Service Manual

Rosemount Tank Radar Rex


Chapter 5 Calibration

5.3.2

308012En, Ed.2
May 2013

Hand dipping
Staff
Only one person should perform the manual ullage measurements in
order to guarantee good repeatability between measurements.

Hand dip tape


Use only one tape for the calibration. The tape should be made of steel
and calibrated by an approved testing institute. It must also be free from
bends and kinks.
The thermal expansion factor and calibration temperature shall also be
provided.

Manual dip hatch


A dip hatch should be available close to the level gauge. If the dip hatch
is far away from the level gauge, differences in roof movements may
result in large errors.

Procedure
Follow these instructions when you make hand dip measurements:

hand dip until you obtain three consecutive readings within 1 mm

correct the tape according to the calibration record

note the hand dipped ullage and the RTG level reading simultaneously.

Do not calibrate when

5-4

the tank is emptying or filling

agitators are running

when there are windy conditions

when there is foam on the surface.