PERLINDUNGAN

Oleh:
RAIS BIN MAAT
Institut latihan dan Pembangunan
Infrastruktur Ikram

Perlindungan

IKRAM

TUJUAN PERLINDUNGAN

Menyelamatkan nyawa manusia & haiwan


Mengelakkan kecederaan kepada manusia
Mengelakkan kemusnahan harta benda
Mengelakkan kerosakan mesen-mesen
elektrik
Mengelakkan kerugian
Image dan reputasi sesebuah organisasi
Perlindungan

IKRAM

CIRI-CIRI PERLINDUNGAN
Bertindak pantas tetapi hanya apabila betulbetul perlu
Sensitif tetapi pada keadaan yang perlu
Stabil
Mempunyai kepemilihan (selectability)
Keboleharapan (reliability)
Boleh membezakan diantara temporary
overload dan real overload
Perlindungan

IKRAM

PEMBEZALAYANAN
(DISCRIMINATION)
Mengadakan perbezaan tahap arus atau
masa atau kedua-duanya sekali pada setiap
peringkat litar supaya bahagian yang
mengalami kerosakan dapat dihadkan agar
ia tidak melibatkan bahagian lain.
Pembezalayanan Arus
Pembezalayanan Masa
Pembezalayanan Arus dan Masa
Perlindungan

IKRAM

DISCRIMINATION

Bhg ini saja


trip
Perlindungan

IKRAM

DISCRIMINATION
(CURRENT)

Perlindungan

IKRAM

Perlindungan

IKRAM

DISCRIMINATION CURRENT

Perlindungan

IKRAM

JENIS-JENIS PERLINDUNGAN

Arus lebih (litar pintas)


Beban lebih (kW berlebihan)
Bocor ke bumi (earth leakage)
Rosak ke bumi (earth fault)
Kilat dan Voltage Surge (lightning)
Lampau panas (overheating)
Single phasing
Reverse phase rotation

Perlindungan

IKRAM

ARUS LEBIH
Berlaku litar pintas, nilai arus dalam
kiloampiar (kA)
Arus sebesar ini tidak mampu ditanggung
oleh litar walaupun untuk jangka masa yang
pendek pun (1 saat) dan ia akan merosakan
pemasangan atau peralatan
Pemutus litar hendaklah memutuskan litar
secepat yang mungkin (< 1 saat)
Perlindungan

IKRAM

10

BEBAN LEBIH
Disebabkan beban kilowatt yang berlebihan
dari yang telah dikadarkan (rated)
Tiada kerosakan pada litar
Nilai arusnya tidak terlalu tinggi (<150%)
Beban lebih yang kecil dan berbentuk
sementara boleh ditanggung oleh litar tanpa
kesan yang memudaratkan
Perlindungan

IKRAM

11

HAD BEBAN LEBIH


BEBAN DLM % DARI
BEBAN DIHADKAN

MASA

100%

CONTINUOUS

120%

WITHIN 5 MINUTES

150%

NOT MORE THAN 1


SECOND

Perlindungan

IKRAM

12

BOCOR KE BUMI
Terdapat arus mengalir ke bahagianbahagian
logam
yang
dibumikan
disebabkan penebatan yang telah lemah
Nilai arusnya kecil, lazimnya dihadkan
kepada tidak lebih 10 peratus dari arus
kadaran

Perlindungan

IKRAM

13

ROSAK KE BUMI
Sama seperti litar pintas tetapi ia berlaku
diantara konduktor fasa atau neutral ke
bumi
Arus kerosakan dalam kA

Perlindungan

IKRAM

14

ALAT PERLINDUNGAN

Fius
MCB (Miniature Circuit Breaker)
RCCB/ELCB (Residual Current C.Breaker)
RCBO (RCCB with Over current protection)
MCCB (Molded Case Circuit Breaker)
ACB (Air Circuit Breaker)

Perlindungan

IKRAM

15

PRINSIP KERJA
Haba (fius dan thermal overload relay)
Magnet (MCB, MCCB, RCCB)
Haba & Magnet (MCCB jenis tertentu)

Perlindungan

IKRAM

16

FIUS
Alat perlindungan paling awal dicipta yang
menggunakan prinsip apabila arus mengalir
haba akan terhasil dan haba yang banyak
hasil dari arus yang tinggi boleh
meleburkan elemen fius dan memutuskan
bekalan

Perlindungan

IKRAM

17

JENIS-JENIS FIUS
Fius dawai
Fius katrij (catridge fuse)
Fius HRC (high rupturing capacity) atau
HBC (high breaking capacity)

Perlindungan

IKRAM

18

FIUS DAWAI

Murah
Dalam bentuk gelong standard 5A,10A,15A
Tiada melting point tertentu
Apabila terbakar merosakkan fuse base &
carrier akibat arka yang kuat
Sesuai untuk pole fuse, fius tiang lampu
jalan dimana risiko kebakaran rendah

Perlindungan

IKRAM

19

FIUS DAWAI

Perlindungan

IKRAM

20

FIUS DAWAI

Perlindungan

IKRAM

21

FIUS KATRIJ
Elemen fius berada didalam bekas kaca
lutsinar dan logam penutup dikedua-dua
hujungnya.
Elemen fius boleh dilihat
Untuk kadaran arus yang kecil bagi voltan
240V, kadaran yang lebih untuk 12V DC.
Banyak digunakan di dalam peralatan
elektrik dan kenderaan.
Perlindungan

IKRAM

22

FIUS
KATRIJ

Perlindungan

IKRAM

23

FIUS HRC
Kadaran kA nya tinggi sehingga 100kA
Terdapat melting point
Elemen fius berada didalam arc quenching
powder (serbok silicon halus)
Bahagian luar dibuat dari bahan ceramik
yang kukuh (porcelain)
Telinga fius (tag) dikedua-dua hujung fius
dibina kukuh
Perlindungan

IKRAM

24

HRC FUSE CROSS SECTION

Perlindungan

IKRAM

25

FIUS HRC
(Centre tag
Dan Off tag)

Perlindungan

IKRAM

26

FIUS HRC
EMPATSEGI

Perlindungan

IKRAM

27

RCCB/ELCB
Residual
current
circuit
breaker
menggunakan prinsip keseimbangan medan
magnet diantara pengalir hidup dan neutral
(jenis satu fasa) atau keseimbangan medanmedan didalam sistem tiga fasa (jenis tiga
fasa).
Ia memberikan perlindungan bocor ke bumi
/ rosak ke bumi dan tidak memberi
perlindungan arus lebih atau beban lebih.
Perlindungan

IKRAM

28

RCCB

Perlindungan

IKRAM

29

RCCB

Perlindungan

IKRAM

30

RCCB

Perlindungan

IKRAM

31

KADARAN RCCB

Arus beban 40A, 63A, 100A, 1ph, 3ph


Kepekaan 10mA, 30mA, 100mA, 300mA
10mA (kidding machine)
30mA (litar soket outlet 13A)
100mA (litar lampu DB satu fasa)
300mA (litar lampu DB tiga fasa)
Nota: RCCB tiga fasa sudah tidak digalakkan
lagi penggunaannya.
Perlindungan

IKRAM

32

RCCB 10mA

Perlindungan

IKRAM

33

RCCB
63A, 30mA

Perlindungan

IKRAM

34

Perlindungan

IKRAM

35

SOLID EARTHING
Bermakna perlindungan yang tidak
menggunakan RCCB/ELCB dengan syarat
rintangan pembumian adalah baik dan
pemasangan tiada kemungkinan dihampiri
oleh kanak-kanak dan orang awam yang
tiada pengetahuan khusus mengenai bahaya
elektrik. Hanya fius atau MCB sahaja
digunakan untuk tujuan perlindungan.
Perlindungan

IKRAM

36

EARTH FAULT CURRENT FLOW

Perlindungan

IKRAM

37

SISTEM PEMBUMIAN

CPC circuit protective conductor


Terminal bumi DB
Earthing conductor
Earthing electrode
Equipotential bonding

Perlindungan

IKRAM

38

BAHAGIAN
BAHAGIAN
SISTEM
PEMBUMIAN

Perlindungan

IKRAM

39

SAIZ-SAIZ
PENGALIR
BUMI

Perlindungan

IKRAM

40

ELEKTROD
BUMI

Perlindungan

IKRAM

41

EARTH CHAMBER

Perlindungan

IKRAM

42

EARTH CLIP

Perlindungan

IKRAM

43

EARTH
BAR
CLIP

Perlindungan

IKRAM

44

TEST
POINT

Perlindungan

IKRAM

45

MINIATURE CIRCUIT BREAKER


(MCB)

Ia dicipta untuk menggantikan fius sebab fius perlu


ditukar setiap kali ianya terbakar.
Menggunakan prinsip medan magnet
Tindakannya pantas, sesuai untuk arus lebih
Kadaran kA tidak tinggi
Terdapat gelong bersiri dengan konduktor membawa
arus beban
Apabila terpelantik disebabkan arus lebih ia boleh di
RESET dan digunakan semula tanpa perlu
menggantikannya dengan yang baru.
Untuk kegunaan satu fasa, sehingga 32A
Perlindungan

IKRAM

46

MINIATURE CIRCUIT BREAKER

Perlindungan

IKRAM

47

MCB

Perlindungan

IKRAM

48

Perlindungan

IKRAM

49

MOULDED CASE CIRCUIT BREAKER


(MCCB)

Prinsip asas sama dengan MCB


Untuk kegunaan tiga fasa, sehingga 1600A
Menggantikan fius suis atau ACB
Mempunyai shunt trip coil untuk earth fault
trip dan juga overload trip
Kadaran kA sehingga 50kA
Boleh ditatah menggunakan geganti
Perlindungan

IKRAM

50

MCCB

Perlindungan

IKRAM

51

AIR CIRCUIT BREAKER (ACB)


ACB yang asas adalah sebuah pengasing
sahaja, tidak boleh trip sendiri kecuali
dipasang shunt trip coil yang disambungkan
kepada geganti.
Mengandungi 3 atau 4 kutub
Diperbuat dari logam oleh itu ia kuat dan
kukuh berbanding dengan MCCB
Kadaran kA sehingga 50kA
Kadaran arus dari 600A hinggalah 8000A
Perlindungan

IKRAM

52

ACB

Perlindungan

IKRAM

53

SHUNT TRIP COIL


Gelong kecil yang menarik mechanism
pemutus litar untuk terpelantik.
Mendapat bekalan dari busbar atau bateri
melalui kawalan trip contact geganti.
Kadaran voltan: 240AC, 30V DC
Short time rating

Perlindungan

IKRAM

54

SHUNT TRIP COIL

Perlindungan

IKRAM

55

ALATUBAH ARUS (C.T)


Menggunakan prinsip alatubah
mendapatkan arus yang kecil tetapi
nisbah tertentu supaya sesuai
kadaran geganti atau meter.
Mengelakkan sambungan terus
busbar supaya lebih selamat dan
dikendalikan.
Perlindungan

IKRAM

untuk
dengan
dengan
kepada
mudah

56

CURRENT TRANSFORMER

Perlindungan

IKRAM

57

CURRENT TRANSFORMER

Perlindungan

IKRAM

58

CURRENT
TRANSFORMER

Perlindungan

IKRAM

59

CURRENT TRANSFORMER

Perlindungan

IKRAM

60

Perlindungan

IKRAM

61

CT & RELAY CONNECTION FOR HT INSTALLATION


2 O/C & 1 E/F

Perlindungan

IKRAM

62

Z C.T
BUSBAR

Perlindungan

IKRAM

63

Z C.T

Perlindungan

IKRAM

64

Z C.T
BUSBAR

Perlindungan

IKRAM

65

JENIS ALATUBAH ARUS


Jenis Perlindungan sambungan
ke geganti
Jenis Pengukuran sambungan ke
ammeter, kW meter, kWh meter,
P.F meter, P.F regulator.
Perlindungan

IKRAM

66

KLAS ALATUBAH ARUS


Kelas Perlindungan kelas 5P dan 10P
Kelas Pengukuran kelas 0.1 hingga 5

Perlindungan

IKRAM

67

KLAS C.T PERLINDUNGAN


5P5, 5P10, 5P15, 5P20, 5P30
10P5, 10P10, 10P15, 10P20, 10P30
First number composite error / ALF
(accuracy limit factor)
P protection type
Second number multiple of fault current
Perlindungan

IKRAM

68

KLAS C.T PENGUKURAN

0.1 (Lab / calibration function)


0.2 (Accurate revenue application)
0.5 (Revenue application)
1.0 (Normal application)
3.0 (Non revenue application)
5.0 (Estimate reading)

Perlindungan

IKRAM

69

KETEPATAN C.T
Klas

5P

10P

Perlindungan

Current error at
rated primary
current (%)
1
3

IKRAM

Accuracy Limit
Factor (ALF) /
Composit Error
5

10

70

BURDEN C.T
Kuasa alatubah arus dalam VA kadaran
standard ialah 2.5, 5, 7.5, 10, 15, 30VA.
Beban
tanggungan
ialah
wayer
penyambungan ke geganti atau meter,
gelong didalam geganti atau meter.
Mengatasi susut voltan pada kabel
sambungan.
Perlindungan

IKRAM

71

UJIAN-UJIAN C.T
Ujian Nisbah (Primary Injection)
Ujian Kemagnetan
Ujian Kekutuban (Polarity Test)

Perlindungan

IKRAM

72

PRIMARY INJECTION TEST

Perlindungan

IKRAM

73

UJIAN KEKUTUBAN

Perlindungan

IKRAM

74

MAGNETISATION TEST

Perlindungan

IKRAM

75

MAGNETISATION
CURVE

Perlindungan

IKRAM

76

GEGANTI
Satu
komponen
perlindungan
yang
berfungsi untuk menentukan pada tahap
kerosakan
tertentu yang memerlukan
pemutus litar terpelantik. Tahap kerosakan
adalah nilai tatahan yang di set terlebih
dahulu. Trip contact akan tertutup dan
menyalurkan bekalan kepada shunt trip coil
untuk membuka pemutus litar.
Perlindungan

IKRAM

77

GEGANTI BEBAN LEBIH


Selalunya digunakan untuk motor. Biasanya
mempunyai dua ciri-ciri yang berbeza
dimana ia boleh menampung beban lebih
yang tinggi semasa motor masih sejuk
Cold or starting curve during starting
Hot or running curve when motor is hot,
usually after being on full load for more
than 30 minutes
Perlindungan

IKRAM

78

GEGANTI ARUS LEBIH


Can have any of the following
characteristics:
Inverse definite minimum time (IDMT)
Definite time high set with a time delay
Instantaneous operate in about 20-40ms
Microprosessor relays usually combine all
the three characteristics
Perlindungan

IKRAM

79

PRINSIP GEGANTI
Magnetic effect
Thermal effect
Magnetic and Thermal effect

Perlindungan

IKRAM

80

JENIS-JENIS GEGANTI
Geganti sertamerta (instantenous relay)
Geganti lewat masa (IDMT relay Inverse
Definite Minimum Time)

Perlindungan

IKRAM

81

JENIS-JENIS GEGANTI

Attracted armature relay


Induction relay
Thermal relay
Mechanical relay
Static relay

Perlindungan

IKRAM

82

ATTRACTED ARMATURE RELAY


Comprises an iron-cored electromagnet that
attracts movable armature, which is hinged
to operate relay contacts
Instantaneous operation
AC relays have split magnetic pole with
shading loop fitted on one half of the pole
to prevent relay chattering
Perlindungan

IKRAM

83

INDUCTION RELAYS
Comprises an electromagnetic system
similar to induction kWh meter
Has two electromagnets with rotating disc
in between two magnets. Can be energised
from a single or two different inputs
Widely used for IDMT relays. Time control
by controlling amount of disc movement.
Current setting adjustment by use of plug
bridge for selection of suitable tapping
Perlindungan

IKRAM

84

THERMAL RELAYS
Utilises bending of a bimetallic strip when
heated by a current
Used for overload protection because of its
slow action to heat the bimetallic strip

Perlindungan

IKRAM

85

STATIC RELAYS

Utilising electronic components


Faster action
Better accuracy and consistency
Low CT and PT burdens
Multiple characteristics
Support additional features communication, fault
recording, operating time measurement,
current/voltage reading and built-in circuit breaker
failure protection

Perlindungan

IKRAM

86

MECHANICAL RELAY
Respond to pressure,
temperature, fluid flow, etc

Perlindungan

IKRAM

liquid

level,

87

BINAAN GEGANTI
Hinged Armature Type
Induction Cub
Magnetic Overload with Plunger (Oil Dash
Pot)
Attracted Armature (Inst. O/C & E/F)

Perlindungan

IKRAM

88

TIME LAG FUSE


Geganti peringkat awal dimana time lag
fuse diselarikan dengan gelong trip coil.
Apabila fius lebur semua arus akan melalui
trip coil dan trip contact akan menutup dan
memberi tenaga kepada shunt trip coil
untuk membuka pemutus litar.

Perlindungan

IKRAM

89

Trip Coil

Perlindungan

Time Lag Fuse

IKRAM

90

TIME LAG FUSE

Perlindungan

IKRAM

91

KADARAN TIME LAG FUSE

Perlindungan

SWG 17

15A

SWG 18

12.5A

SWG 19

10A

SWG 21

7.5A

SWG 22

6.25A

SWG 23

5A

SWG 29

2.5A
IKRAM

92

Perlindungan

IKRAM

93

Perlindungan

IKRAM

94

GEGANTI OIL DASH POT


Geganti arus lebih/beban lebih generasi kedua
selepas time lag fuse.
Menggunakan minyak silicon sebagai damper
untuk mendapatkan stability.
Harganya murah, bersaiz kecil, boleh dipercayai,
stabil tetapi tidak begitu tepat dan tatahannya agah
rumit dan mengambil masa.
Sesuai untuk papan suis utama dan papan suis
kecil dimana ketepatan bukanlah perkara kritikal.
Perlindungan

IKRAM

95

OIL DASH POT

Perlindungan

IKRAM

96

OIL DASH POT

Perlindungan

IKRAM

97

Perlindungan

IKRAM

98

OIL DASH POT

Perlindungan

IKRAM

99

INSTANTENOUS O/C, O/L


Generasi ketiga selepas oil dash pot, terdapat plug
setting bridge untuk memilih tatahan arus, trip
coil, trip contact dan indicator flag.
Hanya tatahan arus sahaja perlu dibuat
Lebih tepat dan mudah ditatah
Tidak perlukan minyak
Harganya lebih mahal
Selalunya jenis attracted armature & plunger

Perlindungan

IKRAM

100

GEGANTI
SERTAMERTA
EARTH FAULT

Perlindungan

IKRAM

101

INSTANTENOUS EARTH FAULT RELAY

Perlindungan

IKRAM

102

EARTH
FAULT
RELAY
TERMINAL

Perlindungan

IKRAM

103

Perlindungan

IKRAM

104

TERMINAL CONNECTION
12
TRIP CIRCUIT
34
TRIP CIRCUIT
56
KOSONG
78
KOSONG
9 10 C.T CONNECTION

Perlindungan

IKRAM

105

CONNECTION
AT THE BACK
OF THE
RELAY

Perlindungan

IKRAM

106

CONNECTION DIAGRAM

Perlindungan

IKRAM

107

STATIC
OVERCURRENT
RELAY

Perlindungan

IKRAM

108

STATIC
EARTH
FAULT
RELAY

Perlindungan

IKRAM

109

STATIC
O/C & E/F
RELAY

Perlindungan

IKRAM

110

INSTANTENOUS E/F
Jenis yang sama dengan geganti
instantenous o/c tetapi ia disambungkan
kepada alatubah arus yang dipasang pada
neutral busbar untuk mengesan earth
fault/earth leakage.
Tatahan hanya pada 10% atau 0.5A
Hanya satu sahaja diperlukan
Jenis attracted armature
Perlindungan

IKRAM

111

INSTANTENOUS E/F
CAG 11 Fixed settings up to 20 amps a.c
or d.c
CAG 12 10 40%, 20 80%, 50
200% of 0.5A, 1A or 5A a.c adjustable in
seven equal steps, 30 120% of 5A and 80
320% of 5A a.c
CAG 13 100 400%, 200 800% or
400 1500% of 0.5A, 1 A or 5A
Perlindungan

IKRAM

112

CURRENT SETTING
THREE TYPES OF SETTING:
Fixed setting (CAG 11)
Variable in seven equal steps by plug
tapping bridge (CAG 12)
Continuously variable by knurled knob
against a calibrated scale (CAG 13)

Perlindungan

IKRAM

113

INSTANTANEOUS
E/F
RELAY

Perlindungan

IKRAM

114

TRIP
CONTACT

Drop Flag
Perlindungan

IKRAM

Trip coil

115

DROP FLAG
TRIP
INDICATOR

Perlindungan

IKRAM

116

CONTINUOUSLY
ADJUSTABLE
RELAY
CAG 13

Perlindungan

IKRAM

117

IDMT O/C, O/L


Mempunyai dua tatahan iaitu arus dan masa: PSM
(plug setting multiplier) untuk arus dan TMS (time
multiplier setting / time dial) untuk masa.
PSM dalam unit arus (2.5A hingga 10A) atau %
(50% hingga 200%) tetapi TMS hanyalah satu
angka pendharab dari 0 hingga 1. Masa dalam saat
diperolehi dari geraf berdasarkan gandaan arus
kerosakan.
Selalunya jenis induction disc atau solid state
relay.
Perlindungan

IKRAM

118

PLUG SETTING MULTIPLIER


(PSM)/PLUG BRIDGE (O/C RELAY)

50%

75%

2.5A 3.75A

Perlindungan

100% 125% 150% 175% 200%


5A

6.25A 7.5A 8.25A

IKRAM

10A

119

IDMT RELAY
The highest current tap is automatically
selected when the plug is removed, so that
adjustments can be made on load without
open-circuiting the current transformer
It has high torque movement to ensure
consistent timing even under adverse
conditions, and a low burden and overshoot
Adjustment of the time setting is made by
rotating a knurled moulded disc against a
graduated time multiplier scale
Perlindungan

IKRAM

120

STARTING CURRENT
Starting current is 103% to 105% of current
setting
Closing current is 115% of current setting
(117% if fitted with a mechanical operation
indicator)

Perlindungan

IKRAM

121

TIME SETTING
0 1.3 seconds at 10 times current setting
or 0 3.0 seconds at 10 times current
setting
Resetting time with time multiplier at 1.0
the resetting time are 4 seconds and 9
seconds respectively

Perlindungan

IKRAM

122

IDMT
RELAY

Perlindungan

IKRAM

123

Perlindungan

IKRAM

124

IDMT RELAY

Perlindungan

IKRAM

125

JENIS-JENIS IDMT

Long Time Delay Standby (GDG 12)


Inverse Time O/C & E/F (CDG 11)
Very Inverse (GDG 13)
Definite Minimum Time
Inverse Definite Minimum Time

Perlindungan

IKRAM

126

RELAY
CHARACTERISTIC

Perlindungan

IKRAM

127

INST. &
IDMT
RELAY

Perlindungan

IKRAM

128

TIME
GRADING

Perlindungan

IKRAM

129

GRADING
MARGIN

Perlindungan

IKRAM

130

Perlindungan

IKRAM

131

IDMT E/F
Serupa dengan IDMT O/C tetapi disambung kepada
c.t neutral untuk perlindungan earth fault atau earth
leakage.
Hanya satu unit sahaja diperlukan
PSM dari 10% hingga 40% dalam 7 step yang sama
Lazimnya tatahan TMS ialah pada kedudukan 0.1
tetapi bukanlah satu kemestian
Terdapat fixed contact dan moving contact

Perlindungan

IKRAM

132

PLUG SETTING MULTIPLIER


(PSM)/PLUG BRIDGE (E/F RELAY)

10%

15%

20%

25%

30%

35%

40%

0.5A 0.75A 1.0A 1.25A 1.5A 1.75A 2.0A

Perlindungan

IKRAM

133

DIRECT &
INDIRECT
ACTING

Perlindungan

IKRAM

134

EARTH LEAKAGE RELAY


(ELR)
Untuk penggunaan papan suis berkadaran
100A hingga 400A.
Disambungkan kepada Z c.t
Tatahan arus dari 30mA hingga 1000mA
melalui micro switch atau terminal yang
berlainan
Terdapat juga jenis tatahan arus dan masa
Perlindungan

IKRAM

135

Perlindungan

IKRAM

136

Perlindungan

IKRAM

137

Perlindungan

IKRAM

138

Perlindungan

IKRAM

139

ELR CONNECTION DIAGRAM

Perlindungan

IKRAM

140

SINGLE PHASING RELAY


Apabila salah satu fasa mengalami
gangguan bekalan peralatan tiga fasa akan
mengalami perjalanan yang tidak sempurna
dan boleh mengakibatkan kerosakan.
Geganti ini akan menyebabkan pemutus
litar terbuka jika salah satu fasanya
mengalami gangguan.
Selalunya dipasang pada pemula motor tiga
fasa yang besar seperti air-condition chiller.
Perlindungan

IKRAM

141

REVERSE PHASE SEQUENCE RELAY


Sekali sekala turutan fasa akan terbalik
disebabkan berlaku kesilapan dalam kerjakerja penyambungan kabel. Motor tiga fasa
akan berpusing terbalik, dan boleh
membahayakan atau merosakan peralatan
tertentu seperti mesen atau air condition
chiller.
Geganti ini akan menyebabkan pemula
motor tidak dapat berfungsi untuk
menjalankan motor.
Perlindungan

IKRAM

142

UNDERVOLTAGE RELAY
Jika voltan bekalan jatuh ketahap yang
ditetapkan seharusnya bekalan perlu
diputuskan untuk menghindarkan bahaya
dan
gangguan.
Geganti
ini
akan
menyebabkan pemutus litar akan terbuka
jika berlaku keadaan sedemikian.

Perlindungan

IKRAM

143

RESTRICTED E/F RELAY


Geganti REF dipasang untuk melindungi
alatubah atau generator jika berlaku
kerosakan ke bumi didalam alat-alat
tersebut. Ia hanya melindungi peralatan
tersebut dan bukannya pemasangan,
perlindungan ini kadang-kadang dipanggil
sebagai unit protection.

Perlindungan

IKRAM

144

CURRENT SETTING O/C


Bergantung kepada kehendak maksima
sesuatu pemasangan tetapi nilai tepat
tatahan pada PSM (Plug Setting multiplier)
tidak selalu boleh diperolehi. Oleh itu nilai
tertinggi paling hampir dipilih, selalunya
pada peringkat commissioning tatahan di
set pada 75% atau 3.75A.

Perlindungan

IKRAM

145

CURRENT SETTING E/F


Current setting untuk E/F relay lazimnya
ialah pada 10% atau 0.5A
Ia tidak bergantung kepada kehendak
maksima sesuatu pemasangan

Perlindungan

IKRAM

146

TIME SETTING O/C & E/F


Selalunya TMS (Time Multiplier Setting) di
set pada kedudukan 0.1 tetapi bukanlah satu
kemestian, ia perlu dipastikan dengan
membuat pengiraan time grading supaya
hanya pada tatah arus dan masa tertentu
sahaja geganti tersebut perlu bertindak.

Perlindungan

IKRAM

147

DURATION OF DISTURBANCES

Overvoltage (microsecond)
Short circuit (milisecond)
Earth fault (milisecond)
Undervoltage (milisecond)
Underfrequency (second)

Perlindungan

IKRAM

148

TIME
CURRENT
CHARACTERISTIC

Perlindungan

IKRAM

149

TIME
CURRENT
CHARACTERISTIC

Perlindungan

IKRAM

150

TIME
CURRENT
CHARACTERISTIC

Perlindungan

IKRAM

151

UJIAN PRIMARY INJECTION

Untuk menentukan nisbah alatubah arus


Untuk menatah geganti
Dibuat sebelum bekalan disambungkan
Alat primary injection test set digunakan

Perlindungan

IKRAM

152

UJIAN SECONDARY
INJECTION
Untuk menguji geganti agar dapat berfungsi
seperti apa yang diharapkan
Untuk menatah geganti
Arus dialirkan terus kepada geganti tanpa
penglibatkan alatubah arus
Boleh dilakukan tanpa memutuskan bekalan
Dilakukan dalam kerja-kerja senggaraan
Menggunakan alatuji secondary injection
test set
Perlindungan

IKRAM

153

UJIAN PELANTIKAN
Ujian pelantikan (trip test) dilakukan
setelah tatahan di set untuk memastikan
sistem perlindungan dan pemutus litar dapat
betul-betul berfungsi apabila berlaku
keadaan tidak normal yang telah ditentukan
sebelumnya. Ini termasuklah geganti, sistem
pendawaian, penamatan, gelong shunt trip
secara keseluruhannya.
Perlindungan

IKRAM

154

TRIPPING SUPPLIES
AC Voltage sometimes used to trip ACB,
weakness that trip supply may be lost at
critical moment
DC Voltage Most common type of
tripping power because of high reliability.
Normally 30V for small stations, 110V for
major intake points and outdoor substations
and 220V in large power stations. Bigger
DC system are more expensive
Perlindungan

IKRAM

155

DC TRIPPING SUPPLY
For 110V supply, common to have two
battery chargers and two battery banks.
Normally connected in parallel but may be
separated for maintenance or boost charge
Normally only trip coil per CB but possible
to have two such coils on special
requirement
Perlindungan

IKRAM

156

INDEX OF
PROTECTION

Perlindungan

IKRAM

157

LIGHTENING
PROTECTION

Perlindungan

IKRAM

158

ORANG KOMPETEN
Orang kompeten yang dibenarkan membuat
atau mengendoskan ujian-ujian yang dibuat
ialah Jurutera Perkhidmatan yang berdaftar
dengan Suruhanjaya Tenaga dan masih sah
untuk melaksanakan kerja tersebut.

Perlindungan

IKRAM