Вы находитесь на странице: 1из 1

SUMMARY , DURING INSPECTION OF CHEMICAL INJECTION NOZZLE INSTALLATION INSPECTION AT UTILITY , ON 27 AUGUST 2014

SL
NO

SPECIAL
COMMODTY NO

FLOW
DIRECTION

SLOT
OEIENTATION

LENGTH: FLANGE
BOTTOM TO CLOSED
END(mm)

SLOT SIZE:
LENGTH x WIDTH(mm)

LENGTH:FLANGE END
BOTTOM TO TOP OF
SLOT(mm)

LENGTH:FLANGE
TOP TO BOTTOM
OF PIPE(mm)
(INSIDE PIPE)

313

20 X 3

283

332

COMMENTS

SP-338

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

SP-337

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

313

20 X 3

283

332

SP-336

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

313

20 X 3

283

332

SP-332

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

341

50 X 5

265

358

SP-330

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

410

50 X 5

341

SP-329

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

410

50 X 5

SP-328

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

410

50 X 5

SP-331

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

410

50 X 5

SP-326

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

440

50 X 5

SP-333

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

333

20 X 3

300

360

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION
2) MECHANICAL MARKING FOUND ON QUILL
BODY

SP-327

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

342

50 X 5

267

360

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION
2) REQUIRED PIKOTEK GASKETS

12

SP-335

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

560

50 X 5

485

690

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION
2) REQUIRED PIKOTEK GASKETS

13

SP-334

DOWN STREAM
SIDE OF
INJECTION COIL
WITH RESPECT TO
FLOW DIRECTION

335

20 X 3

300

360

10

11

REMARKS

LENGTH:ACTUAL
LENGTH:FLANGE TOP
QUILL DIMENSION (L)
TO CENTRE OF THE
VALUE IN mm
HEADER LINE IN mm

INSTALLED

291

294.5

INSTALLED

291

294.5

INSTALLED

291

289.5

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION

INSTALLED

287

289

470

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION

INSTALLED

366

259.5

341

470

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION
2)BOTTOM OF CLOSED END TO BE CLEANED.

INSTALLED

363

364.5

341

470

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION

INSTALLED

365

357.5

341

470

1) TEMPORARY GASKET FOUND ON FLANGE


JOINT , FLANGE FACE SHOULD BE CLEANED
PRIOR TO INSTALLATION
2) MECHANICAL MARKING FOUND ON QUILL
BODY

INSTALLED

362

359.5

370

520

INSTALLED

391

383.5

INSTALLED

309

307.1

290

310

1)INSTALLED WITH SPIRAL


WOUND GASKET

507

446

1)INSTALLED WITH SPIRAL


WOUND GASKET

307

314.14

1) PICKLING TO BE DONE
2) PMI TO BE DONE

1) REQUIRED PIKOTEK GASKETS

1) FBE COATING REPAIRED


ATTACH , REPAIR REPORT
2)INSTALLED WITH SPIRAL
WOUND GASKET

Вам также может понравиться