PowerGate inverters offer market-leading reliability, efficiency and ease-of-use for large-scale grid-connected
photovoltaic systems. A single-enclosure solution, the utility-grade PowerGate incorporates a high-efficiency
transformer and both AC and DC switchgear that disconnect the inverter at night, minimizing tare losses. A highly
efficient MPPT tracking algorithm and intelligent wake-up routine further maximize net energy harvest. The
PowerGate is certified to UL-1741 and is available with a variety of local and remote data monitoring options.
Utility-Grade Design
Single enclosure minimizes field wiring Integrated highefficiency transformer Optional integrated sub-array
combiner Internal AC and DC switchgear Top and
bottom cable entry Top-lifting eye-bolts and forklift base
Superior Energy Harvesting
PV Sub-arrays
See
Note 2
See
Note 4
See
Note 3
AC
Breaker
n
To
Grid
3
DC Surge
Protection
See
Note 1
AC Surge
Protection
Notes:
1.
Optional fused sub-array combiner simplifies array wiring and allows
optional PV-Zone sub-array monitoring
2.
Contactor provides backfeed protection and automatic array fault
isolation
3.
Integrated high-efficiency transformer
4.
Integrated AC contactor opens at night and minimizes standby losses
5.
Pre-charge circuit minimizes in-rush current and nuisance trips
See Note 5
Control
Page 1 of 2
D
208
84
100
92.5
30
AE-30-60-PV
F
E
240
120/240
73
37
90
46
NA
93
96
2 x 75 Amps
1300 [591]
7.16
Power (kWac)
Model #
Voltage Suffix
AC Output Voltage (L-L Vac)
Nom Current/Phase (Amps)
Max Fault Current/Phase (Amps)
CEC Efficiency (%)
Nominal DC Current (Amps)
Optional PV Sub- Array Combiner (# of fused strings)
Max. Weight (lbs) [kg]
Max Heat Dissipation (kBTU/hour)
75
AE-75-60-PV
D
F
A
208
240
480
208
181
91
260
230
115
95
NA
95.5
240
6 x 100 Amps
2600 [1180]
10.5
Power (kWac)
Model #
Voltage Suffix
AC Output Voltage (L-L Vac)
Nom Current/Phase (Amps)
Max Fault Current/Phase (Amps)
CEC Efficiency (%)
Nominal DC Current (Amps)
Optional PV Sub- Array Combiner (# of fused strings)
Max. Weight (lbs) [kg]
Max Heat Dissipation (kBTU/hour)
135
AE-135-60-PV
D
F
208
240
375
325
469
407
95
NA
431
9 x 100 Amps
3500 [1600]
18.5
A
480
163
205
95.5
A
480
36
45
93
D
208
278
350
94.5
50
AE-50-60-PV
F
240
121
152
93
160
3 x 100 Amps
1778 [808]
9.3
D
208
139
175
94.5
100
AE-100-60-PV
F
240
241
290
95
319
6 x 100 Amps
3250 [1475]
13.6
225
AE-225-60-PV
A
D
480
208
270
625
330
960
94.5
NA
718
12 x 100 Amps
5650 [2570]
44.3
A
480
60
75
93
A
480
121
150
94.5
500
AE-500-60-PV-A
A
480
602
720
95
1595
30 x 100 Amps
5400 [2455]
79
330-600
295-600
600
59.5 - 60.5
+/- 10
1
<3
95-97
Fan Forced
<65
-20 to 50
50
NEMA 3R
11 gauge Powder
Coated Steel - Seismic
Zone 4
Relative humidity(%)
Altitude (ft) [m]
Display
Computer interface / type
Communicaton Protocol
Standard Warranty
Certification
Compliances
95
6000 [1830]
LCD 4 Line x 20
RS232, RS485
Modbus
5 Year
UL 1741
IEEE 929, 1547, 519,
ANSI 62.41
Optional Features
PV View Remote Monitoring
PV Zone Sub-Array Monitoring
Environmental monitoring
External revenue grade meter
Ground Fault Interrupt
Note: To achieve 295 volts Low tap must be specified at time of order. Unit will derate if grid voltage is < nominal.
Dimensions:
Please see model specific data sheets.
All specifications subject to change without notice.
Ph. 905.639.4692
Fx. 905.639.0961
pvsales@satcon.com
www.satcon.com
Datasheet AEAll_Models_2