Вы находитесь на странице: 1из 1

Current in Amperes: x 1 at 25 kV, x 52.083 at 0.48 kV, x 1.736 at 14.4 kV and x 1.250 at 20 kV.

1000
2000 kVA FLA

11-LVCB GE ECS
Sensor:800.0 [A]
LTCS:1.00 LTM:0.90 LTB:2
Inst:10.00

5-Fuse
S&C SMU40 SLO 14.4KV
Rating: 100.0 [A]
14.40 [kV]

100

7-Transformer
Z=5.80 []
P=2000 [kVA]
0.48 [kV]
FLA=46.19 [A]

13-Motor Starting
Full Load:180.0 [A]
Locked Rotor:1800 [A]
Acc. Time:6.00 [s]
9-LVCB GE ECS
Sensor:800.0 [A]
LTM:0.90 LTB:2
STM: STB:
Inst:10.00

10-Motor Starting
Full Load:180.0 [A]
Locked Rotor:1800 [A]
Acc. Time:6.00 [s]

Time in Seconds

10

6-Cable
2/0 AWG (Aluminium)
CROSS LINK POLY.
(1/phase) 25.00 [kV]

4-Rel.Def.Time
Tap Range:[0.05 / 2.4] Tap:1.00
Pick Up:120.00 [A] TD:.5
CT:600:5 at 20.00 [kV]

3-Relay WEST CO-9


Tap Range:[0.25 / 12.0] Tap:7.00
Pick Up:840.00 [A] TD:4.0
CT:600:5 at 25.00 [kV]

12-LVCB GE ECS
Sensor:800.0 [A]
LTCS:1.00 LTM:0.90 LTB:2
Inst:10.00
14-Motor Starting
Main-Bus
Full Load:180.0 [A]
Locked Rotor:1800 [A]
Acc.Breaker-1
Time:6.00 [s]
52

51

51

Relay-1

0.1

51

600:5

15-Motor Starting
Fuse-1
Full Load:180.0
[A]
Locked Rotor:1800 [A]
Acc. Time:6.00 [s]

2000 INRUSH

CABLE-1
XFMR-1

16-LVCB GE ECS
Secondary Bus
Sensor:800.0 [A]
LTM:0.90 LTB:2 B1
STM: STB:
Inst:10.00
M
M1

B2

B3

M2

M3

B4

M4

Test Point ATest Point B


0.01
0.5

10

100

1000

TIME CURRENT CHARACTERISTIC CURVES


BY:
NO:
PLOTTING VOLTAGE:

25 kV

Study: F:\CYME\CYMTCC\Examples\demo.tcc

DATE:

10000

Вам также может понравиться