
Enabled
IBF/52G
52G TRIP On (VO3)
OFF
Enabled
TRIG OS G60B
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS T60U
ANY TRIP On (VO4)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events

86G-1A TRIP
Enabled
86G-2A TRIP
Enabled

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
VIRTUAL OUTPUTS (continued from last page)
Virtual Output 3 ID
Virtual Output 3 Events
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5 ID
Virtual Output 5 Events
Virtual Output 6 ID
Virtual Output 6 Events
Virtual Output 8 ID
Virtual Output 8 Events

52G TRIP
Enabled
ANY TRIP
Enabled
BLOCK
Enabled
OSC TRIG
Enabled
Alarm
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 19

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base

No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 20

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Fri Aug 23 16:09:27 2013 Version: 6.00 Settings (Enabled Features)

PAGE 21

GTG G60A_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.0X
DESCRIPTION: GTG G60A
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function
GOOSEOut 1 ID
GOOSEOut 1 Destination MAC
GOOSEOut 1 VLAN Priority
GOOSEOut 1 VLAN ID
GOOSEOut 1 ETYPE APPID
GOOSEOut 1 ConfRev
GOOSEOut 1 Retransmission Curve
GOOSEOut 2 Function
GOOSEOut 2 ID
GOOSEOut 2 Destination MAC
GOOSEOut 2 VLAN Priority
GOOSEOut 2 VLAN ID
GOOSEOut 2 ETYPE APPID
GOOSEOut 2 ConfRev
GOOSEOut 2 Retransmission Curve
GOOSEOut 3 Function

Enabled
GOOSEOut_1
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_2
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
TX CONFIGURABLE GOOSE (continued from last page)
GOOSEOut 3 ID
GOOSEOut 3 Destination MAC
GOOSEOut 3 VLAN Priority
GOOSEOut 3 VLAN ID
GOOSEOut 3 ETYPE APPID
GOOSEOut 3 ConfRev
GOOSEOut 3 Retransmission Curve
GOOSEOut 4 Function
GOOSEOut 4 ID
GOOSEOut 4 Destination MAC
GOOSEOut 4 VLAN Priority
GOOSEOut 4 VLAN ID
GOOSEOut 4 ETYPE APPID
GOOSEOut 4 ConfRev
GOOSEOut 4 Retransmission Curve
GOOSEOut 5 Function
GOOSEOut 5 ID
GOOSEOut 5 Destination MAC
GOOSEOut 5 VLAN Priority
GOOSEOut 5 VLAN ID
GOOSEOut 5 ETYPE APPID
GOOSEOut 5 ConfRev
GOOSEOut 5 Retransmission Curve
GOOSEOut 6 Function
GOOSEOut 6 ID
GOOSEOut 6 Destination MAC
GOOSEOut 6 VLAN Priority
GOOSEOut 6 VLAN ID
GOOSEOut 6 ETYPE APPID
GOOSEOut 6 ConfRev
GOOSEOut 6 Retransmission Curve
GOOSEOut 7 Function
GOOSEOut 7 ID
GOOSEOut 7 Destination MAC
GOOSEOut 7 VLAN Priority
GOOSEOut 7 VLAN ID
GOOSEOut 7 ETYPE APPID
GOOSEOut 7 ConfRev
GOOSEOut 7 Retransmission Curve
GOOSEOut 8 Function
GOOSEOut 8 ID
GOOSEOut 8 Destination MAC
GOOSEOut 8 VLAN Priority
GOOSEOut 8 VLAN ID
GOOSEOut 8 ETYPE APPID
GOOSEOut 8 ConfRev
GOOSEOut 8 Retransmission Curve

GOOSEOut_3
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_4
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_5
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_6
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_7
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_8
00 00 00 00 00 00
4
0
0
1
Relaxed

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband
MMXU1: A phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband
MMXU3: PF phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel
SPCSO 33 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max
IEC61850 GGIO4 Analog 9 Value

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min
IEC61850 GGIO4 Analog 25 max

100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt
Clear XSWI16 OpCnt

No
No
No
No
No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 15
Digital Channel 16
Digital Channel 17
Digital Channel 18
Digital Channel 19
Digital Channel 20
Digital Channel 21
Digital Channel 22
Digital Channel 23
Digital Channel 24
Digital Channel 25
Digital Channel 26
Digital Channel 27
Digital Channel 28
Digital Channel 29
Digital Channel 30
Digital Channel 31
Digital Channel 32
Digital Channel 33
Digital Channel 34
Digital Channel 35
Digital Channel 36
Digital Channel 37
Digital Channel 38
Digital Channel 39
Digital Channel 40
Digital Channel 41

3
Automatic Overwrite
25 %
OSC TRIG On (VO6)
64 samples/cycle
86G-1B TRIP On (VO1)
STATOR DIFF OP A
STATOR DIFF OP B
STATOR DIFF OP C
3RD HARM NTRL UV PKP
3RD HARM NTRL UV OP
3RD HARM NTRL UV DPO
AUX OV 1 PKP
AUX OV 1 OP
AUX OV 1 DPO
86G-2B TRIP On (VO2)
VOLTS PER HERTZ 1 PKP
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 1 DPO
VOLTS PER HERTZ 2 PKP
VOLTS PER HERTZ 2 OP
VOLTS PER HERTZ 2 DPO
LOSS EXCIT PKP
LOSS EXCIT OP
LOSS EXCIT DPO
GEN UNBAL PKP
GEN UNBAL OP
GEN UNBAL DPO
52G TRIP On (VO3)
PH DIST Z2 OP AB
PH DIST Z2 OP BC
PH DIST Z2 OP CA
DIR POWER 1 OP
DIR POWER 2 OP
POWER SWING TRIP
UNDERFREQ 1 PKP
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
24A (FE 1) DPO
GEN UNBAL STG2 OP
ACCDNT ENRG OP
SRC2 VT FUSE FAIL OP
PHASE UV1 OP
PHASE OV1 OP
PHASE TOC1 PKP
PHASE TOC1 OP

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
OSCILLOGRAPHY (continued from last page)
Digital Channel 42
Digital Channel 43
Digital Channel 44
Digital Channel 45
Digital Channel 47
Digital Channel 48
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

PHASE TOC1 DPO


OVERFREQ 1 PKP
OVERFREQ 1 OP
OVERFREQ 1 DPO
86G1A On(P7a)
86G2A On(P7c)
Stator Diff Iad
Stator Rest Iar
Stator Diff Ibd
Stator Rest Ibr
Stator Diff Icd
Stator Rest Icr
Stator Gnd Vn 3rd
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ia RMS
SRC2
Ib RMS
SRC2
Ic RMS
SRC1
Ia RMS
SRC1
Ib RMS
SRC1
Ic RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5

Continuous
OFF
10000 msec
Stator Gnd Vn 3rd
SRC2
P
SRC2
PF
SRC1
Vx RMS
SRC1
Vx Mag

USER-PROGRAMMABLE LEDS
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input
USER PROGRAMMABLE LEDS
LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE

ANY TRIP On (VO4)


Alarm On (VO8)
3RD HARM NTRL UV OP
Latched
59N(DE1) OP
Latched
STATOR DIFF OP A
Latched
STATOR DIFF OP B
Latched
STATOR DIFF OP C
Latched
VOLTS PER HERTZ 1 OP
Latched
VOLTS PER HERTZ 2 OP
Latched
LOSS EXCIT STG1 OP
Latched
LOSS EXCIT STG2 OP
Latched
PH DIST Z2 OP AB
Latched
PH DIST Z2 OP BC
Latched
PH DIST Z2 OP CA
Latched
POWER SWING TRIP
Latched
DIR POWER 1 OP
Latched

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
USER PROGRAMMABLE LEDS (continued from last page)
LED 15: OPERAND
LED 15: TYPE
LED 16: OPERAND
LED 16: TYPE
LED 17: OPERAND
LED 17: TYPE
LED 18: OPERAND
LED 18: TYPE
LED 19: OPERAND
LED 19: TYPE
LED 20: OPERAND
LED 20: TYPE
LED 21: OPERAND
LED 21: TYPE
LED 22: OPERAND
LED 22: TYPE
LED 24: OPERAND
LED 24: TYPE
LED 25: OPERAND
LED 25: TYPE

UNDERFREQ 1 OP
Latched
SRC2 VT FUSE FAIL OP
Latched
GEN UNBAL OP
Latched
OVERFREQ 1 OP
Latched
PHASE UV1 OP
Latched
PHASE OV1 OP
Latched
ACCDNT ENRG OP
Latched
PHASE TOC1 OP
Latched
86G1A Off(P7a)
Self-Reset
86G2A On(P7c)
Self-Reset

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG G60B

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary

12000 A
5A
1A
1A
12000 A
5A
1A
1A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio
VT M5: Phase VT Connection
VT M5: Phase VT Secondary
VT M5: Phase VT Ratio
VT M5: Auxiliary VT Connection
VT M5: Auxiliary VT Secondary
VT M5: Auxiliary VT Ratio

Delta
120.0 V
150.00 :1
Vn
240.0 V
50.00 :1
Delta
25.0 V
1.00 :1
Vag
25.0 V
1.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Reverse Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

60 Hz
ABC
OFF
LINE (SRC 2)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT

NEUTRL
F1
None

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
SIGNAL SOURCES (continued from last page)
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT

F5
F5
LINE
M1
None
F5
None

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19
FlexLogic Entry 20
FlexLogic Entry 21
FlexLogic Entry 22
FlexLogic Entry 23
FlexLogic Entry 24
FlexLogic Entry 25
FlexLogic Entry 26
FlexLogic Entry 27
FlexLogic Entry 28
FlexLogic Entry 29
FlexLogic Entry 30
FlexLogic Entry 31
FlexLogic Entry 32
FlexLogic Entry 33
FlexLogic Entry 34
FlexLogic Entry 35
FlexLogic Entry 36
FlexLogic Entry 37
FlexLogic Entry 38
FlexLogic Entry 39
FlexLogic Entry 40
FlexLogic Entry 41
FlexLogic Entry 42
FlexLogic Entry 43
FlexLogic Entry 44

3RD HARM NTRL UV OP


59N(DE1) OP
STATOR DIFF OP
OR(3)
= 86G-1B TRIP (VO1)
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 2 OP
LOSS EXCIT STG1 OP
LOSS EXCIT STG2 OP
GEN UNBAL STG1 OP
OR(5)
= 86G-2B TRIP (VO2)
PH DIST Z2 OP
DIR POWER 1 OP
PHASE TOC1 OP
ACCDNT ENRG OP
POWER SWING TRIP
UNDERFREQ 1 OP
OR(6)
= 52G TRIP (VO3)
86G-1B TRIP On (VO1)
86G-2B TRIP On (VO2)
52G TRIP On (VO3)
OR(3)
= ANY TRIP (VO4)
52G/b On(H7a)
SRC2 VT FUSE FAIL OP
OR(2)
= BLOCK (VO5)
ANY TRIP On (VO4)
POSITIVE ONE SHOT
TRIG OSC On(U7a)
POSITIVE ONE SHOT
OR(2)
= OSC TRIG (VO6)
24A (FE 1) OP
GEN UNBAL STG2 OP
OVERFREQ 1 OP
PHASE OV1 OP
PHASE UV1 OP
SRC2 VT FUSE FAIL OP
OR(6)
= Alarm (VO8)
END

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
FLEXELEMENTS
FLEXELEMENTS 1: Function
FLEXELEMENTS 1: Name
FLEXELEMENTS 1: InputPlus
FLEXELEMENTS 1: InputMinus
FLEXELEMENTS 1: InputMode
FLEXELEMENTS 1: Compare Mode
FLEXELEMENTS 1: Direction Type
FLEXELEMENTS 1: Pickup
FLEXELEMENTS 1: Hysteresis
FLEXELEMENTS 1: DeltaTUnits
FLEXELEMENTS 1: DeltaT
FLEXELEMENTS 1: Pickup Delay
FLEXELEMENTS 1: Reset Delay
FLEXELEMENTS 1: Block
FLEXELEMENTS 1: Target
FLEXELEMENTS 1: Events
GROUPED ELEMENTS
GROUP 1
DISTANCE
DISTANCE [GROUP 1]
Source
Memory Duration
Force Self-Polar
Force Mem-Polar

Enabled
24A
Volts Per Hertz 1
OFF
ABSOLUTE
LEVEL
OVER
1.060 pu
3.0 %
Milliseconds
20
10.000 s
60.000 s
OFF
Self-reset
Enabled

LINE (SRC 2)
10 cycles
OFF
OFF

PHASE DISTANCE [GROUP 1]


PHASE DISTANCE Z2: Function
PHASE DISTANCE Z2: Direction
PHASE DISTANCE Z2: Shape
PHASE DISTANCE Z2: Xfmr Vol Connection
PHASE DISTANCE Z2: Xfmr Curr Connection
PHASE DISTANCE Z2: Reach
PHASE DISTANCE Z2: RCA
PHASE DISTANCE Z2: Rev Reach
PHASE DISTANCE Z2: Rev Reach RCA
PHASE DISTANCE Z2: Comp Limit
PHASE DISTANCE Z2: DIR RCA
PHASE DISTANCE Z2: DIR Comp Limit
PHASE DISTANCE Z2: Quad Right Blinder
PHASE DISTANCE Z2: Quad Right Blinder RCA
PHASE DISTANCE Z2: Quad Left Blinder
PHASE DISTANCE Z2: Quad Left Blinder RCA
PHASE DISTANCE Z2: Supervision
PHASE DISTANCE Z2: Volt Level
PHASE DISTANCE Z2: Delay
PHASE DISTANCE Z2: Block
PHASE DISTANCE Z2: Target
PHASE DISTANCE Z2: Events

Enabled
Forward
Mho
Dy11
Dy11
15.36 ohms
90 deg
0.02 ohms
85 deg
90 deg
90 deg
90 deg
10.00 ohms
85 deg
10.00 ohms
85 deg
0.200 pu
0.000 pu
0.800 s
BLOCK On (VO5)
Latched
Enabled

POWER SWING DETECT [GROUP 1]


Function
Source
Shape
Mode
Supv
Fwd Reach
Quad Fwd Mid
Quad Fwd Out
Fwd Rca
Rev Reach
Quad Rev Mid
Quad Rev Out
Rev Rca
Outer Limit Angle
Middle Limit Angle

Enabled
LINE (SRC 2)
Quad Shape
Two Step
0.600 pu
4.01 ohms
4.01 ohms
4.01 ohms
89 deg
8.89 ohms
8.89 ohms
8.89 ohms
90 deg
120 deg
90 deg

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
POWER SWING DETECT [GROUP 1] (continued from last page)
Inner Limit Angle
Outer Rgt Bld
Outer Lft Bld
Midle Rgt Bld
Midle Lft Bld
Inner Rgt Bld
Inner Lft Bld
Delay 1 Pickup
Delay 1 Reset
Delay 2 Pickup
Delay 3 Pickup
Delay 4 Pickup
Seal-In Delay
Trip Mode
Block
Target
Event

60 deg
8.21 ohms
8.21 ohms
8.21 ohms
8.21 ohms
2.74 ohms
2.74 ohms
0.140 s
0.050 s
0.017 s
0.320 s
0.070 s
0.400 s
Delayed
BLOCK On (VO5)
Latched
Enabled

STATOR DIFFERENTIAL [GROUP 1]


Function
Line End Source
Neutral End Source
Pickup
Slope 1
Break 1
Slope 2
Break 2
Block
Targets
Events

Enabled
LINE (SRC 2)
NEUTRL (SRC 1)
0.100 pu
10 %
1.15 pu
80 %
4.00 pu
OFF
Latched
Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events
GENERATOR UNBALANCE [GROUP 1]
Function
Source
Inom
Stage 1 Pickup
Stage 1 K-Value
Stage 1 Tmin
Stage 1 Tmax
Stage 1 K-Reset
Stage 2 Pickup
Stage 2 Pickup Delay
Block
Target
Events
VOLTAGE ELEMENTS
PHASE UV [GROUP 1]
PHASE UV1: Function
PHASE UV1: Signal Source
PHASE UV1: Mode

Enabled
LINE (SRC 2)
Phasor
0.864 pu
IEC Curve B
0.53
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled
Enabled
LINE (SRC 2)
0.752 pu
8.00 %
8.00
0.001 s
1000.0 s
227.0 s
5.60 %
1.0 s
OFF
Latched
Enabled

Enabled
LINE (SRC 2)
Phase to Phase

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
PHASE UV [GROUP 1] (continued from last page)
PHASE UV1: Pickup
PHASE UV1: Curve
PHASE UV1: Delay
PHASE UV1: Minimum Voltage
PHASE UV1: Block
PHASE UV1: Target
PHASE UV1: Events

0.800 pu
Definite Time
10.00 s
0.000 pu
BLOCK On (VO5)
Latched
Enabled

PHASE OV [GROUP 1]
PHASE OV1: Function
PHASE OV1: Source
PHASE OV1: Pickup
PHASE OV1: Delay
PHASE OV1: Reset Delay
PHASE OV1: Block
PHASE OV1: Target
PHASE OV1: Events

Enabled
LINE (SRC 2)
1.200 pu
3.00 s
0.00 s
BLOCK On (VO5)
Latched
Enabled

AUXILIARY OV [GROUP 1]
AUXILIARY OV 1: Function
AUXILIARY OV 1: Source
AUXILIARY OV 1: Pickup
AUXILIARY OV 1: Pickup Delay
AUXILIARY OV 1: Reset Delay
AUXILIARY OV 1: Block
AUXILIARY OV 1: Target
AUXILIARY OV 1: Events

Enabled
NEUTRL (SRC 1)
0.021 pu
5.00 s
0.00 s
OFF
Latched
Enabled

VOLTS PER HERTZ [GROUP 1]


VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: VHZ Voltage Mode
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
VOLTS PER HERTZ 2: Function
VOLTS PER HERTZ 2: Source
VOLTS PER HERTZ 2: VHZ Voltage Mode
VOLTS PER HERTZ 2: Pickup
VOLTS PER HERTZ 2: Curves
VOLTS PER HERTZ 2: TD Multiplier
VOLTS PER HERTZ 2: T Reset
VOLTS PER HERTZ 2: Block
VOLTS PER HERTZ 2: Target
VOLTS PER HERTZ 2: Events

Enabled
LINE (SRC 2)
Phase to Ground
1.10 pu
Inverse A
7.00
600.0 s
SRC2 VT FUSE FAIL OP
Latched
Enabled
Enabled
LINE (SRC 2)
Phase to Ground
1.18 pu
Definite Time
2.00
600.0 s
SRC2 VT FUSE FAIL OP
Latched
Enabled

LOSS OF EXCITATION [GROUP 1]


Function
Source
Center 1
Radius 1
UV Supervision Enable 1
Pickup Delay 1
Center 2
Radius 2
UV Supervision Enable 2
Pickup Delay 2
UV Supervision
Block
Target
Events

Enabled
LINE (SRC 2)
11.66 ohm
9.22 ohm
Enabled
0.060 s
24.47 ohm
22.03 ohm
Enabled
0.600 s
0.900 pu
SRC2 VT FUSE FAIL OP
Latched
Enabled

ACCIDENTAL ENERGIZATION [GROUP 1]

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
ACCIDENTAL ENERGIZATION [GROUP 1] (continued from last page)
Function
Source
Accidental Energization Arming Mode
Accidental Energization OC Pickup
Accidental Energization UV Pickup
Accidental Energization Offline
Block
Target
Events
STATOR GROUND
STATOR GROUND SOURCE [GROUP 1]
Source
3RD HARMONIC NTRL UV [GROUP 1]
Function
Pickup
Delay
Max Power
Min Power
Volt Supervision
Block
Target
Events
POWER
SENSITIVE DIRECTIONAL POWER
SENSITIVE DIRECTIONAL POWER [GROUP 1]
SENS DIR POWER1: Function
SENS DIR POWER1: Signal Source
SENS DIR POWER1: Sensitive Directional Power RCA
SENS DIR POWER1: Sensitive Directional Power Calibration
SENS DIR POWER1: Stage 1 SMIN
SENS DIR POWER1: Stage 1 Delay
SENS DIR POWER1: Stage 2 SMIN
SENS DIR POWER1: Stage 2 Delay
SENS DIR POWER1: Block
SENS DIR POWER1: Target
SENS DIR POWER1: Events
CONTROL ELEMENTS
UNDERFREQUENCY
UNDERFREQUENCY 1: Function
UNDERFREQUENCY 1: Block
UNDERFREQUENCY 1: Source
UNDERFREQUENCY 1: Min Volt/Amp
UNDERFREQUENCY 1: Pickup
UNDERFREQUENCY 1: Pickup Delay
UNDERFREQUENCY 1: Reset Delay
UNDERFREQUENCY 1: Target
UNDERFREQUENCY 1: Events

Enabled
LINE (SRC 2)
UV AND OFFLINE
0.200
0.500
52G/b On(H7a)
OFF
Latched
Enabled

NEUTRL (SRC 1)
Enabled
0.3000 pu
0.00 s
3.000 pu
0.000 pu
0.500 pu
OFF
Self-reset
Enabled

Enabled
LINE (SRC 2)
180 deg
0.00 deg
0.024 pu
10.00 s
0.024 pu
10.00 s
BLOCK On (VO5)
Latched
Enabled

Enabled
BLOCK On (VO5)
LINE (SRC 2)
0.85 pu
56.40 Hz
20.000 s
0.000 s
Latched
Enabled

OVERFREQUENCY
OVERFREQUENCY 1: Function
OVERFREQUENCY 1: Block
OVERFREQUENCY 1: Source
OVERFREQUENCY 1: Pickup
OVERFREQUENCY 1: Pickup Delay
OVERFREQUENCY 1: Reset Delay
OVERFREQUENCY 1: Target
OVERFREQUENCY 1: Events

Enabled
BLOCK On (VO5)
LINE (SRC 2)
64.80 Hz
1.000 s
0.000 s
Latched
Enabled

DIGITAL ELEMENTS
Digital Element 1 Function
Digital Element 1 Name
Digital Element 1 Input
Digital Element 1 Pickup Delay

Enabled
59N
AUX OV 1 OP
0.000 s

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
DIGITAL ELEMENTS (continued from last page)
Digital Element 1 Reset Delay
Digital Element 1 Pickup Led
Digital Element 1 Block
Digital Element 1 Target
Digital Element 1 Events
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function
VT FUSE FAILURE 1: Neutral Wire Open Detection
VT FUSE FAILURE 1: 3rd Harmonic Pickup
VT FUSE FAILURE 2: Function
VT FUSE FAILURE 2: Neutral Wire Open Detection
VT FUSE FAILURE 2: 3rd Harmonic Pickup
VT FUSE FAILURE 3: Function
VT FUSE FAILURE 3: Neutral Wire Open Detection
VT FUSE FAILURE 3: 3rd Harmonic Pickup
VT FUSE FAILURE 4: Function
VT FUSE FAILURE 4: Neutral Wire Open Detection
VT FUSE FAILURE 4: 3rd Harmonic Pickup
FREQUENCY OOB ACCUMULATION
Freq OOB Accumulator Source
Freq OOB Accumulator Min V A
Freq OOB Accumulator Block
Freq OOB Accumulator Target
Freq OOB Accumulator Events
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events

0.000 s
Enabled
OFF
Latched
Enabled

Disabled
Disabled
0.100 pu
Enabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
NEUTRL (SRC 1)
0.10 pu
OFF
Self-reset
Disabled

52G/b
2.0 ms
Enabled
Cont Ip 2
2.0 ms
Disabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
86G1A
2.0 ms
Enabled
86G2A
2.0 ms
Enabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
TRIG OSC
2.0 ms
Enabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
CONTACT INPUT THRESHOLDS
52G/b, Cont Ip 2, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
86G1A, 86G2A, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
TRIG OSC, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

84 Vdc
84 Vdc
84 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P2] Contact Output 8 ID
[P2] Contact Output 8 Operate
[P2] Contact Output 8 Seal-In
[P2] Contact Output 8 Events
[P3] Contact Output 9 ID
[P3] Contact Output 9 Operate
[P3] Contact Output 9 Seal-In
[P3] Contact Output 9 Events
[P4] Contact Output 10 ID
[P4] Contact Output 10 Operate
[P4] Contact Output 10 Seal-In
[P4] Contact Output 10 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[U1] Contact Output 13 ID
[U1] Contact Output 13 Operate
[U1] Contact Output 13 Seal-In
[U1] Contact Output 13 Events
[U2] Contact Output 14 ID
[U2] Contact Output 14 Operate
[U2] Contact Output 14 Seal-In
[U2] Contact Output 14 Events
[U3] Contact Output 15 ID
[U3] Contact Output 15 Operate
[U3] Contact Output 15 Seal-In
[U3] Contact Output 15 Events
[U5] Contact Output 17 ID
[U5] Contact Output 17 Operate
[U5] Contact Output 17 Seal-In
[U5] Contact Output 17 Events
[U6] Contact Output 18 ID
[U6] Contact Output 18 Operate
[U6] Contact Output 18 Seal-In
[U6] Contact Output 18 Events

TRIP 86G-1B
86G-1B TRIP On (VO1)
OFF
Enabled
TRIP 86G-2B
86G-2B TRIP On (VO2)
OFF
Enabled
TRIP 52G TC1
52G TRIP On (VO3)
OFF
Enabled
TRIP 52G TC2
52G TRIP On (VO3)
OFF
Enabled
ANY TRIP (A)
ANY TRIP On (VO4)
OFF
Enabled
24(A)
24A (FE 1) OP
OFF
Enabled
46(A)
GEN UNBAL STG2 OP
OFF
Enabled
81O(A)
OVERFREQ 1 OP
OFF
Enabled
VTFF
SRC2 VT FUSE FAIL OP
OFF
Enabled
27P(A)
PHASE UV1 OP
OFF
Enabled
59P(A)
PHASE OV1 OP
OFF
Enabled
IBF/52G
52G TRIP On (VO3)
OFF
Enabled
TRIG OS G60B
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS T60U
ANY TRIP On (VO4)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events

86G-1B TRIP
Enabled
86G-2B TRIP
Enabled

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
VIRTUAL OUTPUTS (continued from last page)
Virtual Output 3 ID
Virtual Output 3 Events
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5 ID
Virtual Output 5 Events
Virtual Output 6 ID
Virtual Output 6 Events
Virtual Output 8 ID
Virtual Output 8 Events

52G TRIP
Enabled
ANY TRIP
Enabled
BLOCK
Enabled
OSC TRIG
Enabled
Alarm
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 19

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base

No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 20

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Fri Aug 23 16:14:11 2013 Version: 6.00 Settings (Enabled Features)

PAGE 21

GTG G60B_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 1 G60AB\
DEVICE DEFINITION
FILES
ORDER CODE: G60-N04-HKH-F8M-H6P-M8M-P6P-U6P-W67
VERSION: 6.00
DESCRIPTION: GTG G60B
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

PLANTA DE ETAN
Generator 761X201
Overall Unit Protection - T60U

GE Energy

Setting Calculation Sheet


Overall Unit Protection
A) Transformer and Generator Data
Transformer:
Generator:

220 kV (HV)
281.25 MVAG

18.0 kV (LV)
System:

300 MVAT

225/300MVA, YNd1

220 kV (HVS)

UAT:

11.5 MVAUAT

B) Relay , PT and CT Data


Relay Model: GE T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
Relay Ranges: Percent Differential: 0.05 to 1.00 * 5A in 0.01 steps
Slope 1: 15-100%, Slope 2: 50-100%, Break 1: 1.0-2.0, Break 2: 2.0-30.0
Winding F1 Phase CT Ratio: 12,000 / 5
Generator Neutral Side CTs, SRC1, W1
Winding F5 Phase VT Ratio: 18,000 / 120
VT1,SRC1,W2,N = 150
Vsec = 69.3
Winding M1 Phase CT Ratio: 2,000 / 5
UAT HV CTs, SRC3, W3
Winding M5 Phase CT Ratio: 2,000 / 5
GSU HV CTs, SRC2, W2
Winding M5 Neutral CT Ratio: 2,000 / 5
GSU HV Side Neutral CT, SRC2, W2
C) Differential Protection (87U) Settings Calculations
Setting Philosophy: 87U function uses internally compensated values of current. Differential current
setting (IDIFF ) = IF1 + IM1 + IM5. Differential instantaneous function will operate for faults within the
differential zone. The 87U function will be blocked using the average adaptive 2nd harmonic inrush
inhibit function as well as the 5th harmonic overexcitation inhibit function. Reference winding is F1.
Reference Winding and Magnitude Compensation Calculations
IF1 = (MVAT) / (3 * LV) = 9,622 A

Imargin = CTF1/IF1 = 1.247

IM1 = (MVAUAT) / (3 * LVUAT) =

962 A

Imargin = CTM1/IM1 = 2.079

IM5 = (MVAT-MVAUAT) / (3 * HV) =

757 A

Imargin = CTM5/IM5 = 2.642

Magnitude Compensation F1= [CTF1 x kV(LV)] / [CTF1 x kV(LV)] = 1.00 = MCF1


Magnitude Compensation M1= [CTM1 x kV(LVUAT)] / [CTF1 x kV(LV)] = 0.06 = MCM1
Magnitude Compensation M5= [CTM5 x kV(HV)] / [CTF1 x kV(LV)] = 2.04 = MCM5
Expected Currents Through Each Winding During Normal Operation
IF1 = (MVAG) / (3 * LV) = 9,021 A, =
0.752 pu x MCF1 / IF1pu =
IM1 = (MVAUAT) / (3 * LVUAT) =
IM5 = (MVAG-MVAUAT) / (3 * HV) =
IDIFF = IF1 + IM1 + IM5 =

1.000 pu

0.053 pu x MCM1 / IF1pu =

-0.005 pu

708 A, =
0.354 pu x MCM5 / IF1pu =
0.036 pu ==> use 0.3pu pickup for % Diff

-0.959 pu

962 A, =

Expected Currents Through Each Winding During Startup Operation


IF1 = Max LCI current =
550 A, =
0.046 pu
IDIFF = IF1 + IM1 + IM5 = 0.046 pu ==> use 0.15pu pickup for % Diff

Section 2

T60U_R0

PLANTA DE ETAN
Generator 761X201
Overall Unit Protection - T60U

GE Energy

Recommended Settings:
Normal
Percent Differential Pickup Setting :
0.30
pu
Percent Differential Slope 1 Setting :
25%
Percent Differential Break 1 Setting :
2.0
pu
Percent Differential Slope 2 Setting :
90%
Percent Differential Break 2 Setting :
5.0
pu
Inrush Inhibit Function: Adapt. 2nd
Inrush Inhibit Mode: 2-out-3
Inrust Inhibit Level:
20%
Overexcitation Inhibit Function:
5th
Overexcitation Inhibit Level:
20%
Instantaneous Differential Pickup :
4.0

Startup
0.15
25%
1.0
50%
2.0
Adapt. 2nd
2-out-3
20%
5th
20%
disabled

pu
pu
pu

TRANSFORMER SETTINGS AND CTs


Nomber of Windings:
Rated(MVA)
Nom. (kV)
Connection
Grounding
Angle WRT
CT primary
CT sec. tap
Inom. Prim.
Inom.Sec.

W1
300
18
DELTA
NO
0
12000
5
9622.5
4.009

Rotations

ABC

DIFF / RSTR CHARACTERISTIC

3
W2
300
220
WYE
YES
-330
2000
5
787.3
1.968

W3
W4
W5
11.5
0
0
18
13.8
230
DELTA
WYE ZIG-ZAG
NO
YES
NO
0
-30
0
2000 104.34
1000
5
5
5
368.9
0.0
0.0
0.922 0.000
0.000

Select Magnitude Ref. Winding:

TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle

IA

IB

IC

3.76
0.0

3.76
-120.0

3.76
120.0

1.77
-150.0

1.77
90.0

1.77
-30.0

W6

DIFFERENTIALDiff. min. PKP


Kneepoint 1
Kneepoint 2

0
69
WYE
YES
0
1000
5
0.0
0.000

RESTRAINT GRAPH
0.30 Slope1
25.0
2.00
5.00 Slope2
90.0

Pre-calculated graph points


Id/Ir, (%) Ph A
Ph B
Ph C
25.0
25.0
25.0

>>Pre-calculated ratio of the point from the


characteristic, corresponding to the same
restraint as per the actual Id/Ir ratio. The trip
occurs, when the actual Id/Ir ratio,(%) is bigger
than the pre-calculated Id/Ir ratio, (%)

ACTUAL VALUES

I diff, pu
12

Operating Characteristic

11
10
9

0.92
60.0

0.92
-60.0

0.00
0.0

0.00
0.0

0.00
0.0

0.00

0.00

0.00

0.0

0.0

0.0

W5
Magnitude
Angle
W6
Magnitude
Angle

DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.00
0.00
Angle
-180.0
-300.0

Icd
0.00
-60.0

RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.75
0.75

Icr
0.75

8
7
6

0.92
-180.0

Magnitude Ref. Winding #:

5
4

Actual Differential/Restraint Ratio


Actual
ph A % ph B % ph C %
Id/Ir ratio
0.0
0.0
0.0

3
2
1

DIFF. OPERATION

0
0

Slope characteristics

0.00
0.0

0.00
0.0

6
Iad

0.00
0.0

7
Ibd

9
Icd

10

11
12
I restr, pu

NO TRIP
Ia
No trip

Ib
No trip

Ic
No trip

E) HV Winding Phase Overcurrent (50/51T) Settings Calculations


Setting Philosophy: Set relay for IEC B (Very Inverse) curve. Set High Voltage winding (W2) TOC
unit pickup for 1.27 x GSU ONAF rating. Set TOC time dial to coordinate with the transformer's
secondary and/or tertiary winding thermal and mechanical withstand curves per C57.109-1993.
Phase TOC1 Pickup: 1,000 A, =
0.500 CT multiples
Time Dial: 0.60
Phase IOC1 Pickup: 10,000 A, =
5.00 CT multiples
F) HV Winding Ground Overcurrent (51TN) Settings Calculations
Setting Philosophy: Set relay for IEC A (Inverse) curve. Set GSU neutral-ground TOC unit to
pickup for 25% of the neutral-ground CT rating. Set TOC time dial to operate at 1.0 second for the
transformer ground fault contribution.
Ground TOC1 Pickup:
500 A, =
0.25 CT multiples
Time Dial : 0.29
Section 2

T60U_R0

PLANTA DE ETAN
Generator 761X201
Overall Unit Protection - T60U

GE Energy

CURRENT IN AMPERES X 10 AT 220000 VOLTS


.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

GSU-1
FLA
50/51T T60
BUS-1

5 6 7 8 9 10000
1000
900
800
700
600
500

400

400

300

300
50T
51T

200

GSU-1
225 / 300 MVA
220 - 18 kV
10%

100
90
80
70
60
50
40

TIME IN SECONDS

200

2000/5

100
90
80
70
60
50
40

GTG GEN1

30

30

20

20

10
9
8
7
6
5

50/51T T60
GE T60
51/50 IEC
Curve B (BS142)
CT Ratio = 2000/5
Tap = 0.5 (1000A)
Time Multiplier = 0.6
Inst. Pickup = 5 (10000A)

4
3

10
9
8
7
6
5

GSU-1
225000 / 300000 kVA
10%

4
3

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

.2

GSU-1
225000 / 300000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

TIME IN SECONDS

1000
900
800
700
600
500

.5 .6

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 220000 VOLTS

General Electric
Company

EasyPower

50/51T

TIME-CURRENT CURVES
FAULT:

PHASE

DATE:

Aug 23, 2013

BY:
REVISION: 0
PLANTA DE ETAN

Section 2

T60U_R0

General Electric
Company

EasyPower

50/51T

TIME-CURRENT CURVES
PLANTA DE ETAN
Generator 761X201
Overall Unit Protection - T60U

GE Energy

FAULT:

PHASE

DATE:

Aug 23, 2013

BY:
REVISION: 0

PLANTA DE ETAN

CURRENT IN AMPERES X 10 AT 220000 VOLTS


.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

57
2

51TN GSU-1
FLA

BUS-1

400

400
300

3.656

300

5 6 7 8 9 10000
1000
900
800
700
600
500

11
.

1000
900
800
700
600
500

.5 .6

200

200
51TN

100
90
80
70
60
50

100
90
80
70
60
50

70
4

40
30
20

GSU-1
225000 / 300000 kVA
10%

10
9
8
7
6
5

10
9
8
7
6
5

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

.2

GSU-1
225000 / 300000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 220000 VOLTS

General Electric
Company

EasyPower

51TN

TIME-CURRENT CURVES
FAULT:

GROUND

DATE:

Aug 23, 2013

BY:
REVISION: 0
PLANTA DE ETAN

Section 2

T60U_R0

TIME IN SECONDS

20

GTG GEN1

0.

30

19.608

51TN
GE T60
51N/50N IEC
Curve A (BS142)
CT Ratio = 2000/5
Tap = 0.25 (500A)
Time Multiplier = 0.29

40

TIME IN SECONDS

GSU-1
225 / 300 MVA
220 - 18 kV
10%

2000/5

CURRENT IN AMPERES X 10 AT 220000 VOLTS

General Electric
Company

EasyPower

TIME-CURRENT CURVES
PLANTA DE ETAN
Generator 761X201
Overall Unit Protection - T60U

51TN

GE Energy

FAULT:

GROUND

DATE:

Aug 23, 2013

BY:
REVISION: 0

PLANTA DE ETAN

Section 2

T60U_R0

PLANTA DE ETAN
Generator 761X201
Overall Unit Protection - T60U

GE Energy

G) Volts-per-hertz (24) Settings Calculations


Setting Philosophy: Set to protect transformer based on theTypical Transformer V/Hz composite of
curves in C37.91, Guide for Protective Relay Applications to Power Transformers.
V/Hz 1 Pickup :
1.10 pu V/Hz
V/Hz 1 Curve Shape : Inverse A
V/Hz 1 TD Multiplier : 0.80
V/Hz 1 Reset :
600 seconds
Transformer V/Hz Protection

1.40

1.35

1.30

1.25

1.20

1.15

1.10

1.05

1.00
1

10

100
24

Section 2

T60U_R0

1000

10000

Transformer

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsA Deadband
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsA Deadband
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 33 ctlModel
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 Value
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 25 max
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max

1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI11 OpCnt
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt
Clear XSWI16 OpCnt

No
No
No
No
No
No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

4
Automatic Overwrite
25 %
TRIG OSC On (VO2)
64 samples/cycle
XFMR INST DIFF OP
XFMR PCNT DIFF OP
PHASE IOC1 OP
PHASE TOC1 OP
GROUND TOC1 OP
VOLTS PER HERTZ 1 OP
86U On (VO1)
Xfmr Iad Mag
Xfmr Ibd Mag
Xfmr Icd Mag
Xfmr Iar Mag
Xfmr Ibr Mag
Xfmr Icr Mag
Xfmr Harm2 Iad Mag
Xfmr Harm5 Iad Mag
Xfmr Harm2 Ibd Mag
Xfmr Harm5 Ibd Mag
Xfmr Harm2 Icd Mag
Xfmr Harm5 Icd Mag
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ig RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate

Continuous
OFF
60000 msec

DEMAND
Current Method
Power Method
Interval
Trigger

Thermal Exponential
Thermal Exponential
15 MIN
OFF

USER-PROGRAMMABLE LEDS
LED TEST
Function
Control

Enabled
ANY SELF TESTS

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input

ANY TRIP On (VO3)


ANY SELF TESTS

USER PROGRAMMABLE LEDS


LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE

XFMR INST DIFF OP


Latched
XFMR PCNT DIFF OP
Latched
PHASE IOC1 OP
Latched
PHASE TOC1 OP
Latched
GROUND TOC1 OP
Latched
VOLTS PER HERTZ 1 OP
Latched

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG T60U

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary
CT M5: Phase CT Primary
CT M5: Phase CT Secondary
CT M5: Ground CT Primary
CT M5: Ground CT Secondary

12000 A
5A
12000 A
5A
2000 A
5A
1A
1A
2000 A
5A
2000 A
5A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio

Wye
69.3 V
150.00 :1
Vag
66.4 V
1.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

60 Hz
ABC
GEN (SRC 1)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT

GEN
F1
F1
F5
None
GSU HV
M5
M5
None
None

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
SIGNAL SOURCES (continued from last page)
SOURCE 3: Name
SOURCE 3: Phase CT
SOURCE 3: Ground CT
SOURCE 3: Phase VT
SOURCE 3: Auxiliary VT
TRANSFORMER
GENERAL
Number Of Windings
Reference Winding Selection
Phase Compensation
Load Loss At Rated Load
Rated Winding Temperature Rise
No Load Loss
Type Of Cooling
Top-oil Rise Over Ambient
Thermal Capacity
Winding Thermal Time Constant

UAT
M1
M1
None
None

3
Winding 1
Internal (software)
460 kW
65C (oil)
145 kW
FA
35 C
100.00 kWh/C
2.00 min

WINDINGS
WINDING 1: Source
WINDING 1: Rated MVA
WINDING 1: Nominal Phs-phs Voltage
WINDING 1: Connection
WINDING 1: Grounding
WINDING 1: Angle Wrt Winding 1
WINDING 1: Resistance
WINDING 2: Source
WINDING 2: Rated MVA
WINDING 2: Nominal Phs-phs Voltage
WINDING 2: Connection
WINDING 2: Grounding
WINDING 2: Angle Wrt Winding 1
WINDING 2: Resistance
WINDING 3: Source
WINDING 3: Rated MVA
WINDING 3: Nominal Phs-phs Voltage
WINDING 3: Connection
WINDING 3: Grounding
WINDING 3: Angle Wrt Winding 1
WINDING 3: Resistance

GEN (SRC 1)
300.000 MVA
18.000 kV
Delta
Not within zone
0.0 deg
0.0021 ohms
GSU HV (SRC 2)
300.000 MVA
220.000 kV
Wye
Within zone
-330.0 deg
0.1573 ohms
UAT (SRC 3)
11.500 MVA
18.000 kV
Delta
Not within zone
-330.0 deg
0.1573 ohms

THERMAL INPUTS
Winding Currents
Ambient Temperature Sensor
Ambient Temperature January Average
Ambient Temperature February Average
Ambient Temperature March Average
Ambient Temperature April Average
Ambient Temperature May Average
Ambient Temperature June Average
Ambient Temperature July Average
Ambient Temperature August Average
Ambient Temperature September Average
Ambient Temperature October Average
Ambient Temperature November Average
Ambient Temperature December Average
Top Oil Temperature Sensor

GEN (SRC 1)
RRTD Input 1
-20 C
-30 C
-10 C
10 C
20 C
30 C
30 C
30 C
20 C
10 C
10 C
-10 C
RRTD Input 1

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
FLEXCURVE C (continued from last page)
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18

PHASE IOC1 OP
PHASE TOC1 OP
XFMR INST DIFF OP
XFMR PCNT DIFF OP
VOLTS PER HERTZ 1 OP
OR(5)
= 86U (VO1)
86U On (VO1)
GROUND TOC1 OP
OR(2)
= ANY TRIP (VO3)
TRIG OSC On(P7a)
POSITIVE ONE SHOT
ANY TRIP On (VO3)
POSITIVE ONE SHOT
OR(2)
= TRIG OSC (VO2)
END

GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]
Function
Pickup
Slope 1
Break 1
Break 2
Slope 2
Inrush Inhibit Function
Inrush Inhibit Mode
Inrush Inhibit Level
Overexcitation Inhibit Function
Overexcitation Inhibit Level
Block
Target
Events

Enabled
0.300 pu
25 %
2.000 pu
5.000 pu
90 %
Adapt. 2nd
2-out-of-3
20.0 % fo
5th
20.0 % fo
OFF
Latched
Enabled

INSTANTANEOUS DIFFERENTIAL [GROUP 1]


Function
Pickup
Block
Target
Events
PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events

Enabled
4.000 pu
OFF
Latched
Enabled

Enabled
GSU HV (SRC 2)
Phasor
0.950 pu
IEC Curve B
0.60
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
PHASE IOC [GROUP 1]
PHASE IOC1: Function
PHASE IOC1: Source
PHASE IOC1: Pickup
PHASE IOC1: Delay
PHASE IOC1: Reset Delay
PHASE IOC1: Block A
PHASE IOC1: Block B
PHASE IOC1: Block C
PHASE IOC1: Target
PHASE IOC1: Events

Enabled
GSU HV (SRC 2)
5.000 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled

GROUND CURRENT
GROUND TOC [GROUP 1]
GROUND TOC1: Function
GROUND TOC1: Source
GROUND TOC1: Input
GROUND TOC1: Pickup
GROUND TOC1: Curve
GROUND TOC1: TD Multiplier
GROUND TOC1: Reset
GROUND TOC1: Block
GROUND TOC1: Target
GROUND TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.250 pu
IEC Curve A
0.29
Instantaneous
OFF
Latched
Enabled

RESTRICTED GROUND FAULT [GROUP 1]


RGF1: Function
RGF1: Source
RGF1: Pickup
RGF1: Slope
RGF1: Pickup Delay
RGF1: Reset Delay
RGF1: Block
RGF1: Target
RGF1: Events
VOLTAGE ELEMENTS
VOLTS PER HERTZ [GROUP 1]
VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: VHZ Voltage Mode
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
GROUP 2
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 2]
Function
Pickup
Slope 1
Break 1
Break 2
Slope 2
Inrush Inhibit Function
Inrush Inhibit Mode
Inrush Inhibit Level
Overexcitation Inhibit Function
Overexcitation Inhibit Level
Block
Target
Events

Enabled
GSU HV (SRC 2)
0.050 pu
50 %
10.00 s
1.00 s
OFF
Latched
Enabled

Enabled
GEN (SRC 1)
Phase to Ground
1.10 pu
Inverse A
0.80
600.0 s
OFF
Latched
Enabled

Enabled
0.150 pu
25 %
1.000 pu
2.000 pu
50 %
Adapt. 2nd
2-out-of-3
20.0 % fo
5th
20.0 % fo
OFF
Latched
Enabled

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
PHASE CURRENT
PHASE TOC [GROUP 2]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.950 pu
IEC Curve B
0.60
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

PHASE IOC [GROUP 2]


PHASE IOC1: Function
PHASE IOC1: Source
PHASE IOC1: Pickup
PHASE IOC1: Delay
PHASE IOC1: Reset Delay
PHASE IOC1: Block A
PHASE IOC1: Block B
PHASE IOC1: Block C
PHASE IOC1: Target
PHASE IOC1: Events

Enabled
GSU HV (SRC 2)
5.000 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled

GROUND CURRENT
GROUND TOC [GROUP 2]
GROUND TOC1: Function
GROUND TOC1: Source
GROUND TOC1: Input
GROUND TOC1: Pickup
GROUND TOC1: Curve
GROUND TOC1: TD Multiplier
GROUND TOC1: Reset
GROUND TOC1: Block
GROUND TOC1: Target
GROUND TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.250 pu
IEC Curve A
0.29
Instantaneous
OFF
Latched
Enabled

RESTRICTED GROUND FAULT [GROUP 2]


RGF1: Function
RGF1: Source
RGF1: Pickup
RGF1: Slope
RGF1: Pickup Delay
RGF1: Reset Delay
RGF1: Block
RGF1: Target
RGF1: Events
VOLTAGE ELEMENTS
VOLTS PER HERTZ [GROUP 2]
VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: VHZ Voltage Mode
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
CONTROL ELEMENTS
SETTING GROUPS
Function

Enabled
GSU HV (SRC 2)
0.050 pu
50 %
10.00 s
1.00 s
OFF
Latched
Enabled

Enabled
GEN (SRC 1)
Phase to Ground
1.10 pu
Inverse A
0.80
600.0 s
OFF
Latched
Enabled

Enabled

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
SETTING GROUPS (continued from last page)
Block
Group 2 Activate On
Group 3 Activate On
Group 4 Activate On
Group 5 Activate On
Group 6 Activate On
Group 1 Name
Group 2 Name
Group 3 Name
Group 4 Name
Group 5 Name
Group 6 Name
Events
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function
VT FUSE FAILURE 1: Neutral Wire Open Detection
VT FUSE FAILURE 1: 3rd Harmonic Pickup
VT FUSE FAILURE 2: Function
VT FUSE FAILURE 2: Neutral Wire Open Detection
VT FUSE FAILURE 2: 3rd Harmonic Pickup
VT FUSE FAILURE 3: Function
VT FUSE FAILURE 3: Neutral Wire Open Detection
VT FUSE FAILURE 3: 3rd Harmonic Pickup
VT FUSE FAILURE 4: Function
VT FUSE FAILURE 4: Neutral Wire Open Detection
VT FUSE FAILURE 4: 3rd Harmonic Pickup
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events

OFF
87TSSX On(H7c)
OFF
OFF
OFF
OFF

Disabled

Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu

Cont Ip 1
2.0 ms
Disabled
87TSSX
2.0 ms
Enabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
TRIG OSC
2.0 ms
Enabled
Cont Ip 6
2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
Cont Ip 9
2.0 ms
Disabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
CONTACT INPUT THRESHOLDS
Cont Ip 1, 87TSSX, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
TRIG OSC, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
Cont Ip 9, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

84 Vdc
84 Vdc
33 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[H5] Contact Output 5 ID
[H5] Contact Output 5 Operate
[H5] Contact Output 5 Seal-In
[H5] Contact Output 5 Events
[H6] Contact Output 6 ID
[H6] Contact Output 6 Operate
[H6] Contact Output 6 Seal-In
[H6] Contact Output 6 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[P6] Contact Output 12 ID
[P6] Contact Output 12 Operate
[P6] Contact Output 12 Seal-In
[P6] Contact Output 12 Events

PH TRIP 86U
86U On (VO1)
OFF
Enabled
TRIP 52L TC1
GROUND TOC1 OP
OFF
Enabled
TRIP 52L TC2
GROUND TOC1 OP
OFF
Enabled
IBF 52L TC1
GROUND TOC1 OP
OFF
Enabled
IBF 52L TC2
GROUND TOC1 OP
OFF
Disabled
ALARM
ANY TRIP On (VO3)
OFF
Enabled
TRG OSC G60A
ANY TRIP On (VO3)
OFF
Enabled
TRG OSC G60B
ANY TRIP On (VO3)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events

86U
Enabled
TRIG OSC
Enabled
ANY TRIP
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base

No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode

1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

Fri Aug 23 17:31:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

T60U_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 2 T60U\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: GTG T60U
TEXT COLOR
IEC 61850 GOOSE UINTEGERS INPUTS (continued from last page)
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

PLANTA DE ETAN
Generator 761X201
Step-Up Transformer Protection - T60U

GE Energy

Setting Calculation Sheet


Step-Up Transformer Protection
A) Transformer and Generator Data
Transformer:
Generator:

220 kV (HV)
281.25 MVAG

300 MVAT

18.0 kV (LV)
System:

225/300MVA, YNd1

220 kV (HVS)

B) Relay , PT and CT Data


Relay Model: GE T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
Relay Ranges: Percent Differential: 0.05 to 1.00 * 5A in 0.01 steps
Slope 1: 15-100%, Slope 2: 50-100%, Break 1: 1.0-2.0, Break 2: 2.0-30.0
Winding F1 Phase CT Ratio: 12,000 / 5
Generator Neutral Side CTs, SRC1, W1
Winding F5 Phase VT Ratio: 18,000 / 120
VT1,SRC1,W2,N = 150
Vsec = 69.3
Winding M5 Phase CT Ratio: 2,000 / 5
GSU HV CTs, SRC2, W2
Winding M5 Neutral CT Ratio: 2,000 / 5
GSU HV Side Neutral CT, SRC2, W2
C) Differential Protection (87T) Settings Calculations
Setting Philosophy: 87T function uses internally compensated values of current. Differential current
setting (IDIFF ) = IF1 + IM5. Differential instantaneous function will operate for faults within the
differential zone. The 87T function will be blocked using the average adaptive 2nd harmonic inrush
inhibit function as well as the 5th harmonic overexcitation inhibit function. Reference winding is F1.
Reference Winding and Magnitude Compensation Calculations
IF1 = (MVAT) / (3 * LV) = 9,622 A
Imargin = CTF1/IF1 = 1.247
IM5 = (MVAT) / (3 * HV) =

787 A

Imargin = CTM5/IM5 = 2.540

Magnitude Compensation F1= [CTF1 x kV(LV)] / [CTF1 x kV(LV)] = 1.00 = MCF1


Magnitude Compensation M5= [CTM5 x kV(HV)] / [CTF1 x kV(LV)] = 2.04 = MCM5
Expected Currents Through Each Winding During Normal Operation
IF1 = (MVAG) / (3 * LV) = 9,021 A, =
0.752 pu x MCF1 / IF1pu = 1.000 pu
IM5 = (MVAG) / (3 * HV) =
IDIFF = IF1 + IM5 =
Recommended Settings:

Section 3

738 A, =
0.369 pu x MCM5 / IF1pu =
0.000 pu ==> use 0.3pu pickup for % Diff

-1.000 pu

Percent Differential Pickup Setting : 0.30


pu
Percent Differential Slope 1 Setting : 25%
Percent Differential Break 1 Setting :
2.0
pu
Percent Differential Slope 2 Setting : 90%
Percent Differential Break 2 Setting :
5.0
pu
Inrush Inhibit Function: Adapt. 2nd
Inrush Inhibit Mode: 2-out-3
Inrust Inhibit Level: 20%
Overexcitation Inhibit Function:
5th
Overexcitation Inhibit Level: 20%
Instantaneous Differential Pickup :
4.0
T60U_R0

PLANTA DE ETAN
Generator 761X201
Step-Up Transformer Protection - T60U

GE Energy

TRANSFORMER SETTINGS AND CTs


Nomber of Windings:
Rated(MVA)
Nom. (kV)
Connection
Grounding
Angle WRT
CT primary
CT sec. tap
Inom. Prim.
Inom.Sec.

W1
300
18
DELTA
NO
0
12000
5
9622.5
4.009

Rotations

ABC

DIFF / RSTR CHARACTERISTIC

2
W2
300
220
WYE
YES
-330
2000
5
787.3
1.968

W3

W5
Magnitude
Angle
W6
Magnitude
Angle

W5

W6

0
0
0
18
13.8
230
DELTA
WYE ZIG-ZAG
NO
YES
NO
0
-30
0
2000 104.34
1000
5
5
5
0.0
0.0
0.0
0.000 0.000
0.000

Select Magnitude Ref. Winding:

TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle

W4

IA

IB

IC

3.76
0.0

3.76
-120.0

3.76
120.0

1.85
-150.0

1.85
90.0

1.85
-30.0

DIFFERENTIALDiff. min. PKP


Kneepoint 1
Kneepoint 2

0
69
WYE
YES
0
1000
5
0.0
0.000

RESTRAINT GRAPH
0.30 Slope1
25.0
2.00
5.00 Slope2
90.0

Pre-calculated graph points


Id/Ir, (%) Ph A
Ph B
Ph C
25.0
25.0
25.0

>>Pre-calculated ratio of the point from the


characteristic, corresponding to the same
restraint as per the actual Id/Ir ratio. The trip
occurs, when the actual Id/Ir ratio,(%) is bigger
than the pre-calculated Id/Ir ratio, (%)

ACTUAL VALUES

I diff, pu
12

Operating Characteristic

11
10
9

0.00
0.0

0.00
0.0

0.00
0.0

0.00
0.0

0.00
0.0

0.00

0.00

0.00

0.0

0.0

0.0

DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.00
0.00
Angle
0.0
-120.0

Icd
0.00
-240.0

RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.75
0.75

Icr
0.75

8
7
6

0.00
0.0

Magnitude Ref. Winding #:

5
4

Actual Differential/Restraint Ratio


Actual
ph A % ph B % ph C %
Id/Ir ratio
0.0
0.0
0.0

3
2
1

DIFF. OPERATION

0
0

Slope characteristics

0.00
0.0

0.00
0.0

6
Iad

0.00
0.0

7
Ibd

9
Icd

10

11
12
I restr, pu

NO TRIP
Ia
No trip

Ib
No trip

Ic
No trip

E) HV Winding Phase Overcurrent (50/51T) Settings Calculations


Setting Philosophy: Set relay for IEC B (Very Inverse) curve. Set High Voltage winding (W2) TOC
unit pickup for 1.27 x GSU ONAF rating. Set TOC time dial to coordinate with the transformer's
secondary and/or tertiary winding thermal and mechanical withstand curves per C57.109-1993.
Phase TOC1 Pickup: 1,000 A, =
0.500 CT multiples
Time Dial: 0.60
Phase IOC1 Pickup: 10,000 A, =
5.00 CT multiples
F) HV Winding Ground Overcurrent (51TN) Settings Calculations
Setting Philosophy: Set relay for IEC A (Inverse) curve. Set GSU neutral-ground TOC unit to
pickup for 25% of the neutral-ground CT rating. Set TOC time dial to operate at 1.0 second for the
transformer ground fault contribution.
Ground TOC1 Pickup:
500 A, =
0.25 CT multiples
Time Dial : 0.29

Section 3

T60U_R0

PLANTA DE ETAN
Generator 761X201
Step-Up Transformer Protection - T60U

GE Energy

CURRENT IN AMPERES X 10 AT 220000 VOLTS


.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

GSU-1
FLA
50/51T T60
BUS-1

5 6 7 8 9 10000
1000
900
800
700
600
500

400

400

300

300
50T
51T

200

GSU-1
225 / 300 MVA
220 - 18 kV
10%

100
90
80
70
60
50
40

TIME IN SECONDS

200

2000/5

100
90
80
70
60
50
40

GTG GEN1

30

30

20

20

10
9
8
7
6
5

50/51T T60
GE T60
51/50 IEC
Curve B (BS142)
CT Ratio = 2000/5
Tap = 0.5 (1000A)
Time Multiplier = 0.6
Inst. Pickup = 5 (10000A)

4
3

10
9
8
7
6
5

GSU-1
225000 / 300000 kVA
10%

4
3

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

.2

GSU-1
225000 / 300000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

TIME IN SECONDS

1000
900
800
700
600
500

.5 .6

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 220000 VOLTS

General Electric
Company

EasyPower

50/51T

TIME-CURRENT CURVES
FAULT:

PHASE

DATE:

Aug 23, 2013

BY:
REVISION: 0
PLANTA DE ETAN

Section 3

T60U_R0

PLANTA DE ETAN
Generator 761X201
Step-Up Transformer Protection - T60U

GE Energy

CURRENT IN AMPERES X 10 AT 220000 VOLTS


.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

57
2

51TN GSU-1
FLA

BUS-1

400

400
300

3.656

300

5 6 7 8 9 10000
1000
900
800
700
600
500

11
.

1000
900
800
700
600
500

.5 .6

200

200
51TN

100
90
80
70
60
50

100
90
80
70
60
50

70
4

40
30
20

GSU-1
225000 / 300000 kVA
10%

10
9
8
7
6
5

10
9
8
7
6
5

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

.2

GSU-1
225000 / 300000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 220000 VOLTS

General Electric
Company

EasyPower

51TN

TIME-CURRENT CURVES
FAULT:

GROUND

DATE:

Aug 23, 2013

BY:
REVISION: 0
PLANTA DE ETAN

Section 3

T60U_R0

TIME IN SECONDS

20

GTG GEN1

0.

30

19.608

51TN
GE T60
51N/50N IEC
Curve A (BS142)
CT Ratio = 2000/5
Tap = 0.25 (500A)
Time Multiplier = 0.29

40

TIME IN SECONDS

GSU-1
225 / 300 MVA
220 - 18 kV
10%

2000/5

PLANTA DE ETAN
Generator 761X201
Step-Up Transformer Protection - T60U

GE Energy

G) Volts-per-hertz (24) Settings Calculations


Setting Philosophy: Set to protect transformer based on theTypical Transformer V/Hz composite of
curves in C37.91, Guide for Protective Relay Applications to Power Transformers.
V/Hz 1 Pickup :
1.10 pu V/Hz
V/Hz 1 Curve Shape : Inverse A
V/Hz 1 TD Multiplier : 0.80
V/Hz 1 Reset :
600 seconds
Transformer V/Hz Protection

1.40

1.35

1.30

1.25

1.20

1.15

1.10

1.05

1.00
1

10

100
24

Section 3

T60U_R0

1000

10000

Transformer

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsA Deadband
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsA Deadband
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 33 ctlModel
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 Value
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 25 max
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max

1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI11 OpCnt
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt
Clear XSWI16 OpCnt

No
No
No
No
No
No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

4
Automatic Overwrite
25 %
TRIG OSC On (VO2)
64 samples/cycle
XFMR INST DIFF OP
XFMR PCNT DIFF OP
PHASE IOC1 OP
PHASE TOC1 OP
GROUND TOC1 OP
VOLTS PER HERTZ 1 OP
86T On (VO1)
63PTX On(H7A)
Xfmr Iad Mag
Xfmr Ibd Mag
Xfmr Icd Mag
Xfmr Iar Mag
Xfmr Ibr Mag
Xfmr Icr Mag
Xfmr Harm2 Iad Mag
Xfmr Harm5 Iad Mag
Xfmr Harm2 Ibd Mag
Xfmr Harm5 Ibd Mag
Xfmr Harm2 Icd Mag
Xfmr Harm5 Icd Mag
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ig RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate

Continuous
OFF
60000 msec

DEMAND
Current Method
Power Method
Interval
Trigger

Thermal Exponential
Thermal Exponential
15 MIN
OFF

USER-PROGRAMMABLE LEDS
LED TEST
Function
Control

Enabled
ANY SELF TESTS

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input

ANY TRIP On (VO3)


ANY SELF TESTS

USER PROGRAMMABLE LEDS


LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE

XFMR INST DIFF OP


Latched
XFMR PCNT DIFF OP
Latched
PHASE IOC1 OP
Latched
PHASE TOC1 OP
Latched
GROUND TOC1 OP
Latched
VOLTS PER HERTZ 1 OP
Latched
63PTX On(H7A)
Latched

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG T60T

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary
CT M5: Phase CT Primary
CT M5: Phase CT Secondary
CT M5: Ground CT Primary
CT M5: Ground CT Secondary

12000 A
5A
12000 A
5A
1A
1A
1A
1A
2000 A
5A
2000 A
5A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio

Wye
69.3 V
150.00 :1
Vag
66.4 V
1.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

60 Hz
ABC
GEN (SRC 1)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT

GEN
F1
F1
F5
None
GSU HV
M5

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
SIGNAL SOURCES (continued from last page)
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT
TRANSFORMER
GENERAL
Number Of Windings
Reference Winding Selection
Phase Compensation
Load Loss At Rated Load
Rated Winding Temperature Rise
No Load Loss
Type Of Cooling
Top-oil Rise Over Ambient
Thermal Capacity
Winding Thermal Time Constant

M5
None
None

2
Winding 1
Internal (software)
460 kW
65C (oil)
145 kW
FA
35 C
100.00 kWh/C
2.00 min

WINDINGS
WINDING 1: Source
WINDING 1: Rated MVA
WINDING 1: Nominal Phs-phs Voltage
WINDING 1: Connection
WINDING 1: Grounding
WINDING 1: Angle Wrt Winding 1
WINDING 1: Resistance
WINDING 2: Source
WINDING 2: Rated MVA
WINDING 2: Nominal Phs-phs Voltage
WINDING 2: Connection
WINDING 2: Grounding
WINDING 2: Angle Wrt Winding 1
WINDING 2: Resistance

GEN (SRC 1)
300.000 MVA
18.000 kV
Delta
Not within zone
0.0 deg
0.0021 ohms
GSU HV (SRC 2)
300.000 MVA
220.000 kV
Wye
Within zone
-330.0 deg
0.1573 ohms

THERMAL INPUTS
Winding Currents
Ambient Temperature Sensor
Ambient Temperature January Average
Ambient Temperature February Average
Ambient Temperature March Average
Ambient Temperature April Average
Ambient Temperature May Average
Ambient Temperature June Average
Ambient Temperature July Average
Ambient Temperature August Average
Ambient Temperature September Average
Ambient Temperature October Average
Ambient Temperature November Average
Ambient Temperature December Average
Top Oil Temperature Sensor

GEN (SRC 1)
RRTD Input 1
-20 C
-30 C
-10 C
10 C
20 C
30 C
30 C
30 C
20 C
10 C
10 C
-10 C
RRTD Input 1

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2

VOLTS PER HERTZ 1 OP


PHASE IOC1 OP

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
FLEXLOGIC EQUATION EDITOR (continued from last page)
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19
GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]
Function
Pickup
Slope 1
Break 1
Break 2
Slope 2
Inrush Inhibit Function
Inrush Inhibit Mode
Inrush Inhibit Level
Overexcitation Inhibit Function
Overexcitation Inhibit Level
Block
Target
Events
INSTANTANEOUS DIFFERENTIAL [GROUP 1]
Function
Pickup
Block
Target
Events

PHASE TOC1 OP
63PTX On(H7A)
XFMR INST DIFF OP
XFMR PCNT DIFF OP
OR(6)
= 86T (VO1)
86T On (VO1)
GROUND TOC1 OP
OR(2)
= ANY TRIP (VO3)
Cont Ip 5 On(P7A)
POSITIVE ONE SHOT
ANY TRIP On (VO3)
POSITIVE ONE SHOT
OR(2)
= TRIG OSC (VO2)
END

Enabled
0.300 pu
25 %
2.000 pu
5.000 pu
90 %
Adapt. 2nd
2-out-of-3
20.0 % fo
5th
20.0 % fo
OFF
Latched
Enabled
Enabled
4.000 pu
OFF
Latched
Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.950 pu
IEC Curve B
0.60
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

PHASE IOC [GROUP 1]


PHASE IOC1: Function
PHASE IOC1: Source
PHASE IOC1: Pickup
PHASE IOC1: Delay
PHASE IOC1: Reset Delay
PHASE IOC1: Block A

Enabled
GSU HV (SRC 2)
5.000 pu
0.00 s
0.00 s
OFF

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
PHASE IOC [GROUP 1] (continued from last page)
PHASE IOC1: Block B
PHASE IOC1: Block C
PHASE IOC1: Target
PHASE IOC1: Events
GROUND CURRENT
GROUND TOC [GROUP 1]
GROUND TOC1: Function
GROUND TOC1: Source
GROUND TOC1: Input
GROUND TOC1: Pickup
GROUND TOC1: Curve
GROUND TOC1: TD Multiplier
GROUND TOC1: Reset
GROUND TOC1: Block
GROUND TOC1: Target
GROUND TOC1: Events
RESTRICTED GROUND FAULT [GROUP 1]
RGF1: Function
RGF1: Source
RGF1: Pickup
RGF1: Slope
RGF1: Pickup Delay
RGF1: Reset Delay
RGF1: Block
RGF1: Target
RGF1: Events
VOLTAGE ELEMENTS
VOLTS PER HERTZ [GROUP 1]
VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: VHZ Voltage Mode
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
CONTROL ELEMENTS
SETTING GROUPS
Function
Block
Group 2 Activate On
Group 3 Activate On
Group 4 Activate On
Group 5 Activate On
Group 6 Activate On
Group 1 Name
Group 2 Name
Group 3 Name
Group 4 Name
Group 5 Name
Group 6 Name
Events
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function
VT FUSE FAILURE 1: Neutral Wire Open Detection
VT FUSE FAILURE 1: 3rd Harmonic Pickup
VT FUSE FAILURE 2: Function
VT FUSE FAILURE 2: Neutral Wire Open Detection
VT FUSE FAILURE 2: 3rd Harmonic Pickup

OFF
OFF
Latched
Enabled

Enabled
GSU HV (SRC 2)
Phasor
0.250 pu
IEC Curve A
0.29
Instantaneous
OFF
Latched
Enabled
Enabled
GSU HV (SRC 2)
0.050 pu
50 %
10.00 s
1.00 s
OFF
Latched
Enabled

Enabled
GEN (SRC 1)
Phase to Ground
1.10 pu
Inverse A
0.80
600.0 s
OFF
Latched
Enabled

Enabled
OFF
Cont Ip 2 On(H7C)
OFF
OFF
OFF
OFF

Disabled

Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
VT FUSE FAILURE (continued from last page)
VT FUSE FAILURE 3: Function
VT FUSE FAILURE 3: Neutral Wire Open Detection
VT FUSE FAILURE 3: 3rd Harmonic Pickup
VT FUSE FAILURE 4: Function
VT FUSE FAILURE 4: Neutral Wire Open Detection
VT FUSE FAILURE 4: 3rd Harmonic Pickup
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events

Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu

63PTX
2.0 ms
Enabled
Cont Ip 2
2.0 ms
Disabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
Cont Ip 5
2.0 ms
Disabled
Cont Ip 6
2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
Cont Ip 9
2.0 ms
Disabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled

CONTACT INPUT THRESHOLDS


63PTX, Cont Ip 2, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
Cont Ip 5, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
Cont Ip 9, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

84 Vdc
84 Vdc
33 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[H5] Contact Output 5 ID
[H5] Contact Output 5 Operate
[H5] Contact Output 5 Seal-In

PH TRIP 86T
86T On (VO1)
OFF
Enabled
TRIP 52L TC1
GROUND TOC1 OP
OFF
Enabled
TRIP 52L TC2
GROUND TOC1 OP
OFF
Enabled
IBF 52L TC1
GROUND TOC1 OP
OFF

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
CONTACT OUTPUTS (continued from last page)
[H5] Contact Output 5 Events
[H6] Contact Output 6 ID
[H6] Contact Output 6 Operate
[H6] Contact Output 6 Seal-In
[H6] Contact Output 6 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[P6] Contact Output 12 ID
[P6] Contact Output 12 Operate
[P6] Contact Output 12 Seal-In
[P6] Contact Output 12 Events

Enabled
IBF 52L TC2
GROUND TOC1 OP
OFF
Disabled
ALARM
ANY TRIP On (VO3)
OFF
Enabled
TRG OSC G60A
ANY TRIP On (VO3)
OFF
Enabled
TRG OSC G60B
ANY TRIP On (VO3)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events

86T
Enabled
TRIG OSC
Enabled
ANY TRIP
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value

Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base

Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Mon Aug 26 11:29:56 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

T60T_UR_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 3 T60T\
DEVICE DEFINITION
FILES
ORDER CODE: T60-N04-HKH-F8M-H6P-M8N-P6P-U6P-WXX
VERSION: 6.00
DESCRIPTION: GTG T60T
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

PLANTA DE ETAN
Generator 761X201
Bus Protection - C60

GE Energy

Setting Calculation Sheet


Generator Bus Protection (ANSI Devices 25, 27DB, 50/27, 50/62BF, 50/51AT, 59BN)
A) Generator and UAT Data
Generator: 281.25 MVAG

18 kV

60 Hz
18 kVHV

UAT: 8.5 /11.5 MVA ONAN/ONAF

B) Relay , PT and CT Data


Relay Manufacturer: General Electric - Multilin
Relay Model: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
Winding F1 Phase CT Ratio: 12,000 / 5, Generator Breaker (SCR1)
Winding F5 Phase VT Ratio: 18,000 / 120V, VT4, Delta(SRC1), N =
Winding M1 Phase CT Ratio:
2,000 / 5, Aux Bus (SCR3)
Winding M5 Phase VT Ratio: 18,000 / 120V, VT1, Wye (SRC2), N =

150 :1 Vsec =

120 V

150 :1 Vsec =

69.3 V

C) Undervoltage Dead Bus Detection (27DB) Settings Calculations


Setting philosophy: Set to operate at voltage below 0.5 per unit for 2 seconds.
Set Phase UV2 (SRC2) pickup and time delay for = 0.5 pu Volts @ 2.0 seconds
D) Accidental Energization Protection (50/27) Settings Calculations
Setting Philosophy: The scheme is armed if the breaker is open and voltage is below
0.5 per unit via a Timer with 5 second pickup and 250 msec dropout, ensuring the
machine is offline. If an Inadvetrant Energization occurs, the breaker will close,
voltage will be present, and current will flow into the machine. The PHASE IOC2 will
pickup and actuate 50/27 (VO2) before the 250ms dropout of the timer.
Set Phase UV1 (SRC1) pickup for = 0.5 pu Volts
Set Timer 2 for 5.0 seconds pickup delay, 0.250 seconds dropout.
Set Phase IOC2 (SRC1) pickup for 0.2 pu amperes =
2,400 Primary Amps
TIMER
PUV1-A
PUV1-B
PUV1-C

AND
1

5sec
250ms

PIOC2

AND
2

TRIP

PUV1
AND1
TIMER
POC1
AND2

ON LINE
0
0
0
1
0

OFF LINE
1
1
1
0
0

AE
0
0
1*
1
1

* - till 250ms dropout

50/27 SCHEME

E) Breaker Failure Protection (50/62BF) Settings Calculations


Setting Philosophy: The scheme is armed by the IBF input and 52G/a contact, and
will operate under fault conditions or abnormal system operations. Intentional time
delay is set for 10.5 cycles with a 1 cycle dropout to operate before unit critical clearing time.
Set Timer 1 =
0.175 seconds pickup delay, 0.017 seconds dropout.

TIMER
AMP SUPV
IBF
52G/a

175ms

AND

TRIP
17ms

50/62BF SCHEME

Section 6

C60_R0

PLANTA DE ETAN
Generator 761X201
Bus Protection - C60

GE Energy

FAULT
OCCURS

NORMAL CLEARING TIME

LOCKOUT
RELAY
RELAY
OPERATION

NORMAL
CLEARING

BREAKER
INTERRUPTING
TIME

MARGIN

5 CYCLES

5 CYCLES

0.5
CYC

INOPERATIVE
BREAKER

5.5 CYCLES

10.5 CYCLES
B.F. TIMER

BACK-UP
BREAKER
INTERRUPTING
TIME

(16 CYCLES + RELAY TIME)


BREAKER FAILURE TOTAL CLEARING TIME

F) Aux Bus Phase Overcurrent (50/51AT) Settings Calculations


Setting Philosophy: Set relay for IEC B (Very Inverse) curve. Set High Voltage side winding TOC
unit pickup for 1.25 x UAT rating. Set TOC time dial to coordinate with the transformer
thermal and mechanical withstand curves per C57.109-1993.
Phase TOC3 Pickup Setting :
465 A, =
0.233 x CT
Time Dial : 0.65
Phase IOC3 Pickup Setting : 12,000 A, =
6.00 x CT

G) Generator Bus Ground Fault Detection (59BN) Settings Calculations


Setting philosophy: The relay calculates the zero sequence voltage (3V 0) from the VT phase inputs.
Set relay to operate for a ground fault on the generator bus delta system and coordinate with the G60
59N function set at 5 volts for 5 seconds.
Set Neutral OV2 (SRC2) pickup and time delay for = 5.0 V ( 0.072 pu) @ 6 sec.
VA

E30 under normal conditions is VA + VB + VC = 0:


VC

VB

E30 under an "A" phase to ground fault is VA + VB + VC = 0+3VB-60+3VC-120 = 3V-90:


VC

VB
E30

Section 6

C60_R0

PLANTA DE ETAN
Generator 761X201
Bus Protection - C60

GE Energy

CURRENT IN AMPERES X 10 AT 18000 VOLTS


.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

UAT_1
FLA
50/51AT

5 6 7 8 9 10000
1000
900
800
700
600
500

GTG GEN1

400

400

300

300
50T
51T

200

UAT_1
8.5 / 11.5 MVA
18 - 6.9 kV
10%

100
90
80
70
60
50

AUXBUS

40

TIME IN SECONDS

200

2000/5

100
90
80
70
60
50
40

30

30

20

20

50/51AT
GE T60
51/50 IEC
Curve B (BS142)
CT Ratio = 2000/5
Tap = 0.233 (465A)
Time Multiplier = 0.65
Inst. Pickup = 6 (12000A)

10
9
8
7
6
5
4
3

UAT_1
8500 / 11500 kVA
10%

10
9
8
7
6
5
4
3

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

.2

UAT_1
8500 / 11500 kVA
INRUSH

.1
.09
.08
.07
.06
.05

TIME IN SECONDS

1000
900
800
700
600
500

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

50/51AT
94452A
.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 18000 VOLTS

General Electric
Company

EasyPower

50/51AT

TIME-CURRENT CURVES
FAULT:

PHASE

DATE:

Aug 26, 2013

BY:
REVISION: 0
PLANTA~1

Section 6

C60_R0

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

19200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband
MMXU1: A phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband
MMXU3: PF phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel
SPCSO 33 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max
IEC61850 GGIO4 Analog 9 Value

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min
IEC61850 GGIO4 Analog 25 max

100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt
Clear XSWI16 OpCnt

No
No
No
No
No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 15
Digital Channel 16
Digital Channel 17
Digital Channel 18
Digital Channel 19
Digital Channel 20
Digital Channel 21
Digital Channel 22
Digital Channel 23
Digital Channel 24
Digital Channel 25
Digital Channel 26
Digital Channel 28
Digital Channel 29
Digital Channel 30
Digital Channel 32
Digital Channel 33
Digital Channel 34
Digital Channel 36
Digital Channel 37
Digital Channel 38
Digital Channel 42
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5

6
Automatic Overwrite
25 %
ANY TRIP On (VO4)
64 samples/cycle
IBF On(H7C)
52G/a Off(H7A)
TRIP 86BF IOn (H1)
50/62BF On (VO1)
50BF On (VO3)
TRIP 86IE IOn (H4)
50/27 On (VO2)
BKR FAIL 1 T1 OP
PHASE IOC3 OP A
PHASE IOC3 OP B
PHASE IOC3 OP C
PHASE TOC3 OP A
PHASE TOC3 OP B
PHASE TOC3 OP C
NEUTRAL OV2 OP
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
PHASE UV2 OP A
PHASE UV2 OP B
PHASE UV2 OP C
SRC1 VT FUSE FAIL OP
SRC2 VT FUSE FAIL OP
52G/a On(H7A)
TRIP 52G TC1 IOn (H2)
TRIP 52G TC2 IOn (H3)
ANY TRIP (A) IOn (P1)
50BF (A) IOn (P2)
VTFF IOn (P3)
PHASE IOC2 OP A
PHASE IOC2 OP B
PHASE IOC2 OP C
TRIG OS T60U IOn (U3)
TRIG OS G60A IOn (U4)
TRIG OS G60B IOn (U5)
59BN IOn (H6)
SRC1
Ia RMS
SRC1
Ib RMS
SRC1
Ic RMS
SRC1
Vag RMS
SRC1
Vbg RMS

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
OSCILLOGRAPHY (continued from last page)
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12

SRC1
SRC2
SRC2
SRC2
SRC1
SRC2
SRC2

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate

Continuous
OFF
60000 msec

DEMAND
Current Method
Power Method
Interval
Trigger

Thermal Exponential
Thermal Exponential
15 MIN
OFF

USER-PROGRAMMABLE LEDS
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input

Vcg RMS
Vag RMS
Vbg RMS
Vcg RMS
V_0 Mag
V_0 Mag
V_2 Mag

ANY TRIP On (VO4)


ANY SELF TESTS

USER PROGRAMMABLE LEDS


LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE
LED 15: OPERAND
LED 15: TYPE

50/62BF On (VO1)
Latched
50/27 On (VO2)
Latched
50BF On (VO3)
Latched
52G/a On(H7A)
Self-Reset
IBF Off(H7C)
Self-Reset
TRIP 86BF IOn (H1)
Latched
TRIP 52G TC1 IOn (H2)
Latched
TRIP 52G TC2 IOn (H3)
Latched
TRIP 86IE IOn (H4)
Latched
TRIP 86U IOn (H5)
Latched
ANY TRIP (A) IOn (P1)
Latched
50BF (A) IOn (P2)
Latched
VTFF IOn (P3)
Latched
PHASE IOC3 OP
Self-Reset
PHASE TOC3 OP
Self-Reset

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

C60

SYSTEM SETUP
AC INPUTS

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary

13000 A
1A
13000 A
1A
700 A
1A
700 A
1A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio
VT M5: Phase VT Connection
VT M5: Phase VT Secondary
VT M5: Phase VT Ratio
VT M5: Auxiliary VT Connection
VT M5: Auxiliary VT Secondary
VT M5: Auxiliary VT Ratio

Delta
110.0 V
136.36 :1
Vag
120.0 V
2400.00 :1
Wye
63.5 V
13636.00 :1
Vag
120.0 V
2400.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

50 Hz
ABC
BUS (SRC 2)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT
SOURCE 3: Name
SOURCE 3: Phase CT
SOURCE 3: Ground CT
SOURCE 3: Phase VT
SOURCE 3: Auxiliary VT
SOURCE 4: Name
SOURCE 4: Phase CT
SOURCE 4: Ground CT
SOURCE 4: Phase VT
SOURCE 4: Auxiliary VT

GEN
F1
None
F5
None
BUS
None
None
M5
None
HV BUS
None
None
None
F5
HV RUN
None
None
None
M5

BREAKERS
Breaker 1 Function
Breaker 1 Push Button Control
Breaker 1 Name
Breaker 1 Mode
Breaker 1 Open
Breaker 1 Block Open
Breaker 1 Close
Breaker 1 Block Close
Breaker 1 Phase A/3-Pole Closed
Breaker 1 Phase A/3-Pole Opened
Breaker 1 Phase B Closed
Breaker 1 Phase B Opened
Breaker 1 Phase C Closed
Breaker 1 Phase C Opened
Breaker 1 Toperate

Enabled
Disabled
Bkr 1
3-Pole
OFF
OFF
OFF
OFF
52G/a On(H7A)
52G/a Off(H7A)
OFF
OFF
OFF
OFF
0.070 s

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
BREAKERS (continued from last page)
Breaker 1 External Alarm
Breaker 1 Alarm Delay
Breaker 1 Manual Close Recal Time
Breaker 1 Out Of Service
Breaker 1 Events

OFF
0.020 s
0.100 s
OFF
Disabled

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19
FlexLogic Entry 20
FlexLogic Entry 21
FlexLogic Entry 22
FlexLogic Entry 23
FlexLogic Entry 24
FlexLogic Entry 25
FlexLogic Entry 26
FlexLogic Entry 27
FlexLogic Entry 28
FLEXLOGIC TIMERS
Timer 1: Type
Timer 1: Pickup Delay
Timer 1: Dropout Delay
Timer 2: Type
Timer 2: Pickup Delay
Timer 2: Dropout Delay
GROUPED ELEMENTS
GROUP 1
PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC3: Function
PHASE TOC3: Signal Source
PHASE TOC3: Input
PHASE TOC3: Pickup
PHASE TOC3: Curve

BKR FAIL 1 T1 OP
= 50BF (VO3)
50BF On (VO3)
TIMER 1
= 50/62BF (VO1)
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
AND(3)
TIMER 2
PHASE IOC2 OP
AND(2)
= 50/27 (VO2)
PHASE TOC3 OP
PHASE IOC3 OP
OR(2)
= 50/51AT (VO6)
50/62BF On (VO1)
50/27 On (VO2)
50/51AT On (VO6)
59BN(DE1) OP
OR(4)
= ANY TRIP (VO4)
SRC1 VT FUSE FAIL OP
SRC2 VT FUSE FAIL OP
OR(2)
= VTFF (VO5)
END
millisecond
175
20
millisecond
5000
250

Enabled
HV BUS (SRC 3)
Phasor
0.233 pu
IEC Curve B

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
PHASE TOC [GROUP 1] (continued from last page)
PHASE TOC3: TD Multiplier
PHASE TOC3: Reset
PHASE TOC3: Voltage Restraint
PHASE TOC3: Block A
PHASE TOC3: Block B
PHASE TOC3: Block C
PHASE TOC3: Target
PHASE TOC3: Events

0.65
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

PHASE IOC [GROUP 1]


PHASE IOC2: Function
PHASE IOC2: Source
PHASE IOC2: Pickup
PHASE IOC2: Delay
PHASE IOC2: Reset Delay
PHASE IOC2: Block A
PHASE IOC2: Block B
PHASE IOC2: Block C
PHASE IOC2: Target
PHASE IOC2: Events
PHASE IOC3: Function
PHASE IOC3: Source
PHASE IOC3: Pickup
PHASE IOC3: Delay
PHASE IOC3: Reset Delay
PHASE IOC3: Block A
PHASE IOC3: Block B
PHASE IOC3: Block C
PHASE IOC3: Target
PHASE IOC3: Events

Enabled
GEN (SRC 1)
0.200 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled
Enabled
HV BUS (SRC 3)
6.000 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled

BREAKER FAILURE [GROUP 1]


BF1: Function
BF1: Mode
BF1: Source
BF1: Current Supervision
BF1: Use Seal-In
BF1: Three Pole Initiate
BF1: Block
BF1: Phase Current Supv Pickup
BF1: Neutral Current Supv Pickup
BF1: Use Timer 1
BF1: Timer 1 Pickup Delay
BF1: Use Timer 2
BF1: Timer 2 Pickup Delay
BF1: Use Timer 3
BF1: Timer 3 Pickup Delay
BF1: Breaker Pos1 Phase A/3P
BF1: Breaker Pos2 Phase A/3P
BF1: Breaker Test On
BF1: Phase Current HiSet Pickup
BF1: Neutral Current HiSet Pickup
BF1: Phase Current LoSet Pickup
BF1: Neutral Current LoSet Pickup
BF1: LoSet Time Delay
BF1: Trip Dropout Delay
BF1: Target
BF1: Events
BF1: Phase A Initiate
BF1: Phase B Initiate
BF1: Phase C Initiate
BF1: Breaker Pos1 Phase B
BF1: Breaker Pos1 Phase C
BF1: Breaker Pos2 Phase B
BF1: Breaker Pos2 Phase C

Enabled
3-Pole
GEN (SRC 1)
No
No
IBF On(H7C)
OFF
1.050 pu
1.050 pu
Yes
0.000 s
No
0.000 s
No
0.000 s
52G/a On(H7A)
OFF
OFF
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
Latched
Enabled
OFF
OFF
OFF
OFF
OFF
OFF
OFF

VOLTAGE ELEMENTS

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
PHASE UV [GROUP 1]
PHASE UV1: Function
PHASE UV1: Signal Source
PHASE UV1: Mode
PHASE UV1: Pickup
PHASE UV1: Curve
PHASE UV1: Delay
PHASE UV1: Minimum Voltage
PHASE UV1: Block
PHASE UV1: Target
PHASE UV1: Events
PHASE UV2: Function
PHASE UV2: Signal Source
PHASE UV2: Mode
PHASE UV2: Pickup
PHASE UV2: Curve
PHASE UV2: Delay
PHASE UV2: Minimum Voltage
PHASE UV2: Block
PHASE UV2: Target
PHASE UV2: Events

Enabled
GEN (SRC 1)
Phase to Phase
0.500 pu
Definite Time
0.00 s
0.000 pu
SRC1 VT FUSE FAIL OP
Self-reset
Enabled
Enabled
BUS (SRC 2)
Phase to Ground
0.500 pu
Definite Time
2.00 s
0.000 pu
SRC2 VT FUSE FAIL OP
Self-reset
Enabled

NEUTRAL OV [GROUP 1]
NEUTRAL OV 2: Function
NEUTRAL OV 2: Source
NEUTRAL OV 2: Pickup
NEUTRAL OV 2: Curve
NEUTRAL OV 2: Pickup Delay
NEUTRAL OV 2: Reset Delay
NEUTRAL OV 2: Block
NEUTRAL OV 2: Target
NEUTRAL OV 2: Events

Enabled
BUS (SRC 2)
0.072 pu
Definite Time
6.00 s
0.00 s
OFF
Latched
Enabled

CONTROL ELEMENTS
SYNCHROCHECK
SYNCHROCHECK1: Function
SYNCHROCHECK1: Block
SYNCHROCHECK1: V1 Source
SYNCHROCHECK1: V2 Source
SYNCHROCHECK1: Max Volt Diff
SYNCHROCHECK1: Max Angle Diff
SYNCHROCHECK1: Max Freq Diff
SYNCHROCHECK1: Freq Hysteresis
SYNCHROCHECK1: Dead Source Select
SYNCHROCHECK1: Dead V1 Max Volt
SYNCHROCHECK1: Dead V2 Max Volt
SYNCHROCHECK1: Live V1 Min Volt
SYNCHROCHECK1: Live V2 Min Volt
SYNCHROCHECK1: Target
SYNCHROCHECK1: Events
SYNCHROCHECK2: Function
SYNCHROCHECK2: Block
SYNCHROCHECK2: V1 Source
SYNCHROCHECK2: V2 Source
SYNCHROCHECK2: Max Volt Diff
SYNCHROCHECK2: Max Angle Diff
SYNCHROCHECK2: Max Freq Diff
SYNCHROCHECK2: Freq Hysteresis
SYNCHROCHECK2: Dead Source Select
SYNCHROCHECK2: Dead V1 Max Volt
SYNCHROCHECK2: Dead V2 Max Volt
SYNCHROCHECK2: Live V1 Min Volt
SYNCHROCHECK2: Live V2 Min Volt
SYNCHROCHECK2: Target
SYNCHROCHECK2: Events
DIGITAL ELEMENTS
Digital Element 1 Function

Enabled
OFF
GEN (SRC 1)
BUS (SRC 2)
900 V
10 deg
0.17 Hz
0.03 Hz
None
0.30 pu
0.30 pu
0.70 pu
0.70 pu
Latched
Enabled
Enabled
OFF
HV BUS (SRC 3)
HV RUN (SRC 4)
14400 V
10 deg
0.17 Hz
0.03 Hz
None
0.30 pu
0.30 pu
0.70 pu
0.70 pu
Latched
Enabled
Enabled

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
DIGITAL ELEMENTS (continued from last page)
Digital Element 1 Name
Digital Element 1 Input
Digital Element 1 Pickup Delay
Digital Element 1 Reset Delay
Digital Element 1 Pickup Led
Digital Element 1 Block
Digital Element 1 Target
Digital Element 1 Events
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function
VT FUSE FAILURE 1: Neutral Wire Open Detection
VT FUSE FAILURE 1: 3rd Harmonic Pickup
VT FUSE FAILURE 2: Function
VT FUSE FAILURE 2: Neutral Wire Open Detection
VT FUSE FAILURE 2: 3rd Harmonic Pickup
VT FUSE FAILURE 3: Function
VT FUSE FAILURE 3: Neutral Wire Open Detection
VT FUSE FAILURE 3: 3rd Harmonic Pickup
VT FUSE FAILURE 4: Function
VT FUSE FAILURE 4: Neutral Wire Open Detection
VT FUSE FAILURE 4: 3rd Harmonic Pickup
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events
CONTACT INPUT THRESHOLDS
52G/a, IBF, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
Cont Ip 5, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
Cont Ip 9, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

59BN
NEUTRAL OV2 OP
0.000 s
0.000 s
Enabled
OFF
Latched
Enabled

Enabled
Disabled
0.100 pu
Enabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu
Disabled
Disabled
0.100 pu

52G/a
2.0 ms
Enabled
IBF
2.0 ms
Enabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
Cont Ip 5
2.0 ms
Enabled
Cont Ip 6
2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
Cont Ip 9
2.0 ms
Disabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled
84 Vdc
84 Vdc
84 Vdc

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[H5] Contact Output 5 ID
[H5] Contact Output 5 Operate
[H5] Contact Output 5 Seal-In
[H5] Contact Output 5 Events
[H6] Contact Output 6 ID
[H6] Contact Output 6 Operate
[H6] Contact Output 6 Seal-In
[H6] Contact Output 6 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P2] Contact Output 8 ID
[P2] Contact Output 8 Operate
[P2] Contact Output 8 Seal-In
[P2] Contact Output 8 Events
[P3] Contact Output 9 ID
[P3] Contact Output 9 Operate
[P3] Contact Output 9 Seal-In
[P3] Contact Output 9 Events
[P4] Contact Output 10 ID
[P4] Contact Output 10 Operate
[P4] Contact Output 10 Seal-In
[P4] Contact Output 10 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[U3] Contact Output 15 ID
[U3] Contact Output 15 Operate
[U3] Contact Output 15 Seal-In
[U3] Contact Output 15 Events
[U4] Contact Output 16 ID
[U4] Contact Output 16 Operate
[U4] Contact Output 16 Seal-In
[U4] Contact Output 16 Events
[U5] Contact Output 17 ID
[U5] Contact Output 17 Operate
[U5] Contact Output 17 Seal-In
[U5] Contact Output 17 Events

TRIP 86BF
50/62BF On (VO1)
OFF
Enabled
TRIP 52G TC1
50BF On (VO3)
OFF
Enabled
TRIP 52G TC2
50BF On (VO3)
OFF
Enabled
TRIP 86IE
50/27 On (VO2)
OFF
Enabled
TRIP 86U
50/51AT On (VO6)
OFF
Enabled
59BN
59BN(DE1) OP
OFF
Enabled
ANY TRIP (A)
ANY TRIP On (VO4)
OFF
Enabled
50BF (A)
50BF On (VO3)
OFF
Enabled
VTFF
VTFF On (VO5)
OFF
Enabled
52G DB CLS
PHASE UV2 OP
OFF
Enabled
52G DB PMS
PHASE UV2 OP
OFF
Enabled
TRIG OS T60U
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS G60A
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS G60B
ANY TRIP On (VO4)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events
Virtual Output 4 ID
Virtual Output 4 Events

50/62BF
Enabled
50/27
Enabled
50BF
Enabled
ANY TRIP
Enabled

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
VIRTUAL OUTPUTS (continued from last page)
Virtual Output 5 ID
Virtual Output 5 Events
Virtual Output 6 ID
Virtual Output 6 Events

VTFF
Enabled
50/51AT
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode

0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base

1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Mon Aug 26 14:45:54 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

GTG C60_R0.URS
C:\PROJECTS\2013\PLANTA DE ETEN\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-N04-HKH-F8M-H6P-M8M-P6P-U6P-WXX
VERSION: 6.0X
DESCRIPTION: C60
TEXT COLOR
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

Rev. A

COORDINACIN PROTECCIONES
ANEXO II

RFE-1-YE_-EEC-IDO-001

Pg/Page 176 de/of


288

ANEXO II:

ESTUDIO DE PROTECCIONES SUBESTACIN 220 kV

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

ACCESIBILIDAD:

CONTROLADA

S. Ruge

J. lvarez

J. Pardo

A. Montoya

Elaborado por
nombre/firma

Revisado por
nombre/firma

05/09/2014

Rev.

Fecha

NO CONTROLADA

J. Serrano

Emisin inicial

PA

Descripcin

Estado

Aprobado por
nombre/firma

PROYECTO AMPLIACIN 14
SUBESTACIN REQUE 220 kV

ESTUDIO DE COORDINACIN DE PROTECCIONES

ESCALA

SIN

FORMATO

A4

REFERENCIA REP

PE-AM14-ETEN-D066

REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

HOJA

REV

ESTUDIO DE COORDINACIN DE PROTECCIONES

TABLA DE CONTENIDO
1.

OBJETIVO.............................................................................................................................................................. 9

2.

DESCRIPCIN DEL SISTEMA................................................................................................................................ 9

2.1.

UBICACIN DEL PROYECTO ...................................................................................................................................... 9

2.2.

DIAGRAMA UNIFILAR DEL REA DE INFLUENCIA DEL PROYECTO ...................................................................... 10

3.

METODOLOGA................................................................................................................................................... 10

4.

ALCANCE ............................................................................................................................................................ 11

5.

DOCUMENTOS DE REFERENCIA........................................................................................................................ 11

6.

INFORMACIN TCNICA.................................................................................................................................... 11

6.1.

PARMETROS DE LNEAS DE TRANSMISIN ........................................................................................................ 12

6.2.

PARMETROS DE TRANFORMADOR DE POTENCIA .............................................................................................. 12

6.3.

PARMETROS DE TRANSFORMADORES DE INSTRUMENTACIN ...................................................................... 12

6.4.

DISPOSITIVOS DE PROTECCIN INVOLUCRADOS EN EL PROYECTO .................................................................. 14

7.
7.1.

FILOSOFA Y CRITERIOS DE LAS FUNCIONES DE PROTECCIN ....................................................................... 15


PROTECCIN DE LNEAS DE TRANSMISIN ......................................................................................................... 15

7.1.1

Filosofa de proteccin .................................................................................................................................... 15

7.1.2

Criterios de ajuste para las funciones de proteccin ........................................................................................ 18

7.2.

TRANSFORMADOR DE POTENCIA .......................................................................................................................... 25

7.2.1

Filosofa de proteccin .................................................................................................................................... 25

7.2.2

Criterios de ajuste para las funciones de proteccin ........................................................................................ 25

7.3.

PROTECCIN DE ACOPLE ....................................................................................................................................... 26

7.3.1

Filosofa de proteccin .................................................................................................................................... 26

7.3.2

Criterios de ajuste para las funciones de proteccin ........................................................................................ 27

7.4.

PROTECCIN DE SUBESTACIONES ........................................................................................................................ 28

7.4.1

Filosofa de proteccin .................................................................................................................................... 28

7.4.2

Criterios de ajuste para las funciones de proteccin ........................................................................................ 29

8.
8.1.

AJUSTES DE LAS FUNCIONES DE PROTECCIN ................................................................................................ 34


PROTECCIN DE LNEAS DE TRANSMISIN ......................................................................................................... 34

8.1.1

Lnea Reque Eten (2L2-6) 220 kV, extremo Reque ..................................................................................... 34

8.1.2

Lnea Reque Eten (2L2-6) 220 kV, extremo Eten ........................................................................................ 45

8.2.

TRANSFORMADOR DE POTENCIA .......................................................................................................................... 48

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

2/79

8.2.1

Funcin de sobrecorriente de fases de tiempo inverso y tiempo definido (51/50) .......................................... 48

8.2.2

Funcin de sobrecorriente de tierra de tiempo inverso y tiempo definido (51N/50N) .................................... 48

8.3.

PROTECCIN DE ACOPLE ....................................................................................................................................... 49

8.3.1

Funcin de sobrecorriente de fases de tiempo inverso y tiempo definido (51/50) .......................................... 49

8.3.2

Funcin de sobrecorriente de tierra de tiempo inverso y definido y tierra (51N/50N) .................................... 50

8.4.

PROTECCIN DE SUBESTACIONES ........................................................................................................................ 50

8.4.1

Funcin diferencial de barras (87B) ................................................................................................................ 50

8.4.2

Zona muerta campo de acople 220 kV ........................................................................................................... 55

8.4.3

Funcin falla interruptor (50BF) ..................................................................................................................... 55

8.5.

ANLISIS DE PROTECCIN SOBRECORRIENTE..................................................................................................... 56

8.5.1

Lnea Reque Eten (2L2-6) 220 kV, extremo Reque ..................................................................................... 56

8.5.2

Lnea Reque Eten (2L2-6) 220 kV, extremo Eten ........................................................................................ 57

9.
9.1.

AJUSTES DE LOS DISPOSITIVOS DE PROTECCIN EXISTENTES ........................................................................ 57


SUBESTACIN REQUE 220 KV ................................................................................................................................ 57

9.1.1

Lnea Reque Guadalupe 1 y 2 220 kV .......................................................................................................... 57

9.1.2

Lnea Reque Chiclayo Oeste 1 y 2 220 kV ................................................................................................... 57

9.2.

SUBESTACIN CHICLAYO OESTE 220 KV ............................................................................................................... 58

9.2.1

Lnea Chiclayo Oeste Reque 1 y 2 220 kV ................................................................................................... 58

9.2.2

Lnea Chiclayo Oeste La Nia 220 kV .......................................................................................................... 58

9.2.3

Lnea Chiclayo Oeste Piura Oeste 220 kV .................................................................................................... 58

9.2.4

Lnea Chiclayo Oeste Carhuaquero 220 kV .................................................................................................. 58

9.2.5

Transformador T93-261 220 kV ..................................................................................................................... 59

9.2.6

Transformador T16-260 220 kV ..................................................................................................................... 59

9.2.7

Transformador T14-260 220 kV ..................................................................................................................... 59

9.3.

SUBESTACIN LA NIA 220 KV .............................................................................................................................. 60

9.4.

SUBESTACIN PIURA OESTE 220 KV...................................................................................................................... 60

9.5.

SUBESTACIN CARHUAQUERO 220 KV ................................................................................................................. 60

9.6.

SUBESTACIN TRUJILLO NORTE 220 KV ................................................................................................................ 60

9.7.

SUBESTACIN GUADALUPE 220 KV ....................................................................................................................... 61

9.7.1

Lnea Guadalupe Reque 1 y 2 220 kV .......................................................................................................... 61

9.7.2

Lnea Guadalupe Trujillo Norte 1 y 2 220 kV ............................................................................................... 62

9.7.3

Transformador T92-261 220 kV ..................................................................................................................... 63

9.7.4

Transformador T17-261 220 kV ..................................................................................................................... 63

9.7.5

Transformador T13-261 220 kV ..................................................................................................................... 63

10.

VERIFICACIN Y AJUSTES RECOMENDADOS DE LOS DISPOSITIVOS DE PROTECCIN EXISTENTES EN EL


REA DE INFLUENCIA ....................................................................................................................................... 64

10.1.

SUBESTACIN REQUE 220 KV ................................................................................................................................ 64

10.2.

SUBESTACIN GUADALUPE 220 KV ....................................................................................................................... 64

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

3/79

10.3.
11.

SUBESTACIN CHICLAYO OESTE 220 KV ............................................................................................................... 65


CONCLUSIONES Y RECOMENDACIONES ........................................................................................................... 66

REFERENCIAS ................................................................................................................................................................. 67

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

4/79

NDICE DE TABLAS

Tabla 1:

Parmetros elctricos de las lneas de transmisin proyecto Ampliacin 14 Subestacin Reque 220 kV ............12

Tabla 2:

Parmetros del transformador de potencia .............................................................................................................12

Tabla 3:

Parmetros de transformadores de corriente ..........................................................................................................13

Tabla 4:

Parmetros de transformadores de tensin .............................................................................................................13

Tabla 5:

Dispositivos de proteccin Involucrados en el proyecto ...........................................................................................14

Tabla 6:

Clculo SIR Lnea Reque Eten 220 kV ..............................................................................................................16

Tabla 7:

Esquema propuesto de sobretensin zona norte .....................................................................................................23

Tabla 8:

Datos tcnicos de la proteccin diferencial de barras en 220 kV .............................................................................29

Tabla 9:

Condiciones de operacin proteccin diferencial de barras .....................................................................................32

Tabla 10: Ajustes funcin 87L lnea Reque Eten 220 kV, extremo Reque ........................................................................34
Tabla 11: Verificacin de operacin de la proteccin diferencial de lnea - fallas internas, escenario de mnimos niveles de
cortocircuito - lnea Reque Eten 220 kV ..............................................................................................................36
Tabla 12: Verificacin de operacin de la proteccin diferencial de lnea - fallas externas, escenario de mnimos niveles de
cortocircuito - lnea Reque Eten 220 kV ..............................................................................................................38
Tabla 13: Verificacin de operacin de la proteccin diferencial de lnea - fallas internas, escenario de mximos niveles de
cortocircuito - lnea Reque Eten 220 kV ..............................................................................................................40
Tabla 14: Verificacin de operacin de la proteccin diferencial de lnea - fallas externas, escenario de mximos niveles de
cortocircuito - lnea Reque Eten 220 kV ..............................................................................................................42
Tabla 15: Ajustes funcin 67N lnea Reque Eten 220 kV, extremo Reque .......................................................................44
Tabla 16: Ajustes funcin SOTF - Reque Eten 220 kV, extremo Reque ...............................................................................45
Tabla 17: Ajustes funcin 87L lnea Reque Eten 220 kV, extremo Eten ...........................................................................45
Tabla 18: Ajustes funcin 67N lnea Reque Eten 220 kV, extremo Eten ..........................................................................47
Tabla 19: Ajustes funcin SOTF - Reque Eten 220 kV, extremo Eten..................................................................................47
Tabla 20: Ajuste arranque falla interruptor subestacin Eten 220 kV .....................................................................................48
Tabla 21: Ajustes funcin 51/50 Transformador Eten 220/18 kV, nivel 220 kV .................................................................48
Tabla 22: Ajustes funcin 51N Transformador Eten 220/18 kV, nivel 220 kV ....................................................................49
Tabla 23: Ajustes esenciales funcin diferencial de barras (87B) unidad centralizada rel MiCOM P741 ..............................50
Tabla 24: Simulaciones proteccin diferencial de barras, rel MiCOM P741, fallas internas, demanda mnima ....................51
Tabla 25: Simulaciones proteccin diferencial de barras, rel MiCOM P741, fallas externas, demanda mxima ...................52
Tabla 26: Ajuste zona muerta de acople subestacin Reque 220 kV.......................................................................................55
Tabla 27: Ajuste arranque falla interruptor subestacin Reque 220 kV ...................................................................................56
Tabla 28: Ajustes actuales funcin de sobrecorriente lnea Reque Guadalupe 1 y 2 (L-2236 y L-2237) 220 kV, extremo
Reque ......................................................................................................................................................................57
Tabla 29: Ajustes actuales funcin de sobrecorriente lnea Reque Chiclayo Oeste 1 y 2 (L-2296 y L-2297) 220 kV, extremo
Reque ......................................................................................................................................................................57
Tabla 30: Ajustes actuales funcin de sobrecorriente lnea Chiclayo Oeste - Reque 1 y 2 (L-2296 y L-2297) 220 kV, extremo
Chiclayo Oeste .........................................................................................................................................................58

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

5/79

Tabla 31: Ajustes actuales funcin de sobrecorriente lnea La Nia Chiclayo Oeste (L-2239) 220 kV, extremo Chiclayo
Oeste .......................................................................................................................................................................58
Tabla 32: Ajustes actuales funcin de sobrecorriente lnea Piura Oeste Chiclayo Oeste (L-2238) 220 kV, extremo Chiclayo
Oeste .......................................................................................................................................................................58
Tabla 33: Ajustes actuales funcin de sobrecorriente lnea Carhuaquero Chiclayo Oeste (L-2240) 220 kV, extremo Chiclayo
Oeste .......................................................................................................................................................................58
Tabla 34: Ajustes actuales funcin de sobrecorriente transformador T93-261 220 kV ...........................................................59
Tabla 35: Ajustes actuales funcin de sobrecorriente transformador T16-260 220 kV ...........................................................59
Tabla 36: Ajustes actuales funcin de sobrecorriente transformador T14-260 220 kV ...........................................................59
Tabla 37: Ajustes actuales funcin de sobrecorriente lnea La Nia Chiclayo Oeste (L-2239) 220 kV, extremo La Nia ....60
Tabla 38: Ajustes actuales funcin de sobrecorriente lnea Piura Oeste Chiclayo Oeste (L-2238) 220 kV, extremo Piura
Oeste .......................................................................................................................................................................60
Tabla 39: Ajustes actuales funcin de sobrecorriente lnea Carhuaquero Chiclayo Oeste (L-2240) 220 kV, extremo
Carhuaquero ...........................................................................................................................................................60
Tabla 40: Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 1 (L-2234) 220 kV, extremo Trujillo
Norte .......................................................................................................................................................................60
Tabla 41: Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 2 (L-2235) 220 kV, extremo Trujillo
Norte .......................................................................................................................................................................61
Tabla 42: Ajustes actuales funcin distancia lnea Guadalupe Reque 1 (L-2236) 220 kV, extremo Guadalupe ..................61
Tabla 43: Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 1 (L-2236) 220 kV, extremo Guadalupe .....61
Tabla 44: Ajustes actuales funcin de distancia lnea Guadalupe Reque 2 (L-2237) 220 kV, extremo Guadalupe ..............61
Tabla 45: Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 2 (L-2237) 220 kV, extremo Guadalupe .....62
Tabla 46: Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 1 (L-2234) 220 kV, extremo
Guadalupe ...............................................................................................................................................................62
Tabla 47: Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 2 (L-2235) 220 kV, extremo
Guadalupe ...............................................................................................................................................................62
Tabla 48: Ajustes actuales funcin de sobrecorriente transformador T92-261 220 kV ...........................................................63
Tabla 49: Ajustes actuales funcin de sobrecorriente transformador T17-261 220 kV ...........................................................63
Tabla 50: Ajustes actuales funcin de sobrecorriente transformador T13-261 220 kV ...........................................................63
Tabla 51: Ajustes recomendados funcin de sobrecorriente lnea Reque Guadalupe 1 y 2 (L-2236 y L-2237) 220 kV,
extremo Reque ........................................................................................................................................................64
Tabla 52: Ajustes recomendados funcin de sobrecorriente lnea Reque Chiclayo Oeste 1 y 2 (L-2296 y L-2297) 220 kV,
extremo Reque ........................................................................................................................................................64
Tabla 53: Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 1 (L-2236) 220 kV, extremo Guadalupe .....64
Tabla 54: Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 2 (L-2237) 220 kV, extremo Guadalupe .....65
Tabla 55: Ajustes recomendados funcin de sobrecorriente lnea Chiclayo Oeste - Reque 1 y 2 (L-2296 y L-2297) 220 kV,
extremo Chiclayo Oeste ...........................................................................................................................................65

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

6/79

NDICE DE FIGURAS

Figura 1:

Ubicacin geogrfica de la subestacin Reque 220 kV en las redes del SEIN ......................................................9

Figura 2:

Diagrama Unifilar simplificado de la Subestacin Reque 220 kV .......................................................................10

Figura 3:

Esquema de proteccin de lnea subestacin Reque 220 kV ..............................................................................17

Figura 4:

Esquema de proteccin de lnea subestacin Eten 220 kV.................................................................................18

Figura 5:

Esquema elctrico proteccin diferencial de lnea ..............................................................................................19

Figura 6:

Caracterstica de operacin funcin diferencial de lnea rels SEL 411L ............................................................19

Figura 7:

Esquema 67N en comparacin direccional ........................................................................................................21

Figura 8:

Lgica de disparo SOTF SEL 411L ..................................................................................................................22

Figura 9:

Lgica de la proteccin Falla Interruptor 50BF ..................................................................................................24

Figura 10:

Esquema de proteccin transformador de potencia ...........................................................................................25

Figura 11:

Esquema de proteccin baha de acople subestacin Reque 220 kV .................................................................27

Figura 12:

Esquema diferencial de barras distribuida ..........................................................................................................29

Figura 13:

Proteccin diferencial de barras .........................................................................................................................30

Figura 14:

Principio de proteccin diferencial de barras ......................................................................................................30

Figura 15:

Caracterstica del esquema de proteccin diferencial de barras utilizado por los rels MiCOM P74X ................31

Figura 16:

Disposicin del TC en el campo de acople ..........................................................................................................33

Figura 17:

Lgica de la proteccin Falla Interruptor 50BF ..................................................................................................34

Figura 18:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas escenario de mnimos
niveles de cortocircuito - modo normal .............................................................................................................37

Figura 19:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas - escenario de mnimos
niveles de cortocircuito - modo de seguridad extendido ....................................................................................38

Figura 20:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas escenario de mnimos
niveles de cortocircuito - modo normal .............................................................................................................39

Figura 21:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas - escenario de mnimos
niveles de cortocircuito - modo de seguridad extendido ....................................................................................40

Figura 22:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas escenario de mximos
niveles de cortocircuito - modo normal .............................................................................................................41

Figura 23:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas - escenario de mximos
niveles de cortocircuito - modo de seguridad extendido ....................................................................................42

Figura 24:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas escenario de mximos
niveles de cortocircuito - modo normal .............................................................................................................43

Figura 25:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas - escenario de mximos
niveles de cortocircuito - modo de seguridad extendido ....................................................................................44

Figura 26:

Verificacin de operacin proteccin diferencial de barras ante fallas internas ..................................................54

Figura 27:

Verificacin de operacin proteccin diferencial de barras ante fallas externas..................................................55

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

7/79

NDICE DE ANEXOS
Anexo 1: Esquema de proteccin de la lnea subestacin Reque 220 kV
Anexo 2: Esquema de proteccin de lnea subestacin Eten 220 kV
Anexo 3: Esquema de proteccin baha de acople subestacin Reque 220 kV
Anexo 4: Tabla de coordinacin funciones de sobrecorriente en 220 kV

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

8/79

1.

OBJETIVO

Presentar los resultados del estudio de coordinacin de protecciones de la baha de lnea hacia la subestacin Eten (reserva
fra de generacin) para el proyecto Ampliacin 14 Subestacin Reque 220 kV, los cuales estn orientados a asegurar la
proteccin de los equipos elctricos y a garantizar la adecuada coordinacin con los dispositivos de proteccin instalados en
las subestaciones adyacentes al proyecto.

2.

DESCRIPCIN DEL SISTEMA

Actualmente ISA REP se encuentra desarrollando las obras necesarias para la ejecucin del proyecto Ampliacin 14,
correspondiente a la construccin de la nueva baha de lnea Reque Eten 220 kV, la subestacin Reque 220 kV es una
subestacin exterior tipo intemperie y tiene una configuracin doble barra ms un seccionador de transferencia. Con la
construccin de la nueva baha de lnea a Eten, quedar conformada por seis campos (cinco campos de lnea y uno de
acople), mientras que la subestacin Eten es una subestacin sin barra, de conexin directa entre transformador de potencia
y lnea de transmisin. Este proyecto se encuentra localizado en la provincia de Chiclayo, Departamento de Lambayeque en la
costa norte de Per.

2.1.

UBICACIN DEL PROYECTO

En la Figura 1 se puede observar la ubicacin geogrfica de la subestacin Reque 220 kV sobre las redes del SEIN.

Figura 1:

Ubicacin geogrfica de la subestacin Reque 220 kV en las redes del SEIN

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

9/79

2.2.

DIAGRAMA UNIFILAR DEL REA DE INFLUENCIA DEL PROYECTO

En la Figura 2 se presenta el diagrama unifilar correspondiente al rea de influencia de la subestacin Reque 220 kV y las
obras asociadas a la Ampliacin 14. La topologa de la red mostrada corresponde al SEIN en el ao 2014 con la ejecucin del
proyecto.
Eten

CONVENCIONES
500 kV

La Nia
Chiclayo Oeste

220 kV

138 kV
Guadalupe

60 kV
33 kV

Reque

23, 24

La Nia

18 kV
10 kV
Expansin Bsica
Guadalupe

Kiman Ayllu

C. Corona

Shahuindo

Trujillo Nueva

Cajamarca

Trujillo Nueva

Trujillo Norte

Chimbote
Trujillo Norte

SVC
T. Noroes.
Cao

Chimbote

Motil
Porvenir

A. Chicama

T. Sur

Figura 2:

3.

T. Nor.

Diagrama Unifilar simplificado de la Subestacin Reque 220 kV

METODOLOGA

Siguiendo los criterios descritos por ISA-REP y COES en el documento Criterios de Ajuste y Coordinacin de los Sistemas de
Proteccin del SEIN [1], sern calculados los ajustes nuevos del proyecto Ampliacin 14 Subestacin Reque 220 kV, lnea
Reque Eten 220 kV los cuales sern verificados a travs del programa especializado para la simulacin de sistemas
elctricos DIgSILENT PowerFactory 14.1.3. Los ajustes sern calculados en un escenario de mnima demanda (avenida
mnima) y sern verificados en un escenario de mxima generacin (estiaje mximo). Adicionalmente, sern evaluadas las

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

10/79

protecciones aledaas al proyecto ante diferentes eventos simulados, con el objetivo de asegurar la correcta operacin de las
protecciones adyacentes y as minimizar el impacto de la entrada del proyecto.

4.

ALCANCE

El alcance del presente estudio comprende el clculo de ajustes bsicos para las funciones de proteccin que sern habilitadas
en los siguientes rels, los cuales estn asociados con los campos de las subestaciones Reque 220 kV y Eten 220 kV:

Rels SEL 411L (Rel de proteccin multifuncional de lnea Subestacin Reque 220 kV y Subestacin Eten 220 kV)

Rel T60T (Rel de proteccin multifuncional de transformador funcin de sobrecorriente Subestacin Eten 220 kV)

Rel MiCOM Alstom P742 (Unidad de campo para proteccin diferencial de barras Subestacin Reque 220 kV )

Rel MiCOM Alstom P741 (Unidad central para proteccin diferencial de barras Subestacin Reque 220 kV)

5.

DOCUMENTOS DE REFERENCIA

Documentacin HMV

Documento No. PE-AM14-ETEN-D090_50-ETEN-PVD-0090-PC. Flujo de Cargas [2]

Documento No. PE-AM14-ETEN-D091_50-ETEN-PVD-0091-PC. Estudio de Cortocircuito [3]

Plano No. PE-AM14-ETEN-K005_10-ETEN-ACS-0104-SC. Diagrama Unifilar [4].

Planos No. PE-AM14-ETEN-K002_10-ETEN-ACS-0101-SC. Rev. B. Diagramas de Principio [5]

Documento No. PE-AM14-ETEN-D040_10-ETEN-ACS-0061-FC.


transformadores de medida [6]

Documento No. PE-AM14-ETEN-D067_10-ETEN-ACS-0060-FC. Memoria de clculo de conductores y barrajes [7]

Documento No. PE-AM14-TRU-D066_60-TRU-PRB-2256-PE. Estudio de Coordinacin de Protecciones [8]

Memoria

de

clculo

cargabilidad

de

Documento No. PE-AM14-REQ-D066_60-REQ-PRB-2256-PE. Estudio de Coordinacin de Protecciones [9]


Documentacin ISA REP.

Documento Criterios de Ajuste y Coordinacin de los Sistemas de Proteccin del SEIN [1]
Documentacin Otros

Documento No. RFE-1-YTU-EDU-IDO-302-REV. F Unifilar Proteccin y Medida

Documento No. RFE-1-ADA-EDU-ABB-111-REV. B Diagrama Unifilar del Proyecto

6.

INFORMACIN TCNICA

En el presente documento se dan a conocer los resultados del estudio de coordinacin de protecciones de la baha de lnea
hacia la subestacin Eten para el proyecto Ampliacin 14 - Subestacin Reque 220 kV, con base en los Criterios de Ajuste y
Coordinacin de los Sistemas de Proteccin del SEIN [1].
Adicionalmente, como informacin de entrada para la realizacin del estudio de coordinacin de protecciones se tuvo en
cuenta los resultados obtenidos previamente en el Estudio de Flujo de Carga [2] y de Cortocircuito [3], los cuales fueron
elaborados empleando la ltima base de batos publicada por el COES, desarrollada en el programa DIgSILENT PowerFactory
(Digital Simulation and Network Calculation) Versin 14.1.3.
Finalmente, con base en los criterios tcnicos de ajuste y a los resultados de flujo de potencia y cortocircuito, se
recomendaron los ajustes de los rels de proteccin involucrados en el proyecto, buscando aislar slo la parte del sistema

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

11/79

donde ocurra el evento y de esta forma, garantizar una adecuada operacin del sistema de protecciones. La verificacin de los
ajustes seleccionados se realiz en el software DIgSILENT PowerFactory 14.1.3.
En este tem se presenta la informacin tcnica disponible para la realizacin del estudio de coordinacin de protecciones.

6.1.

PARMETROS DE LNEAS DE TRANSMISIN

En la Tabla 1 se presentan los parmetros de las lneas de transmisin involucradas en el proyecto, los cuales fueron
obtenidos de la base de datos del SEIN en el software DIgSILENT PowerFactory 14.1.3 y la base de datos del COES ECP
2010 [10]:
Tabla 1: Parmetros elctricos de las lneas de transmisin proyecto Ampliacin 14 Subestacin Reque 220 kV
Secuencia Positiva

Secuencia Cero

Acople Mutuo

Nivel de
Tensin [kV]

Longitud
[km]

Capacidad
Nominal [A]

R1 []

X1 []

B1 [S]

R0 []

X0 []

B0 [S]

Roo []

X0o []

Reque Eten 2L2-6

220

2,92

729

0,1539

1,4857

9,5338

1,1972

3,5624

6,0152

---

---

Reque Chiclayo
Oeste L-2296

220

13,78

400

1,0833

6,0975

51,94

4,4337

15,8113

31,5306

3,3624

8,4684

Reque Chiclayo
Oeste L-2297

220

13,78

400

1,0833

6,0975

51,94

4,4337

15,8113

31,5306

3,3624

8,4684

Reque Guadalupe
L-2236

220

72,4

400

5,6915 32,0361 272,8924 23,2947 83,0723 165,6619 17,6662

44,493

Reque Guadalupe
L-2237

220

72,4

400

5,6915 32,0361 272,8924 23,2947 83,0723 165,6619 17,6662

44,493

Lnea

6.2.

PARMETROS DE TRANFORMADOR DE POTENCIA

En la Tabla 2 se presentan los parmetros del transformador de potencia involucrado en el proyecto.


Tabla 2: Parmetros del transformador de potencia
Tensin Nominal [kV]
Subestacin

Transformador

Eten 220 kV

GSU

6.3.

HV

LV

220

18

Potencia Nominal [MVA]

Impedancia de Cortocircuito
Base de 265 MVA
[%]

Grupo de
Conexin

265

13,25

YNd1

PARMETROS DE TRANSFORMADORES DE INSTRUMENTACIN

En la Tabla 3 y Tabla 4 se presentan las caractersticas tcnicas de los transformadores de corriente y transformadores de
tensin respectivamente, asociados al proyecto.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

12/79

Tabla 3: Parmetros de transformadores de corriente

Subestacin

Reque 220 kV

Nivel de
Tensin [kV]

Campo

Reque
Eten
2L2-6

220

Nomenclatura

Ncleo

Relacin de
Transformacin (Ap/As)

Clase y
Precisin

Burden
(VA)

N1

(2500 1250 - 625)/1

0,2 S

7,5

N2

(2500 1250 - 625)/1

5P20

15

N3

(2500 1250 - 625)/1

5P20

15

N4

(2500 1250 - 625)/1

5P20

15

N1

(2000 1000 - 500)/5

0,2 S

30

N2

(2000 1000 - 500)/5

5P20

30

N3

(2000 1000 - 500)/5

5P20

30

N4

(2000 1000 - 500)/5

5P20

30

N1

2000/5

---

---

N2

2000/5

---

---

N1

(2000 1000 - 500)/5

0,2 S

30

N2

(2000 1000 - 500)/5

5P20

30

N3

(2000 1000 - 500)/5

5P20

45

TC-2616

Eten
Reque
2L2-6
TC-1*

TRF GSU
Eten 220 kV

220
CT

Eten
Reque
2L2-6

TC-2*

* De acuerdo a la corriente nominal del transformador GSU vista del lado de alta tensin y la capacidad nominal de la lnea Reque Eten
2L2-6 220 kV, se selecciona la relacin de transformacin 1000/5 A, debido a que en los diagramas unifilares RFE-1-ADA-EDU-ABB-111
y RFE-1-YTU-EDU-IDO-302 no se especifica la relacin utilizada.

Tabla 4: Parmetros de transformadores de tensin


Subestacin

Campo

Reque 220 kV Reque Eten 2L2-6


Eten 220 kV

Eten Reque 2L2-6

Relacin de Transformacin
(kVp/Vs)

Clase

Burden
(VA)

N1

220/3 : 100/3

0,2 3P

30

N2

220/3 : 100/3

0,2 3P

30

N1

220/3 : 110/3

0,2

25

N2

220/3 : 110/3

3P

25

Nomenclatura Devanado

TT-2536
TT-1

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

13/79

Subestacin

Campo

TT-2

6.4.

Relacin de Transformacin
(kVp/Vs)

Clase

Burden
(VA)

N1

220/3 : 110/3

0,2

25

N2

220/3 : 110/3

3P

25

N3

220/3 : 110/3

3P

25

Nomenclatura Devanado

DISPOSITIVOS DE PROTECCIN INVOLUCRADOS EN EL PROYECTO

En la Tabla 5 se presenta un listado de los rels de proteccin que sern instalados en las subestaciones Reque 220 kV y Eten
220 kV. Adicionalmente, se muestran las funciones de proteccin actualmente implementadas en las subestaciones
adyacentes.
Tabla 5: Dispositivos de proteccin Involucrados en el proyecto
Subestacin

Campo

Reque Eten
2L2-6

Reque Chiclayo
Oeste L-2296

Reque Chiclayo
Oeste L-2297

Nivel de
tensin
[kV]

220

220

220

Descripcin

Campo de Lnea

Campo de Lnea

Campo de Lnea

Reque 220 kV

Reque
Guadalupe L-2236

Reque
Guadalupe L-2237

220

220

Campo de Lnea

Campo de Lnea

Acoplamiento

220

Campo de Acople

Barras

220

Barraje

Marca

Referencia

Part Number

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

ALSTOM

MICOM
P742

P742311A1M0510J

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

ALSTOM

MICOM
P742

P742311A1M0510J

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

ALSTOM

MICOM
P742

P742311A1M0510J

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

ALSTOM

MICOM
P742

P742311A1M0510J

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

ALSTOM

MICOM
P742

P742311A1M0510J

87B

SEL

SEL 421

04214611XC2X5H74545XX

51/50, 51N/50N, 25

P742311A1M0510J

87B

P74133BA6M0510K

87B, 50BF

ALSTOM
ALSTOM

MiCOM
P742
MiCOM
P741

Funciones
87L, 67N, SOTF, 59,
79, 25, 67NCD
87L, 67N, SOTF, 59,
79, 25, 67NCD
87B
87L, 67N, SOTF, 59,
79, 25
87L, 67N, SOTF, 59,
79, 25
87B
87L, 67N, SOTF, 59,
79, 25
87L,67N, SOTF, 59,
79, 25
87B
21, 67N, SOTF, 59,
79, 25, 68
21, 67N, SOTF, 59,
79, 25, 68
87B
21, 67N, SOTF, 59,
79, 25, 68
21, 67N, SOTF, 59,
79, 25, 68

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

14/79

Subestacin

Eten 220 kV

Campo

Eten Reque 2L26

TRF GSU

Nivel de
tensin
[kV]

220

220

Chiclayo Oeste Reque L-2296

220

Chiclayo Oeste Reque L-2297

220

Guadalupe - Reque
L-2236

220

Guadalupe - Reque
L-2237

220

Descripcin

Referencia

Part Number

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

---

T60T

---

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

SEL

SEL 411L

0411L0X6X1C7CCXH575D5XX

Siemens

7SA612

---

Siemens

7SA522

---

ABB

REL670

---

ABB

REL670

---

Campo de Lnea

Campo de
transformacin
Campo de Lnea

Chiclayo Oeste
220 kV
Campo de Lnea

Campo de Lnea

Guadalupe
220 kV

7.

Marca

Campo de Lnea

Funciones
87L, 67N, SOTF, 59,
79, 25, 50BF,
67NCD
87L,67N, SOTF, 59,
79, 25, 50BF,
67NCD
51, 50, 51N, 50N
87L, 67N, SOTF, 59,
79, 25, 68
87L,67N, SOTF, 59,
79, 25, 68
87L, 67N, SOTF, 59,
79, 25, 68
87L,67N, SOTF, 59,
79, 25, 68
21, 67N, SOTF, 59,
79, 25, 68
21, 67N SOTF,, 59,
79, 25, 68
21, 67N, SOTF, 59,
79, 25, 68
21, 67N, SOTF, 59,
79, 25, 68

FILOSOFA Y CRITERIOS DE LAS FUNCIONES DE PROTECCIN

En esta seccin se presenta la filosofa, criterios y ajustes recomendados para los dispositivos de proteccin que hacen parte
del alcance del presente estudio.

7.1.

PROTECCIN DE LNEAS DE TRANSMISIN

7.1.1 Filosofa de proteccin


En las subestaciones Reque 220 kV y Eten 220 kV, las bahas de la lnea Reque Eten (2L2-6) 220 kV, contarn con dos
rels de proteccin marca SEL referencia SEL 0411L0X6X1C7CCXH575D5XX, que ofrecern una proteccin redundante y se
implementarn las siguientes funciones de proteccin: diferencial de lnea (ANSI 87L) que ser la funcin principal, y como
funcin de respaldo el sobrecorriente direccional de tierra (ANSI 67N), sobretensin (ANSI 59), Cierre en falla (SOTF),
verificacin de sincronismo (ANSI 25) y recierre (ANSI 79), adicionalmente se contar con un esquema de teleproteccin
sobrecorriente de tierra por comparacin direccional (67NCD) y en el extremo de Eten, se habilitar la funcin de falla
interruptor (ANSI 50BF).
Normalmente el recierre es arrancado por las funciones de proteccin diferencial de lnea (87L) y sobrecorriente de tierra por
comparacin direccional (67NCD). El bloqueo de recierre se emitir una vez se tenga actuacin de las funciones 50BF y 59.
Las protecciones principal y secundaria tienen la capacidad de ejecutar el recierre por 87L y 67NCD.
Los sistemas de recierre automtico se implementan para restaurar la parte desconectada del sistema de transmisin, una
vez que la falla transitoria se ha extinguido. En algunos sistemas de transmisin, el recierre se utiliza para mejorar la
estabilidad del sistema, dado que es un medio para restaurar rpidamente elementos crticos de transmisin de potencia.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

15/79

La eleccin del tipo de recierre a usar depende del nivel de tensin, de requerimientos del sistema, de consideraciones de
estabilidad y de la proximidad de generadores.
Segn el esquema de proteccin (RFE-1-YTU-EDU-IDO-302-REV. F) el interruptor ubicado en la subestacin Eten 220 kV,
se acciona tanto ante una orden de disparo de la proteccin de la lnea SEL 411L como la proteccin relacionada al
transformador GSU. De acuerdo a la norma IEEE Std C37.91-2008 IEEE Guide for Protecting Power Transformers, los
transformadores de potencia no son reenergizados ante un esquema de recierre automtico excepto cuando el transformador
est conectado a una lnea o barra que son reenergizadas luego de un disparo debido a la orden de la proteccin asociada a la
lnea o barra. Es probable la reenergizacin del transformador, si es usado un interruptor de puesta a tierra automtico en el
lado de alta del transformador y un esquema de recierre de alta velocidad es utilizado en la lnea.
Dado que la lnea Reque Eten 220 kV es tan corta y tiene prximo un transformador de potencia y unidades de generacin
de la central Eten, no se recomienda habilitar la funcin de recierre automtico (ANSI 79), ya que se considera que puede
traer ms riesgos que beneficios, si se habilita el recierre automtico en la lnea el generador podra presentar daos en caso
de que se energice ante una prdida de sincronismo.
En la Figura 3 y la Figura 4 , se muestra el esquema de proteccin a implementar en la lnea de la subestacin Reque 220 kV
y la subestacin Eten 220 kV respectivamente. La funcin de proteccin distancia (ANSI 21) no se est considerando, ya que
se realiz el clculo del SIR (Source to Line Impedance) para la lnea Reque Eten 220 kV y sta se cataloga como una lnea
corta, a continuacin se explica el clculo:
SIR

Xs
XL

Ecuacin (1)

Donde:
V

X S Reactancia de la fuente, X s

3I f

X L Reactancia de la Lnea

Tabla 6: Clculo SIR Lnea Reque Eten 220 kV


LNEA

VOLTAJE
[kV]

RL
[Ohm]

XL
[Ohm]

FALLA 3F
FRANCA
BARRA 220 kV
SE REQUE [kA]

XS
[Ohm]

SIR

TIPO DE
LNEA

ETEN

2,92

220

0,1538

1,4856

4,34

29,27

19,70

Lnea Corta

REQUE

2,92

220

0,1538

1,4856

2,37

53,59

36,08

Lnea Corta

DESDE HASTA

Reque - Eten 2L2-6 REQUE


Eten - Reque 2L2-6

LONGITUD
[km]

ETEN

En la Tabla 6, se observa que el SIR es superior a 4, por lo tanto se cataloga la lnea como una lnea corta de acuerdo la
norma IEEE Std. C37.113-1999 Guide for Protective Relay Applications to Transmission Lines, para este tipo de lneas se
recomienda el uso de esquemas de proteccin completamente selectivos como la funcin diferencial de lnea (87L) como
funcin principal y como funcin de respaldo se tendr la funcin 67N. No se recomienda el uso de la proteccin distancia
como funcin principal, dado que factores tales como la resistencia de arco o la impedancia de falla pueden causar
subalcance en el rel. Esta recomendacin sirve para mejorar la selectividad del conjunto de protecciones en el sistema
relacionado, de esta forma se siguen los lineamientos generales para el ajuste de protecciones elctricas en lneas de
transmisin, la filosofa recomendada por los fabricantes de los rels y la gua IEEE Std. C37.113-1999 IEEE Gua de
aplicacin para rels de proteccin en lneas de transmisin.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

16/79

Figura 3:

Esquema de proteccin de lnea subestacin Reque 220 kV (Anexo 1)

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

17/79

Figura 4:

Esquema de proteccin de lnea subestacin Eten 220 kV (Anexo 2)

7.1.2 Criterios de ajuste para las funciones de proteccin


7.1.2.1 Funcin diferencial de lnea (87L)
Los criterios a definir en la proteccin diferencial SEL 411L, son aquellos recomendados por el fabricante [11] para su
correcta operacin, teniendo en cuenta su principio de funcionamiento.
Principio de funcionamiento
En un esquema diferencial de corriente, se miden las corrientes que atraviesan las dos terminales de la lnea. Normalmente,
la corriente que sale de un extremo debe ser igual a la que entra en el otro, es decir, en condiciones normales, la diferencia de
corriente es cercana a cero. Sin embargo, existen pequeas variaciones por el efecto capacitivo de la lnea y los errores de
medida en los equipos de instrumentacin.
Esta proteccin compara las fases y las componentes de secuencia negativa y cero en cada uno de los extremos de la lnea,
luego realiza la verificacin y el clculo de la siguiente relacin:
IL
IR

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

18/79

Donde:

I L : Corriente fasorial en el extremo local

I R : Corriente fasorial en el extremo remoto

Figura 5:

Esquema elctrico proteccin diferencial de lnea

La relacin calculada anteriormente, se ubica en un plano complejo (alpha) que determinar el comportamiento de la
proteccin diferencial en operacin normal, falla interna y externa. Ante operacin normal y para fallas externas, la relacin
ser 1 180, y para fallas internas, el vector resultante ser 1 0. En la Figura 6, se presenta la caracterstica de operacin
de la proteccin SEL 411L (la seccin delimitada por el ajuste 87LANG, corresponde a la zona de bloqueo y por fuera de sta
ser la regin de operacin).

Figura 6:

Caracterstica de operacin funcin diferencial de lnea rels SEL 411L

Lo mencionado anteriormente, se tendr en condiciones ideales del sistema. Se deben considerar adicionalmente, los errores
presentes debido al ngulo de carga (diferencia angular entre terminal remota y local), no homogeneidad de los sistemas,
errores por asimetra del canal de comunicaciones y por saturacin de los transformadores de corriente.
La proteccin SEL 411L dispone de tres (3) elementos diferenciales (uno de fases 87LP, uno de secuencia negativa 87LQ y
uno de secuencia cero 87LG).
El rea de bloqueo est definida por el parmetro 87LXA, el radio exterior 87LXR y el radio interior 1/87LXR (la caracterstica
es igual para cada uno de los elementos). Los ajustes recomendados para la proteccin diferencial de lnea, se muestran a
continuacin:

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

19/79

Extensin angular 87LXA: Considerando los errores mencionados (mximo ngulo de carga, no homogeneidad de
los sistemas, asimetra del canal y saturacin de los transformadores de corriente), se recomienda un ajuste de 195
grados. El ajuste mencionado aplica para todos los elementos diferenciales

El radio exterior 87LXR, y radio interior 1/87LXR: Define el radio exterior y se ajusta para excluir de la zona de
bloqueo todas las fallas trifsicas internas. El fabricante recomienda un valor de 6 para 87LR y 1/6 para el radio
interno. Lo ajustes mencionados aplican para todos los elementos diferenciales

Elemento 87LPP: Se ajusta para detectar adecuadamente las fallas internas. Se habilita por encima de la corriente
de carga capacitiva de la lnea. Los elementos 87LQP (secuencia negativa) y 87LGP (secuencia cero) se utilizarn
para detectar las fallas internas desbalanceadas, se ajusta normalmente al 10% de la corriente nominal secundaria
con referencia al CTR mximo

Lgica E87LXS: la lgica se utiliza para deshabilitar los elementos diferenciales de modo normal de fases, secuencia
negativa y cero en el evento de malfuncionamiento o desconexin de un transformador de corriente, y habilitando
los elementos diferenciales de modo extendido, los cuales son menos sensibles en todas las condiciones

7.1.2.2 Funcin de sobrecorriente direccional residual (67N)


En la lnea Reque Eten 220 kV del proyecto Ampliacin 14, subestacin Reque 220 kV, las protecciones de sobrecorriente
de tierra (67N) sern ajustadas con un arranque de 120 Aprim, el cual se considera adecuado, ya que los desbalances
normales en el SEIN no superan dicho valor, y solo ser alcanzado el umbral durante condiciones de fallas a tierra (ver
referencia [10]).
El dial se ajustar realizando fallas de alta impedancia. Sin embargo, los tiempos de disparo de la proteccin deben ser
superiores a los ajustados en la proteccin distancia (zona 2), entre 0,7 y 1,0 segundos (considerando este elemento como
proteccin de respaldo de la proteccin principal).
Se debe verificar que el ajuste recomendado permita detectar fallas a tierra de 50 ohm en el extremo remoto, para el
escenario de mnimas corrientes de cortocircuito. As mismo, se debe verificar que el ajuste propuesto se encuentre por
encima de los desbalances normales de la red, esta verificacin se debe realizar al momento de la energizacin de las lneas.

0,14
I

Tap

0 , 02

Dial

Curva IEC Normal Inversa

Donde:
Dial: Multiplicador de tiempo.
t: Tiempo de operacin en segundos, [s].
I: Valor de corriente registrada por el dispositivo de proteccin, [A].
Tap: Valor de ajuste de la corriente de arranque, [A].
Adems, se habilitar una etapa de tiempo definido para despejar fallas hasta el 50% de la lnea, verificando que ante la
condicin de mximas corrientes de cortocircuito, no se active esta etapa para fallas ms all de la lnea protegida, el tiempo
de operacin se ajustar en 0,25 s.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

20/79

Por otra parte, se debe tener en cuenta que el tiempo de disparo de la proteccin de sobrecorriente de tierra, debe ser superior
al tiempo de disparo ante la peor condicin de desbalance por discrepancia de polos del interruptor ubicado en la subestacin
remota.

7.1.2.3 Esquemas de teleproteccin


Esquema de comparacin direccional (67NCD)
Este esquema, utiliza funciones de sobrecorriente para detectar adecuadamente las fallas dentro de la lnea. En la Figura 7, se
ilustra las lgicas presentes en el esquema 67NCD. Este esquema es completamente dependiente del canal y requiere que la
falla sea asimtrica a tierra y dentro de la lnea. El esquema de comparacin direccional opera si se tiene arranque de la
funcin 67N y recepcin del canal de teleproteccin. En caso de que la falla sea en direccin reversa se tendr bloqueo del
envo de teleproteccin y por lo tanto del esquema.

I2

I1

&
67N

67NR

&
Rx

Rx

Tx

Tx

EMISIN
CD

EMISIN
CD

Figura 7:

67N

67NR

Esquema 67N en comparacin direccional

7.1.2.4 Funcin cierre en falla (SOTF)


La lgica de cierre en falla se habilita por la indicacin de posicin cerrado del interruptor del campo asociado con la lnea en
estudio y se activar por medio del disparo de un elemento de sobrecorriente instantneo. El ajuste del elemento de
sobrecorriente instantneo consiste en la simulacin de una falla trifsica en la barra local, restando a la corriente total de la
falla, el aporte de corriente a travs de la lnea a proteger y tomando el 50% del valor obtenido. Este ajuste debe ser superior a
la mxima corriente de carga de la lnea.
La lgica de cierre en falla se debe habilitar por cambios en el estado de la posicin del interruptor (transicin de cerrado a
abierto). La funcin debe ser bloqueada 1 s despus de dar orden de cierre sobre el interruptor.
Las protecciones SEL 411L permiten que ciertos elementos de proteccin ejecuten el disparo durante un tiempo ajustable
despus del cierre del interruptor, los cuales se definen en la ecuacin lgica TRSOTF; la lgica opera en dos etapas,
validando una posible condicin SOTF y habilitando la duracin de la proteccin SOTF. A continuacin, en la Figura 8 se
muestra la lgica de la funcin SOTF.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

21/79

Figura 8:

Lgica de disparo SOTF SEL 411L

7.1.2.5 Funcin discrepancia de polos


El ajuste del tiempo para el disparo por discrepancia de polos debe ser coordinado con el tiempo del recierre, de tal modo que
la temporizacin del recierre sea inferior a la del rel de discrepancia de polos. Tambin se debe coordinar la temporizacin de
la discrepancia de polos con el tiempo de operacin de los rels de sobrecorriente de tierra instalados para proteger equipos
ubicados en las cercanas de la lnea que presenta la discrepancia de polos; de tal modo que el tiempo de operacin de dichos
rels, sea superior al tiempo de operacin de la discrepancia de polos.
El tiempo para el disparo por discrepancia de polos se recomienda ajustarlo en 1,5 s (ofreciendo un respaldo de la proteccin
de discrepancia de polos, propia de los interruptores, la cual se recomienda ajustar en 1 s).

7.1.2.6 Esquema de recierre (79) y Verificacin de sincronismo (25)


Para mantener el esquema actualmente implementado en la zona, se habilitar la funcin de recierre automtico para iniciar
solo ciclo de recierre monopolar ante fallas monofsicas.
Tiempos muertos de recierre
El tiempo muerto de recierre debe ser mayor al tiempo necesario para la extincin del arco secundario y menor al tiempo
mximo permisible de recierre.
Tiempo muerto para el ciclo de recierre monofsico = 0,5 s. (lneas de 220 kV)
Tiempo de reclamo = 180 s.
Verificacin de sincronismo
Los criterios de ajuste para la verificacin de sincronismo son:

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

22/79

El umbral de lnea viva y barra viva se ajusta al 80% de la tensin nominal

El umbral de lnea muerta y barra muerta se ajusta al 40% de la tensin nominal

Los niveles que permiten el recierre sincronizado para cualquier interruptor del proyecto son:

Mxima diferencia de tensin: 10% de la tensin nominal

Mxima diferencia de ngulo: 30

Mxima diferencia de frecuencia: 0,1 Hz

7.1.2.7 Funcin de sobretensin (59)


De acuerdo con el estudio de coordinacin de protecciones ECP-2010, el COES presenta el esquema de sobretensin presente
para cada una de las zonas del SEIN. Por lo anterior y para mantener dicho esquema, las lneas del proyecto ampliacin 14
seguirn los lineamientos descritos en el Anexo 11 del documento Protecciones Sistmicas (ECP-2010, COES) [10].
El esquema presente en la zona norte es el siguiente:

El rea norte del SEIN es dbil en el extremo norte (Zorritos) y fuerte en las subestaciones Trujillo Chimbote. Esta rea es
susceptible a fenmenos de sobretensin temporales por lo que antes de desconectar cargas por sobretensin, es preferible
desconectar lneas de transmisin y aliviar las sobretensiones.
El esquema propuesto es un esquema escalonado que inicia en la S.E. Zorritos con la lnea de interconexin Per Ecuador
(L-2280) y termina con las lneas de enlace entre Trujillo Chimbote Paramonga. Tambin por ser el enlace Trujillo
Chimbote Paramonga - Zapallal de doble circuito, es preferible desconectar un circuito por cada enlace antes de
interrumpir todo el enlace, por esta razn las lneas de transmisin L-2233, L-2216 y L-2214 tienen ajustes diferentes a los
de las lneas L-2232, L-2215 y L-2212/2213 respectivamente.
Con el seccionamiento de las lneas Chiclayo Oeste Guadalupe (L-2236 y L-2237) por medio de la subestacin
Reque 220 kV, se propone modificar el esquema de sobretensin manteniendo el mismo criterio y/o metodologa de
desconectar primero un circuito por cada enlace para el caso de las lneas paralelas.
A continuacin en la Tabla 7 se presentan los tiempos dispuestos por el esquema de sobretensin de la zona y los tiempos
propuestos para las lneas involucradas en el proyecto Ampliacin 14.
Tabla 7: Esquema propuesto de sobretensin zona norte
Etapa 1
Lnea
L-2280
L-2249
L-2248
L-2238
L-2241
L-2239
L-2240
L-2296

SSEE 1 SSEE 2
Zorritos Machala
Talara Zorritos
Piura Talara
Piura Chiclayo
La Nia Piura
Chiclayo La Nia
Chiclayo Carhuaquero
Chiclayo Reque

Etapa 2

U>

t>

U>>

t>>

(p.u)

(seg)

(p.u)

(seg)

1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15

1,0
1,5
2,0
1,5
2,4
2,6
2,8
3,0

1,18
1,30
1,30
1,30
1,30
1,30
1,30
1,30

0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

23/79

Etapa 1
Lnea
L-2297
L-2236
L-2237
2L2-6
L-2234
L-2235
L-2260
L-2233
L-2232
L-2216
L-2215
L-2214
L-2213
L-2212

SSEE 1 SSEE 2
Chiclayo Reque
Reque Guadalupe
Reque Guadalupe
Reque - Eten
Trujillo Guadalupe
Trujillo Guadalupe
Trujillo Cajamarca
Chimbote Trujillo
Chimbote Trujillo
Paramonga Chimbote
Paramonga Chimbote
Paramonga Zapallal
Paramonga Huacho
Huacho Zapallal

Etapa 2

U>

t>

U>>

t>>

(p.u)

(seg)

(p.u)

(seg)

1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15
1,15

1,8
3,2
1,9
1,9
3,5
2,0
3,8
2,5
4,2
3,0
4,5
3,5
5,0
5,5

1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30
1,30

0,4
0,9
0,5
0,5
1,0
0,5
1,2
0,6
1,4
0,8
1,6
1,0
1,8
2,0

7.1.2.8 Funcin falla interruptor (50BF)


En la proteccin SEL 411L, se cuenta con la funcin falla interruptor de dos etapas, las cuales se describen a continuacin:
Etapa 1: Comanda retrip al propio interruptor, 0,15 s despus del disparo proveniente de la proteccin principal.
Etapa 2: Comanda disparo al propio interruptor, a los interruptores adyacentes a la misma barra y disparo directo transferido
al extremo remoto, 0,25 s despus del disparo proveniente de la proteccin principal.
En lneas de transmisin el nivel de corriente de arranque de la proteccin falla interruptor debe ajustarse encima de la
corriente mxima de carga y menor que la corriente mnima de falla en el extremo remoto de la subestacin Reque.

I mx c arg a I 50BF I mn falla


Lgica de la proteccin falla interruptor
Se recomienda que la funcin falla interruptor opere por corriente y por la habilitacin de una seal de disparo externa.

Figura 9:

Lgica de la proteccin Falla Interruptor 50BF

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

24/79

7.2.

TRANSFORMADOR DE POTENCIA

7.2.1 Filosofa de proteccin


El esquema de proteccin para el transformador GSU de 265 MVA, 220/18 kV de la subestacin Eten, contar con un
esquema diferencial de transformador, para el rel de proteccin T60T con funcin diferencial de transformador ANSI 87T, y
contar adems con funciones de proteccin de respaldo por sobrecorriente de fases ANSI 50/51, sobrecorriente de tierra
ANSI 50N/51N y sobreexcitacin ANSI 24. En la Figura 10 se presenta el esquema de proteccin a implementar en el
transformador de la subestacin Eten asociado al proyecto Ampliacin 14, se aclara que como alcance del estudio solamente
se van a recomendar los ajustes para la funciones de proteccin de sobrecorriente de fases y tierra en el lado de 220 kV.

Figura 10:

Esquema de proteccin transformador de potencia

7.2.2 Criterios de ajuste para las funciones de proteccin


7.2.2.1 Funcin de sobrecorriente de fases de tiempo inverso y tiempo definido (51/50)
Esta funcin acta como proteccin de respaldo a la proteccin diferencial del transformador.
Para el valor de arranque de la funcin de sobrecorriente temporizada se toma como ajuste el menor valor entre 130 % de la
corriente nominal del transformador de potencia del devanado correspondiente y el 120 % de la corriente nominal del
transformador de corriente (TC). Se selecciona una curva del tipo IEC Standard Inverse con un ajuste del dial para garantizar
coordinacin con la corriente Inrush del transformador (12 x In) y con los dispositivos de sobrecorriente instalados en
subestaciones adyacentes.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

25/79

Para el lado de alta tensin del transformador, se recomienda ajustar el dial de tal manera que la proteccin opere en un
tiempo aproximado de 750 ms, ante una falla trifsica en el lado de baja tensin del transformador, garantizando as un
tiempo de operacin superior a 500 ms para la coordinacin con la proteccin ubicada en el lado de baja tensin.
Adicionalmente, para el lado de alta tensin del transformador se ajusta una etapa de sobrecorriente de tiempo definido para
despejar fallas en el transformador de potencia sin sobrepasar al lado de baja tensin. La corriente de arranque se ajusta al
1,5 Icc3F aporte > Iinr = 10InTR ONAN.
Dnde:
Icc3F aporte: Aporte de corriente por el devanado de alta tensin ante falla trifsica en la barra conectada al lado de
baja tensin.
Iinr: Corriente inrush o corriente de magnetizacin del transformador.
InTR ONAN: Corriente nominal del transformador con refrigeracin natural.
La temporizacin de esta etapa se ajusta entre 100 ms 250 ms de modo que se eviten actuaciones indeseadas ante altas
corrientes de energizacin del transformador.

7.2.2.2 Funcin de sobrecorriente de tierra de tiempo inverso y tiempo definido (51N/50N)


Para el valor de arranque de la funcin de sobrecorriente temporizada de tierra se toma un valor de 120 Aprim, dado que los
niveles de desbalance esperados en el sistema son inferiores a este valor. Se selecciona una curva del tipo IEC Standard
Inverse y el ajuste del dial se selecciona de acuerdo con el estudio de cortocircuito, buscando coordinacin con los dispositivos
de sobrecorriente instalados en subestaciones adyacentes.
Para el lado de alta tensin del transformador, se recomienda ajustar el dial de tal manera que guarde un factor de
coordinacin de 250 ms como mnimo respecto a las protecciones de sobrecorriente direccional ubicadas en las lneas Reque
Chiclayo 1 y 2 220 kV (L-2296 y L-2297) extremo Reque ante una falla bifsica a tierra al 50% de estas lnea con una
impedancia de 10 ohm.
Se recomienda habilitar la funcin de sobrecorriente de tiempo definido de tierra, garantizando la selectividad con la etapa de
tiempo definido de las protecciones de sobrecorriente direccional ubicadas en las lneas Reque Chiclayo 1 y 2 220 kV (L2296 y L-2297) extremo Reque ante una falla bifsica a tierra franca al 50% de esta lnea, con una temporizacin de 500 ms.

7.3.

PROTECCIN DE ACOPLE

7.3.1 Filosofa de proteccin


En la Figura 11, se muestra el esquema de proteccin de la baha de acople de la subestacin Reque. Esta baha contar con
un rel marca SEL referencia SEL 04214611XC2X5H74545XX, el cual realizar las funciones de proteccin de sobrecorriente
de fases y tierra (ANSI 51/50/51N/50N) y verificacin de sincronismo (ANSI 25).

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

26/79

Figura 11:

Esquema de proteccin baha de acople subestacin Reque 220 kV (Anexo 3)

7.3.2 Criterios de ajuste para las funciones de proteccin


7.3.2.1 Funcin de sobrecorriente de fases de tiempo inverso y tiempo definido (51/50)
Proteccin de sobrecorriente de fases de tiempo inverso (51)
Para proteger los equipos de medida, se ajustar una caracterstica IEC Normal Inversa con un umbral del 120% de la
corriente nominal del transformador de corriente del campo de acople. El dial se ajusta para despejar fallas francas en el
extremo remoto de las lneas al menos en 1,3 s, considerando que la corriente total de falla circule por el campo de acople.
Proteccin de sobrecorriente de fases de tiempo definido (50)
Como respaldo a la proteccin diferencial de barras, se ajustar un elemento de sobrecorriente de tiempo definido, el cual
despejar fallas francas al 1% de las lneas convergentes a la subestacin en un tiempo de 0,5 s.

7.3.2.2 Funcin de sobrecorriente de tierra de tiempo inverso y definido y tierra (51N/50N)


Proteccin de sobrecorriente de tierra (51N)
Se ajustar una caracterstica IEC Normal Inversa con un umbral del 40% de la corriente nominal del transformador de
corriente del campo de acople. El dial se ajusta para despejar fallas en el extremo remoto de las lneas en 1,3 s, considerando
que la corriente total de falla circule por el campo de acople.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

27/79

Proteccin de sobrecorriente de tierra de tiempo definido (50N)


Como respaldo de la proteccin diferencial de barras, se ajustar un elemento de sobrecorriente de tiempo definido, el cual
despejar fallas a tierra al 1% de las lneas convergentes a la subestacin en un tiempo de 0,5 s.

7.3.2.3 Verificacin de sincronismo (25)


Los criterios de ajuste para la verificacin de sincronismo son:

El umbral de lnea viva y barra viva se ajusta al 80% de la tensin nominal

El umbral de lnea muerta y barra muerta se ajusta al 40% de la tensin nominal

Los niveles que permiten el recierre sincronizado para cualquier interruptor del proyecto son:

7.4.

Mxima diferencia de tensin: 10% de la tensin nominal

Mxima diferencia de ngulo: 30

Mxima diferencia de frecuencia: 0,1 Hz

PROTECCIN DE SUBESTACIONES

7.4.1 Filosofa de proteccin


La subestacin Reque 220 kV, cuenta con una configuracin de doble barra y acoplamiento, para la proteccin del barraje se
tiene implementado un rel de proteccin marca ALSTOM cuyo modelo es MiCOM P74133BA6M0510K (unidad central de
procesamiento) con funcin diferencial de barras distribuida (ANSI 87B), la cual cuenta con unidades de baha modelo
MiCOM P742311A1M0510J por cada campo de la subestacin.
La proteccin diferencial es del tipo porcentual, distribuida para seis (6) bahas y tiene la capacidad de detectar e identificar la
barra fallada a travs de la posicin de los contactos auxiliares de los seccionadores de barra.
La informacin de las seales de corriente y seales de posicin de equipos (seccionador e interruptor) son recogidos por el
controlador de baha de cada celda y llevados a la unidad central para su procesamiento. Los comandos de disparo son
emitidos a todos los interruptores de la barra afectada a travs de sus respectivos controladores de baha.
En la proteccin diferencial se tiene incluido la proteccin de falla interruptor (ANSI 50BF), la cual cuenta con dos etapas de
operacin y es activada bsicamente por dos condiciones; el umbral de corriente de operacin y los disparos de las
protecciones al interruptor fallado. La primera etapa de la proteccin falla interruptor conocido tambin como RETRIP es
dirigido al interruptor en falla a travs de las dos bobinas como una segunda intensin de disparo; si el interruptor no abre se
activa la segunda etapa y emite su disparo a los interruptores de las bahas que alimentan la falla y a travs de un DDT al
extremo remoto de la baha.
Se utilizar un rel de disparo y bloqueo 86B, el cual permitir el bloqueo al cierre del interruptor, una vez se active la funcin
diferencial de barras.
A continuacin, en la Figura 12 se muestra el esquema distribuido a implementar y en la Tabla 8 se muestran los datos
tcnicos de los sistemas de proteccin de la barra de 220 kV en la subestacin Reque.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

28/79

Figura 12:

Esquema diferencial de barras distribuida

Tabla 8: Datos tcnicos de la proteccin diferencial de barras en 220 kV


Bahas en
220 kV
L-2236
L-2237
L-2296
L-2297
2L2-6
Acople de
Barras

Transformador de corriente
2500-1250-625/1 A
15VA-5P20
2500-1250-625/1 A
15VA-5P20
2500-1250-625/1 A
15VA-5P20
2500-1250-625/1 A
15VA-5P20
2500-1250-625/1 A
15VA-5P20
2500-1250-625/1 A
15VA-5P20

Relacin del TC usada


para la 87B

Unidad de Baha de la
87B

625/1 A

P742311A1M0510J

625/1 A

P742311A1M0510J

625/1 A

P742311A1M0510J

625/1 A

P742311A1M0510J

625/1 A

P742311A1M0510J

625/1 A

P742311A1M0510J

Unidad Central de la
87B

P74133BA6M0510K

7.4.2 Criterios de ajuste para las funciones de proteccin


7.4.2.1 Funcin diferencial de barras (87B)
La barra de un sistema de potencia debe estar provista de una proteccin de alta velocidad que minimice los daos en los
equipos y que evite la inestabilidad del sistema, ante condiciones de falla.
El mtodo de proteccin de barras ms comnmente empleado es el principio diferencial en el cual la suma de las corrientes
que entran y salen de la barra debe ser igual a cero, de lo contrario habr ocurrido una falla interna

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

29/79

Figura 13:

Proteccin diferencial de barras

La proteccin diferencial de barras consiste en una unidad central (MiCOM P741) y seis (6) unidades distribuidas (MiCOM
P742), cada una de estas unidades distribuidas se encuentra asociada con una baha de lnea o acople. El elemento de
proteccin primaria del esquema P74P es proteccin diferencial de corriente afectada por fases independientes. La tcnica
utilizada es netamente numrica y emplea anlisis nodal en todo el esquema, basado en criterios de zona y de esquema. El
anlisis se ejecuta en la unidad central, por lo tanto es esencial la comunicacin entre la unidad central y las unidades
perifricas, lo cual se logra a travs de conexin directa en fibra ptica a una tasa de 2,5 Mbps.

Figura 14:

Principio de proteccin diferencial de barras

Principio de operacin: El principio bsico de la proteccin diferencial de barras est basado en la aplicacin de la ley de
Kirchhoff, al comparar la magnitud de corriente que entra y sale de la zona protegida y de la zona de verificacin. Bajo
condiciones normales, la magnitud de la corriente que fluye hacia el rea y hacia la zona de verificacin en cuestin, es igual
a la magnitud de la corriente que fluye hacia afuera, por tanto las corrientes se cancelan. En contraste, cuando una falla
ocurre, la corriente diferencial que se presenta es igual a la corriente de falla derivada. El concepto se muestra en la
Figura 14.
Se pueden utilizar dos mtodos para el esquema de proteccin diferencial, la suma vectorial o la suma instantnea, en este
caso, el algoritmo utilizado por la proteccin P74X es el mtodo de suma instantnea, por muestras. Este mtodo tiene la
ventaja de la cancelacin de componentes armnicas y c.d. de origen externo en el clculo. Otra ventaja de la suma
instantnea radica en la velocidad de la decisin, que est determinada por la frecuencia de muestreo.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

30/79

Figura 15:

Caracterstica del esquema de proteccin diferencial de barras utilizado por los rels MiCOM P74X

La operacin de la proteccin diferencial de barras se basa en la aplicacin de un algoritmo con caracterstica fragmentada,
que compara entre la corriente diferencial (I diff) y la corriente de restriccin (Ibias), solamente se permite el disparo si la
corriente diferencial excede la pendiente ajustada en la caracterstica fragmentada. La caracterstica se define para garantizar
la estabilidad durante fallas externas donde el esquema tiene transformadores de corriente con diferentes caractersticas, que
pueden producir un comportamiento no uniforme.
Los operandos del algoritmo se muestran a continuacin [13] (pg. 152):

idiff (t )

Corriente diferencial

Corriente de restriccin

ibias (t ) i

Es importante que los ajustes de los transformadores de corriente se ingresen completos (corriente nominal primaria y
corriente nominal secundaria), ya que se requieren para calcular parmetros adicionales para el uso en los algoritmos de
deteccin de saturacin que se ejecutan dentro de las unidades perifricas.
El esquema de la proteccin P74X se puede acomodar a diferentes relaciones de transformadores de corriente en toda la zona
protegida, siendo 40 la mxima diferencia entre la mnima y la mxima corriente nominal primaria para los transformadores
de corriente considerados. Esta combinacin debe por tanto ser tenida en cuenta por el esquema y se logra al utilizar
corrientes primarias enviadas por las unidades perifricas a la unidad central, la cual se encarga de los clculos del esquema.
Como se observa en la Figura 15 la operacin de la proteccin diferencial de barras consta de tres zonas de operacin, las
cuales se describen a continuacin:
Zona de supervisin del circuito de corriente
Esta zona se encuentra definida por medio de los parmetros ID>1 y K1. EL objetivo de esta zona es supervisar los circuitos de
corriente asociados con la proteccin diferencial de barras. Esta zona detecta corrientes diferenciales que son originadas en
operacin normal y bajo la condicin de un TC abierto o cortocircuitado (numeral 2.1.1.1.3 de la referencia [13]). Ante esta
situacin, la proteccin emitir una alarma indicando la anomala.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

31/79

El valor de ajuste para la variable ID>1 se recomienda ajustar al 20% de la menor capacidad nominal de las lneas que entran
a la subestacin Reque, es decir, 0,2x400 A=80 A. Este umbral de ajuste, permite detectar desbalances por TCs abiertos o
cortocircuitados para corrientes de carga mayores a 100 A y se encuentra por encima de los desbalances normales que se
generan en el procesamiento de la proteccin diferencial de barras.
La variable K1 se ajusta al 10%, segn las recomendaciones prcticas del fabricante del dispositivo de proteccin.
Zona de operacin elementos diferenciales
La Zona de operacin de los elementos diferenciales es definida por medio de los parmetros I D>2 y K2. El criterio de ajuste
de la variable ID>2 se realizar de acuerdo a los siguientes lineamientos:

Por encima de la corriente mxima de carga por las bahas (se debe considerar un margen del 130% de la
corriente obtenida, con el objetivo de tener un factor de seguridad).

Por debajo de la mnima corriente de cortocircuito en la barra (se debe considerar el 80% del nivel obtenido,
con el objetivo de tener un margen de seguridad del 20%).

La pendiente K2 se ajusta en 65% segn las recomendaciones prcticas del fabricante del dispositivo de proteccin.
Zona de chequeo Check zone
La zona de chequeo monitorea las corrientes que entran y salen de la subestacin y no mira las barras individuales que la
conforman. De esta manera solo se emitir orden de disparo si la falla es vista por la zona de chequeo y la zona de operacin
de los elementos diferenciales.
La caracterstica de operacin de la zona de chequeo est definida segn los parmetros I DCZ>2 y KCZ, los cuales se
recomiendan ajustar iguales a los parmetros de la zona de operacin de los elementos diferenciales.
En la Tabla 9 se presenta la decisin que tomar la proteccin diferencial de barras, segn la magnitud de la corriente
diferencial.
Tabla 9: Condiciones de operacin proteccin diferencial de barras
ID>1

k1*Ibias

ID>2

Estado

Operacin

Normal

No operacin

Normal

No operacin

Normal

No operacin

Falla externa o falla en el circuito

Falla externa con saturacin de TC o alarma de falla de circuito de bloqueo despus de tCF.

Falla en el circuito

Bloqueo y alarma de falla en el circuito despus de tCF.

Falla interna

Disparo

7.4.2.2 Zona muerta campo de acople 220 kV


La disposicin de los transformadores de corriente en el campo de acople es la que se muestra en la Figura 16.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

32/79

Figura 16:

Disposicin del TC en el campo de acople

En la ingeniera concebida para el proyecto Reque, solo un TC es localizado en el campo de acople. Para una falla en la zona
identificada como zona muerta, la proteccin diferencial de barras dispara todos los interruptores asociados con la zona A. Sin
embargo, la falla seguir siendo alimentada por todos los circuitos asociados con la barra B, ya que el elemento diferencial de
sta zona ve la falla externa a la barra.
Para suministrar una proteccin adecuada a este tipo de esquema, se habilita la funcin de zona muerta en el rel MiCOM
P741. Esta funcin es activada cuando el interruptor del campo de acople se encuentre abierto y se detecta corriente por este
campo, lo que conllevar a un disparo de todos los interruptores asociados con la barra B. La supervisin de corriente para la
funcin de zona muerta son elementos no direccionales de fases y tierra.
El umbral de ajustes en fases de la funcin zona muerta se recomienda ajustar al 120% de la capacidad nominal del
transformador de instrumentacin asociado con el campo de acople. El umbral de ajuste para el elemento de tierra se
recomienda ajustar al 40% de la capacidad nominal del TC.

7.4.2.3 Funcin falla interruptor (50BF)


En la proteccin MiCOM P74X, se cuenta con la funcin falla interruptor de dos etapas, la cual puede ser iniciada por un
elemento de proteccin interno o externo. Para el elemento basado en corriente, la condicin de restablecimiento est basada
en la operacin de baja corriente para determinar que el interruptor est abierto, mientras que para la proteccin no basada
en corriente, el criterio de restablecimiento se puede seleccionar por medio de un ajuste para determinar la condicin de falla
interruptor. Es una prctica comn, utilizar elementos de baja corriente en los rels de proteccin para indicar que los polos
del interruptor han interrumpido la corriente de falla o de carga, tal como se requiere.
En cuanto las etapas de proteccin, se describen a continuacin:
Etapa 1: Comanda retrip al propio interruptor, 0,15 s despus del disparo proveniente de la proteccin principal.
Etapa 2: Comanda disparo al propio interruptor, a los interruptores adyacentes a la misma barra y disparo directo transferido
al extremo remoto, 0,25 s despus del disparo proveniente de la proteccin principal.
En lneas de transmisin el nivel de corriente de arranque de la proteccin falla interruptor debe ajustarse encima de la
corriente mxima de carga y menor que la corriente mnima de falla en el extremo remoto de la subestacin Reque.

I mx c arg a I 50BF I mn falla


Para el campo de acople se recomienda ajustar el arranque en corriente de la funcin 50BF en 1,2xIn.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

33/79

Lgica de la proteccin falla interruptor


Se recomienda que la funcin falla interruptor opere por corriente y por la habilitacin de una seal de disparo externa.

Figura 17:

8.

Lgica de la proteccin Falla Interruptor 50BF

AJUSTES DE LAS FUNCIONES DE PROTECCIN

En esta seccin se presentan los ajustes recomendados para los dispositivos de proteccin que hacen parte del alcance del
presente estudio.

8.1.

PROTECCIN DE LNEAS DE TRANSMISIN

8.1.1 Lnea Reque Eten (2L2-6) 220 kV, extremo Reque


La lnea Reque Eten (2L2-6) 220 kV, S/E Reque 220 kV, dispone de dos sistemas de proteccin, compuestos por dos
rels diferenciales de lnea (SEL 411L). A continuacin se presentan los ajustes recomendados para cada una de las
funciones de proteccin.

8.1.1.1 Funcin diferencial de lnea (87L)


En la Tabla 10, se presentan los ajustes bsicos de la funcin diferencial de lnea, segn los criterios expuestos en el numeral
7.1.2.1.
Tabla 10:

Ajustes funcin 87L lnea Reque Eten 220 kV, extremo Reque
CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.1)

Parmetros

AJUSTE

CTRW

625

Relacin de transformacin entrada W

CTRX

200

Relacin de transformacin entrada X

87LTAPW

1,60

Tap del CT para el terminal de corriente W (Rel SE Reque)

87LTAPX

1,6

Tap del CT para el terminal de corriente X (Rel SE Reque)

87LTAPW

5,0

Tap del CT para el terminal de corriente W (Rel SE Eten)

87LTAPX

5,00

Tap del CT para el terminal de corriente X (Rel SE Eten)

87LPP

0,2

Umbral de arranque del elemento diferencial de fases en el modo


normal de seguridad (p.u.). Se ajusta al 20% de la corriente
nominal del TC de mayor relacin de los dos extremos. La
corriente base es la mxima entre las corrientes primarias de los
TCs de los extremos local y remoto, para este caso 1000 A.

87LPR

2,6

Radio del elemento diferencial de fases en el modo normal de


seguridad.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

34/79

Parmetros

AJUSTE

CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.1)

87LPA

195

ngulo de bloqueo del elemento diferencial de fases en el modo


normal de seguridad (grados). Segn recomendacin del
fabricante, este ajuste se recomienda en 195.

87LPPS

0,24

Umbral de arranque del elemento diferencial de fases en el modo


extendido de seguridad (p.u.) Este valor se calcula
automticamente, 1,2*87LPP.

87LPRS

3,12

Radio del elemento diferencial de fases en el modo extendido de


seguridad. Este valor se calcula automticamente, 1,2*87LPR.

87LPAS

234

ngulo de bloqueo del elemento diferencial de fases en el modo


extendido de seguridad (grados). Este valor se calcula
automticamente, 1,2*87LPA.

87LQP

0,1

Umbral de arranque del elemento diferencial de secuencia


negativa en el modo normal de seguridad (p.u.). Se habilita el
elemento diferencial de secuencia negativa con el mnimo valor
de ajuste, 100 Apri. Equivale al 10% de la corriente nominal del
TC de mayor relacin de los dos extremos. La corriente base es la
mxima entre las corrientes primarias de los TCs de los extremos
local y remoto, para este caso 1000 A

87LQR

2,6

Radio del elemento diferencial de secuencia negativa en el modo


normal de seguridad.

87LQA

195

ngulo de bloqueo del elemento diferencial de secuencia


negativa en el modo normal de seguridad (grados)

87LQPS

0,12

Umbral de arranque del elemento diferencial de secuencia


negativa en el modo extendido de seguridad (p.u.) Este valor se
calcula automticamente, 1,2*87LQP.

87LQRS

3,12

Radio del elemento diferencial de secuencia negativa en el modo


extendido de seguridad. Este valor se calcula automticamente,
1,2*87LQR.

87LQAS

234

ngulo de bloqueo del elemento diferencial de secuencia


negativa en el modo extendido de seguridad (grados). Este valor
se calcula automticamente, 1,2*87LQA.

87LGP

0,1

Umbral de arranque del elemento diferencial de tierra en el modo


normal de seguridad (p.u.). Se habilita el elemento diferencial de
tierra con el mnimo valor de ajuste, 100 Apri. Equivale al 10% de
la corriente nominal del TC de mayor relacin de los dos
extremos. La corriente base es la mxima entre las corrientes
primarias de los TCs de los extremos local y remoto, para este
caso 1000 A

87LGR

2,6

Radio del elemento diferencial de tierra en el modo normal de


seguridad

87LGA

195

ngulo de bloqueo del elemento diferencial de tierra en el modo


normal de seguridad (grados)

87LGPS

0,12

Umbral de arranque del elemento diferencial de tierra en el modo


extendido de seguridad (p.u.) Este valor se calcula
automticamente, 1,2*87LGP.

87LGRS

3,12

Radio del elemento diferencial de tierra en el modo extendido de

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

35/79

Parmetros

CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.1)

AJUSTE

seguridad. Este valor se calcula automticamente, 1,2*87LGR.

87LGAS

234

ngulo de bloqueo del elemento diferencial de tierra en el modo


extendido de seguridad (grados). Este valor se calcula
automticamente, 1,2*87LGA.

Verificacin de la funcin diferencial de lnea


Se verific el comportamiento para la funcin diferencial de lnea a partir de los resultados de las simulaciones de fallas
internas y externas a la lnea en los escenarios de mximos y mnimos niveles de cortocircuito, y el posterior procesamiento de
los resultados obtenidos segn las caractersticas de operacin del rel.
Tabla 11:

Tipo

3F

1F

Verificacin de operacin de la proteccin diferencial de lnea - fallas internas, escenario de


mnimos niveles de cortocircuito - lnea Reque Eten 220 kV

Rf

Extremo Reque

Extremo Eten

Reque IL/IR

Eten IL/IR

()

Mag

Ang

Mag

Ang

Error Req>, Ete<

Error Req<,Ete>

Error Req>, Ete<

Error Req<, Ete>

(kA)

()

(kA)

()

Re

Im

Re

Im

Re

Im

Re

Im

3,275 -113,422 2,297 -102,400 1,547

-0,301

1,266

-0,247

0,761

0,148

0,623

0,121

50

0,845

-64,904

1,411

-42,258

0,611

-0,255

0,500

-0,209

1,703

0,711

1,394

0,582

100 0,251

-82,760

1,046

-30,563

0,163

-0,210

0,133

-0,172

2,823

3,639

2,311

2,979

50

3,217 -113,571 2,327 -102,469 1,499

-0,294

1,227

-0,241

0,785

0,154

0,642

0,126

50

50

0,828

-65,138

1,428

-42,323

0,591

-0,249

0,484

-0,203

1,757

0,739

1,438

0,605

50 100 0,243

-84,062

1,056

-30,590

0,151

-0,204

0,124

-0,167

2,859

3,860

2,340

3,159

99

3,160 -113,715 2,359 -102,539 1,452

-0,287

1,189

-0,235

0,809

0,160

0,663

0,131

99

50

0,811

-65,366

1,445

-42,379

0,571

-0,242

0,467

-0,198

1,813

0,769

1,484

0,630

99 100 0,235

-85,441

1,066

-30,611

0,140

-0,199

0,115

-0,163

2,888

4,098

2,364

3,355

3,513 -112,143 2,845 -103,228 1,348

-0,211

1,104

-0,173

0,884

0,139

0,724

0,114

50

0,785

-62,573

1,520

-40,613

0,529

-0,213

0,433

-0,175

1,985

0,800

1,625

0,655

100 0,219

-87,352

1,096

-29,680

0,118

-0,187

0,097

-0,153

2,958

4,674

2,421

3,826

50

3,407 -112,231 2,934 -103,753 1,269

-0,189

1,039

-0,155

0,941

0,140

0,771

0,115

50

50

0,750

-62,755

1,556

-40,889

0,494

-0,198

0,405

-0,162

2,128

0,854

1,742

0,699

50 100 0,204

-90,615

1,115

-29,879

0,099

-0,176

0,081

-0,144

2,953

5,270

2,417

4,314

99

3,309 -112,330 3,028 -104,315 1,196

-0,168

0,979

-0,138

1,002

0,141

0,820

0,115

99

50

0,716

-62,895

1,593

-41,132

0,461

-0,184

0,378

-0,151

2,284

0,912

1,869

0,746

99 100 0,190

-94,335

1,134

-30,059

0,080

-0,167

0,066

-0,137

2,863

5,943

2,344

4,865

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

36/79

Figura 18:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas escenario de
mnimos niveles de cortocircuito - modo normal

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

37/79

Figura 19:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas - escenario de
mnimos niveles de cortocircuito - modo de seguridad extendido

Tabla 12:

Tipo

3F

1F

Verificacin de operacin de la proteccin diferencial de lnea - fallas externas, escenario de


mnimos niveles de cortocircuito - lnea Reque Eten 220 kV

Rf

Extremo Reque

Extremo Eten

()

Mag

Ang

Mag

Ang

(kA)

()

(kA)

()

77,601

Reque IL/IR

Eten IL/IR

Error Req>, Ete< Error Req<, Ete> Error Req>, Ete< Error Req<, Ete>
Re

2,296 -102,399 -1,105

Im

Re

Im

Re

Im

Re

Im

0,000

-0,905

0,000

-1,105

0,000

-0,905

0,000

2,296

50

1,410 137,701 1,410

-42,257

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

100 1,046 149,375 1,046

-30,563

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

66,282

-1,105

0,000

-0,905

0,000

-1,105

0,000

-0,905

0,000

100

3,159 -113,718 3,159

100

50

0,811

-65,371

0,811 114,557

-1,105 -0,001 -0,905 -0,001 -1,105

0,001

-0,905

0,001

100 100 0,235

-85,470

0,236

-1,101 -0,004 -0,901 -0,003 -1,110

0,004

-0,909

0,003

76,782

2,843 -103,217 -1,105

0,000

-0,905

0,000

94,333

2,843

50

1,519 139,352 1,520

-40,607

100 1,095 150,264 1,095

100

3,307 -112,332 3,307

100

50

0,715

-62,898

0,000

-0,905

0,000

-1,105

-1,105

0,001

-0,904

0,001

-1,106 -0,001 -0,905 -0,001

-29,675

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

67,668

-1,105

0,000

-0,905

0,000

-1,105

0,000

-0,905

0,000

-1,105 -0,002 -0,905 -0,001 -1,105

0,002

-0,905

0,001

0,715 117,019

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

38/79

Tipo

Rf

Extremo Reque

()

Mag

Ang

Mag

Ang

(kA)

()

(kA)

()

-94,416

0,190

85,394

100 100 0,189

Figura 20:

Extremo Eten

Reque IL/IR

Eten IL/IR

Error Req>, Ete< Error Req<, Ete> Error Req>, Ete< Error Req<, Ete>
Re

Im

Re

Im

Re

-1,099 -0,004 -0,900 -0,003 -1,111

Im

Re

Im

0,004

-0,910

0,003

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas escenario de
mnimos niveles de cortocircuito - modo normal

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

39/79

Figura 21:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas - escenario de
mnimos niveles de cortocircuito - modo de seguridad extendido

Tabla 13:

Verificacin de operacin de la proteccin diferencial de lnea - fallas internas, escenario de


mximos niveles de cortocircuito - lnea Reque Eten 220 kV
Rf

Tipo

3F

1F

()

Extremo Reque

Extremo Eten

Reque IL/IR

Eten IL/IR

Mag

Ang

Mag

Ang

Error Req>, Ete< Error Req<, Ete> Error Req>, Ete< Error Req<, Ete>

(kA)

()

(kA)

()

Re

Im

Re

Im

Re

Im

Re

Im

4,330

-115,828

2,308

-109,499

2,061

-0,229

1,687

-0,187

0,586

0,065

0,479

0,053

50

0,985

-62,476

1,288

-47,606

0,817

-0,217

0,669

-0,178

1,397

0,371

1,143

0,304

100 0,287

-70,803

0,968

-37,466

0,274

-0,180

0,224

-0,147

3,114

2,049

2,549

1,677

50

4,226

-116,079

2,339

-109,567

1,984

-0,226

1,624

-0,185

0,608

0,069

0,498

0,057

50

50

0,966

-62,736

1,307

-47,724

0,789

-0,212

0,646

-0,173

1,444

0,387

1,182

0,317

50

100 0,277

-71,627

0,979

-37,519

0,259

-0,175

0,212

-0,144

3,234

2,190

2,648

1,793

99

4,128

-116,318

2,370

-109,638

1,912

-0,224

1,565

-0,183

0,630

0,074

0,516

0,060

99

50

0,946

-62,986

1,326

-47,834

0,761

-0,206

0,623

-0,169

1,495

0,405

1,224

0,331

99

100 0,267

-72,497

0,990

-37,566

0,244

-0,171

0,200

-0,140

3,360

2,347

2,750

1,921

4,356

-116,008

2,930

-110,255

1,635

-0,165

1,338

-0,135

0,740

0,075

0,606

0,061

50

0,880

-62,159

1,433

-46,578

0,654

-0,182

0,535

-0,149

1,734

0,483

1,419

0,396

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

40/79

Rf
Tipo

()

Extremo Reque

Extremo Eten

Reque IL/IR

Eten IL/IR

Mag

Ang

Mag

Ang

(kA)

()

(kA)

()

Re

Im

Re

Im

Re

Im

Re

Im

-77,338

1,040

-36,895

0,188

-0,161

0,154

-0,131

3,755

3,200

3,073

2,620

100 0,233

Error Req>, Ete< Error Req<, Ete> Error Req>, Ete< Error Req<, Ete>

50

4,210

-116,170

3,025

-110,815

1,532

-0,144

1,254

-0,118

0,791

0,074

0,647

0,061

50

50

0,843

-62,237

1,470

-46,897

0,611

-0,168

0,500

-0,137

1,859

0,510

1,521

0,417

50

100 0,215

-79,414

1,060

-37,112

0,166

-0,151

0,136

-0,124

4,030

3,668

3,299

3,002

99

4,077

-116,343

3,127

-111,413

1,436

-0,124

1,175

-0,101

0,845

0,073

0,691

0,060

99

50

0,807

-62,254

1,509

-47,181

0,571

-0,154

0,467

-0,126

1,996

0,537

1,634

0,440

99

100 0,196

-81,807

1,081

-37,309

0,143

-0,140

0,117

-0,115

4,348

4,272

3,559

3,497

Figura 22:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas escenario de
mximos niveles de cortocircuito - modo normal

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

41/79

Figura 23:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas internas - escenario de
mximos niveles de cortocircuito - modo de seguridad extendido

Tabla 14:

Verificacin de operacin de la proteccin diferencial de lnea - fallas externas, escenario de


mximos niveles de cortocircuito - lnea Reque Eten 220 kV
Rf

Tipo

()

Extremo Reque

Extremo Eten

Reque IL/IR

Eten IL/IR

Mag

Ang

Mag

Ang

Error Req>, Ete< Error Req<, Ete> Error Req>, Ete< Error Req<, Ete>

(kA)

()

(kA)

()

Re

Im

Re

Im

Re

Im

Re

Im

0,000

-0,905

0,000

3F

2,307

70,502

2,307

-109,498

-1,105

0,000

-0,905

0,000

-1,105

3F

50

1,288

132,349

1,288

-47,603

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

3F

100 0,968

142,467

0,968

-37,465

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

3F

100

4,126

-116,322

4,126

63,678

-1,105

0,000

-0,905

0,000

-1,105

0,000

-0,905

0,000

3F

100

50

0,945

-62,991

0,946

116,944

-1,104 -0,001 -0,904 -0,001 -1,106

0,001

-0,906

0,001

3F

100

100 0,267

-72,515

0,267

107,265

-1,105 -0,004 -0,905 -0,003 -1,105

0,004

-0,905

0,003

1F

2,928

69,756

2,928

-110,244

-1,105

0,000

-0,905

0,000

-1,105

0,000

-0,905

0,000

1F

50

1,432

133,385

1,432

-46,572

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

1F

100 1,040

143,046

1,040

-36,890

-1,105

0,001

-0,905

0,001

-1,105 -0,001 -0,905 -0,001

1F

100

4,074

-116,346

4,075

63,653

-1,105

0,000

-0,905

0,000

-1,106

0,000

-0,905

0,000

1F

100

50

0,806

-62,254

0,806

117,669

-1,105 -0,001 -0,905 -0,001 -1,105

0,001

-0,905

0,001

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

42/79

Rf
Tipo

1F

100

Figura 24:

Extremo Reque

()

Extremo Eten

Mag

Ang

Mag

Ang

(kA)

()

(kA)

()

-81,860

0,197

97,875

100 0,196

Reque IL/IR

Eten IL/IR

Error Req>, Ete< Error Req<, Ete> Error Req>, Ete< Error Req<, Ete>
Re

Im

Re

Im

Re

-1,100 -0,005 -0,900 -0,004 -1,111

Im

Re

Im

0,005

-0,909

0,004

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas escenario de
mximos niveles de cortocircuito - modo normal

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

43/79

Figura 25:

Verificacin operacin proteccin 87L - lnea Reque Eten 220 kV - fallas externas - escenario de
mximos niveles de cortocircuito - modo de seguridad extendido

8.1.1.2 Funcin de sobrecorriente direccional residual (67N)


De acuerdo con el criterio definido en el numeral 7.1.2.2, se recomienda ajustar solo una etapa de tiempo definido con un
arranque de 120 Aprim, temporizada en 250 ms, ya que no se observ una diferencia considerable entre los aportes de
corriente que se presentan en la lnea ante fallas bifsicas a tierra al 99% - 50% - 1% de la lnea, que permitan recomendar
una etapa de tiempo inverso de acuerdo al criterio.
Tambin, esta funcin (67N) acta como respaldo ante una falla bifsica a tierra en bornes del lado de alta tensin del
transformador GSU, ante la operacin en 120 ms de la caracterstica de sobrecorriente fases del rel instalado en el lado de
alta tensin del transformador por el aporte de la componente de fases (Ikss = 4185 A).
Los ajustes propuestos fueron verificados ante fallas en el escenario de mximas corrientes de cortocircuito. En la Tabla 15, se
muestran los ajustes de estos rels.
Tabla 15:

Ajustes funcin 67N lnea Reque Eten 220 kV, extremo Reque
PARMETRO

AJUSTE
(APrim)

AJUSTE
(ASec)

Modo de operacin

Adelante

Adelante

Arranque

120

0,19

Retardo

0,25 s

0,25 s

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

44/79

8.1.1.3 Funcin cierre en falla (SOTF)


Considerando el criterio descrito en el numeral 7.1.2.4 y ante el escenario de mnimas corrientes de cortocircuito, el ajuste
recomendado ser.
Tabla 16:

Ajustes funcin SOTF - Reque Eten 220 kV, extremo Reque

ARRANQUE

AJUSTE
(APrim)

AJUSTE
(ASec)

CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.4)

SOTF

1627

2,6

IFalla-barra - Reque = 5550 A


IAporte-circuito a ajustar=2296 A
IAjuste=0,5(5550-2296)=1627 A

8.1.2 Lnea Reque Eten (2L2-6) 220 kV, extremo Eten


La lnea Reque Eten (2L2-6) 220 kV, S/E Eten 220 kV, dispone de dos sistemas de proteccin, compuestos por dos rels
diferenciales de lnea (SEL 411L). A continuacin se presentan los ajustes recomendados para cada una de las funciones de
proteccin.

8.1.2.1 Funcin diferencial de lnea (87L)


En la Tabla 17, se presentan los ajustes bsicos de la funcin diferencial de lnea, segn los criterios expuestos en el numeral
7.1.2.1.
Tabla 17:

Ajustes funcin 87L lnea Reque Eten 220 kV, extremo Eten
CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.1)

Parmetros

AJUSTE

CTRW

625

Relacin de transformacin entrada W

CTRX

200

Relacin de transformacin entrada X

87LTAPW

1,60

Tap del CT para el terminal de corriente W (Rel SE Reque)

87LTAPX

1,60

Tap del CT para el terminal de corriente X (Rel SE Reque)

87LTAPW

5,00

Tap del CT para el terminal de corriente W (Rel SE Eten)

87LTAPX

5,00

Tap del CT para el terminal de corriente X (Rel SE Eten)

87LPP

0,2

Umbral de arranque del elemento diferencial de fases en el modo


normal de seguridad (p.u.). Se ajusta al 20% de la corriente
nominal del TC de mayor relacin de los dos extremos. La
corriente base es la mxima entre las corrientes primarias de los
TCs de los extremos local y remoto, para este caso 1000 A.

87LPR

2,6

Radio del elemento diferencial de fases en el modo normal de


seguridad.

87LPA

195

ngulo de bloqueo del elemento diferencial de fases en el modo


normal de seguridad (grados). Segn recomendacin del
fabricante, este ajuste se recomienda en 195.

87LPPS

0,24

Umbral de arranque del elemento diferencial de fases en el modo


extendido de seguridad (p.u.) Este valor se calcula
automticamente, 1,2*87LPP.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

45/79

Parmetros

AJUSTE

CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.1)

87LPRS

3,12

Radio del elemento diferencial de fases en el modo extendido de


seguridad. Este valor se calcula automticamente, 1,2*87LPR.

87LPAS

234

ngulo de bloqueo del elemento diferencial de fases en el modo


extendido de seguridad (grados). Este valor se calcula
automticamente, 1,2*87LPA.

87LQP

0,1

Umbral de arranque del elemento diferencial de secuencia


negativa en el modo normal de seguridad (p.u.). Se habilita el
elemento diferencial de secuencia negativa con el mnimo valor
de ajuste, 100 Apri. Equivale al 10% de la corriente nominal del
TC de mayor relacin de los dos extremos. La corriente base es la
mxima entre las corrientes primarias de los TCs de los extremos
local y remoto, para este caso 1000 A

87LQR

2,6

Radio del elemento diferencial de secuencia negativa en el modo


normal de seguridad.

87LQA

195

ngulo de bloqueo del elemento diferencial de secuencia


negativa en el modo normal de seguridad (grados)

87LQPS

0,12

Umbral de arranque del elemento diferencial de secuencia


negativa en el modo extendido de seguridad (p.u.) Este valor se
calcula automticamente, 1,2*87LQP.

87LQRS

3,2

Radio del elemento diferencial de secuencia negativa en el modo


extendido de seguridad. Este valor se calcula automticamente,
1,2*87LQR.

87LQAS

234

ngulo de bloqueo del elemento diferencial de secuencia


negativa en el modo extendido de seguridad (grados). Este valor
se calcula automticamente, 1,2*87LQA.

87LGP

0,1

Umbral de arranque del elemento diferencial de tierra en el modo


normal de seguridad (p.u.). Se habilita el elemento diferencial de
tierra con el mnimo valor de ajuste, 100 Apri. Equivale al 10% de
la corriente nominal del TC de mayor relacin de los dos
extremos. La corriente base es la mxima entre las corrientes
primarias de los TCs de los extremos local y remoto, para este
caso 1000 A

87LGR

2,6

Radio del elemento diferencial de tierra en el modo normal de


seguridad

87LGA

195

ngulo de bloqueo del elemento diferencial de tierra en el modo


normal de seguridad (grados)

87LGPS

0,12

Umbral de arranque del elemento diferencial de tierra en el modo


extendido de seguridad (p.u.) Este valor se calcula
automticamente, 1,2*87LGP.

87LGRS

3,2

Radio del elemento diferencial de tierra en el modo extendido de


seguridad. Este valor se calcula automticamente, 1,2*87LGR.

87LGAS

234

ngulo de bloqueo del elemento diferencial de tierra en el modo


extendido de seguridad (grados). Este valor se calcula
automticamente, 1,2*87LGA.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

46/79

Verificacin de los ajustes de la funcin diferencial


Ver numeral 8.1.1.1.

8.1.2.2 Funcin de sobrecorriente direccional residual (67N)


De acuerdo con el criterio definido en el numeral 7.1.2.2, se recomiendan los ajustes mostrados a continuacin:
El arranque se ajustar en 120 Aprim y tendr un dial calculado de 0,51, ste ocasiona que el rel opere en 1,014 s para una
corriente residual de 4177,6 A, ante falla bifsica a tierra al 99% de la lnea Reque Eten desde la S/E Eten 220 kV. Se
recomienda no habilitar la etapa de tiempo definido, ya que no se observa una diferencia considerable entre los aportes de
corriente que se presentan en la lnea ante fallas bifsicas a tierra al 99% - 50% - 1% de la lnea. Los ajustes propuestos fueron
verificados ante fallas en el escenario de mximas corrientes de cortocircuito. En la Tabla 18, se muestran los ajustes de estos
rels.
Tabla 18:

Ajustes funcin 67N lnea Reque Eten 220 kV, extremo Eten
PARMETRO

AJUSTE
(APrim)

AJUSTE
(ASec)

Modo de operacin

Adelante

Adelante

Arranque

120

0,6

Dial

0,51

0,51

Curva

IEC Normal
Inversa

IEC Normal
Inversa

8.1.2.3 Funcin cierre en falla (SOTF)


Considerando el criterio descrito en el numeral 7.1.2.4 y ante el escenario de mnimas corrientes de cortocircuito, el ajuste
recomendado ser.
Tabla 19:

Ajustes funcin SOTF - Reque Eten 220 kV, extremo Eten

AJUSTE
(APrim)

ARRANQUE

SOTF

1166

AJUSTE
(ASec)

CRITERIO DE AJUSTE
(VER SECCIN 7.1.2.4)

5,83

IFalla-barra Eten = 5490 A


IAporte-circuito a ajustar=3159 A
IAjuste=0,5(5490-3159)=1166 A

8.1.2.4 Funcin falla interruptor (50BF)


La lgica del rel SEL 411L para la funcin 50BF se basa en las rdenes de disparo enviadas por las protecciones de la celda
al interruptor. Cuando una de las protecciones de la celda emite una orden de disparo al interruptor, sta se repite a la
proteccin de falla interruptor, con lo cual arranca un temporizador en la misma (t1). Dicho temporizador cuenta en tanto
contine circulando corriente por los contactos principales del interruptor, es decir, mientras haya un comando de disparo
activo y exista circulacin de corriente por el rel 50BF. En condiciones normales, el interruptor se abrir para interrumpir la
corriente de falla, con lo cual se detendr el temporizador t1 de la funcin 50BF. En caso de que el comando de disparo no
sea ejecutado por el interruptor (condicin de falla interruptor), el temporizador llega hasta el lmite de tiempo ajustado, tras
lo cual la proteccin de falla interruptor emite orden de re-disparo sobre este mismo interruptor (etapa 1). En caso contrario,
finalmente se enviar orden de disparo a todos los interruptores adyacentes y al interruptor propio (etapa 2), interrumpiendo
de esta forma la corriente de falla.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

47/79

Nota: Las ordenes de disparo por etapa 1 y etapa 2 de la funcin de falla interruptor debern ser efectuadas simultneamente
sobre las dos bobinas de apertura de los interruptores.
Los disparos por etapas 1 y 2 del 50BF se efectan definitivos trifsicos sobre ambas bobinas de los interruptores respectivos.
Para calcular el ajuste del rel de falla interruptor para las lneas de transmisin, se simulan fallas 1, 2 y 3 en el extremo
remoto con una resistencia de falla de 50 para determinar la mnima corriente de falla vista por el rel en la subestacin
local. Se toma el 60% del menor valor obtenido, el ajuste obtenido anteriormente debe estar por encima de la corriente
nominal de la lnea (se propone el umbral de 110% de la corriente nominal de la lnea). En la Tabla 20 se muestra el ajuste del
arranque de la funcin falla interruptor.
Tabla 20:
Campo

Ajuste arranque falla interruptor subestacin Eten 220 kV

Tipo de Falla [A]


3

2-T

60% Tipo de Falla [A]


1

2-T

Corriente Nominal [A]

Lnea Reque 2L2-6 1411 1429 1449 1520 846,6 857,4 869,4 912,0

I AJUSTE (Ver *)
I [Aprim] I [Asec]

729

846,6

4,23

* Ajuste siguiendo los lineamientos del COES en los numerales 2.9.1 y 4.5.3

8.2.

TRANSFORMADOR DE POTENCIA

8.2.1 Funcin de sobrecorriente de fases de tiempo inverso y tiempo definido (51/50)


De acuerdo con el criterio definido en el numeral 7.2.2.1, se recomiendan los ajustes mostrados a continuacin:
Los ajustes propuestos fueron verificados ante fallas en el escenario de mximas corrientes de cortocircuito. En la Tabla 21, se
muestran los ajustes de estos rels.
Tabla 21:

Ajustes funcin 51/50 Transformador Eten 220/18 kV, nivel 220 kV

PARMETRO

AJUSTE
(APrim)

AJUSTE
(ASec)

CRITERIO DE AJUSTE
(VER SECCIN 7.2.2.1)

Modo de operacin

No direccional

No direccional

NA

Arranque

904,08

4,52

IArranque = 1,3 Inominal del


transformador

Dial

0,11

0,11

Coordinacin selectiva
protecciones adyacentes

Curva

IEC Normal
Inversa

IEC Normal
Inversa

Coordinacin selectiva
protecciones adyacentes

Arranque (Ie>)

3501

17,51

IArranque = 1,5 Icc3F aporte

0,12 s

Este elemento permitir


despejes rpidos ante fallas
en bornes primarios del
transformador

Retardo

0,12 s

8.2.2 Funcin de sobrecorriente de tierra de tiempo inverso y tiempo definido (51N/50N)


De acuerdo con el criterio definido en el numeral 7.2.2.2, se recomiendan los ajustes mostrados a continuacin:
Los ajustes propuestos fueron verificados ante fallas en el escenario de mximas corrientes de cortocircuito. En la Tabla 22, se
muestran los ajustes de estos rels.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

48/79

Tabla 22:

Ajustes funcin 51N Transformador Eten 220/18 kV, nivel 220 kV

PARMETRO

AJUSTE
(APrim)

AJUSTE
(ASec)

CRITERIO DE AJUSTE
(VER SECCIN 7.2.2.2)

Modo de operacin

No direccional

No direccional

NA

Arranque

120

0,30

IArranque = 120 Aprim

Dial

0,42

0,42

Coordinacin selectiva
protecciones adyacentes

Curva

IEC Normal
Inversa

IEC Normal
Inversa

Coordinacin selectiva
protecciones adyacentes

7,9

IArranque = corriente residual


de aporte ante una falla
bifsica a tierra franca al
50% de la lnea Reque
Chiclayo 220 kV vista por el
rel de la proteccin del
transformador.

0,5 s

Este elemento permitir


garantizar la selectividad
con los sobrecorrientes
direccionales ubicados en
las lneas asociadas a la
subestacin Reque 220 kV.

Arranque (Ie>)

Retardo

8.3.

3160

0,5 s

PROTECCIN DE ACOPLE

8.3.1 Funcin de sobrecorriente de fases de tiempo inverso y tiempo definido (51/50)


Proteccin de sobrecorriente de fases tiempo inverso (51)
Se recomienda ajustar el arranque de esta funcin al 120% de la capacidad nominal del transformador de corriente, por tanto:
Ipick-up=1,2 x 625 A = 750 A
El tipo de curva seleccionada es Normal Inverse IEC. El dial se calcul (0,25) para que ante falla trifsica al 99% de la lnea
Reque - Guadalupe 1 y 2 desde Reque, esta caracterstica opere en 1,3 s, para una corriente de fase de 2768,27 A. Este
tiempo de operacin permite coordinar con las funciones 67N y 21 del rel multifuncional de lnea, adems de la funcin
87B.
Proteccin de sobrecorriente de fases de tiempo definido (50)
El arranque de esta caracterstica se calcul como el 90% del aporte de corriente por el acople ante falla trifsica al 1% de la
lnea Reque Guadalupe 1 y 2 (desde Reque) en el escenario de mximas corrientes de cortocircuito, por lo tanto:
Ipick-up=0,9 x 4697 A = 4227 A
Este arranque solo permitir despejar fallas trifsicas francas al 1% de las lneas Reque Guadalupe 1 y 2 convergentes a la
subestacin, ya que el aporte que se presenta en estas lneas es considerablemente mayor a la corriente vista por las
protecciones de las lneas Reque Chiclayo Oeste 1 y 2 220 kV y Reque Eten 220 kV.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

49/79

El tiempo de operacin se recomienda ajustar en 30 ciclos (0,5 s).

8.3.2 Funcin de sobrecorriente de tierra de tiempo inverso y definido y tierra (51N/50N)


Proteccin de sobrecorriente de tierra tiempo inverso (51N)
Se recomienda ajustar el arranque de esta funcin al 40% de la corriente nominal del transformador de corriente, por tanto:
Ipick-up=0,4 x 625 A = 250 A
El tipo de curva seleccionada es Normal Inverse IEC. El dial se calcul (0,36) para que ante falla a tierra al 99% de la lnea
Reque - Guadalupe 1 y 2 desde Reque, esta caracterstica opere en 1,3 s para una corriente residual de 1608,77 A. Este
tiempo de operacin permite coordinar con las funciones 67N y 21 del rel multifuncional de lnea, adems de la funcin
87B.
Proteccin de sobrecorriente de tierra de tiempo definido (50N)
El arranque de esta caracterstica se calcul como el 90% del aporte de corriente por el acople ante falla bifsica a tierra al 1%
de la lnea Reque Guadalupe 1 y 2 (desde Reque) en el escenario de mximas corrientes de cortocircuito, por lo tanto:
Ipick-up=0,9 x 4940 A = 4446 A
Este arranque solo permitir despejar fallas a tierra francas al 1% de las lneas Reque Guadalupe 1 y 2 convergentes a la
subestacin, ya que el aporte que se presenta en estas lneas es considerablemente mayor a la corriente vista por las
protecciones de las lneas Reque Chiclayo Oeste 1 y 2 220 kV y Reque Eten 220 kV.
El tiempo de operacin se recomienda ajustar en 30 ciclos (0,5 s).
NOTA: Los ajustes de la funcin de sobrecorriente direccional de tierra 67N y 67NCD indicados para la proteccin de la lnea
Reque Eten 220 kV extremo Reque, debern programarse como un grupo de ajustes adicional en la proteccin del acople.

8.4.

PROTECCIN DE SUBESTACIONES

8.4.1 Funcin diferencial de barras (87B)


De acuerdo con los criterios definidos en el numeral 7.4.2.1, los ajustes recomendados, se muestran en la Tabla 23.
Tabla 23:
Parmetro

Ajustes esenciales funcin diferencial de barras (87B) unidad centralizada rel MiCOM P741
Rango

Ajuste

Comentario

DIFF BUSBAR PROT (Phase differential)


CZ Parameters
Phase slope kCZ

0 90 %

65 %

Ajuste de ngulo de pendiente del elemento diferencial afectado por la


zona de verificacin.

IDCZ>2 Current

50 A 30 kA

552 A

Determina la mnima corriente diferencial operativa para el elemento


diferencial afectado por la zona de verificacin.

20 90 %

65%

Ajuste de ngulo de pendiente del elemento diferencial afectado por


todas las zonas de discriminacin.

Zone Parameters
Phase slope k2

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

50/79

Parmetro
ID>2 Current

Rango

Ajuste

Comentario

50 A 30 kA

552 A

Determina la mnima corriente diferencial operativa para el elemento


diferencial afectado por todas las zonas de discriminacin.

10 500 A

80 A

Ajuste para la caracterstica de monitoreo de falla en el circuito de


fases para el mnimo arranque.

0 50 %

10 %

Ajuste del ngulo de pendiente para la caracterstica de monitoreo de


falla en el circuito de fases.

0,0 600,0 s

5,0

Ajuste para el retardo de tiempo operativo de monitoreo de falla en el


circuito de fases.

Common
ID>1 Current
Phase slope k1
ID>1 Alarm Timer

DIFF BUSBAR PROT (Sensitive Earth fault)

Enabled - Disabled

Disabled

Habilita la funcin de proteccin diferencial de tierra. Cuando se


activa, las siguientes funciones son accesibles. Esta funcin no se
habilita ya que la funcin de fases detecta fallas monofsicas hasta de
100 Ohm.

50 A 30 kA

2000 A

Determina la caracterstica de bloqueo del elemento de falla a tierra.

Earth Slope kNCZ

0 90 %

60 %

Ajuste de ngulo de pendiente del elemento diferencial de tierra


afectado por la zona de verificacin.

IDNCZ>2 Current

10 A 30 kA

1250 A

Determina la mnima corriente diferencial operativa para el elemento


diferencial de tierra afectado por la zona de verificacin.

20 90 %

85%

Ajuste de ngulo de pendiente del elemento diferencial de tierra


afectado por todas las zonas de discriminacin.

50 A 30 kA

1000 A

Determina la mnima corriente diferencial operativa para el elemento


diferencial de tierra afectado por todas las zonas de discriminacin.

10 500 A

100 A

Ajuste para la caracterstica de monitoreo de falla en el circuito de


neutro para el mnimo arranque.

0 50 %

25 %

Ajuste del ngulo de pendiente para para la caracterstica de


monitoreo de falla en el circuito de neutro.

0,0 600,0 s

5,0

Ajuste para el retardo de tiempo operativo de monitoreo de falla en el


circuito de neutro.

Diff Earth Fault

IBiasPh>Cur.
CZ Parameters

Zone Parameters
Phase slope kN2
IDN>2 Current
Common
IDN>1 Current
Earth slope kN1
IDN>1 Alarm Timer

Verificacin de los ajustes de la funcin diferencial de barras

A continuacin se procede a verificar los ajustes definidos para la funcin diferencial de barras de la subestacin Reque
220 kV a partir de los resultados de las simulaciones de fallas internas y externas a las lneas y el posterior procesamiento de
los resultados obtenidos segn las caractersticas de operacin del rel.
Tabla 24:

Simulaciones proteccin diferencial de barras, rel MiCOM P741, fallas internas, demanda mnima
Error

Tipo
de
falla

Rf
()

REQUE - GUADALUPE 1

REQUE - GUADALUPE 2

REQUE - CHICLAYO 1

REQUE - CHICLAYO 2

Error

REQUE - ETEN
GUA<, CHI<, ETE<

GUA>, CHI>, ETE>

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Idiff
(kA)

Ibias
(kA)

Idiff
(kA)

Ibias
(kA)

0,855

67,884

0,855

67,884

0,903

67,835

0,903

67,835

2,843

76,782

6,023

6,041

6,657

6,677

10

0,677

89,996

0,677

89,996

0,695

91,253

0,695

91,253

2,641

101,648

5,092

5,116

5,628

5,654

1F

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

51/79

Error
Tipo
de
falla

3F

Rf
()

REQUE - GUADALUPE 1

REQUE - GUADALUPE 2

REQUE - CHICLAYO 1

REQUE - CHICLAYO 2

Error

REQUE - ETEN
GUA<, CHI<, ETE<

GUA>, CHI>, ETE>

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Idiff
(kA)

Ibias
(kA)

Idiff
(kA)

Ibias
(kA)

25

0,424

107,46

0,424

107,46

0,411

110,913

0,411

110,913

2,081

123,614

3,535

3,563

3,907

3,939

50

0,215

113,987

0,215

113,987

0,179

121,571

0,179

121,571

1,519

139,352

2,154

2,192

2,381

2,422

100

0,082

94,606

0,082

94,606

0,028

87,072

0,028

87,072

1,095

150,264

1,166

1,249

1,288

1,381

0,887

66,108

0,887

66,108

0,751

67,14

0,751

67,14

2,296

77,601

5,270

5,293

5,824

5,851

10

0,732

86,171

0,732

86,171

0,594

88,097

0,594

88,097

2,218

99,932

4,597

4,627

5,081

5,114

25

0,489

103,895

0,489

103,895

0,365

107,18

0,365

107,18

1,851

121,282

3,348

3,381

3,700

3,737

50

0,263

113,197

0,263

113,197

0,16

118,229

0,16

118,229

1,41

137,701

2,104

2,143

2,325

2,369

100

0,105

103,09

0,105

103,09

0,024

70,675

0,024

70,675

1,046

149,375

1,156

1,239

1,278

1,369

Tabla 25:

Simulaciones proteccin diferencial de barras, rel MiCOM P741, fallas externas, demanda mxima
Error

Ubicacin

REQ - GDP 1 1%

REQ - GDP 2 1%

REQ - CHIC 1 1%

REQ - CHIC 2 1%

REQ - ETE 1%

Tipo
de
falla

1F

1F

1F

1F

Rf
()

REQUE - GUADALUPE 1

REQUE - GUADALUPE 2

REQUE - CHICLAYO 1

REQUE - CHICLAYO 2

Error

REQUE - ETEN
GUA<, CHI<, ETE<

GUA>, CHI>, ETE>

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Idiff
(kA)

Ibias
(kA)

Idiff
(kA)

Ibias
(kA)

6,218

-113,353

0,846

64,586

1,261

63,396

1,261

63,396

2,86

70,125

0,000

11,824

0,000

13,068

10

5,081

-86,789

0,654

88,285

0,931

89,639

0,931

89,639

2,578

97,039

0,001

9,666

0,001

10,684

25

3,405

-65,401

0,402

104,876

0,525

110,551

0,525

110,551

1,966

118,744

0,001

6,482

0,001

7,164

50

2,061

-51,066

0,212

109,65

0,221

124,099

0,221

124,099

1,424

133,257

0,000

3,932

0,001

4,346

100

1,143

-41,021

0,096

94,101

0,021

132,142

0,021

132,142

1,037

142,999

0,001

2,202

0,001

2,434

0,846

64,586

6,218

-113,353

1,261

63,396

1,261

63,396

2,86

70,125

0,000

11,824

0,000

13,068

10

0,654

88,285

5,081

-86,789

0,931

89,639

0,931

89,639

2,578

97,039

0,001

9,666

0,001

10,684

25

0,402

104,876

3,405

-65,401

0,525

110,551

0,525

110,551

1,966

118,744

0,001

6,482

0,001

7,164

50

0,212

109,65

2,061

-51,066

0,221

124,099

0,221

124,099

1,424

133,257

0,000

3,932

0,001

4,346

100

0,096

94,101

1,143

-41,021

0,021

132,142

0,021

132,142

1,037

142,999

0,001

2,202

0,001

2,434

0,883

64,709

0,883

64,709

5,931

-113,06

1,256

63,392

2,916

69,821

0,000

11,276

0,000

12,462

10

0,68

88,868

0,68

88,868

4,887

-86,497

0,922

90,025

2,617

97,137

0,001

9,297

0,001

10,275

25

0,417

105,668

0,417

105,668

3,314

-65,604

0,515

111,019

1,983

118,932

0,001

6,314

0,001

6,978

50

0,219

110,67

0,219

110,67

2,055

-52,268

0,214

124,516

1,43

133,377

0,000

3,930

0,000

4,344

100

0,099

95,905

0,099

95,905

1,198

-44,024

0,016

133,231

1,039

143,047

0,001

2,328

0,001

2,574

0,883

64,709

0,883

64,709

1,256

63,392

5,931

-113,06

2,916

69,821

0,000

11,276

0,000

12,462

10

0,68

88,868

0,68

88,868

0,922

90,025

4,887

-86,497

2,617

97,137

0,001

9,297

0,001

10,275

25

0,417

105,668

0,417

105,668

0,515

111,019

3,314

-65,604

1,983

118,932

0,001

6,314

0,001

6,978

50

0,219

110,67

0,219

110,67

0,214

124,516

2,055

-52,268

1,43

133,377

0,000

3,930

0,000

4,344

100

0,099

95,905

0,099

95,905

0,016

133,231

1,198

-44,024

1,039

143,047

0,001

2,328

0,001

2,574

0,886

64,714

0,886

64,714

1,292

63,496

1,292

63,496

4,356

-116,008

0,000

8,276

0,000

9,148

10

0,682

88,937

0,682

88,937

0,95

90,204

0,95

90,204

3,263

-90,326

0,001

6,201

0,001

6,853

25

0,417

105,756

0,417

105,756

0,533

111,236

0,533

111,236

1,898

-71,172

0,000

3,608

0,000

3,988

50

0,22

110,757

0,22

110,757

0,224

124,789

0,224

124,789

0,88

-62,159

0,001

1,680

0,001

1,856

1F

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

52/79

Error
Ubicacin

REQ - GDP 1 1%

REQ - GDP 2 1%

REQ - CHIC 1 1%

REQ - CHIC 2 1%

REQ - ETE 1%

Tipo
de
falla

3F

3F

3F

3F

3F

Rf
()

REQUE - GUADALUPE 1

REQUE - GUADALUPE 2

REQUE - CHICLAYO 1

REQUE - CHICLAYO 2

Error

REQUE - ETEN
GUA<, CHI<, ETE<

GUA>, CHI>, ETE>

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Mag
(kA)

Ang
()

Idiff
(kA)

Ibias
(kA)

Idiff
(kA)

Ibias
(kA)

100

0,099

95,998

0,099

95,998

0,022

134,498

0,022

134,498

0,233

-77,338

0,001

0,451

0,001

0,499

5,592

-113,152

0,896

63,349

1,214

64,544

1,214

64,544

2,275

70,687

0,002

10,631

0,002

11,751

10

4,671

-88,293

0,711

85,685

0,921

89,208

0,921

89,208

2,129

95,882

0,000

8,885

0,000

9,821

25

3,228

-67,146

0,455

102,669

0,541

110,116

0,541

110,116

1,704

117,305

0,001

6,146

0,001

6,792

50

1,992

-52,288

0,247

109,413

0,239

124,818

0,239

124,818

1,283

132,261

0,001

3,800

0,001

4,200

100

1,117

-41,682

0,112

98,676

0,033

140,306

0,033

140,306

0,966

142,431

0,001

2,148

0,001

2,374

0,896

63,349

5,592

-113,152

1,214

64,544

1,214

64,544

2,275

70,687

0,002

10,631

0,002

11,751

10

0,711

85,685

4,671

-88,293

0,921

89,208

0,921

89,208

2,129

95,882

0,000

8,885

0,000

9,821

25

0,455

102,669

3,228

-67,146

0,541

110,116

0,541

110,116

1,704

117,305

0,001

6,146

0,001

6,792

50

0,247

109,413

1,992

-52,288

0,239

124,818

0,239

124,818

1,283

132,261

0,001

3,800

0,001

4,200

100

0,112

98,676

1,117

-41,682

0,033

140,306

0,033

140,306

0,966

142,431

0,001

2,148

0,001

2,374

0,93

63,489

0,93

63,489

5,352

-113,231

1,2

64,628

2,301

70,536

0,000

10,177

0,000

11,249

10

0,737

86,09

0,737

86,09

4,514

-88,552

0,906

89,5

2,148

95,945

0,000

8,590

0,000

9,494

25

0,471

103,226

0,471

103,226

3,163

-67,928

0,528

110,462

1,712

117,419

0,000

6,028

0,000

6,662

50

0,256

110,178

0,256

110,178

2,001

-54,024

0,23

125,167

1,287

132,335

0,001

3,829

0,001

4,232

100

0,116

100,168

0,116

100,168

1,178

-45,156

0,028

142,293

0,967

142,461

0,001

2,285

0,001

2,525

0,93

63,489

0,93

63,489

1,2

64,628

5,352

-113,23

2,301

70,536

0,000

10,177

0,000

11,249

10

0,737

86,09

0,737

86,09

0,906

89,5

4,514

-88,552

2,148

95,945

0,000

8,590

0,000

9,494

25

0,471

103,226

0,471

103,226

0,528

110,462

3,163

-67,928

1,712

117,419

0,000

6,028

0,000

6,662

50

0,256

110,178

0,256

110,178

0,23

125,167

2,001

-54,024

1,287

132,335

0,001

3,829

0,001

4,232

100

0,116

100,168

0,116

100,168

0,028

142,293

1,178

-45,156

0,967

142,461

0,001

2,285

0,001

2,525

0,932

63,5

0,932

63,5

1,233

64,68

1,233

64,68

4,33

-115,828

0,000

8,227

0,000

9,093

10

0,738

86,14

0,738

86,14

0,933

89,591

0,933

89,591

3,341

-91,934

0,000

6,349

0,001

7,017

25

0,471

103,29

0,471

103,29

0,546

110,567

0,546

110,567

2,031

-72,802

0,001

3,862

0,001

4,268

50

0,256

110,243

0,256

110,243

0,241

125,263

0,241

125,263

0,985

-62,476

0,000

1,880

0,001

2,078

100

0,116

100,239

0,116

100,239

0,034

141,227

0,034

141,227

0,287

-70,803

0,000

0,558

0,000

0,616

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

53/79

Figura 26:

Verificacin de operacin proteccin diferencial de barras ante fallas internas

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

54/79

Figura 27:

Verificacin de operacin proteccin diferencial de barras ante fallas externas

8.4.2 Zona muerta campo de acople 220 kV


Para calcular el ajuste, se simulan fallas 1, 2 y 3 en la barra de Reque con una resistencia de falla de 5 en el escenario
de mnimos niveles de cortocircuito para determinar la mnima corriente de falla en la subestacin. Se toma el 60% del menor
valor obtenido, el ajuste obtenido anteriormente debe estar por encima del umbral de fases y tierra. En la Tabla 26 se muestra
el ajuste de la zona muerta del campo de acople.
Tabla 26:

Ajuste zona muerta de acople subestacin Reque 220 kV

Tipo de Falla [A]

60% Tipo de Falla [A]

Elemento
3
Barra Reque
220 kV

5260 4682

2-T
5613

2-T

5939 3156,0 2809,2 3367,8 3563,4

Corriente Nominal
[A]

625

UMBRAL EN FASES

UMBRAL EN TIERRA

Criterio

Ajuste
[A]

Criterio

Ajuste
[A]

120 % In CT

750

40 % In CT

250

8.4.3 Funcin falla interruptor (50BF)


La lgica del rel MiCOM P741 para la funcin 50BF se basa en las rdenes de disparo enviadas por las protecciones de la
celda al interruptor. Cuando una de las protecciones de la celda emite una orden de disparo al interruptor, sta se repite a la
proteccin de falla interruptor, con lo cual arranca un temporizador en la misma (t1). Dicho temporizador cuenta en tanto
contine circulando corriente por los contactos principales del interruptor, es decir, mientras haya un comando de disparo
activo y exista circulacin de corriente por el rel 50BF. En condiciones normales, el interruptor se abrir para interrumpir la

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

55/79

corriente de falla, con lo cual se detendr el temporizador t1 de la funcin 50BF. En caso de que el comando de disparo no
sea ejecutado por el interruptor (condicin de falla interruptor), el temporizador llega hasta el lmite de tiempo ajustado, tras
lo cual la proteccin de falla interruptor emite orden de re-disparo sobre este mismo interruptor (etapa 1). En caso contrario,
finalmente se enviar orden de disparo a todos los interruptores adyacentes y al interruptor propio (etapa 2), interrumpiendo
de esta forma la corriente de falla.
Nota: Las ordenes de disparo por etapa 1 y etapa 2 de la funcin de falla interruptor debern ser efectuadas simultneamente
sobre las dos bobinas de apertura de los interruptores.
Los disparos por etapas 1 y 2 del 50BF se efectan definitivos trifsicos sobre ambas bobinas de los interruptores respectivos.
Para calcular el ajuste del rel de falla interruptor para las lneas de transmisin, se simulan fallas 1, 2 y 3 en el extremo
remoto con una resistencia de falla de 50 para determinar la mnima corriente de falla vista por el rel en la subestacin
local. Se toma el 60% del menor valor obtenido, el ajuste obtenido anteriormente debe estar por encima de la corriente
nominal de la lnea (se propone el umbral de 110% de la corriente nominal de la lnea). En la Tabla 27 se muestra el ajuste del
arranque de la funcin falla interruptor.
Tabla 27:

Ajuste arranque falla interruptor subestacin Reque 220 kV

Tipo de Falla [A]

Campo

60% Tipo de Falla [A]

I AJUSTE (Ver *)

I AJUSTE (Ver **)

I [Aprim]

I [I/Ino]

I [Aprim]

I [I/Ino]

400

440

0,70

334,2

0,53

334,2

400

440

0,70

334,2

0,53

504,6

516

400

504,6

0,81

504,6

0,81

648

504,6

516

400

504,6

0,81

504,6

0,81

486,6

706,2

439,2

429,6

729

801,9

1,28

429,6

0,69

N.A.

N.A.

N.A.

N.A.

625

687,5

1,10

687,5

1,10

2-T

2-T

625

713

566

557

375

427,8

339,6

334,2

625

713

566

557

375

427,8

339,6

907

1080

841

860

544,2

648

907

1080

841

860

544,2

Lnea Eten 2L2-6

811

1177

732

716

Acople de Barras

N.A.

N.A.

N.A.

N.A.

Lnea Guadalupe 1
L-2236
Lnea Guadalupe 2
L-2237
Lnea Chiclayo
Oeste 1 L-2296
Lnea Chiclayo
Oeste 2 L-2297

Corriente
Nominal [A]

* Ajuste siguiendo los lineamientos del COES en los numerales 2.9.1 y 4.5.3.
** Ajuste a la mnima corriente de falla, es posible que ante condiciones normales del sistema, el parmetro de corriente de arranque de la funcin 50BF
supere el umbral recomendado en los casos donde se observ que la corriente de falla es menor a la corriente nominal de las lneas, es decir este parmetro
se encontrar activo en la lgica de 50BF

8.5.

ANLISIS DE PROTECCIN SOBRECORRIENTE

A continuacin, se muestra el anlisis de la proteccin de sobrecorriente con los ajustes recomendados en el presente estudio.
Se analiz a partir de la tabla de tiempos presentada en el Anexo 4 (escenario de mximos niveles de cortocircuito).

8.5.1 Lnea Reque Eten (2L2-6) 220 kV, extremo Reque


8.5.1.1 Funcin de sobrecorriente direccional residual (67N)
La funcin direccional de corriente (67N), ser el respaldo de la proteccin diferencial de lnea (87L), en caso de prdida de
canal de comunicaciones o fallas de alta impedancia.
Con los ajustes recomendados en el presente estudio, durante fallas a tierra francas (monofsicas y bifsicas) a lo largo de
toda la lnea Reque Eten 2L2-6 220 kV (desde Reque), se tienen despejes rpidos en el extremo local (Reque 220 kV)
permitiendo una adecuada coordinacin con las lneas adyacentes, y adems acta como respaldo de la proteccin de
sobrecorriente del transformador GSU.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

56/79

8.5.2 Lnea Reque Eten (2L2-6) 220 kV, extremo Eten


8.5.2.1 Funcin de sobrecorriente direccional residual (67N)
La funcin direccional de corriente (67N), ser el respaldo de la proteccin diferencial de lnea (87L), en caso de prdida de
canal de comunicaciones o fallas de alta impedancia.
Con los ajustes recomendados en el presente estudio, se tiene una adecuada coordinacin con las lneas adyacentes.

9.

AJUSTES DE LOS DISPOSITIVOS DE PROTECCIN EXISTENTES

En primer lugar se proceder a presentar los ajustes existentes de las funciones de distancia y de sobrecorriente en el rea de
influencia del Proyecto Ampliacin 14, Subestacin Reque 220 kV, posteriormente se presentar en el Anexo 4 las
verificaciones de los tiempos de operacin para dichos ajustes.

9.1.

SUBESTACIN REQUE 220 KV

9.1.1 Lnea Reque Guadalupe 1 y 2 220 kV


Tabla 28:

SUBESTACIN

Reque 220 kV

Ajustes actuales funcin de sobrecorriente lnea Reque Guadalupe 1 y 2 (L-2236 y L-2237)


220 kV, extremo Reque
BAHA

PROTECCIN

Reque Guadalupe
1y2

TC

PL1-SEL411L
625/1 A
PL2-SEL411L

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0> Pickup

T 3I0> Time
Dial

120 A

0,25 sec

Normal
Inverse

1625 A

0,25 sec

9.1.2 Lnea Reque Chiclayo Oeste 1 y 2 220 kV


Tabla 29:

Ajustes actuales funcin de sobrecorriente lnea Reque Chiclayo Oeste 1 y 2 (L-2296 y L-2297)
220 kV, extremo Reque

SUBESTACIN

BAHA

PROTECCIN

Reque 220 kV

Reque Chiclayo
Oeste 1 y 2

TC

PL1-SEL411L
625/1 A
PL2-SEL411L

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,19 sec

Normal
Inverse

1443 A

0,25 sec

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

57/79

9.2.

SUBESTACIN CHICLAYO OESTE 220 KV

9.2.1 Lnea Chiclayo Oeste Reque 1 y 2 220 kV


Tabla 30:

Ajustes actuales funcin de sobrecorriente lnea Chiclayo Oeste - Reque 1 y 2 (L-2296 y L-2297)
220 kV, extremo Chiclayo Oeste

SUBESTACIN

BAHA

Chiclayo Oeste
220 kV

PROTECCIN

Chiclayo Oeste
Reque 1 y 2

TC

PL1-SEL411L
625/1 A
PL2-SEL411L

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,42 sec

Normal
Inverse

2796 A

0,25 sec

9.2.2 Lnea Chiclayo Oeste La Nia 220 kV


Tabla 31:

Ajustes actuales funcin de sobrecorriente lnea La Nia Chiclayo Oeste (L-2239) 220 kV, extremo
Chiclayo Oeste

SUBESTACIN

BAHA

PROTECCIN

Chiclayo Oeste
220 kV

Chiclayo Oeste
La Nia

PL1-SEL421
PL2-SEL421

TC

600/1 A

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,18 sec

Normal
Inverse

1314 A

0,25 sec

9.2.3 Lnea Chiclayo Oeste Piura Oeste 220 kV


Tabla 32:

Ajustes actuales funcin de sobrecorriente lnea Piura Oeste Chiclayo Oeste (L-2238) 220 kV,
extremo Chiclayo Oeste

SUBESTACIN

BAHA

Chiclayo Oeste
220 kV

PROTECCIN

Chiclayo Oeste
Piura Oeste

PL1-7SA612
PL2-7SA522

TC

600/1 A

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,18 sec

Normal
Inverse

864 A

0,25 sec

9.2.4 Lnea Chiclayo Oeste Carhuaquero 220 kV


Tabla 33:

Ajustes actuales funcin de sobrecorriente lnea Carhuaquero Chiclayo Oeste (L-2240) 220 kV,
extremo Chiclayo Oeste

SUBESTACIN

BAHA

Chiclayo Oeste 220 kV Chiclayo Oeste Carhuaquero

PROTECCIN
PL1-7SA612
PL2-7SA522

TC

Tierra 3I0 Inverse Time (Forward)


3I0p Pickup 3I0p Time Dial

300/1 A

120 A

0,15 sec

IEC Curve
Normal Inverse

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

58/79

9.2.5 Transformador T93-261 220 kV


Tabla 34:
SUBESTACIN

Chiclayo Oeste
220 kV

BAHA

T93261

Ajustes actuales funcin de sobrecorriente transformador T93-261 220 kV


PROTECCIN

PL1-RET670

TC

FASE DMT
I>
Pickup
2400 A

TIERRA DMT

T I> Time Dial

IE>
Pickup

T IE> Time Dial

0,05 sec

1900 A

0,05 sec

FASE IDMT
400/1 A

TIERRA IDMT

Ip
Pickup

T Ip Time
Dial

IEC Curve

IEp
Pickup

T IEp Time
Dial

IEC Curve

340 A

0,18 sec

Normal
Inverse

52 A

0,22 sec

Normal
Inverse

9.2.6 Transformador T16-260 220 kV


Tabla 35:
SUBESTACIN

Chiclayo Oeste
220 kV

BAHA

T16260

Ajustes actuales funcin de sobrecorriente transformador T16-260 220 kV


PROTECCIN

PL1-7UT633

TC

FASE DMT

TIERRA DMT

I>
Pickup

T I> Time Dial

IE>
Pickup

T IE> Time Dial

1828 A

0,1 sec

1828 A

0,1 sec

FASE IDMT
200/1 A

TIERRA IDMT

Ip
Pickup

T Ip Time
Dial

IEC Curve

IEp
Pickup

T IEp Time
Dial

IEC Curve

262 A

0,20 sec

Normal
Inverse

78 A

0,23 sec

Normal
Inverse

9.2.7 Transformador T14-260 220 kV


Tabla 36:
SUBESTACIN

Chiclayo Oeste
220 kV

BAHA

T14260

Ajustes actuales funcin de sobrecorriente transformador T14-260 220 kV


PROTECCIN

PL1-7UT633

TC

FASE DMT

TIERRA DMT

I>
Pickup

T I> Time Dial

IE>
Pickup

T IE> Time Dial

1828 A

0,1 sec

1828 A

0,1 sec

FASE IDMT
200/1 A

TIERRA IDMT

Ip
Pickup

T Ip Time
Dial

IEC Curve

IEp
Pickup

T IEp Time
Dial

IEC Curve

262 A

0,20 sec

Normal
Inverse

78 A

0,23 sec

Normal
Inverse

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

59/79

9.3.

SUBESTACIN LA NIA 220 KV

Tabla 37:

Ajustes actuales funcin de sobrecorriente lnea La Nia Chiclayo Oeste (L-2239) 220 kV, extremo
La Nia

SUBESTACIN

BAHA

PROTECCIN

La Nia
220 kV

La Nia Chiclayo
Oeste

PL1-7SA612
PL2-7SA612

9.4.

SUBESTACIN

Piura Oeste
220 kV

400/1A

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0> Pickup

T 3I0> Time
Dial

120 A

0,14 sec

Very
Inverse

648 A

0,25 sec

Ajustes actuales funcin de sobrecorriente lnea Piura Oeste Chiclayo Oeste (L-2238) 220 kV,
extremo Piura Oeste
BAHA

PROTECCIN

Piura Oeste
Chiclayo Oeste

PL1-7SA612
PL2-7SA612

TC

600/1 A

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,11 sec

Normal
Inverse

882 A

0,25 sec

SUBESTACIN CARHUAQUERO 220 KV

Tabla 39:

Ajustes actuales funcin de sobrecorriente lnea Carhuaquero Chiclayo Oeste (L-2240) 220 kV,
extremo Carhuaquero

SUBESTACIN

BAHA

PROTECCIN

Carhuaquero
220 kV

Carhuaquero
Chiclayo Oeste

PL1-REL670
PL2-REL670

9.6.

Tierra 3I0 Definitve Time


(Forward)

Tierra 3I0 Inverse Time (Forward)

SUBESTACIN PIURA OESTE 220 KV

Tabla 38:

9.5.

TC

TC

300/1 A

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

60 A

0,25 sec

Normal
Inverse

900 A

0,25 sec

SUBESTACIN TRUJILLO NORTE 220 kV

Lnea Trujillo Norte Guadalupe 1 y 2 220 kV


Tabla 40:

Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 1 (L-2234) 220 kV,
extremo Trujillo Norte

SUBESTACIN

BAHA

PROTECCIN

Trujillo Norte
220 kV

Trujillo Norte Guadalupe 1

TC

PL1-7SA612
600/1 A
PL2-7SA522

Tierra 3I0 Inverse Time


(Forward)
3I0p
3I0p
Time
IEC Curve
Pickup
Dial
Normal
90 A
0,20 sec
Inverse

Tierra 3I0 Definitve


Time (Forward)
3I0>
Pickup

T 3I0>
Time Dial

1302 A

0,25 sec

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

60/79

Tabla 41:

Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 2 (L-2235) 220 kV,
extremo Trujillo Norte

SUBESTACIN

BAHA

PROTECCIN

Trujillo Norte
220 kV

Trujillo Norte Guadalupe 2

PL1-PL2
REL670

9.7.

Tierra 3I0 Inverse Time


(Forward)
3I0p
3I0p
Time
IEC Curve
Pickup
Dial
Normal
90 A
0,20 sec
Inverse

TC

600/1 A

Tierra 3I0 Definitve


Time (Forward)
3I0>
Pickup

T 3I0>
Time Dial

1296 A

0,25 sec

SUBESTACIN GUADALUPE 220 KV

9.7.1 Lnea Guadalupe Reque 1 y 2 220 kV


Tabla 42:

Ajustes actuales funcin distancia lnea Guadalupe Reque 1 (L-2236) 220 kV, extremo Guadalupe

SUBESTACIN

BAHA

PROTECCIN

TC

TT

AJUSTES
( Prim)
X
X(-)

Guadalupe
220 kV

Tabla 43:

SUBESTACIN

Guadalupe
220 kV

Tabla 44:

Guadalupe
Reque 1

PL1-7SA612
PL2-7SA612

600/1 A

220 kV
/ 100 V

ZONA ZONA ZONA ZONA


1
2
3
1B
27,23 37,16 45,76
-

ZONA 4
(REVERSA)

ZONA
5

37,16

6,41

52,76

52,76

54,46 54,46 91,52

54,46

12,81

98,52

RE

54,46 54,46 91,52

54,46

12,81

98,52

()

Ko Mag

0,553 0,553 0,553

0,553

0,553

0,553

Ko Ang
()

-8,96

-8,96

-8,96

-8,96

-8,96

-8,96

T(s)

0,4

1,5

oo

Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 1 (L-2236) 220 kV, extremo
Guadalupe
BAHA

PROTECCIN

Guadalupe
Reque 1

PL1-7SA612
PL2-7SA612

TC

Tierra 3I0 Inverse Time (Forward)

600/1 A

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0> Pickup

T 3I0> Time
Dial

120 A

0,24 sec

Normal
Inverse

1590 A

0,25 sec

Ajustes actuales funcin de distancia lnea Guadalupe Reque 2 (L-2237) 220 kV, extremo
Guadalupe

SUBESTACIN

BAHA

PROTECCIN

TC

TT

Guadalupe
220 kV

Guadalupe
Reque 2

PL1-PL2
REL670

600/1 A

220
kV /

AJUSTES ZONA ZONA ZONA


ZONA 4
ZONA 5
( Prim)
1
2
3
(REVERSA) (REVERSA)
X1PP

27,24 37,18 45,76

6,41

OFF

R1PP

4,84

1,13

OFF

6,60

8,14

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

61/79

SUBESTACIN

BAHA

PROTECCIN

TC

TT

AJUSTES ZONA ZONA ZONA


ZONA 4
ZONA 5
( Prim)
1
2
3
(REVERSA) (REVERSA)

100 V

RFPP

81,69 91,67 137,28

t1PP(s)

OFF

1,5

OFF

X0PE

70,62 96,36 118,65

4,53

OFF

R0PE

19,8

27,02 33,26

1,27

OFF

RFPE

81,69 91,67 137,28

19,22

OFF

1,5

OFF

t1PE(s)
Tabla 45:

0,4

19,22

0,4

Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 2 (L-2237) 220 kV, extremo
Guadalupe

SUBESTACIN

BAHA

PROTECCIN

Guadalupe
220 kV

Guadalupe
Reque 2

PL1-PL2
REL670

TC

Tierra 3I0 Inverse Time (Forward)

600/1 A

3I0p
Pickup

3I0p
Time Dial

IEC Curve

120 A

0,24 sec

Normal
Inverse

Tierra 3I0 Definitve


Time (Forward)
3I0>
T 3I0> Time
Pickup
Dial
1590 A

0,25 sec

9.7.2 Lnea Guadalupe Trujillo Norte 1 y 2 220 kV


Tabla 46:

Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 1 (L-2234) 220 kV,
extremo Guadalupe

SUBESTACIN

BAHA

PROTECCIN

TC

PL1-7SA612
Guadalupe 220 kV Trujillo Norte - Guadalupe 1
600/1 A
PL2-7SA522

Tabla 47:

SUBESTACIN

Guadalupe
220 kV

Tierra 3I0 Inverse Time (Forward)


3I0p Pickup 3I0p Time Dial
120 A

0,16 sec

IEC Curve
Normal Inverse

Ajustes actuales funcin de sobrecorriente lnea Trujillo Norte Guadalupe 2 (L-2235) 220 kV,
extremo Guadalupe
BAHA

PROTECCIN

Trujillo Norte Guadalupe 2

PL1-PL2
REL670

TC

600/1 A

Tierra 3I0 Inverse Time


(Forward)
3I0p
3I0p
Time
IEC Curve
Pickup
Dial
Normal
90 A
0,14 sec
Inverse

Tierra 3I0 Definitve


Time (Forward)
3I0>
Pickup

T 3I0>
Time Dial

1050 A

0,25 sec

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

62/79

9.7.3 Transformador T92-261 220 kV


Tabla 48:
SUBESTACIN

Guadalupe
220 kV

BAHA

T92261

Ajustes actuales funcin de sobrecorriente transformador T92-261 220 kV


PROTECCIN

PL1RET670

TC

FASE DMT
I>
Pickup
999 A

TIERRA DMT

T I> Time Dial

IE>
Pickup

T IE> Time Dial

0,05 sec

999 A

0,05 sec

FASE IDMT
300/1 A

TIERRA IDMT

Ip
Pickup

T Ip Time
Dial

IEC Curve

IEp
Pickup

T IEp Time
Dial

IEC Curve

171 A

0,18 sec

Normal
Inverse

54 A

0,16 sec

Normal
Inverse

9.7.4 Transformador T17-261 220 kV


Tabla 49:
SUBESTACIN

Guadalupe
220 kV

BAHA

T17261

Ajustes actuales funcin de sobrecorriente transformador T17-261 220 kV


PROTECCIN

PL17UT633

TC

FASE DMT

TIERRA DMT

I>
Pickup

T I> Time Dial

IE>
Pickup

T IE> Time Dial

1016 A

0,1 sec

1016 A

0,1 sec

FASE IDMT
100/1 A

TIERRA IDMT

Ip
Pickup

T Ip Time
Dial

IEC Curve

IEp
Pickup

T IEp Time
Dial

IEC Curve

127 A

0,21 sec

Normal
Inverse

39 A

0,26 sec

Normal
Inverse

9.7.5 Transformador T13-261 220 kV


Tabla 50:
SUBESTACIN

Guadalupe
220 kV

BAHA

T13261

Ajustes actuales funcin de sobrecorriente transformador T13-261 220 kV


PROTECCIN

PL1RET670

TC

FASE DMT

TIERRA DMT

I>
Pickup

T I> Time Dial

IE>
Pickup

T IE> Time Dial

1016 A

0,1 sec

1016 A

0,1 sec

FASE IDMT
100/1 A

TIERRA IDMT

Ip
Pickup

T Ip Time
Dial

IEC Curve

IEp
Pickup

T IEp Time
Dial

IEC Curve

127 A

0,21 sec

Normal
Inverse

39 A

0,26 sec

Normal
Inverse

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

63/79

10.
VERIFICACIN Y AJUSTES RECOMENDADOS DE LOS DISPOSITIVOS DE PROTECCIN
EXISTENTES EN EL REA DE INFLUENCIA
10.1. SUBESTACIN REQUE 220 KV
Una vez verificados los ajustes de sobrecorriente de las lneas Reque Chiclayo Oeste 1 y 2 220 kV (extremo Reque) y Reque
Guadalupe 1 y 2 220 kV (extremo Reque), se observ que ofrecen poca selectividad con la entrada de la lnea Reque Eten
220 kV, por lo tanto se recomienda reajustar las protecciones de sobrecorriente como se muestra en la Tabla 51 y Tabla 52:
Tabla 51:

Ajustes recomendados funcin de sobrecorriente lnea Reque Guadalupe 1 y 2 (L-2236 y L-2237)


220 kV, extremo Reque

SUBESTACIN

BAHA

Reque 220 kV

Reque Guadalupe
1y2

Tabla 52:

PROTECCIN

TC

PL1-SEL411L
625/1 A
PL2-SEL411L

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0> Pickup

T 3I0> Time
Dial

120 A

0,25 sec

Normal
Inverse

1982 A

0,25 sec

Ajustes recomendados funcin de sobrecorriente lnea Reque Chiclayo Oeste 1 y 2 (L-2296 y L2297) 220 kV, extremo Reque

SUBESTACIN

BAHA

PROTECCIN

Reque 220 kV

Reque Chiclayo
Oeste 1 y 2

TC

PL1-SEL411L
625/1 A
PL2-SEL411L

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,34 sec

Normal
Inverse

3239 A

0,25 sec

10.2. SUBESTACIN GUADALUPE 220 KV


Una vez verificados los ajustes de sobrecorriente de las lneas Guadalupe Reque 1 y 2 220 kV (extremo Guadalupe), se
observ que ofrecen poca selectividad con la entrada de la lnea Reque Eten 220 kV, por lo tanto se recomienda reajustar
las protecciones de sobrecorriente como se muestra en la Tabla 53 y Tabla 54:
Tabla 53:

Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 1 (L-2236) 220 kV, extremo
Guadalupe

SUBESTACIN

BAHA

PROTECCIN

Guadalupe
220 kV

Guadalupe
Reque 1

PL1-7SA612
PL2-7SA612

TC

600/1 A

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0> Pickup

T 3I0> Time
Dial

120 A

0,24 sec

Normal
Inverse

1783 A

0,25 sec

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

64/79

Tabla 54:

SUBESTACIN

Guadalupe
220 kV

Ajustes actuales funcin de sobrecorriente lnea Guadalupe Reque 2 (L-2237) 220 kV, extremo
Guadalupe
BAHA

PROTECCIN

Guadalupe
Reque 2

PL1-PL2
REL670

TC

600/1 A

Tierra 3I0 Inverse Time (Forward)


3I0p
Pickup

3I0p
Time Dial

IEC Curve

120 A

0,24 sec

Normal
Inverse

Tierra 3I0 Definitve


Time (Forward)
3I0>
T 3I0> Time
Pickup
Dial
1783 A

0,25 sec

10.3. SUBESTACIN CHICLAYO OESTE 220 KV


Una vez verificados los ajustes de sobrecorriente de las lneas Chiclayo Oeste Reque 1 y 2 220 kV (extremo Chiclayo Oeste),
se observ que ofrecen poca selectividad con la entrada de la lnea Reque Eten 220 kV, por lo tanto se recomienda reajustar
las protecciones de sobrecorriente como se muestra en la Tabla 55:
Tabla 55:

Ajustes recomendados funcin de sobrecorriente lnea Chiclayo Oeste - Reque 1 y 2 (L-2296 y L2297) 220 kV, extremo Chiclayo Oeste

SUBESTACIN

BAHA

PROTECCIN

Chiclayo Oeste
220 kV

Chiclayo Oeste
Reque 1 y 2

TC

PL1-SEL411L
625/1 A
PL2-SEL411L

Tierra 3I0 Inverse Time (Forward)

Tierra 3I0 Definitve Time


(Forward)

3I0p
Pickup

3I0p Time
Dial

IEC Curve

3I0>
Pickup

T 3I0> Time
Dial

120 A

0,35 sec

Normal
Inverse

2797 A

0,25 sec

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

65/79

11.

CONCLUSIONES Y RECOMENDACIONES

Con el estudio realizado, se determinaron los ajustes de las funciones de proteccin para los diferentes dispositivos ubicados
en las bahas de lnea y barras de la subestacin Reque 220 kV y la baha de lnea Reque en la subestacin Eten. Asimismo, se
verific por medio de simulaciones, su selectividad y seguridad, garantizando una vez sean implementados y debidamente
probados, la operacin adecuada del esquema de protecciones, tanto ante fallas en la subestacin Reque 220 kV y
Eten 220 kV, como en las subestaciones del rea de influencia.
Con los ajustes recomendados para la funcin de sobrecorriente en el lado de alta tensin del transformador GSU se observ
una adecuada selectividad con las protecciones adyacentes, ya que ante fallas trifsicas y monofsicas francas y de alta
impedancia (hasta 5 ohm) en bornes del lado de alta tensin del transformador se obtuvo un tiempo de operacin de 120 ms.
Tambin, se garantiza una adecuada selectividad con las protecciones adyacentes ubicadas en las lneas Reque Guadalupe
1 y 2 220 kV y Reque Chiclayo Oeste 1 y 2 220 kV, ante fallas trifsicas y monofsicas que se presenten en estas lneas.
Una vez realizados los anlisis se obtuvo que los ajustes actuales de la funcin de proteccin distancia en la lnea Guadalupe
Reque 1 y 2 220 kV (extremo Guadalupe) son selectivos con la entrada de la lnea Reque Eten 220 kV, ya que ante una
falla en el lado de baja tensin del transformador GSU no se present incursin en zona 2 y zona 3, y ante fallas monofsicas
y trifsicas francas en el lado de alta tensin opera la zona 3 (1 s), coordinando con la proteccin de sobrecorriente del lado
de alta del transformador (120 ms).
Para fallas en las lneas Reque - Chiclayo Oeste 1 y 2 220 kV al 50% de la lnea, se garantiza selectividad con las protecciones
adyacentes en caso de que la funcin principal (87L) y el esquema de teleproteccin (67NCD) no operen, hasta fallas de alta
impedancia de RFalla 6 ohm.
Al realizar las verificaciones para la funcin de sobrecorriente de tierra (67N), ante fallas monofsicas en la zona de influencia
sistema bajo estudio en las lneas Reque Guadalupe 1 y 2 220 kV, Reque Chiclayo Oeste 1 y 2 220 kV y Reque
Eten 220 kV, se observ la operacin secuencial de las protecciones, ya que opera inicialmente el extremo ms fuerte en la
etapa de tiempo definido de la funcin de sobrecorriente (250 ms) y por su parte, el extremo dbil, logra detectar esta falla en
la etapa de tiempo inverso (en tiempos similares a las protecciones adyacentes). Posterior a la apertura del interruptor en el
extremo fuerte, se acelera el disparo en el extremo dbil operando en 250 ms la etapa de tiempo definido 67N,
garantizndose as una adecuada selectividad entre las protecciones ubicadas en el rea de influencia del estudio.
Si se decide hacer modificaciones sobre los ajustes actuales de los dispositivos asociados a las bahas de lnea de la
subestacin Reque 220 kV y sus extremos remotos, se debe verificar primero que los ajustes en sitio correspondan a los
expuestos en este documento.
Se recomienda la realizacin de pruebas secundarias de inyeccin a los rels de proteccin para verificar su adecuada
operacin con los ajustes propuestos en este documento, y adems durante estas pruebas se debe verificar la operacin de las
funciones diferencial de lnea (ANSI 87L) y diferencial de barras (ANSI 87B) ante fallas internas y su estabilidad ante fallas
externas, considerando diferentes tipos de fallas (trifsicas, bifsicas y monofsicas de alta impedancia).

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

66/79

REFERENCIAS
[1]

COES SINAC (Comit de Operacin Econmica del Sistema Interconectado Nacional). Criterios de Ajuste y
Coordinacin de los Sistemas de Proteccin del SEIN, marzo de 2008.

[2]

HMV Ingenieros Ltda. Documento No. PE-AM14-ETEN-D090_50-ETEN-PVD-0090-PC. Flujo de Cargas.

[3]

HMV Ingenieros Ltda. Documento No. PE-AM14-ETEN-D091_50-ETEN-PVD-0091-PC. Estudio de Cortocircuito.

[4]

HMV Ingenieros Ltda. Plano No. PE-AM14-ETEN-K005_10-ETEN-ACS-0104-SC. Diagrama Unifilar.

[5]

HMV Ingenieros Ltda. Planos No. PE-AM14-ETEN-K002_10-ETEN-ACS-0101-SC. Rev. B. Diagramas de


Principio.

[6]

HMV Ingenieros Ltda. Documento No. PE-AM14-ETEN-D040_10-ETEN-ACS-0061-FC. Memoria de clculo


cargabilidad de transformadores de medida.

[7]

HMV Ingenieros Ltda. Documento No. PE-AM14-ETEN-D067_10-ETEN-ACS-0060-FC. Memoria de clculo de


conductores y barrajes.

[8]

HMV Ingenieros Ltda. Documento No. PE-AM14-TRU-D066_60-TRU-PRB-2256-PE. Estudio de Coordinacin de


Protecciones.

[9]

HMV Ingenieros Ltda. Documento No. PE-AM14-REQ-D066_60-REQ-PRB-2256-PE. Estudio de Coordinacin de


Protecciones.

[10]

COES, Estudio de Coordinacin de las Protecciones del Sistema Elctrico Interconectado Nacional, ECP 2010.

[11]

SCHWEITZER ENGINEERING LABORATORIES, INC. SEL 411L. Advanced Line Differential Protection, Automation
and Control System, Instruction Manual.

[12]

SCHWEITZER ENGINEERING LABORATORIES, INC. Digital Communications for Power System Protection: Security,
Availability and Speed.

[13]

ALSTOM, MiCOM P741, P742, P743. Technical Manual. Differential Busbar Protection Relay.

ESTUDIO DE COORDINACIN DE PROTECCIONES


SUBESTACIN REQUE 220 kV
REFERENCIA ALSTOM

60-ETEN-PRB-2256-PE

REV.

CDIGO REP

HOJA

PE-AM14-ETEN-D066

67/79

ANEXO 1
Esquema de proteccin de la lnea
subestacin Reque 220 kV

ANEXO 2
Esquema de proteccin de lnea
subestacin Eten 220 kV

\
N7G"
2(!">:&
&


OP

''G"

95H

"O"PG"O"P

'76N

73E2310FG11)1C2*H

:;9

:;9
""
:
=

9NG
;>

19G"


:;9"

"B"

N9'12=31''6

:;9
""
:
=

;> 9NG=

'5G"
G"G
GGG




NI376'7

33'
7357B37




''G

19G
OP
"O"PG"O"PG"O"P 

9

012
9'5
5'79

N7G
'5G
2(!">:& G"G
"&
GG

3'3760

5'
"

"


"='"

012
3345647689
6 



!"#$%

5'
G"
5'
"

9'5 '7

8> 8>
 =
;" 9
;"

''
8
"
"'
:;'

'"

5'



 5' "=='"
 26'246967@
" '71737
6 537389
<A<

:-""-

!"#$:%

;0G'

8
=
"
0"0
:;'

NI37
6'7

;2

33'
7357B37

5'
"




":
OP

"
:&

"OPG"OPG"

"05=
=5"

'7

8>
=
9
;"

'
;"

'
;"

:>0

3 

$24%

24

;>
;4

"=="

"&

;0G0
5'G0
"

"


=
;
"
=
>=

8

"
N'4
:;2
"'

5

'2

:>11

T
5'"
"

5'">">5
"

5'"
"

"H"

;>
":& 8>0
51?
:

5'"
"

5'8
"

5';:>
"

5'""""
"


0"

"
"

3'
1@5
)(&M/

'8
":"
'
":"

B5
9C*&
7/)D12(

834
34
;34
34
834
8;34
>34
34
834
;34

L

5'
"


5'


"
"

5'


"
"

;3'

;11

;0

;

;=

;L

N'
E
N7

;"E

"3456
H5

'-'71-

N'
E
N7

;"E

8>
=

"619
=N'"

'6'710

"='"

NI376'7

"L
"
L
 ""RRSS
""R
L
"""

376B359529
B523'56B3
N733B7

8>

"='

137653'71-
<<44537389
949 
&

!"#

137653'71-"
<<44537389
949 
&

!"#

::
8;;&

!#

8>
5
9C*/
7/)D12(

"
"

=

5'
:

"
"

1@5

"
"



5'


"
"

B
87

"
"

0

5'
"

"

"
"

8
"&

!#

8>

"
"

11

N
"
8>
8
97


8GK
)D

0

8>


"
0"0

73373561
5N933'761

73G"G@3xG353G6BG"
T
'27=601$03%R"';8
012$91'%R73G"G='G3NG91G"
bcdAefg hijklmnojpq krcs6steuscufsikls446
N3931$516%R
mftcmlevnwdhettp q 73G"GBG6B@G==G
73G"G@'2G3B2G6BG"R2*C,-1CKJMC,CD).2
73G"G@'2G3B2G6BGR2*C,-./J(21/DDC2*yK/.C.)
73G"G@'2G3B2G6BGR2*C,-1CKJMC,CD).2=)z)'/*+-

7'B

8JD+'71

`
34"/

:>BG"

"
"0


NI376'7

'()*+,-./
/01(2
"

L
"
L
"

L
"""

L
""
0

03
B
3421"

"N
8
;N
;'

8
8

"N
8
;N
;'

8
8

;
"N
>
>N
;:
:"2
:"0
:;1
0G

"H;

;
"N
>
>N
;:
:"2
:"0
:;1
0G=

0LCMC)(0/*/()12(
"-
:-;;I;(JK
-&
51?
-:

L
"""

"L
"

0

=

:;0

"
"8
>; 
:"2 ;

"L
"
"L
"

"=';

24-03-'7
<<44537389
949 
&

!#

ANEXO 3
Esquema de proteccin baha de acople
subestacin Reque 220 kV

ANEXO 4
Tabla de coordinacin funciones de
sobrecorriente en 220 kV (Escenario de
mxima corriente de cortocircuito
FC16AS1)
* La tabla se realiz con los ajustes recomendados en el documento
** 50N funcin de sobrecorriente direccional de tierra de tiempo definido

TRAMO O ELEMENTO PROTEGIDO

Elemento

Lnea Reque - Eten 220 kV


Eten

Reque

Guadalupe

Reque

Guadalupe

PROTECCIN

SEL 411L
SEL 411L

SEL 411L
SEL 411L

SEL 411L
SEL 411L

Siemens 7SA612
Siemens 7SA522

SEL 411L
SEL 411L

REL670
REL670

FUNCIN DE PROTECCIN

67N

67N

67N/50N

67N/50N

67N/50N

67N/50N

Tipo de
falla

Impedancia de falla

0
1
10

0
Lnea Reque - Chiclayo Oeste 1
220 kV

1
10

0
Lnea Reque - Eten 220 kV

Lnea Reque- Guadalupe 2 220 kV

Reque

% de
lnea

[]

Lnea Reque - Guadalupe 1


220 kV

Lnea Reque - Guadalupe 1 220 kV

SUBESTACIN

1
10

Valor de Cortocircuito
en el punto Falla
(Ik'') [kA]

(3I0) [kA]

[s]

[s]

[s]

[s]

[s]

[s]

7,13

6,52

NO

1,014

0,25

1,003

NO

1,084

50

4,61

2,45

NO

1,355

0,25

0,25

9,043

NO

99

5,58

0,83

NO

1,675

0,882

0,25

0,914

NO

5,79

5,29

NO

1,08

0,25

1,154

NO

1,262

50

4,07

2,16

NO

1,425

0,25

0,25

23,708

NO

99

4,79

0,71

NO

1,806

0,958

0,25

0,996

NO

7,26

6,00

NO

1,014

NO

1,054

NO

1,054

50

6,70

3,60

NO

1,080

NO

1,228

NO

1,228

99

6,87

1,70

NO

1,135

NO

1,370

NO

1,370

5,87

4,85

NO

1,074

NO

1,226

NO

1,226

50

5,51

2,96

NO

1,152

NO

1,445

NO

1,445

99

5,60

1,38

NO

1,218

NO

1,66

NO

1,66

7,28

3,58

0,250

1,014

NO

1,052

NO

1,052

50

7,23

3,33

0,250

1,014

NO

1,101

NO

1,101

99

7,20

3,10

0,250

1,014

NO

1,155

NO

1,155

5,88

2,89

0,250

1,072

NO

1,222

NO

1,222

50

5,86

2,70

0,250

1,053

NO

1,285

NO

1,285

99

5,86

2,52

0,250

1,034

NO

1,356

NO

1,356

TRAMO O ELEMENTO PROTEGIDO

Elemento

Lnea Reque - Chiclayo Oeste 1 220 kV


Chiclayo Oeste

Reque

Chiclayo Oeste

Trujillo Norte

Guadalupe

PROTECCIN

SEL 411L
SEL 411L

SEL 411L
SEL 411L

SEL 411L
SEL 411L

SEL 411L
SEL 411L

Siemens 7SA61
Siemens 7SA522

Siemens 7SA612
Siemens 7SA522

FUNCIN DE PROTECCIN

67N/50N

67N/50N

67N/50N

67N/50N

67N/50N

67N/50N

Tipo de
falla

Impedancia de falla

0
1
10

0
Lnea Reque - Chiclayo Oeste 1
220 kV

1
10

0
Lnea Reque - Eten 220 kV

Lnea Trujillo Norte - Guadalupe 1 220 kV

Reque

% de
lnea

[]

Lnea Reque - Guadalupe 1


220 kV

Lnea Reque - Chiclayo Oeste 2 220 kV

SUBESTACIN

1
10

Valor de Cortocircuito
en el punto Falla
(Ik'') [kA]

(3I0) [kA]

[s]

[s]

[s]

[s]

[s]

[s]

7,13

6,52

NO

1,044

NO

1,044

1,799

NO

50

4,61

2,45

NO

1,657

NO

1,657

1,042

NO

99

5,58

0,83

NO

2,456

NO

2,456

0,684

NO

5,79

5,29

NO

1,152

NO

1,152

2,484

NO

50

4,07

2,16

NO

1,818

NO

1,818

1,153

NO

99

4,79

0,71

NO

2,925

NO

2,925

0,742

NO

7,26

6,00

0,250

1,017

NO

1,044

1,847

NO

50

6,70

3,60

0,250

0,250

3,238

NO

2,623

NO

99

6,87

1,70

0,872

0,250

0,886

NO

3,573

NO

5,87

4,85

0,250

1,122

NO

1,155

2,598

NO

50

5,51

2,96

0,717

0,777

4,380

NO

4,217

NO

99

5,60

1,38

0,946

0,25

0,962

NO

7,740

NO

7,28

3,58

NO

1,032

NO

1,032

1,837

NO

50

7,23

3,33

NO

1,066

NO

1,066

2,023

NO

99

7,20

3,10

NO

1,104

NO

1,104

2,255

NO

5,88

2,89

NO

1,140

NO

1,140

2,581

NO

50

5,86

2,70

NO

1,179

NO

1,179

2,936

NO

99

5,86

2,52

NO

1,222

NO

1,222

3,417

NO

TRAMO O ELEMENTO PROTEGIDO

Elemento

Lnea Trujillo Norte - Guadalupe 2 220 kV


Guadalupe

La Nia

Chiclayo Oeste

Piura Oeste

Chiclayo Oeste

PROTECCIN

REL670
REL670

REL670
REL670

Siemens 7SA612
Siemens 7SA612

SEL 421
SEL 421

Siemens 7SA612
Siemens 7SA612

Siemens 7SA612
Siemens 7SA522

FUNCIN DE PROTECCIN

67N

67N

67N/50N

67N/50N

67N/50N

67N

Tipo de
falla

Impedancia de falla

0
1
10

0
Lnea Reque - Chiclayo Oeste 1
220 kV

1
10

0
Lnea Reque - Eten 220 kV

Lnea Piura Oeste - Chiclayo Oeste 220 kV

Trujillo Norte

% de
lnea

[]

Lnea Reque - Guadalupe 1


220 kV

Lnea La Nia - Chiclayo Oeste 220 kV

SUBESTACIN

1
10

Valor de Cortocircuito
en el punto Falla
(Ik'') [kA]

(3I0) [kA]

[s]

[s]

[s]

[s]

[s]

[s]

7,13

6,52

2,059

NO

1,078

NO

1,563

NO

50

4,61

2,45

1,126

NO

NO

NO

NO

NO

99

5,58

0,83

0,719

NO

NO

NO

NO

NO

5,79

5,29

3,008

NO

1,535

NO

2,744

NO

50

4,07

2,16

1,256

NO

NO

NO

NO

NO

99

4,79

0,71

0,783

NO

NO

NO

NO

NO

7,26

6,00

2,122

NO

1,030

NO

1,475

NO

50

6,70

3,60

3,213

NO

0,815

NO

1,132

NO

99

6,87

1,70

4,76

NO

0,605

NO

0,855

NO

5,87

4,85

3,175

NO

1,468

NO

2,518

NO

50

5,51

2,96

5,972

NO

1,096

NO

1,602

NO

99

5,60

1,38

16,744

NO

0,802

NO

1,114

NO

7,28

3,58

2,109

NO

1,036

NO

1,486

NO

50

7,23

3,33

2,358

NO

1,162

NO

1,731

NO

99

7,20

3,10

2,678

NO

1,313

NO

2,080

NO

5,88

2,89

3,150

NO

1,480

NO

2,557

NO

50

5,86

2,70

3,693

NO

1,676

NO

3,309

NO

99

5,86

2,52

4,487

NO

1,922

NO

4,744

NO

TRAMO O ELEMENTO PROTEGIDO

Elemento

Transformador GSU

Transformador T93-261

Transformador T16-260

SUBESTACIN

Carhuaquero

Chiclayo Oeste

Eten 220 kV

Chiclayo Oeste 220 kV

Chiclayo Oeste 220 kV

PROTECCIN

REL670
REL670

Siemens 7SA612
Siemens 7SA522

T60T

RET670

7UT633

FUNCIN DE PROTECCIN

67N/50N

67N

51/51N/50/50N

51/51N/50/50N

51/51N/50/50N

Tipo de
falla

Impedancia
de falla

% de
lnea

[]
0
Lnea Reque - Guadalupe 1
220 kV

1
10

0
Lnea Reque - Chiclayo
Oeste 1 220 kV

1
10

0
Lnea Reque - Eten 220 kV

1
10

Lnea La Carhuaquero- Chiclayo Oeste 220 kV

Valor de Cortocircuito en
el punto Falla

t - Ikss

t - 3Io

(Ik'') [kA]

(3I0) [kA]

[s]

[s]

[s]

[s]

[s]

[s]

7,13

6,52

0,805

NO

0,658

0,952

0,581

1,063

50

4,61

2,45

1,337

NO

1,453

1,116

0,865

2,432

99

5,58

0,83

2,096

NO

1,831

1,379

1,184

8,329

5,79

5,29

0,896

NO

0,724

0,952

0,634

1,24

50

4,07

2,16

1,484

NO

1,450

1,174

0,934

3,02

99

4,79

0,71

2,592

NO

1,776

1,487

1,351

NO

7,26

6,00

0,794

NO

0,647

0,952

0,574

1,042

50

6,70

3,60

0,739

NO

0,745

0,952

0,541

0,944

99

6,87

1,70

0,674

NO

0,790

0,952

0,500

0,834

5,87

4,85

0,884

NO

0,714

0,952

0,627

1,216

50

5,51

2,96

0,810

NO

0,812

0,952

0,584

1,072

99

5,60

1,38

0,736

NO

0,865

1,003

0,539

0,937

7,28

3,58

0,796

NO

0,645

0,952

0,575

1,045

50

7,23

3,33

0,824

NO

0,627

0,952

0,592

1,098

99

7,20

3,10

0,855

NO

0,611

0,952

0,610

1,158

5,88

2,89

0,886

NO

0,711

0,952

0,628

1,220

50

5,86

2,70

0,919

NO

0,690

0,952

0,647

1,288

99

5,86

2,52

0,955

NO

0,669

0,952

0,667

1,367

Elemento

TRAMO O ELEMENTO PROTEGIDO

Transformador T14-260

Transformador T92-261

Transformador T13-261

Transformador T17-261

SUBESTACIN

Chiclayo Oeste 220 kV

Guadalupe 220 kV

Guadalupe 220 kV

Guadalupe 220 kV

PROTECCIN

7UT633

RET670

RET670

7UT633

FUNCIN DE PROTECCIN

51/51N/50/50N

51/51/50/50N

51/51/50/50N

51/51/50/50N

Impedancia de falla

% de
lnea

[]
0
Lnea Reque - Guadalupe 1
220 kV

1
10

0
Lnea Reque - Chiclayo Oeste 1
220 kV

1
10

0
Lnea Reque - Eten 220 kV

1
10

Valor de Cortocircuito
en el punto Falla
(Ik'') [kA]

(3I0) [kA]

[s]

[s]

[s]

[s]

7,13

6,52

1,063

0,76

1,426

1,45

50

4,61

2,45

2,432

0,549

0,988

99

5,58

0,83

8,329

0,407

0,713

0,719

5,79

5,29

1,24

0,892

1,718

1,752

50

4,07

2,16

3,02

0,586

1,064

1,077

99

4,79

0,71

NO

0,432

0,762

0,768

7,26

6,00

1,042

0,770

1,449

1,473

50

6,70

3,60

0,944

0,911

1,762

1,798

99

6,87

1,70

0,834

1,027

2,035

2,083

5,87

4,85

1,216

0,909

1,759

1,794

50

5,51

2,96

1,072

1,093

2,195

2,250

99

5,60

1,38

0,937

1,278

2,672

2,754

7,28

3,58

1,045

0,768

1,444

1,468

50

7,23

3,33

1,098

0,808

1,530

1,557

99

7,20

3,10

1,158

0,852

1,629

1,659

5,88

2,89

1,220

0,907

1,753

1,788

50

5,86

2,70

1,288

0,958

1,872

1,913

99

5,86

2,52

1,367

1,018

2,013

2,059

Rev. A

COORDINACIN PROTECCIONES
ANEXO III

RFE-1-YE_-EEC-IDO-001

Pg/Page 256 de/of


288

ANEXO III:

ESTUDIO DE PROTECCIONES BLACK START

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

PLANTA DE RESERVA FRA


DE GENERACIN DE ETEN S.A

PROYECTO

RESERVA FRA ETEN


CONTRATISTA

UTE RESERVA FRA ETEN

TTULO

Protection Relay Settings


N DE DOCUMENTO PROYECTO

RFE-1-MKA-EEC-WRT-001
Wrtsil doc id: DBAC858439 - | Original doc id:
REV

00

FECHA

21/02/2014

EDITADO PARA

Daniel Byskata

Jukka Salonsaari

Thomas Lnngrn

REALIZADO

REVISADO

APROBADO

Este documento contiene informacin privada y no puede ser duplicado, modificado o divulgado a terceros sin el consentimiento
escrito de COBRA. La nica copia controlada de este documento est en el Sistema Informtico de Gestin Documental de COBRA.

Wrtsil Finland Oy

Protection Relay Settings


Rev. 00

RFE-1-MKA-EEC-WRT-001

CONTROL DE MODIFICACIONES
Revisin
00

Fecha

Modificaciones

21/02/2014

For review

Este documento contiene informacin privada y no puede ser duplicado, modificado o divulgado a terceros sin el consentimiento
escrito de COBRA. La nica copia controlada de este documento est en el Sistema Informtico de Gestin Documental de COBRA.

Sheets:
Created By:
Approved by:
DocID:
Revision:
Status:
CustomerID:

List

Power Plants

Title:
Description:
Project:
Doc Classification:

Protection Relay Settings


MV System
P/13053 Reserva Fria Eten
Confidential

1
Daniel Byskata / 05.12.2013
Thomas Lnngrn / 21.02.2014

DBAC858439
Approved

RFE-1-MKA-EEC-WRT-001

W20V34DF GENERATOR RELAY SETTINGS


Generator rating
Voltage
Frequency
Earth fault current

10550
6600
60
5

kVA
V
Hz
A

Engine rating
Phase CT primary Amperes
PT primary voltage
Cable CT primary Ampere

VAMP 210
Primary / p.u values

8630
1000
6600
50

kW
A
V
A

Curve
type

ANSI

Symbol

Setting

Time setting

51
50

I>
I>>

1,12 x In
2,5 x In

1034 A
2307 A

1.03 p.u
2.31 p.u

k
t

0.2
0.6 s

59

U>
U>>
U>>>

1,05 x Un
1,12 x Un
1,4 x Un

6930 V
7392 V
9240 V

1.05 p.u
1.12 p.u
1.4 p.u

t
t
t

30.0 s
4.0 s
2.0 s

Alarm
Trip
Trip

27

U<
U<<

0,95 x Un
0,88 x Un

6270 V
5808 V

0.95 p.u
0.88 p.u

t
t

30.0 s
20.0 s

Alarm
Trip

32

P<

-4% x Pn

-345 kW

-0.03 p.u

2.0 s

Trip

40

Q1<
Q2<

-30% x Sn
-30% x Sn

-3165 kVAr
-3165 kVAr

-0.28 p.u
-0.28 p.u

2.0 s

Trip

46

I2(k1)

20

Trip

I2(k2)

0.08
Trip

Alarm
Trip
Alarm
Trip

Trip

49

k)

1,06 x In

978 A
60 min

81H
81H
81L
81L

f>
f>>
f<
f<<

1,02 x fn
1,1 x fn
0,98 x fn
0,95 x fn

61.2
66
58.8
57

67N

Io>
'
Uo>

4%
10%

2A

51N
50N

Io>
Io>>

4%
6%

2A
3A

0.04 p.u
0.06 p.u

t
t

1s
0.6 s

59N

Uo>
Uo>>

10%
20%

381 V
762 V

0.1 p.u
0.2 p.u

t
t

2s
1.2 s

0.98 p.u

Hz
Hz
Hz
Hz

0.04 p.u

t
t
t
t

30
4
30
4

0.3 s

Rev

IEC NI Trip
DT
Trip

s
s
s
s

DT
DT

Trip
Trip

Trip
Trip

Trip

VAMP 265
87

DocID: DBAC858439 Status: Approved


CustomerID: RFE-1-MKA-EEC-WRT-001

DI>
Slope1
Ibias
Slope2
Id>2.harm block
DI>>

25
25
3
100
15
5

%
%
%
%

(on)

Document Classification:
Confidential

Trip

Sheet name: Sheet1


Page: 1/2

##

AUXILIARY TRANSFORMER FEEDER RELAY SETTINGS 1BBA76GS002 / BAA901


Operating voltage
Rated frequency
Aux transformer rating

6600 V
60 Hz
500 kVA

Busbar PT Primary
6600 V
voltage
Phase CT primary Amperes
Cable CT primary Amperes

50 A
50 A

VAMP 230
ANSI

Symbol

Setting

51 I>
50 I>>

1,2 x In
2,5 x In

51N Io>
50N Io>>

4%
6%

59 U>
27 U<
59N Uo>
Uo>>
81H f>
81L f<

Primary / p.u values

Time delay

Rev

52 A
109 A

1.05 p.u
2.19 p.u

k
t

0.1
0.2 s

IEC NI Trip
DT
Trip

2A
3A

0.04 p.u
0.06 p.u

t
t

0.8 s
0.1 s

DT
DT

Trip
Trip

1,12 x Un
0,8 x Un

7392 V
5280 V

1.12 p.u
0.8 p.u

t
t

3s
10 s

Trip
Trip

10%
20%

381 V
762 V

0.1 p.u
0.2 p.u

t
t

2.5 s
1.5 s

Trip
Trip

1.1 p.u
0.95 p.u

t
t

3.0 s
3.0 s

Trip
Trip

1,1 x Fn
0,95 x Fn

66 Hz
57 Hz

OUTGOING FEEDER RELAY SETTINGS 1BBA76GS003 / BAO901


Generator rated current
No of DG-sets installed
% of total ouput on this feeder

923 A
1 pcs
100 %

Phase CT primary Amperes


Cable CT primary Ampere

VAMP 50
ANSI

Symbol

Setting

51
50

I>
I>>

1,1 x In
2,5 x In

51N
50N

Io>
Io>>

4%
6%

DocID: DBAC858439 Status: Approved


CustomerID: RFE-1-MKA-EEC-WRT-001

Primary / p.u values

Time delay

1250 A
50 A

Curve
Type

Rev

1015 A
2308 A

0.81 p.u
1.85 p.u

k
t

0.1
0.4 s

IEC NI Trip
DT
Trip

2A
3A

0.04 p.u
0.06 p.u

t
t

0.8 s
0.1 s

DT
DT

Document Classification:
Confidential

Trip
Trip

Sheet name: Sheet1


Page: 2/2

Amps X 10 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

300

1K

500

1K

3K

5K

10K
1K

T60_TA - P
GE Multilin
T60
CT Ratio 1000:5
IEC - Curve C
Pickup = 0,479 (0,01 - 30 xCT Sec)
Time Dial = 0,23
3x = 2,3 s, 5x = 0,767 s, 8x = 0,292 s
Inst = 4 (0,01 - 30 xCT Sec)
Time Delay = 0,2 s

500

1BFT76
FLA

300

1BBT51
FLA
BLACK_START - P
OC1

100

GE Multilin
F650
CT Ratio 1500:5
IEC - Curve C
Pickup = 3,5 (0,05 - 160 Sec - 5A)
Time Dial = 0,25
3x = 2,5 s, 5x = 0,833 s, 8x = 0,317 s
Inst = 25 (0,05 - 160 Sec - 5A)
Time Delay = 0,17 s

50

30

10

500

1000/5
300

1BBT51
11,5 MVA
100

50

10/5

30

Cable_Acom
4-3/C 240

Cable_AcomBS - P

1500/5

10

1BBA51
5

Cable_Acom - P
3

Cable_XFR_BS - P

CB 1BBA51-B

500 kVA (Secondary) 4 %Z


Delta-Wye Solid Grd
0,179 s

,5

1BBT51

1BBA76

,1

,1

1BBT51
Inrush

1BFT76
Inrush

,05

BLACK_START - 3P

,03

T60_TA - 3P

,01
1

10

30

50

100

300

CB29

CB12

CB2
Open

Multiplier = 10 xFLA (9622,504 Amps)


Duration = 8 Cycles

Multiplier = 8 xFLA (4573,072 Amps)


Duration = 6 Cycles

,5

Cable_AcomBS
3-3/C 300

,3

0,03 s

,03

50/5

,5

11,5 MVA (Secondary) 13,5 %Z


Delta-Wye Resistor Grd

,05

BLACK_START

1500/5

1BFT76

,3

CB 1BBA10-A

Seconds

Seconds

Cable_BS - P
5

500

1K

3K

5K

,01
10K

Cable_XFR_BS
1-3/C 300

Cable_BS
3-3/C 300

1BFT76
500 kVA

Amps X 10 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


1,833

10

T60_TA

30

50

100

300

500

1K

3K

5K

Amps BUS GEN (Nom. kV=18, Plot Ref. kV=18)


Black Start
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

Date: 17-11-2014
Fault: Phase

10K

36,67K

ETAP Star 12.0.0C

1MKA76
8,44 MW

Amps 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

300

500

1K

3K

5K

10K

1K

1K

500

500

1000/5
300

300

T60_TA - G

GE Multilin
T60
CT Ratio 10:5
IEC - Curve B
Pickup = 0,3 (0,01 - 30 xCT Sec)
Time Dial = 1
3x = 6,75 s, 5x = 3,38 s, 8x = 1,93 s
Inst = 0,5 (0,01 - 30 xCT Sec)
Time Delay = 5 s

100

50

30

T60_TA

1BBT51
11,5 MVA
100

50

10/5

30

Cable_Acom
4-3/C 240

10

10

1500/5

BLACK_START - SG
OC1
GE Multilin
F650
CT Ratio 50:5
Definite Time
Pickup = 0,2 (0,005 - 16 Sec - 5A)
Time Dial = 0,8
3x = 0,8 s, 5x = 0,8 s, 8x = 0,8 s
Inst = 0,3 (0,005 - 16 Sec - 5A)
Time Delay = 0,1 s

,5

,3

CB 1BBA10-A

Seconds

Seconds

1BBA51

CB 1BBA51-B

BLACK_START

1500/5

50/5

4,9 s

Cable_AcomBS
3-3/C 300

,5

,3

1BBA76

,1

,1

CB29

CB12

CB2
Open

,05

,05

,03

,03

,01
5K

,01
10K

10K

20K

,5

10

30

50

100

300

500

1K

3K

Cable_XFR_BS
1-3/C 300

Cable_BS
3-3/C 300

1BFT76
500 kVA

Amps 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


1

10

30

50

100

300

500

1K

3K

Amps (Plot Ref. kV=3,3)

ETAP Star 12.0.0C

Black Start
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

5K

Date: 17-11-2014
Fault: Ground

1MKA76
8,44 MW

Rev. A

COORDINACIN PROTECCIONES
ANEXO IV

RFE-1-YE_-EEC-IDO-001

Pg/Page 261 de/of


288

ANEXO IV:

LISTADO AJUSTE DE PROTECCIONES ELCTRICAS DEL


SISTEMA DE MEDIA TENSIN

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

n/a

ESTADO

n/a

Edicin Inicial

SERVICIO:

IDOM Typ:

1MKC20

1BPT10

1BFT53

1BFT51

1MBU11AP001-M01

Transformador de Excitacin

Transformador de Aislamiento (LCI)

Transformador de Distribucin MT/BT

Transformador de Distribucin MT/BT

Motor 88WN-1 (Water Injection)


In=38A; Vn=4000V; I_arrq=247A (VALORES
ESTIMADOS)

1BBA51GH002

1BBA51GH003

1BBA51GH004

1BBA51GH005

1BBA51GH006

1BBA51GH007

6600

6600

6600

6600

6600

6600

8439,00 10549,00

224
(Motor)

1500,00

5459,00

3500,00

3500,00

600
(Trafo)

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

1MBU21AP001-M01

Motor 88WN-2 (Water Injection)


In=38A; Vn=4000V; I_arrq=247A (VALORES
ESTIMADOS)
Transformador 600 KVA
6,6/4,16kV; Dy1; 6%

1BBA51GH008

6600

224
(Motor)

600
(Trafo)

0,85

0,90

0,90

0,90

0,90

A
A
A
A

131,26

Inrush
ver curvas

Phase CT primary
Phase CT secondary
GE Multilin 350
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

500
5 Pickup level
50 Time Delay
5

0,05-20,00
0,00-300,00

476,75

Inrush
ver curvas

Phase CT primary
Phase CT secondary
GE Multilin 350
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

800
5 Pickup level
50 Time Delay
5

306,17

Inrush
ver curvas

Phase CT primary
Phase CT secondary
GE Multilin 350
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

500
5 Pickup level
50 Time Delay
5

306,17

Inrush
ver curvas

Phase CT primary
Phase CT secondary
GE Multilin 350
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

500
5 Pickup level
50 Time Delay
5

23,95 A @
6,6kV
(Motor)
(estimado)

155,7 A @
6,6kV
(Motor)
(estimado)

52,49 A
(Trafo)

Inrush Trafo
ver curvas

23,95 A @
6,6kV
(Motor)
(estimado)

155,7 A @
6,6kV
(Motor)
(estimado)

52,49 A
(Trafo)

Inrush Trafo
ver curvas

FLA Motor
Enable Two Speed
Low Speed Switch
GE Multilin 339

GE Multilin 339

A
-

Phase CT primary
Phase CT secondary
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

FLA Motor
Enable Two Speed
Low Speed Switch

A
-

Phase CT primary
Phase CT secondary
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

Input type
Pickup level
Trip time
Reset time

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

A
s
s

0,00-900,00
INST-LIN
DIS-ENA

pu
s

pu
s

Pickup level
6 Curve
0,12 TDM
Reset type

0,04-20,00

0,05-20,00
0,00-300,00

pu
s

Pickup level
11 Curve
0,15 TDM
Reset type

0,04-20,00

0,05-20,00
0,00-300,00

0,04-20,00

pu
s

Pickup level
11 Curve
0,15 TDM
Reset type

0,05-20,00
0,00-300,00

1,00-20,00
0,00-60,00

xCT
s

1,00-20,00
0,00-60,00

xCT
s

[Mech Jam]
7 Mech Jam PKP
0,03 Mech Jam Delay

[Mech Jam]
7 Mech Jam PKP
0,03 Mech Jam Delay

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

1,01-4,50
0,00-30,00

1,01-4,50
0,00-30,00

Valor ajuste

Valor ajuste

Funcin 50SG

PHAS-RMS
0,005160,000
0,00-900,00
0,00-900,00

A
s
s

PHAS
0,3
0,1
0,00

pu
-

0,3
IEC - CURVE C Pickup level
1,2 Time Delay
INST

0,005-3,000
0,00-300,00

pu
s

0,06
0,08

pu
-

0,6
IEC - CURVE C Pickup level
0,8 Time Delay
INST

0,005-3,000
0,00-300,00

pu
s

0,06
0,08

pu
-

0,75
IEC - CURVE C Pickup level
0,5 Time Delay
INST

0,005-3,000
0,00-300,00

pu
s

0,06
0,08

pu
-

0,75
IEC - CURVE C Pickup level
0,5 Time Delay
INST

0,005-3,000
0,00-300,00

pu
s

0,06
0,08

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

A
s
-

xFLA
s

xFLA
s

PHAS
3,5
IEC - CURVE C
0,25
INST
DIS

3,00
5,00

3,00
5,00

Alarm Func
Alarm PKP
Alarm on
run
Alarm on
strt
Trip Func
Trip PKP
Trip on run
Alarm Func
Alarm PKP
Alarm on
run
Alarm on
strt
Trip Func
Trip PKP
Trip on run

Unidades

Input type
Pickup level
Trip time
Rest time

Unidades

Rango
PHAS-RMS
0,05-160,00

0,04-20,00

24
Disabl
Off

[Short-Circuit]
S/C PKP
100
S/C Delay
5
50
5

Input type
Pickup level
Curve shape
Time dial
Reset type
Voltage restraint

Pickup level
6 Curve
0,12 TDM
Reset type

24
Disabl
Off

[Short-Circuit]
S/C PKP
100
S/C Delay
5
50
5

PHAS
25
0,17
0,00

Parmetro

Valor ajuste

Funcin 51P

Unidades

Rango

Inrush
ver curvas

Phase CT primary
Phase CT secondary
GE Multilin F650
Sen. Ground CT prim
Sen. Ground CT secon

922,80

1500
5
50
5

Parmetro

Valor ajuste

Unidades

Parmetro

Rele de Proteccin

I de arranque
/ I nominal

Intensidad nominal
[A]

Factor de potencia
(Cos )

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta
Acometida desde Generador Auxiliar

[kVA]

Funcin 50P

Rango

1MKA76

[kW]

Ajustes generales

Parmetro

COD

REVISIN

Potencia nominal

Edita:

Cliente:

COORDINACIN
COORDINACIN PROTECCIONES
PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a
n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a
n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

SERVICIO:

IDOM Typ:

1MKA76

Acometida desde Generador Auxiliar

1BBA51GH002

6600

Input type
PHAS-RMS
Pickup level 0,05-160,00
Curve shape
Time dial
0,00-900,00
Reset type
INST-LIN

A
s
-

PHAS
0,2
DT 0,8
INST

N/A -

Dead bus voltage level


Live bus voltage level
Dead line voltage level
Live line voltage level
Max voltage difference
N/A Max angle difference
Max frequency slip
Breaker closing time
DL-DB function
LL-DB function
DL-LB function

Valor ajuste

Unidades

Rango

Parmetro

Valor ajuste

Funcin 25

Unidades

Rango

Parmetro

Valor ajuste

Funcin 59P

Unidades

Rango

Parmetro

Valor ajuste

Funcin 27P

Unidades

Rango

Parmetro

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Funcin 51SG

0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
2.00 : 300.00
2.0 : 80.00
10 : 5000
0.01 : 600.00
DIS-ENA
DIS-ENA
DIS-ENA

V
V
V
V
V
V
mHz
s
----

11
55
11
55
8
12
0,2
10
ENA
ENA
DIS

NOTA: en este caso "Bus" = linea desde 1MKA76, y "LINE" = barras


1BBA51. Este interruptor no puede cerrar contra generador en tensin

1MKC20

1BPT10

1BFT53

1BFT51

1MBU11AP001-M01

Transformador de Excitacin

Transformador de Aislamiento (LCI)

Transformador de Distribucin MT/BT

Transformador de Distribucin MT/BT

Motor 88WN-1 (Water Injection)


In=38A; Vn=4000V; I_arrq=247A (VALORES
ESTIMADOS)

0,005-3,000

6600

Pickup level
Curve
TDM
Reset type

0,005-3,000

6600

Pickup level
Curve
TDM
Reset type

0,005-3,000

6600

Pickup level
Curve
TDM
Reset type

0,005-3,000

1BBA51GH006

6600

Pickup level
Curve
TDM
Reset type

1BBA51GH007

6600

1BBA51GH008

6600

1BBA51GH003

1BBA51GH004

1BBA51GH005

pu
-

0,04
DT
7
INST

N/A -

N/A -

N/A

pu
-

0,04
DT
7
INST

N/A -

N/A -

N/A

pu
-

0,04
DT
7
INST

N/A -

N/A -

N/A

0,50-20,00
INST-LIN

pu
-

0,04
DT
7
INST

N/A -

N/A -

N/A

N/A -

N/A -

N/A -

N/A

N/A -

N/A -

N/A -

N/A

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

1MBU21AP001-M01

Motor 88WN-2 (Water Injection)


In=38A; Vn=4000V; I_arrq=247A (VALORES
ESTIMADOS)
Transformador 600 KVA
6,6/4,16kV; Dy1; 6%

ESTADO
Edicin Inicial

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

n/a

ESTADO

n/a

Edicin Inicial

SERVICIO:

IDOM Typ:

Motor 88AK-1 (Atomizing Air System)


In=61A; Vn=4000V; I_arrq=403A
A

1MBT20AN001-M01

1BBA51GH009

6600

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

1MBT30AN001-M01

1BBA51GH010

6600

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

Medida de Tensin

375
(Motor)

38,44 A @
6,6kV
(Motor)

600
(Trafo)

1BBA51GH011

6600

375
(Motor)

38,44 A @
6,6kV
(Motor)

600
(Trafo)

254 A @
6,6kV
(Motor)

FLA Motor
Enable Two Speed
Low Speed Switch
GE Multilin 339

Inrush Trafo
ver curvas

254 A @
6,6kV
(Motor)

52,49 A
(Trafo)

Inrush Trafo
ver curvas

GE Multilin 339

GE Multilin 350

A
-

Phase CT primary
Phase CT secondary
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

FLA Motor
Enable Two Speed
Low Speed Switch

A
-

Phase CT primary
Phase CT secondary
Sen. Ground CT prim
Sen. Ground CT secon

A
A
A
A

Phase VT primary
Phase VT secondary

V
V

38,5
Disabl
Off

[Short-Circuit]
S/C PKP
100
S/C Delay
5
50
5

1,00-20,00
0,00-60,00

xCT
s

38,5
Disabl
Off

[Short-Circuit]
S/C PKP
100
S/C Delay
5
50
5

7200:3
120:3

1,00-20,00
0,00-60,00

xCT
s

[Mech Jam]
7 Mech Jam PKP
0,03 Mech Jam Delay

[Mech Jam]
7 Mech Jam PKP
0,03 Mech Jam Delay

N/A -

1,01-4,50
0,00-30,00

xFLA
s

1,01-4,50
0,00-30,00

xFLA
s

3,00
15,00

3,00
15,00

Alarm Func
Alarm PKP
Alarm on
run
Alarm on
strt
Trip Func
Trip PKP
Trip on run
Alarm Func
Alarm PKP
Alarm on
run
Alarm on
strt
Trip Func
Trip PKP
Trip on run

N/A -

Valor ajuste

Unidades

Rango

Parmetro

Valor ajuste

Funcin 50SG

Unidades

Rango

Parmetro

Unidades

Valor ajuste

Funcin 51P

Rango

Parmetro

Funcin 50P

Valor ajuste

Unidades

Parmetro

Rele de Proteccin

I de arranque
/ I nominal

Intensidad nominal
[A]

[kVA]

52,49 A
(Trafo)

Motor 88AK-2 (Atomizing Air System)


In=61A; Vn=4000V; I_arrq=403A
A

[kW]

Ajustes generales

Factor de potencia
(Cos )

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Potencia nominal

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

N/A

Edita:

Cliente:

COORDINACIN
COORDINACIN PROTECCIONES
PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a
n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a
n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

SERVICIO:

IDOM Typ:

Funcin 59P

Funcin 25

N/A -

N/A -

N/A -

N/A

1BBA51GH010

6600

N/A -

N/A -

N/A -

N/A

Pickup level
Curve
N/A Time dial
UV Phases
Min Voltage

0,00-1,25
DT-IT
0,1-600,0
ANY-TWOALL
0,00-1,25

pu
s
pu

0,00-1,25
0,1-600,0
ANY-TWOALL

pu
s
-

1,00
2ANY

N/A

Unidades

Rango

Parmetro

Unidades

Rango

Parmetro

Unidades

Rango

Parmetro

Unidades

Rango

Valor ajuste

Valor ajuste

Valor ajuste

6600

Valor ajuste

1BBA51GH009

Parmetro

Tensin nominal [V]

Funcin 27P

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Funcin 51SG

Motor 88AK-1 (Atomizing Air System)


In=61A; Vn=4000V; I_arrq=403A
A

1MBT20AN001-M01
Transformador 600 KVA
6,6/4,16kV; Dy1; 6%

Motor 88AK-2 (Atomizing Air System)


In=61A; Vn=4000V; I_arrq=403A
A

1MBT30AN001-M01
Transformador 600 KVA
6,6/4,16kV; Dy1; 6%

Medida de Tensin

1BBA51GH011

6600

0,82
DT Pickup level
0,5 Time delay
ANY OV Phases
0,2

ESTADO
Edicin Inicial

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:

RESERVA FRIA ETEN

LOCALIZACIN: Chiclayo - Lambayeque - PER


N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

ESTADO
Edicin Inicial

SERVICIO:

IDOM Typ:

1MKA77

1MKC20

1BPT10

1BFT53

1BFT51

1MBU11AP001-M01

Acometida desde Generador Auxiliar

Transformador de Excitacin

Transformador de Aislamiento (LCI)

Transformador de Distribucin MT/BT

Transformador de Distribucin MT/BT

Motor 88WN-1 (Water Injection)


In=38A; Vn=4000V; I_arrq=247A (VALORES
ESTIMADOS)

1BBA51GH002

1BBA51GH003

1BBA51GH004

1BBA51GH005

1BBA51GH006

1BBA51GH007

6600

6600

6600

6600

6600

6600

8439,00

224
(Motor)

10549,00

1500,00

5459,00

3500,00

3500,00

600
(Trafo)

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

1MBU21AP001-M01

Motor 88WN-2 (Water Injection)


In=38A; Vn=4000V; I_arrq=247A (VALORES
ESTIMADOS)

1BBA51GH008

6600

1BBA51GH009
Transformador 600 KVA
6,6/4,16kV; Dy1; 6%

0,90

0,90

0,90

224
(Motor)

600
(Trafo)

6600

375
(Motor)

600
(Trafo)

PHAS-RMS
0,005-160,000
0,00-900,00
0,00-900,00

Input type
- PHAS
Pickup level
A
0,3
Curve shape
s
0,1
Time dial
s
0,00
Reset type

PHAS-RMS
0,05-160,00

Valor ajuste

Unidades

Rango

Parmetro

Valor ajuste

Unidades

Funcin 59P

Rango

Parmetro

Valor ajuste

Funcin 27P

Unidades

Rango

Parmetro

Valor ajuste

Unidades

Rango

Parmetro

Rele de Proteccin

Input type
Inrush
Pickup level
GE Multilin F650
ver curvas
Trip time
Rest time

Funcin 51SG

A
s
-

PHAS
0,2
DT 0,8
INST

N/A -

N/A

pu
-

0,04
DT
7
INST

N/A -

N/A

pu
-

0,04
DT
7
INST

N/A -

N/A

pu
-

0,04
DT
7
INST

N/A -

N/A

0,50-20,00
INST-LIN

pu
-

0,04
DT
7
INST

N/A -

N/A

0,00-900,00
INST-LIN

131,26

Pickup level
GE Multilin 350
Time Delay

0,005-3,000
0,00-300,00

pu
s

Pickup level
0,06 Curve
0,08 TDM
Reset type

0,005-3,000

Inrush
ver curvas

476,75

Pickup level
GE Multilin 350
Time Delay

0,005-3,000
0,00-300,00

pu
s

Pickup level
0,06 Curve
0,08 TDM
Reset type

0,005-3,000

Inrush
ver curvas

306,17

Pickup level
GE Multilin 350
Time Delay

0,005-3,000
0,00-300,00

pu
s

Pickup level
0,06 Curve
0,08 TDM
Reset type

0,005-3,000

Inrush
ver curvas

306,17

Pickup level
GE Multilin 350
Time Delay

0,005-3,000
0,00-300,00

pu
s

Pickup level
0,06 Curve
0,08 TDM
Reset type

0,005-3,000

Inrush
ver curvas

Alarm Func
Alarm PKP
Alarm on run
Alarm on strt
GE Multilin 339
Trip Func
Trip PKP
Inrush Trafo
Trip on run
ver curvas
Trip on strt

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

N/A -

N/A -

N/A

Alarm Func
Alarm PKP
Alarm on run
Alarm on strt
GE Multilin 339
Trip Func
Trip PKP
Inrush Trafo
Trip on run
ver curvas
Trip on strt

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

N/A -

N/A -

N/A

Alarm Func
Alarm PKP
Alarm on run
Alarm on strt
GE Multilin 339
Trip Func
Inrush Trafo
Trip PKP
ver curvas
Trip on run
Trip on strt

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

N/A -

N/A -

N/A

23,95 A @
6,6kV
(Motor)
(estimado)

23,95 A @
6,6kV
(Motor)
(estimado)
52,49 A
(Trafo)

Motor 88AK-1 (Atomizing Air System)


In=61A; Vn=4000V; I_arrq=403A
1MBT20AN001-M01

0,90

922,80

52,49 A
(Trafo)

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

0,85

I de arranque
/ I nominal

[kVA]

Intensidad nominal
[A]

[kW]

Funcin 50SG

Factor de potencia
(Cos )

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Potencia nominal

38,44 A @
6,6kV
(Motor)
52,49 A
(Trafo)

155,7 A @
6,6kV
(Motor)
(estimado)

155,7 A @
6,6kV
(Motor)
(estimado)

254 A @
6,6kV
(Motor)

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

0,50-20,00
INST-LIN

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:

RESERVA FRIA ETEN

LOCALIZACIN: Chiclayo - Lambayeque - PER


N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

ESTADO
Edicin Inicial

SERVICIO:

IDOM Typ:

Motor 88AK-2 (Atomizing Air System)


In=61A; Vn=4000V; I_arrq=403A
A

1MBT30AN001-M01

1BBA51GH010

6600

Transformador 600 KVA


6,6/4,16kV; Dy1; 6%

Medida de Tensin

375
(Motor)

38,44 A @
6,6kV
(Motor)

600
(Trafo)

52,49 A
(Trafo)

1BBA51GH011

6600

Alarm Func
Alarm PKP
Alarm on run
Alarm on strt
GE Multilin 339
Trip Func
Inrush Trafo
Trip PKP
ver curvas
Trip on run
Trip on strt
254 A @
6,6kV
(Motor)

GE Multilin 350 -

Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00
Dis-Enable
0,03-1,00
0,00-60,00
0,00-60,00

pu
s
s
pu
s
s

Disab
Enab
0,06
0,08
0,5

N/A -

N/A -

Pickup level
Curve
N/A Time dial
UV Phases
Min Voltage

0,00-1,25 pu
DT-IT
0,1-600,0
s
ANY-TWO-ALL
0,00-1,25 pu

N/A -

0,82
DT Pickup level
0,5 Time delay
ANY OV Phases
0,2

Valor ajuste

Unidades

Rango

Parmetro

Valor ajuste

Unidades

Funcin 59P

Rango

Parmetro

Valor ajuste

Funcin 27P

Unidades

Rango

Parmetro

Unidades

Valor ajuste

Funcin 51SG

Rango

Parmetro

Rele de Proteccin

I de arranque
/ I nominal

[kVA]

Intensidad nominal
[A]

[kW]

Funcin 50SG

Factor de potencia
(Cos )

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Potencia nominal

N/A

0,00-1,25 pu
0,1-600,0
s
ANY-TWO-ALL
-

1,00
2
ANY

Rev. A

CLCULOS ELCTRICOS
ANEXO V

RFE-1-YE__-ECE-IDO-001

Pg/Page 269 de/of


288

ANEXO V:

CURVAS DE SELECTIVIDAD TIEMPO-CORRIENTE DEL


SISTEMA DE MEDIA TENSIN

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Amps 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

300

500

1K

3K

5K

10K

1K

1K

500

500

300

300

T60_TA - G
GE Multilin
T60
CT Ratio 10:5
IEC - Curve B
Pickup = 0,3 (0,01 - 30 xCT Sec)
Time Dial = 1
3x = 6,75 s, 5x = 3,38 s, 8x = 1,93 s
Inst = 0,5 (0,01 - 30 xCT Sec)
Time Delay = 5 s

100

50

30

100

50

30

1500/5
1BBA51

10

T60_TA

CB 1BBA10-A
CB 1BBA51-B

10

CB 1BBA51-E

,5

,3

XFR_Distr - G
OC1

BLACK_START - SG
OC1

GE Multilin
350
CT Ratio 50:5
Definite Time
Pickup = 0,04 (0,005 - 3 xCT Sec)
Time Dial = 7
3x = 0,7 s, 5x = 0,7 s, 8x = 0,7 s
Inst = 0,06 (0,005 - 3 xCT Sec)
Time Delay = 0,08 s

GE Multilin
F650
CT Ratio 50:5
Definite Time
Pickup = 0,2 (0,005 - 16 Sec - 5A)
Time Dial = 0,8
3x = 0,8 s, 5x = 0,8 s, 8x = 0,8 s
Inst = 0,3 (0,005 - 16 Sec - 5A)
Time Delay = 0,1 s

,03

,03

,01
10

30

50

100

300

500

1K

Amps 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


Transf Distribucin
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

Date: 17-11-2014
Fault: Ground

3K

XFR_Distr

,3

,05

50/5

500/5
BLACK_START
50/5

,5

,05

Cable_1BFT53
2-3/C 185

,1

1500/5

,1

,5

Seconds

Seconds

5K

,01
10K

ETAP Star 12.0.0C

1BFT53
3500 kVA

Amps X 100 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

1K

500

1K

3K

5K

10K
1K

GE Multilin
T60
CT Ratio 1000:5
IEC - Curve C
Pickup = 0,479 (0,01 - 30 xCT Sec)
Time Dial = 0,23
3x = 2,3 s, 5x = 0,767 s, 8x = 0,292 s
Inst = 4 (0,01 - 30 xCT Sec)
Time Delay = 0,2 s

1BFT53
FLA

500

300

100

50

500

300

100

50

BLACK_START - P
OC1

30

30

GE Multilin
F650
CT Ratio 1500:5
IEC - Curve C
Pickup = 3,5 (0,05 - 160 Sec - 5A)
Time Dial = 0,25
3x = 2,5 s, 5x = 0,833 s, 8x = 0,317 s
Inst = 25 (0,05 - 160 Sec - 5A)
Time Delay = 0,17 s

10

1500/5
1BBA51

T60_TA

CB 1BBA10-A
CB 1BBA51-B

10

CB 1BBA51-E

Seconds

Seconds

300

T60_TA - P

1500/5

50/5

500/5
BLACK_START
50/5

XFR_Distr

1BFT53
1

3500 kVA (Secondary) 12 %Z


Delta-Wye Solid Grd

XFR_Distr - P
OC1
GE Multilin
350
CT Ratio 500:5
IEC - C
Pickup = 0,75 (0,04 - 20 xCT Sec)
Time Dial = 0,5
3x = 5 s, 5x = 1,67 s, 8x = 0,635 s
Inst = 11 (0,05 - 20 xCT Sec)
Time Delay = 0,15 s

,5

,3

,1

,5

,3

Cable_1BFT53 - P
,1

,05

,05

1BFT53
Inrush

,03

,03

XFR_Distr - 3P

Multiplier = 10 xFLA (40014,38 Amps)


Duration = 8 Cycles

T60_TA - 3P
BLACK_START - 3P

,01
,5

Cable_1BFT53
2-3/C 185

10

30

50

100

300

500

1K

Amps X 100 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


Transf Distribucin
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

Date: 17-11-2014
Fault: Phase

3K

5K

,01
10K

ETAP Star 12.0.0C

1BFT53
3500 kVA

Amps 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

1K

500

300

100

10

30

50

100

500

1K

3K

5K

10K
1K

GE Multilin
F650
CT Ratio 50:5
Definite Time
Pickup = 0,2 (0,005 - 16 Sec - 5A)
Time Dial = 0,8
3x = 0,8 s, 5x = 0,8 s, 8x = 0,8 s
Inst = 0,3 (0,005 - 16 Sec - 5A)
Time Delay = 0,1 s

500

300

100

Excitacin - G
OC1

50

50

GE Multilin
350
CT Ratio 50:5
Definite Time
Pickup = 0,04 (0,005 - 3 xCT Sec)
Time Dial = 7
3x = 0,7 s, 5x = 0,7 s, 8x = 0,7 s
Inst = 0,06 (0,005 - 3 xCT Sec)
Time Delay = 0,08 s

30

10

30

CB 1BBA51-B

XFR_Aislamiento - G
OC1
GE Multilin
350
CT Ratio 50:5
Definite Time
Pickup = 0,04 (0,005 - 3 xCT Sec)
Time Dial = 7
3x = 0,7 s, 5x = 0,7 s, 8x = 0,7 s
Inst = 0,06 (0,005 - 3 xCT Sec)
Time Delay = 0,08 s

,5

,3

50/5

1500/5

500/5
BLACK_START
50/5

,05

,05

,03

,03

10

30

50

100

300

500

1K

Amps 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


Excitacin & LCI
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

Date: 17-11-2014
Fault: Ground

3K

5K

XFR_Aislamiento

50/5

Cable_1MKC20
1-3/C 150

Cable_1BPT10
3-3/C 240

1BPT10
5450/2725/2725 kVA

,3

,1

,5

,1

,5

800/5

Excitacin

1MKC20
1500 kVA

,01

CB 1BBA10-D

CB 1BBA51-C

10

1BBA51

Seconds

Seconds

300

BLACK_START - SG
OC1

,01
10K

ETAP Star 12.0.0C

Amps X 100 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

1K

1BPT10
2725 kVA (Secondary) 2,25 %Z
Delta-Wye Open-Delta
Curve Shift = 1

500

300

1MKC20
FLA

1BPT10
FLA

100

300

500

1K

3K

5K

10K

BLACK_START - P
OC1

1K

GE Multilin
F650
CT Ratio 1500:5
IEC - Curve C
Pickup = 3,5 (0,05 - 160 Sec - 5A)
Time Dial = 0,25
3x = 2,5 s, 5x = 0,833 s, 8x = 0,317 s
Inst = 25 (0,05 - 160 Sec - 5A)
Time Delay = 0,17 s

500

300

100

50

50

Excitacin - P
OC1

30

GE Multilin
350
CT Ratio 500:5
IEC - C
Pickup = 0,3 (0,04 - 20 xCT Sec)
Time Dial = 1,2
3x = 12 s, 5x = 4 s, 8x = 1,52 s
Inst = 6 (0,05 - 20 xCT Sec)
Time Delay = 0,12 s

10

CB 1BBA51-B

GE Multilin
350
CT Ratio 800:5
IEC - C
Pickup = 0,6 (0,04 - 20 xCT Sec)
Time Dial = 0,8
3x = 8 s, 5x = 2,67 s, 8x = 1,02 s
Inst = 6 (0,05 - 20 xCT Sec)
Time Delay = 0,12 s

,5

,3

1MKC20
1

1500 kVA (Secondary) 6 %Z


Wye Open-Delta

0,37 s

Cable_1MKC20 - P
0,05 s

1MKC20
Inrush

1BPT10
Inrush

,05

,03

Multiplier = 10 xFLA (19245,01 Amps)


Duration = 8 Cycles

Multiplier = 10 xFLA (7563,844 Amps)


Duration = 8 Cycles

,03

XFR_Aislamiento - 3P

BLACK_START - 3P

Excitacin - 3P
,01
5

800/5

Excitacin

XFR_Aislamiento

50/5

Cable_1MKC20
1-3/C 150

Cable_1BPT10
3-3/C 240

10

30

50

100

300

500

1K

Amps X 100 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


Excitacin & LCI
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

Date: 17-11-2014
Fault: Phase

3K

5K

1BPT10
5450/2725/2725 kVA
1MKC20
1500 kVA

Cable_1BPT10 - P

,05

500/5
BLACK_START
50/5

,3

,1

50/5

1500/5

,5

,1

,5

CB 1BBA10-D

CB 1BBA51-C

10

XFR_Aislamiento - P
OC1
1

1BBA51

Seconds

Seconds

30

,01
10K

ETAP Star 12.0.0C

Amps X 10 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

300

500

1K

1K

3K

5K

10K
1K

Atomizing_Air - P

500

300

GE Multilin
339
CT Ratio 100:5
Inst = 7 (1 - 20 xCT Sec)
Time Delay = 0,03 s

Cable_88AK-1_XFR
Ampacity

88AK-1_XFR
FLA

Cable_88AK-1
Ampacity

500

300

Atomizing_Air - OL
100

Stall = 42 sec
50

88AK-1-Hot
30

100

GE Multilin
339
CT Ratio 100:5
Thermal Overload
Pickup = 1,1 (1,01 - 1,25 xFLA)
Curve Multiplier = 6

88AK-1-Cold

Stall = 27 sec

1BBA51

50

30

R
10

10

Atomizing_Air

88AK-1_XFR

600 kVA (Secondary) 6 %Z


Wye Open-Delta

Seconds

Seconds

Atomizing_Air - OL-J
GE Multilin
339
Jam
CT Ratio 100:5
Pickup = 3 (1,01 - 4,5 xFLA)
Time Delay = 15 s

Cable_88AK-1_XFR
1-3/C 70

Cable_88AK-1 - P
1

Atomizing_Air - OL-A

,5

,5

GE Multilin
339
CT Ratio 100:5
Start Protection
Accel Trip = 1 (1 - 1 xFLA)
Safe Stall Time Cold = 15

,3

88AK-1_XFR
600 kVA

,3

Cable_88AK-1_XFR - P

,1

,1

,05

Cable_88AK-1
1-3/C 70

,05

88AK-1_XFR
Inrush

,03

,03

Multiplier = 10 xFLA (832,717 Amps)


Duration = 8 Cycles
Atomizing_Air - 3P
,01
,5

10

30

50

100

300

500

1K

3K

5K

,01
10K

Amps X 10 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,825

10

30

50

100

300

500

1K

3K

Amps X 10 (Plot Ref. kV=4)

10K

16,5K

ETAP Star 12.0.0C

AA Motor
Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

5K

Date: 17-11-2014
Fault: Phase

88AK-1
375 kW

Amps X 10 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,5

10

30

50

100

300

500

1K

1K

3K

5K

10K
1K

Water_Injection - P

500

300

Cable_88WN-1
Ampacity

GE Multilin
339
CT Ratio 100:5
Inst = 7 (1 - 20 xCT Sec)
Time Delay = 0,03 s

Cable_88WN-1_XFR
Ampacity

88WN-1_XFR
FLA

500

300

Water_Injection - OL-A
GE Multilin
339
CT Ratio 100:5
Start Protection
Accel Trip = 1 (1 - 1 xFLA)
Safe Stall Time Cold = 6

100

50

88WN-1-Cold
Stall = 15 sec

30

100

50

1BBA51

30

88WN-1-Hot
Stall = 10 sec

R
10

Water_Injection

10

Water_Injection - OL
GE Multilin
339
CT Ratio 100:5
Thermal Overload
Pickup = 1,1 (1,01 - 1,25 xFLA)
Curve Multiplier = 2

Seconds

Seconds

Cable_88WN-1_XFR
1-3/C 70

Water_Injection - OL-J
GE Multilin
339
Jam
CT Ratio 100:5
Pickup = 3 (1,01 - 4,5 xFLA)
Time Delay = 5 s

,5

,3

88WN-1_XFR
600 kVA

,5

,3

88WN-1_XFR
600 kVA (Secondary) 6 %Z
Wye Open-Delta

,1

,05

,1

Cable_88WN-1 - P
Cable_88WN-1_XFR - P

88WN-1_XFR
Inrush

,03

,05

,03

Multiplier = 10 xFLA (832,717 Amps)


Duration = 8 Cycles

88WN-1
224 kW
Water_Injection - 3P

,01
,5

10

30

50

100

300

500

1K

3K

5K

,01
10K

Amps X 10 1BBA51 (Nom. kV=6,6, Plot Ref. kV=6,6)


,825

Cable_88WN-1
1-3/C 70

10

30

50

100

300

500

1K

3K

Amps X 10 (Plot Ref. kV=4)

10K

16,5K

ETAP Star 12.0.0C

Water Injection Motor


Project: Reserva Fra Eten
Location: Chiclayo - Lambayeque - PER
Engineer: IDOM

5K

Date: 17-11-2014
Fault: Phase

Rev. A

CLCULOS ELCTRICOS
ANEXO VI

RFE-1-YE__-ECE-IDO-001

Pg/Page 278 de/of


288

ANEXO VI:

LISTADO AJUSTES DE PROTECCIONES ELCTRICAS


SISTEMA DE BT

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

RESERVA F
Chiclayo - L

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

ESTADO
Edicin Inicial

SERVICIO:

IDOM Typ:

1BFT53

1BFA531BMA52

1BFA511BMA52

1BFT51

1XKA52

1BMA52 (27)

ACOMETIDA 1BFA53 DESDE TRANSFORMADOR


1BFT53. FUNCIONES 27/59 DE LA TENSIN
TRAFO.

ACOPLAMIENTO BARRAS 1BFA53 - 1BMA52.


FUNCIONES 27/59 DE LA TENSIN BARRAS
1BFA53

ACOPLAMIENTO BARRAS 1BMA52 - 1BFA51.


FUNCIONES 27/59 DE LA TENSIN BARRAS
1BFA51

ACOMETIDA 1BFA51 DESDE TRANSFORMADOR


1BFT51. FUNCIONES 27/59 DE LA TENSIN
TRAFO.

1BFA53GH220

1BMA52GH120

1BFA51GH120

1BFA51GH220

480

3500

1,00

480

1,00

480

480

REL TENSIN BARRA 1BMA52

480

1,00

3500

2123

2654

1,00

1,00

0,85

0,85

0,85

0,85

0,80

4210

5000

5000

5000

3192

0,50

0,50

0,50

0,50

0,50

1220 (BFA53)
1820 (BFA53+BMA52)
2795 (TODA BT)

600 (BMA52)
1575 (BMA52 + BFA51)

600 (BMA52)
1820 (BMA52 + BFA53)

975 (BFA51)
1575 (BFA51+BMA52)
2795 (TODA BT)

600 (EMERG)
1970 (BLACK START)

1350
2030
3160

680
1810

680
2030

1130
1810
3160

680
2205

1624
2442
3801

818
2177

818
2442

1359
2177
3801

818
2652

GE Multilin F650

Phase CT primary
Phase CT second.
Ground CT prim
Ground CT secon

A
A
A
A

Ph-Gd VT prim
Ph-Gd VT secon

V
V

Phase CT primary
Phase CT second.

A
A

Ph-Gd VT prim
Ph-Gd VT secon

V
V

Phase CT primary
Phase CT second.

A
A

Ph-Gd VT prim
Ph-Gd VT secon

V
V

Phase CT primary
Phase CT second.
Ground CT prim
Ground CT secon

A
A
A
A

GE Multilin F650

GE Multilin F650

GE Multilin F650

5000
Input type
5
Pickup level
Trip time
480/R3
Reset time
120/R3

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

A
s
s

A
s
s

23
0,25
0

Input type
Pickup level
Curve shape
Time dial
Reset type
Voltage restraint

PHAS-RMS
0,05-160,00

15
0,15
0

Input type
Pickup level
Curve shape
Time dial
Reset type
Voltage restraint

PHAS-RMS
0,05-160,00

PHAS-RMS
0,05-160,00

0,00-900,00
INST-LIN
DIS-ENA

0,00-900,00
INST-LIN
DIS-ENA

5000
Input type
5
Pickup level
Trip time
480/R3
Reset time
120/R3

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

A
s
s

15
0,15
0

Input type
Pickup level
Curve shape
Time dial
Reset type
Voltage restraint

5000
5
Input type
1250
Pickup level
5
Trip time
Reset time
480/R3
120/R3

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

A
s
s

23
0,25
0

Input type
Pickup level
Curve shape
Time dial
Reset type
Voltage restraint

PHAS-RMS
0,05-160,00

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

A
s
s

25
0,3
0

Input type
Pickup level
Curve shape
Time dial
Reset type
Voltage restraint

PHAS-RMS
0,05-160,00

V
V

Phase CT primary
Phase CT second.

A
A

Ph-Gd VT prim
Ph-Gd VT secon

V
V

4000
Input type
5
Pickup level
Trip time
480/R3
Reset time
120/R3

Ph-Gd VT prim
Ph-Gd VT secon

V
V

480/R3
120/R3

ANULADO

0,00-900,00
INST-LIN
DIS-ENA

0,00-900,00
INST-LIN
DIS-ENA

0,00-900,00
INST-LIN
DIS-ENA

A
s
-

5
IEC curve C
0,5
INST
DIS

Input type
Pickup level
Curve shape
Time dial
Reset type

PHAS-RMS
0,05-160,00

A
s
-

3,35
IEC- curve C
INST
DIS

Input type
Pickup level
Curve shape
Time dial
Reset type

PHAS-RMS
0,05-160,00

A
s
-

3,35
IEC- curve C
INST
DIS

Input type
Pickup level
Curve shape
Time dial
Reset type

PHAS-RMS
0,05-160,00

A
s
-

5
IEC curve C
0,5
0
DIS

Input type
Pickup level
Curve shape
Time dial
Reset type

PHAS-RMS
0,05-160,00

A
s
-

4,8
IEC curve C
0,5
Inst
DIS

Input type
Pickup level
Curve shape
Time dial
Reset type

PHAS-RMS
0,05-160,00

ANULADO

0,00-900,00
INST-LIN

0,00-900,00
INST-LIN

0,00-900,00
INST-LIN

0,00-900,00
INST-LIN

0,00-900,00
INST-LIN

Valor ajuste

Unidades

Rango

Parmetro

Valos ajuste

Funcin 51G

Unidades

Rango

Parmetro

Valos ajuste

Funcin 51

Unidades

Rango

Parmetro

5000
5
Input type
1250
Pickup level
5
Trip time
Reset time
480/R3
120/R3

Ph-Gd VT prim
Ph-Gd VT secon

GE Multilin F650

GE Multilin 350

Funcin 50

Valos ajuste

Unidades

Parmetro

Relevador

[kVA]

I de arranque
/ I nominal

[kW]

Ajustes generales

Intensidad
demandada
[A]

Factor de carga

Intensidad nominal
[A]

Factor de potencia
(Cos )

[kVA]

480

ACOMETIDA 1BMA52 DESDE GENERADOR DE


EMERGENCIA XKA52. FUNCIONES TENSIN DE LA 1BMA52GH330
ACOMETIDA.

1BMA52GH330

[kW]

Potencia demandada

Rendimiento
()

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Potencia nominal

A
s
-

15
IEEE E.I.
15
0

A
s
-

N/A

A
s
-

N/A

A
s
-

15
IEEE E.I.
15
0

A
s
-

N/A

ANULADO

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

ESTADO
Edicin Inicial

SERVICIO:

IDOM Typ:

1BFT53

1BFA531BMA52

1BFA511BMA52

1BFT51

1XKA52

1BMA52 (27)

ACOMETIDA 1BFA53 DESDE TRANSFORMADOR


1BFT53. FUNCIONES 27/59 DE LA TENSIN
TRAFO.

ACOPLAMIENTO BARRAS 1BFA53 - 1BMA52.


FUNCIONES 27/59 DE LA TENSIN BARRAS
1BFA53

ACOPLAMIENTO BARRAS 1BMA52 - 1BFA51.


FUNCIONES 27/59 DE LA TENSIN BARRAS
1BFA51

ACOMETIDA 1BFA51 DESDE TRANSFORMADOR


1BFT51. FUNCIONES 27/59 DE LA TENSIN
TRAFO.

Input type
Pickup level
Trip time
Reset time

Input type
Pickup level
Trip time
Reset time

Input type
Pickup level
Trip time
Reset time

Input type
Pickup level
Trip time
Reset time

Input type
ACOMETIDA 1BMA52 DESDE GENERADOR DE
Pickup level
EMERGENCIA XKA52. FUNCIONES TENSIN DE LA
Trip time
ACOMETIDA.
Reset time

REL TENSIN BARRA 1BMA52

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

PHAS-RMS
0,05-160,00
0,00-900,00
0,00-900,00

A
s
s

A
s
s

A
s
s

A
s
s

A
s
s

10
2
0

2
1
0

2
1
0

10
2
0

4
2
0

ANULADO

Input type
Pickup level
Curve shape
Time dial
Reset type

Input type
Pickup level
Curve shape
Time dial
Reset type

Input type
Pickup level
Curve shape
Time dial
Reset type

Input type
Pickup level
Curve shape
Time dial
Reset type

Input type
Pickup level
Curve shape
Time dial
Reset type

PHAS-RMS
0,05-160,00
0,00-900,00
INST-LIN

PHAS-RMS
0,05-160,00
0,00-900,00
INST-LIN

PHAS-RMS
0,05-160,00
0,00-900,00
INST-LIN

PHAS-RMS
0,05-160,00
0,00-900,00
INST-LIN

PHAS-RMS
0,05-160,00
0,00-900,00
INST-LIN

A
s
-

A
s
-

A
s
-

A
s
-

A
s
-

Input mode
Pickup level
Curve shape
N/A Time dial
Minimum voltage
Operation logic
Superv. by breaker

Input mode
Pickup level
Curve shape
N/A Time dial
Minimum voltage
Operation logic
Superv. by breaker

Input mode
Pickup level
Curve shape
N/A Time dial
Minimum voltage
Operation logic
Superv. by breaker

Input mode
Pickup level
Curve shape
N/A Time dial
Minimum voltage
Operation logic
Superv. by breaker

Input mode
Pickup level
Curve shape
N/A Time dial
Minimum voltage
Operation logic
Superv. by breaker

Input Type
PH UV PKP
PH UV CURVE
ANULADO
PH UV DELAY
PH UV PHASES
PH UV MIN VOLTAGE

PHAS-RMS
3-300
0,00-900,00
0-300
ANY-TWO-ALL

DIS-ENA

PHAS-RMS
3-300
0,00-900,00
0-300
ANY-TWO-ALL

DIS-ENA

PHAS-RMS
3-300
0,00-900,00
0-300
ANY-TWO-ALL

DIS-ENA

PHAS-RMS
3-300
0,00-900,00
0-300
ANY-TWO-ALL

DIS-ENA

PHAS-RMS
3-300

V
s
V
-

V
s
V
-

V
s
V
-

V
s
V
-

DIS-ENA

V
s
V
-

PHAS-RMS
0 - 1,25
Def - Inv,
0 - 600
ANY-TWO-ALL
0 -1,25

pu
s
pu

0,00-900,00
0-300
ANY-TWO-ALL

84
DEF
2
72
ANY
DIS

84
DEF
2
72
ANY
DIS

84
DEF
2
72
ANY
DIS

84
DEF
2
72
ANY
DIS

84
DEF
2
72
ANY
DIS

Pickup level
Trip time
Reset time
Operation logic

Pickup level
Trip time
Reset time
Operation logic

Pickup level
Trip time
Reset time
Operation logic

Pickup level
Trip time
Reset time
Operation logic

Pickup level
Trip time
Reset time
Operation logic

Input Type
PH OV PKP
PH OV DELAY
PH OV PHASES

3-300
0,00-900,00
0,00-900,00
ANY-TWO-ALL

3-300
0,00-900,00
0,00-900,00
ANY-TWO-ALL

3-300
0,00-900,00
0,00-900,00
ANY-TWO-ALL

3-300
0,00-900,00
0,00-900,00
ANY-TWO-ALL

3-300
0,00-900,00
0,00-900,00
ANY-TWO-ALL

PHAS-RMS
0 - 1,25
0 - 600
ANY-TWO-ALL

V
s
s
-

132
2
0
ALL

V
s
s
-

132
2
0
ALL

V
s
s
-

V
s
s
-

V
s
s
-

pu
s
-

132
2
0
ALL

132
2
0
ALL

132
2
0
ALL

Valor ajuste

Unidades

Rango

Parmetro

Valor ajuste

Funcin 25

Unidades

Rango

Parmetro

Valor ajuste

Funcin 59P

Unidades

Rango

Parmetro

Valor ajuste

Funcin 27P

Unidades

Rango

Parmetro

Valor ajuste

Funcin 51N

Unidades

Rango

Parmetro

Descripcin corta

COD

REVISIN

Funcin 50N

Dead bus voltage level


Live bus voltage level
Dead line voltage level
Live line voltage level
Max voltage difference
Max angle difference
Max frequency slip
Breaker closing time
DL-DB function
LL-DB function
DL-LB function
Dead bus voltage level
Live bus voltage level
Dead line voltage level
Live line voltage level
Max voltage difference
Max angle difference
Max frequency slip
Breaker closing time
DL-DB function
LL-DB function
DL-LB function

0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
2.00 : 300.00
2.0 : 80.00
10 : 5000
0.01 : 600.00
DIS-ENA
DIS-ENA
DIS-ENA
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
2.00 : 300.00
2.0 : 80.00
10 : 5000
0.01 : 600.00
DIS-ENA
DIS-ENA
DIS-ENA

V
V
V
V
V
V
mHz
s
---V
V
V
V
V
V
mHz
s
----

24
84
24
84
8
12
0,2
10
DIS
ENA
DIS
24
84
24
84
8
12
0,2
10
DIS
ENA
DIS

Dead bus voltage level


Live bus voltage level
Dead line voltage level
Live line voltage level
Max voltage difference
Max angle difference
Max frequency slip
Breaker closing time
DL-DB function
LL-DB function
DL-LB function

0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
2.00 : 300.00
2.0 : 80.00
10 : 5000
0.01 : 600.00
DIS-ENA
DIS-ENA
DIS-ENA

V
V
V
V
V
V
mHz
s
----

24
84
24
84
8
12
0,2
10
DIS
ENA
DIS

Dead bus voltage level


Live bus voltage level
Dead line voltage level
Live line voltage level
Max voltage difference
Max angle difference
Max frequency slip
Breaker closing time
DL-DB function
LL-DB function
DL-LB function

0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
2.00 : 300.00
2.0 : 80.00
10 : 5000
0.01 : 600.00
DIS-ENA
DIS-ENA
DIS-ENA

V
V
V
V
V
V
mHz
s
----

24
84
24
84
8
12
0,2
10
DIS
ENA
DIS

Dead bus voltage level


Live bus voltage level
Dead line voltage level
Live line voltage level
Max voltage difference
Max angle difference
Max frequency slip
Breaker closing time
DL-DB function
LL-DB function
DL-LB function

0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
0.00 : 300.00
2.00 : 300.00
2.0 : 80.00
10 : 5000
0.01 : 600.00
DIS-ENA
DIS-ENA
DIS-ENA

V
V
V
V
V
V
mHz
s
----

24
84
24
84
8
12
0,2
10
DIS
ENA
DIS

N/A

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

ESTADO
Edicin Inicial

SERVICIO:

IDOM Typ:

1BJA80

1BRT53

1MBN50AH010

1BJA12

1BJA76

1BMB52

1BNA91

1BNA59

1BTL52

1BJA20

1BJA51

1BJA11

1BLA91

1BLA92

1SGA81GH003

1BTL51

1BLA51

PLANTA TRATAMIENTO AGUA

TRAFO BYPASS DEL UPS

FUEL HEATING SKID

CCM 2 DE LA TURBINA DE GAS

GENERADOR AUXILIAR: EMERGENCIA


(BACKUP)

CCM ESENCIALES DEL BOP

TABLERO ESENCIALES SALA CONTROL

TABLERO SUBESTACIN

CARGADOR DC #2

CCM ESENCIALES DE LA TURBINA DE GAS

CCM DEL BOP

CCM 1 DE LA TURBINA DE GAS

PANEL OFICINAS

PANEL TALLER

BOMBA ELCTRICA PCI (CONTRAINCIDIOS)

CARGADOR DC #1

AUXILIARES DEL BOP NO ESENCIALES

1BFA53GS111

1BFA53GS122

1BFA53GS142

1BFA53GS241

1BMA52GS141

1BMA52GS142

1BMA52GS211

1BMA52GS212

1BMA52GS241

1BMA52GS311

1BFA51GS141

1BFA51GS241

1BFA51GS311

1BFA51GS312

1BFA51GS342

1BFA51GS411

1BFA51GS422

480

480

480

480

480

480

340

34

450

670

144

180

480

480

416

300

770

480

824

169

215

495

375

940

90

480

480

450

80

480

480

40

50

480

480

400

30

480

480

50

150

1,00

1,00

1,00

1,00

1,00

1,00

0,85

0,90

1,00

0,85

0,85

0,85

482

50

1,00

1,00

340

26

400,00

30,00

482,00

36,00

650,00

1200,00

250,00

400,00

36,00

60,00

96,00

1200,00

800,00

1200,00

110,00

80

340

96,00

96,00

A
A

Pickup (Ir)
630
tr (@6xIr)
630

250-630
0,5-16

A
s

Isd
500
td
2
I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

40-100
0,5-16

A
s

Isd
63 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX100 Frame


Micrologic 6.2A
In rating

A
A

Schneider NS800L
Micrologic 6.3A

Frame
In rating

A
A

Pickup (Ir)
800
tr (@6xIr)
800

0,4 -1
0,7-24

xIn
s

Isd
0,81 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

1500

Schneider NW12
Micrologic 6.0E

Frame
In rating

A
A

Pickup (Ir)
1250
tr (@6xIr)
1250

0,4 -1
0,7-24

xIn
s

Isd
0,96 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

100-250
0,5-16

A
s

Isd
250 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX250 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
250
tr (@6xIr)
250

Schneider NSX400 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
400
tr (@6xIr)
400

160-400
0,5-16

A
s

Isd
400 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX100 Frame


Micrologic 6.2A
In rating

A
A

Pickup (Ir)
100
tr (@6xIr)
100

40-100
0,5-16

A
s

Isd
40 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX100 Frame


Micrologic 6.2A
In rating

A
A

Pickup (Ir)
100
tr (@6xIr)
100

40-100
0,5-16

A
s

Isd
72 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX160 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
160
tr (@6xIr)
160

63-160
0,5-16

A
s

Isd
115 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

1500

Schneider NW12
Micrologic 6.0E

Frame
In rating

A
A

Pickup (Ir)
1250
tr (@6xIr)
1250

0,4 -1
0,7-24

xIn
s

Isd
0,96 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NS800L
Micrologic 6.3A

Frame
In rating

A
A

Pickup (Ir)
800
tr (@6xIr)
800

0,4 -1
0,7-24

xIn
s

Isd
1 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Frame
In rating

A
A

Pickup (Ir)
1250
tr (@6xIr)
1250

0,4 -1
0,7-24

xIn
s

Isd
0,96 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX160 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
160
tr (@6xIr)
160

63-160
0,5-16

A
s

Isd
120 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX100 Frame


Micrologic 6.2A
In rating

A
A

Pickup (Ir)
100
tr (@6xIr)
100

40-100
0,5-16

A
s

Isd
66 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX630 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
630
tr (@6xIr)
630

250-630
0,5-16

A
s

Isd
500 td
8 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX160 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
160
tr (@6xIr)
160

63-160
0,5-16

A
s

Isd
105 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

Schneider NSX160 Frame


Micrologic 6.3A
In rating

A
A

Pickup (Ir)
160
tr (@6xIr)
160

63-160
0,5-16

A
s

Isd
105 td
2 I2t

1,5-10,0
0,0-0,40
On/Off

x Ir
s
'-

1500

1700

Schneider NW12
Micrologic 6.0E

5
Ii
0,3
ON
5
0,3 Ii
ON
5
Ii
0,3
ON
5
Ii
0,3
ON
5
Ii
0,3
ON
5
Ii
0,3
ON
N/A Ii

N/A Ii

N/A Ii
5
Ii
0,3
ON
5
Ii
0,3
ON
5
Ii
0,3
ON
5
0,3 Ii
ON
5
0,3 Ii
ON
N/A

Ii

N/A Ii

N/A Ii

1,5-11,0

x In

Ig
tg
6
I2t
Ig
tg
8
I2t

1,5-15

x In

1,5-15

x In

Ig
tg
8
I2t

1,5-15

x In

Ig
tg
6
I2t

1,5-12

x In

Ig
tg
6
I2t

1,5-12

x In

Ig
tg
6
I2t

1,5-15

1,5-15

x In

x In

Ig
tg
6
I2t
Ig
tg
6
I2t
Ig
tg
8
I2t

1,5-15

x In

1,5-15

x In

Ig
tg
6
I2t

1,5-15

x In

Ig
tg
6
I2t

x In

Ig
tg
6
I2t

1,5-15

1,5-15

1,5-15

1,5-11,0

1,5-15

1,5-15

x In

x In

x In

x In

x In

Ig
tg
6
I2t
Ig
tg
6
I2t
Ig
tg
8
I2t
Ig
tg
8
I2t
Ig
tg
6
I2t

Valor ajuste

Unidades

Rango

Parmetro

Valor ajuste

Funcin G

Unidades

Rango

Parmetro

Valor ajuste

Funcin I

Unidades

Rango

Parmetro

Valor ajuste

Funcin S

Unidades

Rango

Parmetro

Valor ajuste

Unidades

Parmetro

Relevador
Schneider NSX630 Frame
Micrologic 6.3A
In rating

Funcin L

Pickup (Ir)
100
tr (@6xIr)
100

60,00

250,00

80

I max arranque
motor mayor [A]

[kVA]

I de arranque
/ I nominal

[kW]

Ajustes generales

Intensidad
demandada
[A]

Factor de carga

Intensidad nominal
[A]

[kVA]

Factor de potencia
(Cos )

[kW]

Potencia
demandada

Rendimiento
()

Tensin nominal [V]

Identificacin
Tablero - Cubculo

Descripcin corta

COD

REVISIN

Potencia
nominal

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

N/A

0,2-1,0
0-0,4
On/Off

x In
s
-

1
0,5

500-1200
0-0,4
On/Off

A
s
-

N/A

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

N/A

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

500-1200
0-0,4
On/Off

A
s
-

N/A

0,2-1,0
0-0,4
On/Off

x In
s
-

N/A

500-1200
0-0,4
On/Off

A
s
-

N/A

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

N/A

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

0,4-1,0
0-0,4
On/Off

x In
s
-

1
0,5

Edita:

Cliente:

COORDINACIN PROTECCIONES
CLIENTE:
PROYECTO:
RESERVA FRIA ETEN
LOCALIZACIN: Chiclayo - Lambayeque - PER

N DOC.:

RFE-1-YE_-EEC-IDO-001

UNIDADES:

n/a

Rev.

FECHA

REALIZ.

COMP.

APROB.

C.D.:

02.07.01

KKS

n/a

20-11-2014

JMM

PRV

JSA

rea Tc.: ELCTRICA

ESTADO
Edicin Inicial

SERVICIO:

IDOM Typ:

Potencia
demandada

9 Disparo

fijo

170

1EGB70AA351

VALVULA MOTORIZADA DESCARGA TANQUE COMBUSTIBLE 2

BJA51-A-4.1.2

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1EGD61AA351

VALVULA MOTORIZADA ALIMENTACIN COMBUSTIBLE TG Y GEN. AUXILIAR 2

BJA51-A-4.1.3

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1EGD62AA351

VALVULA MOTORIZADA ALIMENTACIN COMBUSTIBLE TG Y GEN. AUXILIAR 1

BJA51-A-4.1.4

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1GAD72AA351

VALVULA MOTORIZADA PTA A TANQUE AGUA 2

BJA51-A-4.1.5

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1GAD73AA351

VALVULA MOTORIZADA PTA A TANQUE AGUA 1

BJA51-A-4.1.6

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1GNK80AA351

VALVULA MOTORIZADA DESCARGA PTA A BALSA EVAPORACIN

BJA51-A-4.2.3

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1GNK90AA351

VALVULA MOTORIZADA DESCARGA PTA A TANQUE HOMOGENEIZACIN

BJA51-A-4.2.4

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1GAD91AA351

VALVULA MOTORIZADA TANQUE AGUA A PTA 2

BJA51-A-4.3.1

480

0,43

0,80

0,85

1,32

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

1GAD81AA351

VALVULA MOTORIZADA TANQUE AGUA A PTA 1

BJA51-A-4.3.3

480

0,43

0,80

0,85

1,32

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170

Unidades

Rango

Unidades

Rango

Valor ajuste

9-14

Parmetro

Rango Ajuste

Valor ajuste

Schneider GV2P16 CCM-5

Parmetro

1,01

Valor ajuste

0,85

Unidades

0,80

Parmetro

0,33

Esq. Tpico

480

[kVA]

Relevador

BJA51-A-4.1.1

[kW]

I de arranque

Intensidad nominal
[A]

VALVULA MOTORIZADA DESCARGA TANQUE COMBUSTIBLE 1

[kVA]

Factor de carga

Factor de potencia
(Cos )

1EGB60AA351

Identificacin
Tablero - Cubculo

Descripcin corta

[kW]

Rendimiento
()

Funcin I magntico

Tensin nominal [V]

Funcin L Trmico

COD

Intensidad demandada
[A]

Ajustes generales

REVISIN

Potencia
nominal

1EGD52AP001-M01 Bomba 1 Alimentacin Combustible a Generador Auxiliar

BJA51-C-1

480

1,10

0,81

0,80

2,00

Schneider GV2P07 CCM-02E

Rango Ajuste

1,6-2,5

2,5 Disparo

fijo

33,5

1GMB61AP001-M01 Bomba 1 Pozo de bombeo Separador aceitosas a Balsa Evaporacin

BJA51-C-3

480

5,50

0,90

0,87

8,40

Schneider GV2P16 CCM-02E

Rango Ajuste

9-14

10,5 Disparo

fijo

170

1GNK61AP001-M01 Bomba 1 Depsito de homogeneizacin y neutralizacin a balsa evaporacin

BJA51-C-4

480

7,50

0,91

0,88

11,30

Schneider GV2P16 CCM-02A

Rango Ajuste

9-14

14,0 Disparo

fijo

170

1GAD60AP001-M01 Bomba Recirculacin Tanque 1GAD60BB010

BJA51-C-6

480

18,50

0,92

0,90

26,80

Schneider GV2P32 CCM-02A

Rango Ajuste

24-32

32,0 Disparo

fijo

416

1GAD70AP001-M01 Bomba Recirculacin Tanque 1GAD70BB010

BJA51-C-7

480

18,50

0,92

0,90

26,80

Schneider GV2P32 CCM-02A

Rango Ajuste

24-32

32,0 Disparo

fijo

416

1EGD53AP001-M01 Bomba 2 Alimentacin Combustible a Generador Auxiliar

BJA51-D-1

480

1,10

0,81

0,80

2,00

Schneider GV2P07 CCM-02E

Rango Ajuste

1,6-2,5

2,5 Disparo

fijo

33,5

1GMB71AP001-M01 Bomba 2 Pozo de bombeo Separador aceitosas a Balsa Evaporacin

BJA51-D-3

480

5,50

0,90

0,87

8,40

Schneider GV2P16 CCM-02E

Rango Ajuste

9-14

10,5 Disparo

fijo

170

1GNK71AP001-M01 Bomba 2 Depsito de homogeneizacin y neutralizacin a balsa evaporacin

BJA51-D-4

480

7,50

0,91

0,88

11,30

Schneider GV2P16 CCM-02A

Rango Ajuste

9-14

14,0 Disparo

fijo

170

1GHC61AP001-M01

Bomba 1 Alimentacin Agua


Desmineralizada a Turbina de Gas

BJA51-D-6

480

18,50

0,92

0,90

26,80

Schneider GV2P32 CCM-02A

Rango Ajuste

24-32

32,0 Disparo

fijo

416

1GHC62AP001-M01

Bomba 2 Alimentacin Agua


Desmineralizada a Turbina de Gas

BJA51-D-7

480

18,50

0,92

0,90

26,80

Schneider GV2P32 CCM-02A

Rango Ajuste

24-32

32,0 Disparo

fijo

416

1MBN50AN001-M01 FUEL HEATING SKID VENT FAN MOTOR 88FDH-1

BJA51-E-1

480

0,40

1,00

0,85

0,60

Schneider GV2P06 CCM-02C

Rango Ajuste

1-1,6

1,0 Disparo

fijo

23

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
32

0,7-1,0
FIJO

x In
s

1
Pickup level
15 s @6xIr

FIJO

400,00

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
32

0,7-1,0
FIJO

x In
s

1
Pickup level
15 s @6xIr

FIJO

400,00

112

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
80

0,7-1,0
FIJO

x In
s

0,88
Pickup level
15 s @6xIr

FIJO

640,00

189

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
40

0,7-1,0
FIJO

x In
s

0,86
Pickup level
15 s @6xIr

FIJO

500,00

Schneider NSX160
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
160
Time dial
160

0,7-1,0
FIJO

x In
s

0,9
Pickup level
15 s @6xIr

FIJO

1250,00

Rango Ajuste

9-14

9 Disparo

fijo

170,00

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

0,85

1,01

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

0,30

0,50

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

480

1,95

2,30

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

BMB52-A-3.2.3

480

0,83

1,30

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

VENTILACIN CONTENEDOR TRAFO 1BFT51

BMB52-A-3.2.4

480

1,10

1,50

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

1BFT53AN001

VENTILACIN CONTENEDOR TRAFO 1BFT53

BMB52-A-3.2.5

480

1,10

1,50

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

1BBT51GH001

VENTILADORES TRANSFORMADOR 1BBT51

BMB52-A-3.2.6

480

1,20

3,00

Schneider GV2P16 CCM-5

Rango Ajuste

9-14

9 Disparo

fijo

170,00

HVAC CONTENEDOR ELECTRNICA

BMB52-D-10.1.1

480

5,20

7,40

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
16

0,7-1,0
FIJO

x In
s

1
Pickup level
15 s @6xIr

FIJO

190,00

13,20

20,80

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
32

0,7-1,0
FIJO

x In
s

1
Pickup level
15 s @6xIr

FIJO

400,00

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
63

0,7-1,0
FIJO

x In
s

1
Pickup level
15 s @6xIr

FIJO

500,00

1GHC82

Grupo de Presin Alimentacin Agua


Desmineralizada a Servicios Auxiliares

BJA51-E-10.11

480

16,50

0,95

0,81

25,80

1SCA79

ESTACIN DE AIRE COMPRIMIDO 1

BJA51-E-10.12

480

13,20

0,90

0,85

20,80

1BAT10GH001

VENTILADORES TRANSFORMADOR 1BAT10 (BACKUP)

BJA51-E-10.13

480

36,00

0,90

0,85

56,60

1GHA81

Grupo de Presin Alimentacin Agua bruta a


Enfriadores Evaporativos / Potabilizadora

BJA51-E-10.21

480

18,50

0,95

0,85

27,60

1SDT30AN010

WATER WASH SKID

BJA51-E-4

480

81,54

1,00

0,85

115,30

1EGA72AA351

VALVULA MOTORIZADA CARGA TANQUE COMBUSTIBLE 1

BMB52-A-3.1.1

480

0,33

0,80

0,85

1,01

Schneider GV2P16 CCM-5

1EGA73AA351

VALVULA MOTORIZADA CARGA TANQUE COMBUSTIBLE 2

BMB52-A-3.1.2

480

0,33

0,80

0,85

1,01

1GAF81AA351

VALVULA MOTORIZADA CARGA TANQUE AGUA 1

BMB52-A-3.1.3

480

0,33

0,80

0,85

1GAF82AA351

VALVULA MOTORIZADA CARGA TANQUE AGUA 2

BMB52-A-3.1.4

480

0,33

0,80

1EGD50AA351

VALVULA MOT. ALIMENTACIN TANQUE DIARIO GEN. AUX.

BMB52-A-3.1.6

480

0,33

0,80

1UBA51AN001

VENTILACIN CONTENEDOR MT

BMB52-A-3.2.1

480

1BAC10GH001

AUX. ACCIONAMIENTOS INTERRUPTOR GENERADOR

BMB52-A-3.2.2

1UBA52AN001

VENTILACIN CONTENEDOR BT

1BFT51AN001

1SCA80

ESTACIN DE AIRE COMPRIMIDO 2

BMB52-D-10.1.2

480

1BNA52

TABLERO DE ESENCIALES

BMB52-D-10.1.3

480

1GAF_1GH001

ISLA DE CARGA AGUA BRUTA

BMB52-D-10.2.2

480

1BAT10GH001

VENTILADORES TRANSFORMADOR PRINCIPAL 1BAT10

BMB52-D-10.2.3

480

36,00

1SGA81GH002

TABLERO PCI (BOMBA JOCKEY)

BMB52-D-10.3.1

480

1EGA_1GH001

ISLA DE CARGA COMBUSTIBLE

BMB52-D-10.3.2

480

0,90

0,85

175

25,11

48,74

146

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
63

0,7-1,0
FIJO

x In
s

0,95
Pickup level
15 s @6xIr

FIJO

500,00

56,60

112

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
80

0,7-1,0
FIJO

x In
s

0,88
Pickup level
15 s @6xIr

FIJO

640,00

2,20

3,46

24

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
16

0,7-1,0
FIJO

x In
s

0,7
Pickup level
15 s @6xIr

FIJO

190,00

31,00

48,74

146

Schneider NSX100
TMD

CCM-04

Frame
Rating Plug

A
A

Pickup level
100
Time dial
63

0,7-1,0
FIJO

x In
s

0,95
Pickup level
15 s @6xIr

FIJO

500,00

0,90

0,85

Rev. A

CLCULOS ELCTRICOS
ANEXO VII

RFE-1-YE__-ECE-IDO-001

Pg/Page 284 de/of


288

ANEXO VII:

CURVAS DE SELECTIVIDAD TIEMPO-CORRIENTE SISTEMA


DE BT

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

Amps X 100 1BFA53 (Nom. kV=0,48, Plot Ref. kV=0,48)


,5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

1BBA51

Cable_1BFT53
Ampacity
500

500

1BFT53
FLA

CB-Motor

XFR_Distr - P
OC1

300

1BFT53-F1 - P - 51
OC1

10

100

Cable_1BFT53 - P
5

1BFT53
3500 kVA (Secondary) 14 %Z
Delta-Wye Solid Grd
1

1BFT53-F1 - P - 50
OC1

,1

GE Multilin
F650
CT Ratio 5000:5
Inst = 23 (0,05 - 160 Sec - 5A)
Time Delay = 0,25 s

Merlin Gerin MICROLOGIC 6.0


Sensor = 1250
LT Pickup = 0.96 (1200 Amps)
LT Band = 2
ST Pickup = 5 (6000 Amps)
ST Band = 0.3 (I^x)t = IN
Inst. Pickup = 6 (7500 Amps)

,3

0,09 s

1BFT53
Inrush

10

1BFA53

1BMA52

CB-BJA12

1BJA12

CB-Motor
1BFT53-F1
- 3P F1 - 3P
ACOP 53-51

30

50

100

300

500

1K

Amps X 100 1BFA53 (Nom. kV=0,48, Plot Ref. kV=0,48)


COORDINACIN BT (FASES)
Project:
Location:
Contract:
Engineer:
Filename:

CB 1BFA53-A

,03

XFR_Distr - 3P

,01
,5

1BFT53-F1

,3

,05

GE Multilin
F650
CT Ratio 5000:5
Inst = 15 (0,05 - 160 Sec - 5A)
Time Delay = 0,15 s

,03

,5

,1

ACOP 53-51 F1 - P - 50
OC1

,05

1BFT53
3500 kVA

CB-BJA12

,5

Seconds

2-3/C 185

10

GE Multilin
F650
CT Ratio 5000:5
IEC - Curve C
Pickup = 3,35 (0,05 - 160 Sec - 5A)
Time Dial = 0,5
3x = 5 s, 5x = 1,67 s, 8x = 0,635 s

Cable_1BFT53

50

30

ACOP 53-51 F1 - P - 51
OC1

XFR_Distr

GE Multilin
F650
CT Ratio 5000:5
IEC - Curve C
Pickup = 5 (0,05 - 160 Sec - 5A)
Time Dial = 0,5
3x = 5 s, 5x = 1,67 s, 8x = 0,635 s

30

Seconds

GE Multilin
350
CT Ratio 500:5
IEC - C
Pickup = 0,75 (0,04 - 20 xCT Sec)
Time Dial = 0,5
3x = 5 s, 5x = 1,67 s, 8x = 0,635 s
Inst = 11 (0,05 - 20 xCT Sec)
Time Delay = 0,15 s

100

50

CB 1BBA51-E
300

Reserva Fra Eten


Chiclayo - Lambayeque - PER
IDOM
\\ATBCN\industrial\4 ENCARGOS\17595\CD\02 INGENIERA\07 ELCTRICO\04 C

Date:
SN:
Rev:
Fault:

21-11-2014
IDOMINGCON
Base
Phase

3K

5K

,01
10K

ETAP Star 12.0.0C

88TK-2
200 HP

CB 53/52
ACOP 53-51 F1
R

Amps X 1000 1BFA53 (Nom. kV=0,48, Plot Ref. kV=0,48)


,5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

Cable_1BFT53
Ampacity
ACOP 53-51 F1 - N - 50
OC1

500

300

500

CB 1BBA51-E
300

GE Multilin
F650
CT Ratio 5000:5
Inst = 2,07 (0,05 - 160 Sec - 5A)
Time Delay = 1 s

100

1BBA51

100

1BFT53-F1 - N - 50
OC1
50

Seconds

Seconds

10

GE Multilin
F650
CT Ratio 1250:5
ANSI - Extremely Inverse
Pickup = 15 (0,05 - 160 Sec - 5A)
Time Dial = 50
3x = 33 s, 5x = 12,4 s, 8x = 6,28 s

2-3/C 185

30

1BFT53-F1 - G - 51
OC1

10

Cable_1BFT53

50

GE Multilin
F650
CT Ratio 5000:5
Inst = 10,07 (0,05 - 160 Sec - 5A)
Time Delay = 2 s

30

XFR_Distr

1BFT53
3500 kVA

,5

,5

,3

,3

1BFT53-F1

CB 1BFA53-A
1BFA53

CB-BJA12
,1

,1

Merlin Gerin MICROLOGIC 6.0


Sensor = 1250
Ground Pickup = J (1200 Amps)
Ground Band = 0.3 (I^x)t = IN

,05

,05

1BMA52

CB-BJA12

1BJA12

,03

,03

CB-Motor

,01
,5

10

30

50

100

300

500

1K

Amps X 1000 1BFA53 (Nom. kV=0,48, Plot Ref. kV=0,48)


COORDINACIN BT (NEUTRO)
Project:
Location:
Contract:
Engineer:
Filename:

Reserva Fra Eten


Chiclayo - Lambayeque - PER
IDOM
\\ATBCN\industrial\4 ENCARGOS\17595\CD\02 INGENIERA\07 ELCTRICO\04 C

Date:
SN:
Rev:
Fault:

21-11-2014
IDOMINGCON
Base
Ground

3K

5K

,01
10K

ETAP Star 12.0.0C

88TK-2
200 HP

CB 53/52
ACOP 53-51 F1
R

Rev. A

CLCULOS ELCTRICOS
ANEXO VIII

RFE-1-YE__-ECE-IDO-001

Pg/Page 287 de/of


288

ANEXO VIII:

CLCULO MNIMA CORRIENTE CORTOCIRCUITO

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

One-Line Diagram - OLV1


Red Elctrica Peruana
220 kV
3022 MVAsc

S.E. Reque
220 kV

0
0 kV

7,93
7,94

0,014
AL

kA 82,9

ETEN: CORTOCIRCUITO

20/11/2014

ESTUDIO MNIMO CORTOCIRCUITO

2,92 km
Narcissus

GENERADOR EMERGENCIA 2123 kVA

Xd = 13,3%

CONECTADO A 1BMA52 EN ISLA

GENERADOR AUXILIAR Y PRINCIPAL DESCONECTADOS

S.E. Etn
220 kV

7,28

TRAFOS MT/BT 3500 kVA Uk=14%

0 kV
7,3
kA 83

0,014

SOLO CCM GENERALES CONECTADOS

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

0
0 kV 3
9,34

39,17

kA 86,2

0,175
Isolated Phase CU
8 m

Isolated Phase CU
35 m
R

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

18 kV
9021 A
1MKA10
225 MW
17 %Xd"

CU

40 m
4-3/C 240

1BBA51
6,6 kV

6,66
kA 84,4

0
0 kV

6,19
0,294

Open

0,197

Open

Open

Open

Open

Open

Open

CU

CU

CU

Yd1
20 m
3-3/C 300

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z
6,6 kV
922,9 A
1BJA76
0,48 kV

CU

40 m
1-3/C 150

Open
20 m
1-3/C 300

70 m
1-3/C 70

CU

100 m
1-3/C 70
CU

120 m
3-3/C 300

1BBA76
6,6 kV

CU

CU

CU

40 m
3-3/C 240

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

CU

70 m
1-3/C 70

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z
CU

1BFT53
3500 kVA
6,6/0,505 kV
14 %Z

Dyn11

CU

50 m
1-3/C 70

100 m
1-3/C 70

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z
CU
CU

50 m
1-3/C 70

50 m
1-3/C 70

40 m
2-3/C 185

50 m
1-3/C 70

1BFT51
3500 kVA
6,6/0,505 kV
14 %Z

Dyn11

Excitacin 1MKC10
1MKA76
944 kVA
8,44 MW1BFA53
23,2
16 %Xd"
7 kA
0,48 kV
-80

LCI 1BPA10_1
2725 kVA

88WN-1
224 kW

LCI 1BPA10_2
2725 kVA
0
0 kV

,9

1BMA52
0,48 kV

19,43

27,4

3,98

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

5 kA
-83,
8

21,9
5

0
0 kV

26,57

0,854

19,5

0,067

kA 81,8

1BFA51
0,48 kV

0
0 kV

2,54
Open

Open

Open
W-1BJA12

CARGAS 1BJA76
270 kVA

Open

CU

MBN50 AH010
450 kVA

1BJA80
400 kVA

CGDE

0,918

0,48 kV

28,68

0,48 kV
3191 A
1XKA52
2123 kW
10,7 %Xd"

19:36:43

nov 21, 2014

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

page 1

W-1BMB52

50 m
6-3/C 300

Project File: Eten_protecciones

0 kV
29,5
5

0
kA 86,4

Open

Open

1BNB52
0,38 kV

4,02

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

0
0 kV

4,
0,077 1 kA -5
9,9

CARGAS 1BNB52
82,2 kVA

W-1BMB20

Open

Sistema PCI
200 kW