Вы находитесь на странице: 1из 24

SS-PRC018-EN

Split System
Cooling Product &
Performance Data
XB 10
TTB012-024
1, 1 & 2 Tons

PUB. NO. 22-1689-05-0603 (EN)

General
Features
Split System Cooling
Units . . . Designed With
Your Needs In Mind.
TTB Split systems represent a new
approach to designing products for
The Trane Company. The design teams
mission is . . . to bring a system to the
marketplace that will meet your job
requirements every time . . . And at a
competitive price.
Tranes experienced design team used
the newest computer technology and
an entirely new manufacturing process
to develop a new standard in split
systems. Couple the Trane reputation
for quality and reliability in split system
air conditioners with improvements in
efficiency, flexibility and installation
ease . . . and you have systems that
prove Its Hard to Stop a Trane.

Manufacturing Control
Tranes exclusive control over the design
and manufacturing of all major components is unique in the industry. This
approach assures us total control over
both the quality and reliability of these
components. It also allows us to custom
match components to deliver the best in
split system performance.
Designing the Details
Careful attention was given to designing
the details from control wiring to the
access panels. TTB units feature timesaving color coded wiring and removable
panels which allow complete access to
all major components and controls. All
outdoor units feature external high and
low pressure gauge port connections,
and service valves for easy diagnosing
and servicing of the unit are provided.
Standardized Cabinets
In addition all cabinets have been
standardized; so when you are servicing
an outdoor unit or an air handler all
components are in the same location
from unit to unit.
UL Listed and ARI Certified
Trane meets or exceeds all nationally
recognized agency safety and design
standards. Each unit is UL approved,
and labeled in accordance to UL
Standard 1995, including approval for
use in Canada. Each unit is rated in
accordance with ANSI ARI Standard
210/240 and 270.

2003 American Standard Inc. All Rights Reserved

22-1689-05-0603 (EN)

Contents

General Features

Features and Benefits

Optional Equipment
Low Outdoor Ambient Cooling
A.R.I. Standard Capacity Rating Conditions

Selection Procedure
Model Number Nomenclature

General Data
TTB012C100A
TTB018C100A
TTB024C100A

22-1689-05-0603 (EN)

5
5
5

6
6

7
7
9
11

Ratings with Auxiliary Devices

13

Performance Data Cooling

14

TTB012C
TTB018C
TTB024C

14
15
17

Electrical Data

19

Dimensions

20

Mechanical Specification Options

21

Features and
Benefits

Climatuff compressor
All Aluminum Spine Fin coil

5-year limited warranty on


compressor, coil and 5 years on
parts (Residential use)

Polyslate gray cabinet

Extended warranties available

Full coil protection

S.E.E.T. design testing

Corrosion resistant finish and fasteners

100% line run test

Internal high/low pressure &


temperature protection

Low ambient cooling to 55F. as


shipped

Liquid line filter-drier

Low ambient cooling to 40F. with


EDC accessory AY28X079

Single-side service access


Multi-use liquid and suction line
service valves

Low ambient cooling to 30F. with


EDC accessory AY28X079 and TXV

HCFC-22 refrigerant

22-1689-05-0603 (EN)

Features and
Benefits

Optional Equipment
] indicates accessories included).
OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [
Indoor Thermostats Electronic Setback ............................................................................................................ TAYSTAT300C [
Electronic, 1 Htg. (Gas)/1 Clg. (Non Prog.) .......................................................................... TAYSTAT370 [
Electronic, 1 Htg. (Elec.)/ 1 Clg. (Non Prog.)3 ..................................................................... TAYSTAT371[
Heating/Cooling Horizontal ................................................................................................. AY28X092 [
Cooling Only with Fan Switch .............................................................................................. BAYSTAT304 [
Heating/Cooling Vertical ................................................................................................. BAYSTAT305 [
Thermostat Locking Cover .................................................................................................... BAY28X190 [
Outdoor Thermostats 46F. to -10F. (Adjustable) (TTB018-024) .......................................................................... TAYSTAT250B [
Evaporator Defrost Control .......................................................................................................................................... AY28X079 [
Indoor Fan Delay Relay Kit ........................................................................................................................................ BAY24X045 [
Quick-Start Kit (TTB012-024C) .................................................................................................................................. BAY41X228 [
Isolators .................................................................................................................................................................... BAYISLT100 [
Outdoor Temperature Sensor .. (TAYSTAT300C) ................................................................................................. TAYSENS100A [

]
]
]
]
]
]
]
]
]
]
]
]
]

1 Not used with programmable thermostats


2 When field inner connecting lines exceed 60 linear ft. of length refer to the Application Guide (Pub. 22-3238-02)

BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.)
5/8" ODM (90 bend, one end), 5/8" & 1/4" tubing ................................................................................................ TAYREFLN1__* [ ]
3/4" ODM (90 bend, one end), 3/4" & 5/16" tubing .............................................................................................. TAYREFLN2__* [ ]
* Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number.
Example: TAYREFLN220

Low Outdoor Ambient Cooling


Low Ambient
Cooling
FCCV Accutron
Thermal Expansion Valve (TXV)

As
Manufactured

Evaporator
Defrost Control

55F
55F

40F
30F

A.R.I. Standard Capacity Rating Conditions


A.R.I. STANDARD 210/240 RATING CONDITIONS (A) Cooling 80F. D.B., 67F. W.B. air entering indoor coil, 95F. D.B. air
entering outdoor coil.

22-1689-05-0603 (EN)

Selection
Procedure

Model Number Nomenclature


1

10

11

PRODUCT TYPE
Split Cooling - TTA, TTB, TTN, TTR TTP,
TTX, TTY, TTZ
Split Heat Pump - TWA, TWN, TWP,
TWR, TWX, TWY, TWZ
Package Cooling TCC, TCH, TCD, TCX, TCM, TCP, TCY
Package Heat Pump - WCC, WCD, WCH,
WCZ, WCM, WCP, WCX, DCX, WCY
Air Handler - TWE, TWG, TVF
Gas/Electric - YCC, YCD, YCH, YCP, YCX,
YCY, YCZ
Coils - TXA, TXE, TXC, TXH, CCB, CUB

MINOR DESIGN
MODIFICATION
SECONDARY FUNCTIONS
Gas/Electric - Gas Heating
Furnaces - Cooling Airflow
Air Handlers - Flow Control
POWER SUPPLY AND FUEL
MAJOR DESIGN MODIFICATION

SPLIT SYSTEM COUPLING SYSTEMS


1 - 5 TONS
0 - Brazed
PRIMARY CAPACITY
Example: 024 = 24 MBTUH = 2 Tons

22-1689-05-0603 (EN)

General
Data
OUTDOOR UNIT 12
SOUND RATING (DECIBELS) 2
POWER CONNS. V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR.
MAX. (AMPS)
PROT. RTG.
MIN. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN TYPE
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP.
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
(O.D. UNIT) NP CHRG. 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
FCCV
RESTRICTOR ORIFICE SIZE
DIMENSIONS
OUTDOOR UNIT CRATED (IN.)
UNCRATED
WEIGHT
SHIPPING (LBS.)
NET (LBS.)

TTB012C100A
82
200/230/1/60
11
15
15
CLIMATUFF
1-1
200/230/1/60
8.0 - 45
NO
NO
YES
PROPELLER
13.7 - 1
DIRECT - 1
1600
1 - 1/8
1650
200/230/1/60
0.83
SPINE FIN
1 - 24
6.62
3/8
R-22
2/12-LB/OZ
YES
5/8
1/4

TTB012C100A

1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER


EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON
A.R.I. STANDARD 210/240.
2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.
3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.
ONLY USE HACR CIRCUIT BREAKERS OR FUSES.
4 STANDARD AIR - DRY COIL - OUTDOOR
5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT
NAMEPLATE AND SERVICE INSTRUCTION.
6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID
60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING
SOFTWARE PUB. NO. 32-3312-01.
7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT
NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO
COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM
FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT
SELECTION CURRENT.
8 NO MEANS NO START COMPONENTS
YES MEANS QUICK START KIT COMPONENTS
PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

0.049
H X W X D
24.75 X 20 X 20
SEE OUTLINE DWG.

SPLIT SYSTEM

118
112

CONDENSING UNIT WITH COOLING COILS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

CCBA18A4AC
FIXED ORIFICE

CUBA18A4AC
FIXED ORIFICE

TXA018C4
FACT INS 49

TXA024C4
CHG TO 49

TXA025C4
CHG TO 49

TXC018C4
FACT INS 49

TXC024C4
CHG TO 49

15800
10000
450
1.73
9.15/10.00

15800
10000
450
1.73
9.15/10.00

14800
9700
525
1.61
9.20/10.00

14400
9000
450
1.55
9.30/10.00

14700
9500
450
1.56
9.40/10.05

14800
9700
525
1.61
9.20/10.00

14400
9000
450
1.55
9.30/10.00

TXC024D4
CHG TO 49

TXC025C4
CHG TO 49

TXC025D4
CHG TO 49

TXH025A4
CHG TO 49

14400
9000
450
1.55
9.30/10.00

14700
9500
450
1.56
9.40/10.05

14700
9500
450
1.56
9.40/10.05

16200
10200
450
1.74
9.30/10.00

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

CONDENSING UNIT WITH AIR HANDLERS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)
See

2TFB4018A1
FACT INS 49

2TFB4024A1
CHG TO 49

TVF018A14
FACT INS 49

TVF025A14
CHG TO 49

TWE018C14
FACT INS 49

TWE024C14
CHG TO 49

TWG018A14
FACT INS 49

16800
10900
450
1.78
9.45/10.00

16700
10800
450
1.82
9.20/10.00

15100
10000
450
1.56
9.65/10.50

14900
9800
450
1.62
9.20/10.00

14600
9300
450
1.56
9.35/10.20

14400
9100
450
1.55
9.30/10.20

14500
9300
450
1.56
9.30/10.00

page 13 for combinations with Auxiliary Devices.

22-1689-05-0603 (EN)

General
Data

TTB012C100A

CONDENSING UNIT WITH AIR HANDLERS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

TWG025A14
CHG TO 49
14200
9100
450
1.49
9.55/10.00

See page 13 for combinations with Auxiliary Devices.

22-1689-05-0603 (EN)

General
Data
OUTDOOR UNIT 12
SOUND RATING (DECIBELS) 2
POWER CONNS. V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR.
MAX. (AMPS)
PROT. RTG.
MIN. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN TYPE
DIA.(IN) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP.
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
(O.D. UNIT) NP CHRG. 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
FCCV
RESTRICTOR ORIFICE SIZE
DIMENSIONS
OUTDOOR UNIT CRATED (IN.)
UNCRATED
WEIGHT
SHIPPING (LBS.)
NET (LBS.)

TTB018C100A
82
200/230/1/60
11
15
15
CLIMATUFF
1-1
200/230/1/60
8.0 - 45
NO
NO
YES
PROPELLER
13.7 - 1
DIRECT - 1
1600
1 - 1/8
1650
200/230/1/60
0.83
SPINE FIN
1 - 24
6.62
3/8
R-22
3/3-LB/OZ
YES
5/8
1/4

TTB018C100A

1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER


EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON
A.R.I. STANDARD 210/240.
2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.
3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.
ONLY USE HACR CIRCUIT BREAKERS OR FUSES.
4 STANDARD AIR - DRY COIL - OUTDOOR
5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT
NAMEPLATE AND SERVICE INSTRUCTION.
6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID
60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING
SOFTWARE PUB. NO. 32-3312-01.
7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT
NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO
COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM
FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT
SELECTION CURRENT.
8 NO MEANS NO START COMPONENTS
YES MEANS QUICK START KIT COMPONENTS
PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

0.049
H X W X D
24.75 X 20 X 20
SEE OUTLINE DWG.

SPLIT SYSTEM

118
112

CONDENSING UNIT WITH COOLING COILS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

CCBA18A4AC
FIXED ORIFICE

CCBA24A4AC
FIXED ORIFICE

CUBA18A4AC
FIXED ORIFICE

CUBA24A4AC
FIXED ORIFICE

CUBB24A4AC
FIXED ORIFICE

TXA018C4
FACT INS 49

TXA024C4
CHG TO 49

16600
11100
600
1.80
9.20/10.00

16600
11400
620
1.79
9.25/10.10

16600
11100
600
1.80
9.20/10.00

16600
11400
620
1.79
9.25/10.10

16600
11400
620
1.79
9.25/10.10

17000
11400
600
1.82
9.35/10.00

16800
11600
630
1.81
9.30/10.05

TXA025C4
CHG TO 49

TXC018C4
FACT INS 49

TXC024C4
CHG TO 49

TXC024D4
CHG TO 49

TXC025C4
CHG TO 49

TXC025D4
CHG TO 49

TXH025A4
CHG TO 49

17100
12700
640
1.83
9.35/10.00

16600
11100
600
1.80
9.20/10.00

16800
11600
630
1.81
9.30/10.05

16800
11600
630
1.81
9.30/10.05

17100
12700
640
1.83
9.35/10.00

17100
12700
640
1.83
9.35/10.00

17200
11900
640
1.85
9.30/10.00

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

CONDENSING UNIT WITH AIR HANDLERS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)
See

2TFB4018A1
FACT INS 49

2TFB4024A1
CHG TO 49

2TFB4030A1
CHG TO 49

TVF018A14
FACT INS 49

TVF024A14
CHG TO 49

TVF025A14
CHG TO 49

TWE018C14
FACT INS 49

17800
12500
600
1.84
9.70/10.00

17900
13000
670
1.89
9.45/10.00

17800
12800
665
1.95
9.15/10.00

17300
12700
600
1.78
9.70/10.40

17400
13300
650
1.86
9.35/10.15

17500
13400
655
1.83
9.55/10.40

17100
11600
600
1.77
9.65/10.00

page 13 for combinations with Auxiliary Devices.

22-1689-05-0603 (EN)

General
Data

TTB018C100A

CONDENSING UNIT WITH AIR HANDLERS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)
See

TWE024C14
CHG TO 49

TWG018A14
FACT INS 49

TWG025A14
CHG TO 49

16800
11600
625
1.79
9.40/10.00

16500
11400
600
1.77
9.30/10.00

16600
12100
620
1.74
9.55/10.00

page 13 for combinations with Auxiliary Devices.

10

22-1689-05-0603 (EN)

General
Data
OUTDOOR UNIT 12
SOUND RATING (DECIBELS) 2
POWER CONNS. V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR.
MAX. (AMPS)
PROT. RTG.
MIN. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN TYPE
DIA.(IN) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP.
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
(O.D. UNIT) NP CHRG. 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
FCCV
RESTRICTOR ORIFICE SIZE
DIMENSIONS
OUTDOOR UNIT CRATED (IN.)
UNCRATED
WEIGHT
SHIPPING (LBS.)
NET (LBS.)

TTB024C100A
80
208/230/1/60
15
25
20
CLIMATUFF
1-1
200/230/1/60
11.6 - 60
NO
NO
YES
PROPELLER
13.7 - 1
DIRECT - 1
1550
1 - 1/8
1650
200/230/1/60
0.83
SPINE FIN
1 - 24
6.62
3/8
R-22
3/10-LB/OZ
YES
3/4
5/16

TTB024C100A

1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER


EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON
A.R.I. STANDARD 210/240.
2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.
3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.
ONLY USE HACR CIRCUIT BREAKERS OR FUSES.
4 STANDARD AIR - DRY COIL - OUTDOOR
5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT
NAMEPLATE AND SERVICE INSTRUCTION.
6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID
60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING
SOFTWARE PUB. NO. 32-3312-01.
7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT
NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO
COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM
FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT
SELECTION CURRENT.
8 NO MEANS NO START COMPONENTS
YES MEANS QUICK START KIT COMPONENTS
PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

0.057
H X W X D
24.75 X 20 X 20
SEE OUTLINE DWG.

SPLIT SYSTEM

130
125

CONDENSING UNIT WITH COOLING COILS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)
See

CCBA24A4AC
FIXED ORIFICE

CCBA30A4AC
FIXED ORIFICE

CCBB30A4AC
FIXED ORIFICE

CUBA24A4AC
FIXED ORIFICE

CUBA30A4AC
FIXED ORIFICE

CUBB24A4AC
FIXED ORIFICE

CUBB30A4AC
FIXED ORIFICE

22000
14900
800
2.40
9.15/10.00

21200
14500
775
2.36
9.00/10.00

22000
16200
800
2.39
9.20/10.00

22000
14900
800
2.40
9.15/10.00

21200
14500
775
2.36
9.00/10.00

22000
14900
800
2.40
9.15/10.00

22000
16200
800
2.39
9.20/10.00

TXA024C4
FACT INS 57

TXA025C4
FACT INS 57

TXA030C4
CHG TO 57

TXA031C4
CHG TO 57

TXA035C4
CHG TO 57

TXA036C4
CHG TO 57

TXC024C4
FACT INS 57

22200
15000
800
2.44
9.10/10.00

21800
15500
800
2.37
9.20/10.00

22200
15400
825
2.40
9.25/10.00

22400
16400
835
2.41
9.30/10.00

22000
15100
825
2.37
9.30/10.00

22800
16800
850
2.43
9.40/10.00

21400
14500
800
2.34
9.15/10.00

TXC024D4
FACT INS 57

TXC025C4
FACT INS 57

TXC025D4
FACT INS 57

TXC030C4
CHG TO 57

TXC030D4
CHG TO 57

TXC031C4
CHG TO 57

TXC031D4
CHG TO 57

21400
14500
800
2.34
9.15/10.00

21800
15500
800
2.37
9.20/10.00

21800
15500
800
2.37
9.20/10.00

22200
15400
825
2.40
9.25/10.00

22200
15400
825
2.40
9.25/10.00

22400
16400
835
2.41
9.30/10.00

22400
16400
835
2.41
9.30/10.00

page 13 for combinations with Auxiliary Devices.

22-1689-05-0603 (EN)

11

General
Data

TTB024C100A

CONDENSING UNIT WITH COOLING COILS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

TXC035C4
CHG TO 57

TXC035D4
CHG TO 57

TXC036C4
CHG TO 57

TXC036D4
CHG TO 57

TXC037C4
CHG TO 57

TXH025A4
FACT INS 57

TXH033A4
FACT INS 57

22000
15100
825
2.37
9.30/10.00

22000
15100
825
2.37
9.30/10.00

22800
16800
850
2.43
9.40/10.00

22800
16800
850
2.43
9.40/10.00

22800
16800
850
2.43
9.40/10.00

21400
14500
800
2.33
9.20/10.00

22400
16400
840
2.38
9.40/10.00

CONDENSING UNIT WITH AIR HANDLERS

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

2TFB4018A1
CHG TO 57

2TFB4024A1
FACT INS 57

2TFB4030A1
CHG TO 57

TVF018A14
CHG TO 57

TVF024A14
CHG TO 57

TVF025A14
CHG TO 57

TVF030A14
CHG TO 57

21800
14600
675
2.29
9.50/10.00

22200
15500
800
2.39
9.30/10.00

22200
15800
825
2.44
9.10/10.00

21600
15000
675
2.34
9.25/10.20

22200
16300
800
2.40
9.25/10.20

22400
16500
800
2.38
9.40/10.40

23000
17700
850
2.43
9.45/10.40

TVF036A14
CHG TO 57

TWE018C14
CHG TO 57

TWE024C14
CHG TO 57

TWE030C14
CHG TO 57

TWE036C14
CHG TO 57

TWG018A14
CHG TO 57

TWG025A14
CHG TO 57

23000
17600
860
2.50
9.20/10.10

20800
13600
675
2.26
9.20/10.00

21000
14300
775
2.30
9.15/10.00

21800
15700
810
2.38
9.15/10.05

22600
16300
835
2.44
9.25/10.15

20400
13600
675
2.24
9.10/10.00

21000
14700
785
2.23
9.40/10.00

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)

EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
EER/SEER (BTU/WATT-HR.)
See

TWG030A14
CHG TO 57
21800
15400
815
2.36
9.25/10.00

page 13 for combinations with Auxiliary Devices.

12

22-1689-05-0603 (EN)

Ratings with
Auxiliary Devices
COMBINATIONS WITH FAN DELAY RELAY KIT AND/OR TXV KIT

When models are matched with an indoor air handler or coil that has a flow control check valve or expansion valve flow control, the addition of an indoor fan delay relay and/or TXV kit
may increase the system SEER. See charts below for ratings.
OUTDOOR
MODEL

INDOOR
MODEL

TTB012C100A
TTB012C100A *
TTB012C100A
TTB012C100A *
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB012C100A
TTB018C100A
TTB018C100A *
TTB018C100A
TTB018C100A *
TTB018C100A
TTB018C100A *
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A
TTB018C100A

2TFB4018A1
2TFB4018A1
2TFB4024A1
2TFB4024A1
CCBA18A4AC
CUBA18A4AC
TXA018C4
TXA024C4
TXA025C4
TXC018C4
TXC024C4
TXC024D4
TXC025C4
TXC025D4
TXH025A4
2TFB4018A1
2TFB4018A1
2TFB4024A1
2TFB4024A1
2TFB4030A1
2TFB4030A1
CCBA18A4AC
CCBA24A4AC
CUBA18A4AC
CUBA24A4AC
CUBB24A4AC
TXA018C4
TXA024C4
TXA025C4
TXC018C4
TXC024C4
TXC024D4
TXC025C4
TXC025D4
TXH025A4

FAN
DELAY
KIT

TXV
KIT

CFM

SEER

COOLING
CAPACITY

FI
FI
FI
FI
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
FI
FI
FI
FI
FI
FI
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y

NB
NB
NB
NB
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NB
NB
NB
NB
NB
NB
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO

450
450
450
450
450
450
535
450
450
535
450
450
450
450
450
600
600
650
650
650
650
600
620
600
620
620
600
630
640
600
630
630
640
640
640

10.50
10.50
10.25
10.25
10.15
10.15
10.25
10.25
10.35
10.25
10.25
10.25
10.35
10.35
10.30
10.75
10.75
10.50
10.50
10.25
10.25
10.20
10.40
10.20
10.40
10.40
10.30
10.30
10.35
10.30
10.30
10.30
10.35
10.35
10.30

16600
16600
16400
16400
15800
15800
14800
14400
14700
14800
14400
14400
14700
14700
16200
17500
17500
17600
17600
17500
17500
16600
16600
16600
16600
16600
17000
16800
17100
17000
16800
16800
17100
17100
17200

FI - FACTORY INSTALLED

22-1689-05-0603 (EN)

B - BLEED TXV

OUTDOOR
MODEL

INDOOR
MODEL

TTB024C100A
TTB024C100A *
TTB024C100A
TTB024C100A *
TTB024C100A
TTB024C100A *
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A
TTB024C100A

2TFB4018A1
2TFB4018A1
2TFB4024A1
2TFB4024A1
2TFB4030A1
2TFB4030A1
CCBA24A4AC
CCBA30A4AC
CCBB30A4AC
CUBA24A4AC
CUBA30A4AC
CUBB24A4AC
CUBB30A4AC
TXA018C4
TXA024C4
TXA025C4
TXA030C4
TXA031C4
TXA035C4
TXA036C4
TXA037C4
TXC018C4
TXC024C4
TXC024D4
TXC025C4
TXC025D4
TXC030C4
TXC030D4
TXC031C4
TXC031D4
TXC035C4
TXC035D4
TXC036C4
TXC036D4
TXC037C4
TXH025A4
TXH033A4

NB - NON-BLEED TXV

13

FAN
DELAY
KIT

TXV
KIT

CFM

SEER

COOLING
CAPACITY

FI
FI
FI
FI
FI
FI
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y

NB
NB
NB
NB
NB
NB
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO

675
675
800
800
815
815
800
775
800
800
775
800
800
675
800
800
825
835
825
850
850
675
800
800
800
800
825
825
835
835
825
825
850
850
850
800
840

10.50
10.50
10.25
10.25
10.00
10.00
10.10
10.10
10.20
10.10
10.10
10.10
10.20
10.05
10.10
10.25
10.30
10.30
10.30
10.40
10.40
10.05
10.10
10.10
10.25
10.25
10.30
10.30
10.30
10.30
10.30
10.30
10.40
10.40
10.40
10.20
10.40

21600
21600
22000
22000
21800
21800
22000
21200
22000
22000
21200
22000
22000
20400
22200
21800
22200
22400
22000
22800
22800
20400
22200
22200
21800
21800
22200
22200
22400
22400
22000
22000
22800
22800
22800
21400
22400

* - START KIT REQUIRED

Performance Data
Cooling
TTB012C WITH TXC018C4 AT 550 CFM
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOT.
CAP.
13.1
14.3
15.5
16.7

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
10.0
11.3
12.6
13.3*
8.4
9.7
11.0
11.8
6.6
7.9
9.2
10.0
4.8
6.0
7.3
8.2

59
63
67
71

12.8
13.8
14.9
16.0

9.9
8.2
6.4
4.6

11.1
9.5
7.7
5.8

12.4
10.8
9.0
7.1

13.0*
11.6
9.8
7.9

1.57
1.60
1.62
1.65

59
63
67
71

12.2
13.2
14.1
15.2

9.6
8.0
6.2
4.3

10.9
9.3
7.4
5.5

12.2
10.5
8.7
6.8

12.5*
11.4
9.5
7.6

1.70
1.72
1.74
1.76

59
63
67
71

11.6
12.5
13.4
14.3

9.4
7.7
5.9
4.0

10.6
9.0
7.2
5.3

11.7*
10.3
8.4
6.5

12.0*
11.1
9.2
7.4

1.82
1.84
1.86
1.88

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
TWG025A14
RATED
450
0.95
0.95
0.92
LOW
400
0.94
0.89
0.92
HIGH
500
0.97
1.00
0.91
TXA018C4
RATED
550
1.00
1.00
1.00
LOW
450
0.97
0.91
1.01
HIGH
600
1.01
1.04
0.98
TXA018C4+BAY24X045
RATED
550
1.00
0.94
1.00
LOW
475
0.98
0.89
1.01
HIGH
600
1.01
0.98
0.99
TXA024C4
RATED
450
0.97
0.94
0.95
LOW
400
0.95
0.89
0.96
HIGH
500
0.99
0.99
0.94
TXA024C4+BAY24X045
RATED
450
0.97
0.94
0.95
LOW
400
0.95
0.89
0.96
HIGH
500
0.99
0.99
0.94
TXA025C4
RATED
450
0.99
0.99
0.96
LOW
400
0.97
0.93
0.97
HIGH
500
1.01
1.03
0.95
TXA025C4+BAY24X045
RATED
450
0.99
0.99
0.96
LOW
400
0.97
0.93
0.97
HIGH
500
1.01
1.03
0.95
TXC018C4
RATED
550
1.00
1.00
1.00
LOW
450
0.96
0.91
1.01
HIGH
600
1.01
1.04
0.98
TXC018C4+BAY24X045
RATED
550
1.00
0.94
1.00
LOW
475
0.98
0.89
1.01
HIGH
600
1.01
0.98
0.99
TXC024C4
RATED
450
0.97
0.94
0.95
LOW
400
0.95
0.89
0.96
HIGH
500
0.99
0.99
0.94
TXC024C4+BAY24X045
RATED
450
0.97
0.94
0.95
LOW
400
0.95
0.89
0.96
HIGH
500
0.99
0.99
0.94
TXC024D4
RATED
450
0.97
0.94
0.95
LOW
400
0.95
0.89
0.96
HIGH
500
0.99
0.99
0.94
TXC024D4+BAY24X045
RATED
450
0.97
0.94
0.95
LOW
400
0.95
0.89
0.96
HIGH
500
0.99
0.99
0.94
TXC025C4
RATED
450
0.99
0.99
0.96
LOW
400
0.97
0.93
0.97
HIGH
500
1.01
1.03
0.95
TXC025C4+BAY24X045
RATED
450
0.99
0.99
0.96
LOW
400
0.97
0.93
0.97
HIGH
500
1.01
1.03
0.95
TXC025D4
RATED
450
0.99
0.99
0.96
LOW
400
0.97
0.93
0.97
HIGH
500
1.01
1.03
0.95
TXC025D4+BAY24X045
RATED
450
0.99
0.99
0.96
LOW
400
0.97
0.93
0.97
HIGH
500
1.01
1.03
0.95
TXH025A4
RATED
450
1.09
1.05
1.07
LOW
400
1.07
1.00
1.08
HIGH
500
1.11
1.10
1.06
TXH025A4+BAY24X045
RATED
450
1.09
1.05
1.07
LOW
400
1.07
1.00
1.08
HIGH
500
1.11
1.10
1.06

TOTAL
KW
1.46
1.49
1.52
1.54

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


AIRFLOW
TOTAL CAPACITY
SENSIBLE CAPACITY
LOW
HIGH

450
600

0.96
1.01

TTB012C

0.91
1.04

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
2TFB4018A1
RATED
450
1.11
1.10
1.09
LOW
400
1.08
1.05
1.10
HIGH
500
1.13
1.16
1.08
2TFB4024A1
RATED
450
1.10
1.09
1.11
LOW
400
1.07
1.04
1.12
HIGH
500
1.12
1.15
1.10
CCBA18A4AC
RATED
450
1.06
1.02
1.06
LOW
400
1.04
0.97
1.07
HIGH
500
1.08
1.07
1.05
CCBA18A4AC+BAY24X045
RATED
450
1.06
1.02
1.06
LOW
400
1.04
0.97
1.07
HIGH
500
1.08
1.07
1.05
CUBA18A4AC
RATED
450
1.06
1.02
1.06
LOW
400
1.04
0.97
1.07
HIGH
500
1.08
1.07
1.05
CUBA18A4AC+BAY24X045
RATED
450
1.06
1.02
1.06
LOW
400
1.04
0.97
1.07
HIGH
500
1.08
1.07
1.05
TVF018A14
RATED
450
1.01
1.03
0.96
LOW
400
0.99
0.96
0.97
HIGH
500
1.03
1.09
0.95
TVF025A14
RATED
450
1.00
1.01
1.00
LOW
400
0.98
0.95
1.01
HIGH
500
1.02
1.06
0.99
TWE018C14
RATED
450
0.98
0.95
0.96
LOW
400
0.96
0.90
0.97
HIGH
500
1.00
1.00
0.95
TWE024C14
RATED
450
0.97
0.94
0.95
LOW
400
0.94
0.89
0.96
HIGH
500
0.99
0.99
0.94
TWG018A14
RATED
450
0.97
0.96
0.96
LOW
400
0.96
0.91
0.97
HIGH
500
0.99
1.01
0.95

14

22-1689-05-0603 (EN)

Performance Data
Cooling
TTB018C WITH TXC018C4 AT 600 CFM
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOT.
CAP.
14.7
15.9
17.2
18.6

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
11.4
12.8
14.2
14.9*
9.6
11.0
12.4
13.3
7.6
9.0
10.4
11.3
5.5
7.0
8.3
9.3

TOTAL
KW
1.62
1.65
1.68
1.72

59
63
67
71

14.1
15.3
16.6
17.9

11.2
9.4
7.4
5.3

12.6
10.8
8.8
6.7

14.0
12.2
10.2
8.1

14.5*
13.1
11.1
9.0

1.74
1.77
1.80
1.84

59
63
67
71

13.4
14.5
15.7
16.9

10.8
9.0
7.0
5.0

12.3
10.4
8.4
6.3

13.5*
11.8
9.8
7.8

13.9*
12.8
10.8
8.7

1.88
1.91
1.94
1.97

59
63
67
71

12.6
13.7
14.8
16.0

10.5
8.7
6.7
4.6

11.9
10.1
8.1
6.0

12.9*
11.5
9.5
7.4

13.2*
12.5
10.4
8.4

2.02
2.04
2.07
2.10

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
CUBB24A4AC
RATED
600
0.99
1.02
0.99
LOW
550
0.98
0.98
1.00
HIGH
700
1.01
1.09
0.99
CUBB24A4AC+BAY24X045
RATED
600
0.99
1.02
0.99
LOW
550
0.98
0.98
1.00
HIGH
700
1.01
1.09
0.99
TVF018A14
RATED
600
1.04
1.13
0.99
LOW
525
1.02
1.06
1.00
HIGH
675
1.05
1.19
0.98
TVF024A14
RATED
700
1.05
1.20
1.04
LOW
575
1.03
1.09
1.04
HIGH
750
1.06
1.25
1.03
TVF025A14
RATED
700
1.06
1.21
1.02
LOW
575
1.04
1.10
1.02
HIGH
750
1.07
1.26
1.01
TWE018C14
RATED
600
1.03
1.05
0.98
LOW
525
1.01
0.98
0.99
HIGH
675
1.05
1.11
0.97
TWE024C14
RATED
600
1.01
1.03
0.98
LOW
550
1.00
0.99
0.99
HIGH
700
1.03
1.10
0.97
TWG018A14
RATED
600
1.00
1.03
0.98
LOW
525
0.98
0.97
0.99
HIGH
675
1.01
1.08
0.97
TWG025A14
RATED
600
1.00
1.06
0.96
LOW
550
0.99
1.02
0.97
HIGH
700
1.02
1.14
0.95
TXA018C4
RATED
600
1.03
1.03
1.01
LOW
525
1.01
0.96
1.02
HIGH
675
1.04
1.08
1.00
TXA018C4+BAY24X045
RATED
600
1.03
1.02
1.01
LOW
525
1.01
0.97
1.02
HIGH
675
1.05
1.08
1.00
TXA024C4
RATED
600
1.01
1.02
0.99
LOW
550
1.00
0.98
1.00
HIGH
725
1.03
1.12
0.98
TXA024C4+BAY24X045
RATED
600
1.00
1.02
0.99
LOW
550
0.99
0.98
1.00
HIGH
725
1.02
1.11
0.98
TXA025C4
RATED
600
1.02
1.10
1.00
LOW
550
1.01
1.05
1.01
HIGH
725
1.04
1.20
0.99
TXA025C4+BAY24X045
RATED
700
1.04
1.17
1.03
LOW
575
1.02
1.06
1.03
HIGH
725
1.04
1.19
1.02
TXC018C4
RATED
600
1.00
1.00
1.00
LOW
525
0.98
0.94
1.01
HIGH
675
1.02
1.05
0.99
TXC018C4+BAY24X045
RATED
600
1.02
1.02
1.01
LOW
525
1.00
0.97
1.02
HIGH
675
1.03
1.08
1.00
TXC024C4
RATED
600
1.01
1.02
0.99
LOW
550
1.00
0.98
1.00
HIGH
725
1.03
1.12
0.98
TXC024C4+BAY24X045
RATED
600
1.00
1.02
0.99
LOW
550
0.99
0.98
1.00
HIGH
725
1.02
1.11
0.98
TXC024D4
RATED
600
1.01
1.02
0.99
LOW
550
1.00
0.98
1.00
HIGH
725
1.03
1.12
0.98
TXC024D4+BAY24X045
RATED
600
1.00
1.02
0.99
LOW
550
0.99
0.98
1.00
HIGH
725
1.02
1.11
0.98

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


AIRFLOW
TOTAL CAPACITY
SENSIBLE CAPACITY
LOW
HIGH

525
675

0.98
1.02

0.94
1.05

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
2TFB4018A1
RATED
600
1.06
1.11
1.01
LOW
525
1.04
1.04
1.02
HIGH
675
1.08
1.17
1.00
2TFB4024A1
RATED
700
1.07
1.17
1.05
LOW
600
1.05
1.08
1.06
HIGH
800
1.08
1.24
1.03
2TFB4030A1
RATED
700
1.06
1.16
1.07
LOW
600
1.04
1.08
1.09
HIGH
800
1.07
1.23
1.06
CCBA18A4AC
RATED
600
1.00
1.00
1.00
LOW
525
0.98
0.94
1.01
HIGH
675
1.01
1.05
0.99
CCBA18A4AC+BAY24X045
RATED
600
1.00
1.00
1.00
LOW
525
0.98
0.94
1.01
HIGH
675
1.01
1.05
0.99
CCBA24A4AC
RATED
600
0.99
1.02
0.99
LOW
550
0.98
0.98
1.00
HIGH
700
1.01
1.09
0.99
CCBA24A4AC+BAY24X045
RATED
600
0.99
1.02
0.99
LOW
550
0.98
0.98
1.00
HIGH
700
1.01
1.09
0.99
CUBA18A4AC
RATED
600
1.00
1.00
1.00
LOW
525
0.98
0.94
1.01
HIGH
675
1.01
1.05
0.99
CUBA18A4AC+BAY24X045
RATED
600
1.00
1.00
1.00
LOW
525
0.98
0.94
1.01
HIGH
675
1.01
1.05
0.99
CUBA24A4AC
RATED
600
0.99
1.02
0.99
LOW
550
0.98
0.98
1.00
HIGH
700
1.01
1.09
0.99
CUBA24A4AC+BAY24X045
RATED
600
0.99
1.02
0.99
LOW
550
0.98
0.98
1.00
HIGH
700
1.01
1.09
0.99

22-1689-05-0603 (EN)

TTB018C

15

Performance Data
Cooling

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
TXC025C4
RATED
600
1.02
1.10
1.00
LOW
550
1.01
1.05
1.01
HIGH
725
1.04
1.20
0.99
TXC025C4+BAY24X045
RATED
700
1.04
1.17
1.03
LOW
575
1.02
1.06
1.03
HIGH
725
1.04
1.19
1.02
TXC025D4
RATED
600
1.02
1.10
1.00
LOW
550
1.01
1.05
1.01
HIGH
725
1.04
1.20
0.99

TTB018C

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
TXC025D4+BAY24X045
RATED
700
1.04
1.17
1.03
LOW
575
1.02
1.06
1.03
HIGH
725
1.04
1.19
1.02
TXH025A4
RATED
600
1.03
1.04
1.01
LOW
550
1.02
1.00
1.02
HIGH
725
1.05
1.14
1.00
TXH025A4+BAY24X045
RATED
600
1.03
1.04
1.01
LOW
550
1.02
1.00
1.02
HIGH
725
1.05
1.14
1.00

16

22-1689-05-0603 (EN)

Performance Data
Cooling
TTB024C WITH TXC024C4 AT 800 CFM
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOT.
CAP.
19.1
20.7
22.4
24.1

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
14.9
16.8
18.6
19.5*
12.6
14.4
16.3
17.5
9.9
11.8
13.6
14.8
7.2
9.0
10.9
12.1

TOTAL
KW
2.09
2.14
2.20
2.26

59
63
67
71

18.3
19.8
21.4
23.1

14.6
12.2
9.5
6.8

16.5
14.1
11.4
8.7

18.3*
15.9
13.2
10.5

18.8*
17.2
14.5
11.8

2.22
2.28
2.34
2.40

59
63
67
71

17.2
18.6
20.1
21.7

14.1
11.7
9.1
6.3

16.0
13.6
10.9
8.2

17.5*
15.5
12.8
10.0

17.9*
16.7
14.0
11.3

2.36
2.42
2.49
2.55

59
63
67
71

16.1
17.5
18.9
20.3

13.7
11.3
8.6
5.9

15.6
13.2
10.4
7.7

16.6*
15.0
12.3
9.6

17.0*
16.2
13.6
10.8

2.51
2.57
2.63
2.70

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
CUBA30A4AC
RATED
800
0.99
1.01
1.02
LOW
675
0.97
0.94
1.03
HIGH
875
1.00
1.05
1.01
CUBA30A4AC+BAY24X045
RATED
800
0.99
1.01
1.01
LOW
675
0.97
0.94
1.03
HIGH
875
1.00
1.05
1.00
CUBB24A4AC
RATED
800
1.03
1.03
1.03
LOW
700
1.01
0.98
1.04
HIGH
900
1.04
1.08
1.02
CUBB24A4AC+BAY24X045
RATED
800
1.03
1.03
1.03
LOW
700
1.01
0.98
1.04
HIGH
900
1.04
1.08
1.02
CUBB30A4AC
RATED
800
1.03
1.11
1.02
LOW
700
1.01
1.04
1.03
HIGH
900
1.04
1.17
1.01
CUBB30A4AC+BAY24X045
RATED
800
1.03
1.11
1.02
LOW
700
1.01
1.04
1.03
HIGH
900
1.04
1.17
1.01
TVF018A14
RATED
700
1.02
1.04
1.01
LOW
600
1.00
0.97
1.02
HIGH
750
1.03
1.08
1.00
TVF024A14
RATED
800
1.04
1.11
1.03
LOW
700
1.02
1.04
1.04
HIGH
900
1.05
1.18
1.02
TVF025A14
RATED
800
1.05
1.12
1.02
LOW
700
1.03
1.05
1.03
HIGH
900
1.06
1.19
1.01
TVF030A14
RATED
900
1.08
1.22
1.05
LOW
750
1.06
1.11
1.05
HIGH
950
1.09
1.26
1.04
TVF036A14
RATED
900
1.08
1.21
1.08
LOW
750
1.06
1.10
1.09
HIGH
975
1.09
1.26
1.06
TWE018C14
RATED
700
0.98
0.95
0.97
LOW
600
0.95
0.89
0.98
HIGH
750
0.99
0.98
0.96
TWE024C14
RATED
800
0.99
1.00
0.99
LOW
675
0.96
0.93
1.00
HIGH
875
1.00
1.04
0.98
TWE030C14
RATED
800
1.02
1.07
1.02
LOW
700
1.00
1.01
1.03
HIGH
900
1.03
1.13
1.01
TWE036C14
RATED
800
1.05
1.10
1.04
LOW
725
1.04
1.06
1.05
HIGH
950
1.07
1.19
1.03
TWG018A14
RATED
700
0.96
0.96
0.97
LOW
600
0.94
0.90
0.98
HIGH
750
0.97
0.98
0.96
TWG025A14
RATED
800
0.98
1.02
0.96
LOW
700
0.96
0.96
0.97
HIGH
900
0.99
1.07
0.95
TWG030A14
RATED
800
1.02
1.05
1.01
LOW
725
1.01
1.01
1.02
HIGH
925
1.04
1.13
1.00
TXA018C4+BAY24X045
RATED
700
0.96
0.92
0.98
LOW
600
0.93
0.87
0.99
HIGH
750
0.97
0.95
0.97
TXA024C4
RATED
800
1.04
1.04
1.04
LOW
700
1.02
0.99
1.05
HIGH
900
1.05
1.09
1.03
TXA024C4+BAY24X045
RATED
800
1.04
1.04
1.04
LOW
700
1.02
0.99
1.05
HIGH
900
1.05
1.09
1.03

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


AIRFLOW
TOTAL CAPACITY
SENSIBLE CAPACITY
LOW
HIGH

700
900

0.98
1.01

0.94
1.05

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
2TFB4018A1
RATED
700
1.01
1.02
0.98
LOW
600
0.98
0.94
0.99
HIGH
800
1.03
1.08
0.97
2TFB4024A1
RATED
800
1.02
1.06
1.02
LOW
700
1.00
0.99
1.03
HIGH
900
1.04
1.11
1.01
2TFB4030A1
RATED
900
1.02
1.11
1.05
LOW
775
1.00
1.03
1.06
HIGH
1025
1.03
1.17
1.04
CCBA24A4AC
RATED
800
1.03
1.03
1.03
LOW
700
1.01
0.98
1.04
HIGH
900
1.04
1.08
1.02
CCBA24A4AC+BAY24X045
RATED
800
1.03
1.03
1.03
LOW
700
1.01
0.98
1.04
HIGH
900
1.04
1.08
1.02
CCBA30A4AC
RATED
800
0.99
1.01
1.02
LOW
675
0.97
0.94
1.03
HIGH
875
1.00
1.05
1.01
CCBA30A4AC+BAY24X045
RATED
800
0.99
1.01
1.01
LOW
675
0.97
0.94
1.03
HIGH
875
1.00
1.05
1.00
CCBB30A4AC
RATED
800
1.03
1.11
1.02
LOW
700
1.01
1.04
1.03
HIGH
900
1.04
1.17
1.01
CCBB30A4AC+BAY24X045
RATED
800
1.03
1.11
1.02
LOW
700
1.01
1.04
1.03
HIGH
900
1.04
1.17
1.01
CUBA24A4AC
RATED
800
1.03
1.03
1.03
LOW
700
1.01
0.98
1.04
HIGH
900
1.04
1.08
1.02
CUBA24A4AC+BAY24X045
RATED
800
1.03
1.03
1.03
LOW
700
1.01
0.98
1.04
HIGH
900
1.04
1.08
1.02

22-1689-05-0603 (EN)

TTB024C

17

Performance Data
Cooling

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
TXA025C4
RATED
800
1.02
1.06
1.01
LOW
700
1.00
1.00
1.02
HIGH
900
1.03
1.13
1.00
TXA025C4+BAY24X045
RATED
800
1.02
1.06
1.01
LOW
700
1.00
1.00
1.02
HIGH
900
1.03
1.13
1.00
TXA030C4
RATED
800
1.04
1.05
1.02
LOW
725
1.03
1.01
1.03
HIGH
925
1.06
1.13
1.01
TXA030C4+BAY24X045
RATED
800
1.04
1.05
1.02
LOW
725
1.03
1.01
1.03
HIGH
925
1.06
1.13
1.01
TXA031C4
RATED
800
1.04
1.10
1.02
LOW
725
1.03
1.05
1.03
HIGH
950
1.06
1.19
1.01
TXA031C4+BAY24X045
RATED
800
1.04
1.10
1.02
LOW
725
1.03
1.05
1.03
HIGH
950
1.06
1.19
1.01
TXA035C4
RATED
800
1.03
1.04
1.01
LOW
725
1.02
1.00
1.02
HIGH
925
1.05
1.11
1.00
TXA035C4+BAY24X045
RATED
800
1.03
1.04
1.01
LOW
725
1.02
1.00
1.02
HIGH
925
1.05
1.11
1.00
TXA036C4
RATED
900
1.07
1.17
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXA036C4+BAY24X045
RATED
900
1.07
1.18
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXA037C4
RATED
900
1.07
1.17
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXA037C4+BAY24X045
RATED
900
1.07
1.18
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.09
1.21
1.04
TXC018C4+BAY24X045
RATED
700
0.96
0.92
0.98
LOW
600
0.93
0.87
0.99
HIGH
750
0.97
0.95
0.97
TXC024C4
RATED
800
1.00
1.00
1.00
LOW
700
0.98
0.94
1.01
HIGH
900
1.01
1.05
0.99
TXC024C4+BAY24X045
RATED
800
1.04
1.04
1.04
LOW
700
1.02
0.99
1.05
HIGH
900
1.05
1.09
1.03
TXC024D4
RATED
800
1.00
1.00
1.00
LOW
700
0.98
0.94
1.01
HIGH
900
1.01
1.05
0.99
TXC024D4+BAY24X045
RATED
800
1.04
1.04
1.04
LOW
700
1.02
0.99
1.05
HIGH
900
1.05
1.09
1.03
TXC025C4
RATED
800
1.02
1.06
1.01
LOW
700
1.00
1.00
1.02
HIGH
900
1.03
1.13
1.00
TXC025C4+BAY24X045
RATED
800
1.02
1.07
1.01
LOW
700
1.00
1.00
1.02
HIGH
900
1.03
1.13
1.00
TXC025D4
RATED
800
1.02
1.06
1.01
LOW
700
1.00
1.00
1.02
HIGH
900
1.03
1.13
1.00
TXC025D4+BAY24X045
RATED
800
1.02
1.07
1.01
LOW
700
1.00
1.00
1.02
HIGH
900
1.03
1.13
1.00
TXC030C4
RATED
800
1.04
1.05
1.02
LOW
725
1.03
1.01
1.03
HIGH
925
1.06
1.13
1.01

TTB024C

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)


MBTUH MBTUH SYST
INDOOR MODEL
CFM
TOT
SEN
KW
TXC030C4+BAY24X045
RATED
800
1.04
1.05
1.02
LOW
725
1.03
1.01
1.03
HIGH
925
1.06
1.13
1.01
TXC030D4
RATED
800
1.04
1.05
1.02
LOW
725
1.03
1.01
1.03
HIGH
925
1.06
1.13
1.01
TXC030D4+BAY24X045
RATED
800
1.04
1.05
1.02
LOW
725
1.03
1.01
1.03
HIGH
925
1.06
1.13
1.01
TXC031C4
RATED
800
1.04
1.10
1.02
LOW
725
1.03
1.05
1.03
HIGH
950
1.06
1.19
1.01
TXC031C4+BAY24X045
RATED
800
1.04
1.10
1.02
LOW
725
1.03
1.06
1.03
HIGH
950
1.07
1.19
1.01
TXC031D4
RATED
800
1.04
1.10
1.02
LOW
725
1.03
1.05
1.03
HIGH
950
1.06
1.19
1.01
TXC031D4+BAY24X045
RATED
800
1.04
1.10
1.02
LOW
725
1.03
1.06
1.03
HIGH
950
1.07
1.19
1.01
TXC035C4
RATED
800
1.03
1.04
1.01
LOW
725
1.02
1.00
1.02
HIGH
925
1.05
1.11
1.00
TXC035C4+BAY24X045
RATED
800
1.03
1.04
1.01
LOW
725
1.02
1.00
1.02
HIGH
925
1.05
1.11
1.00
TXC035D4
RATED
800
1.03
1.04
1.01
LOW
725
1.02
1.00
1.02
HIGH
925
1.05
1.11
1.00
TXC035D4+BAY24X045
RATED
800
1.03
1.04
1.01
LOW
725
1.02
1.00
1.02
HIGH
925
1.05
1.11
1.00
TXC036C4
RATED
900
1.07
1.17
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXC036C4+BAY24X045
RATED
900
1.07
1.18
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXC036D4
RATED
900
1.07
1.17
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXC036D4+BAY24X045
RATED
900
1.07
1.18
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXC037C4
RATED
900
1.07
1.17
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXC037C4+BAY24X045
RATED
900
1.07
1.17
1.05
LOW
750
1.05
1.08
1.05
HIGH
950
1.08
1.21
1.04
TXH025A4
RATED
800
1.00
1.00
1.00
LOW
700
0.98
0.94
1.01
HIGH
900
1.01
1.05
0.99
TXH025A4+BAY24X045
RATED
800
1.00
1.00
1.00
LOW
700
0.98
0.94
1.01
HIGH
900
1.01
1.05
0.99
TXH033A4
RATED
800
1.04
1.10
1.01
LOW
725
1.03
1.05
1.02
HIGH
950
1.06
1.18
1.00
TXH033A4+BAY24X045
RATED
800
1.04
1.10
1.01
LOW
725
1.03
1.05
1.02
HIGH
950
1.06
1.18
1.00

18

22-1689-05-0603 (EN)

Electrical
Data

SCHEMATIC DIAGRAMS
TTB012-024C

LEGEND

SYMBOL

From Dwg. 21C149013 P03


22-1689-05-0603 (EN)

19

Dimensions

TTB012-024 OUTLINE DRAWING


NOTE: ALL DIMENSIONS ARE IN MM (INCHES)

MODEL

TTB012C

5/8

1/4

TTB018C

5/8

1/4

TTB024C

3/4

5/16

NOTE: TABLE IN INCHES ONLY.

From Dwg. 21D147830 Rev. 2


20

22-1689-05-0603 (EN)

Mechanical
Specification Options

General
This unit is fully charged from the factory
for up to 15 feet of piping. This unit is
designed to operate at outdoor ambient
temperatures as high as 115F. Cooling
capacities matched with a wide selection
of air handlers and furnace coils that are
A.R.I. certified. The unit is UL listed for
outdoor application.
Casing
Unit casing is constructed of heavy
gauge, galvanized steel and painted with
a weather-resistant powder paint.
Refrigerant Controls
Refrigeration system controls include
condenser fan and compressor
contactor. High and low pressure controls
are inherent to the compressor. A factory
installed liquid line drier is standard.
Compressor
The Climatuff compressor features a
5-year limited warranty, internal over
temperature and pressure protection,
total dipped hermetic motor windings.
Other features include: roto lock suction
and discharge refrigerant connections,
centrifugal oil pump and low vibration
and noise.

22-1689-05-0603 (EN)

21

Condenser Coil
The Spine Fin coil is continuously
wrapped, corrosion resistant aluminum
with minimum brazed joints. This coil is
3/8 inch O.D. seamless aluminum glued
to a continuous aluminum fin. The coil is
protected on all four sides by louvered
panels and has a 5-year limited warranty.
Low Ambient Cooling
As shipped, this unit has a cooling
capability to 55F. The addition of an
evaporator defrost control permits
operation to 40F. The addition of an
evaporator defrost control with TXV
permits low ambient cooling to 30F.
Accessories
Thermostats Cooling only and heat/
cooling (manual and automatic
changeover). Sub-base to match thermostat and locking thermostat cover.
Quick Start Kit Required for system
with reciprocating compressors when
applied with indoor coils with non-bleed
expansion devices. Low voltage operation: to 180 V. for systems with reciprocating compressors; to 187 V. for
systems with scroll compressors.
Evaporator Defrost Control See Low
Ambient Cooling.

Notes

22

22-1689-05-0603 (EN)

Notes

22-1689-05-0603 (EN)

23

Trane
A business of
American Standard Companies
www.trane.com

Literature Order
Order Number
Number

SS-PRC007-EN
SS-PRC018-EN

File Number
Number

PL-UN-SS-PRC018-EN
06/03

Supersedes

SS-PRC007-EN
TTB-D-7
12/00 2/02

Stocking Location

PI Louisville & Webb/Mason Houston


Webb/Mason-Houston

Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.

P.I.

Вам также может понравиться