Академический Документы
Профессиональный Документы
Культура Документы
Surabaya - Indonesia
A.
B.
C.
GENERAL CHARACTERISTICS
Design standars
Transformer type
Service Condition
Type of oil
Number of phase
Frequency
:
:
:
:
:
:
D3 SPLN 2007
Totally Oil Filled
Outdoor
Mineral Oil
3
Phase
50
Hz
TECHNICAL SPECIFICATION
Capacity
High voltage
Low Voltage
Vector Group
Cooling
Temperature Rise :
- Oil
- Winding
No load losses at nominal voltage
Full load losses at nominal tapping
Impedance voltage at nominal tapping
Off load current at nominal voltage
Temperature Insulation Class
Sound Pressure Level at 0.3m
Off Circuit tapping value
:
:
:
:
:
:
:
:
:
:
:
:
:
:
125
20
400
YNd5
ONAN
50
55
250
1600
4
2.5
A
53
+ 2 x 2.5%
:
:
:
High Voltage
24
125
50
Low Voltage
1.1
3
25% load
98.62
98.89
Voltage Regulation
Volt
%
5801
3.32
5918
1.36
E.
K
K
Watts
Watts
%
%
dB
kVA
kV
V
LIST OF TEST
Routine Test :
- Measurement of the resistance value and checking of polarities
- Measurement of the ratio on all taps
- No load test for measurement of the no load and no load current
- Short circuit test for determination of the on load loss and impedance
- Applied voltage test
- Induced Voltage test
Type test :
- Temperature rise test
- Full wave impuls test ( 1.2 / 50 us )
:
:
:
:
:
:
Yes
No
:
:
Test other than the above mentioned list needs further confirmation
Revision
Original
Date
3-Feb-15
Dsg.
YRZ
Chk
App.
Client / project
No
Page
0003263-A-5
1/2
TECHNICAL SPECIFICATIONS
Surabaya - Indonesia
F.
ACCESSORIES
- Name Plate and Rating Plate
- HV and LV Porcelain Bushings
- Oil Filling Valve
- Oil Draining Valve w/ Sampling Valve
- Lifting Lugs
- Roller w/ base
- Grounding Terminal, 2 unit
G.
APPROXIMATE DRAWING
H.
I.
DEVIATIONS / EXCEPTIONS
- None
J.
NOTES
- None
:
:
:
:
:
:
1300
700
1700
430
1300
Grey
mm
mm
mm
liter
kg
The above dimensions and masses are approximate and provided to give a general description of our proposed
transformer .
Revision
Original
Date
3-Feb-15
Dsg
MCR
Chk
App.
Client / project
No
Page
0003263-A-5
2/2