Вы находитесь на странице: 1из 1

PROJECT :

CLIENT:
PROJ. NO. :
UNIT :

DATE :
BY :
REV :
DOC NO.:
Storage Tank - Emergency Venting Calculation

Input Data
Tank Diameter
Height of Liquid in Tank
Tank Design Pressure
Vapor Molecular Weight
Stored Liquid Latent Heat
Relieving Temperature
Environemtal Factor (F)

m
m
mbarg
---btu/lb
C
----

12.5
7.55
10
18
970.6
100
1

Calculation Results
Wetted area
Wetted area
Fire Heat Input
Relieving Temperature
Venting Capacity for Fire
Venting Capacity for Fire
Venting Capacity for Fire

m2
ft2
btu
R
SCFH
Nm3/hr
kg/hr

296.49
3191.37
14090000
672
274169
7359
5913