Proposed Office Development at Tower 2, PJ Sentral EE5

Batch 29 Group 2

EE10

BASE

MS15
25

GOLD

ELECTRICAL
LIGHTING LEVELS

COST
IMPLICATI
ON
RM
250,000

1 Base Building Design

Base Building design office luminance level is designed to be around 500 Lux
as per IES/CIBSE recommendation.

2 MS1512 Design

In accordance to MS1525 Clause 6.2.2 (Table 13), the illuminance level for
building is designed to the maintained levels of 300 to 400 Lux
(recommended for general building areas and office). Maximum permissible
Lighting Power Density is 15W/m2 as per MS1525 Clause 6.3 (Table 14).

3 Gold Design

The building is designed to maintain the office lighting luminance level of no


more than specified in MS1525:2007 for 90% of NLA as measured at the
working plane 800mm measured from the floor level.

4 Summary of Scoring

Points Score in
Criteria
Summary of
Costing

Base Line

MS1525

Gold

RM750,000.00

RM550,000.00

RM781,200.00

Incremental cost of RM 231,200 to upgrade from MS1525 compliant to Gold


rating.

GBI NRNC Gold (Vertical Fins) RM 9.5 millions

Proposed Office Development at Tower 2, PJ Sentral EE5


Batch 29 Group 2

GBI NRNC Gold (Vertical Fins) RM 9.5 millions

5 Objective

To ensure office lighting level is not over-designed.

6 Requirements/ Target Code

1 Point: Demonstrate that office lighting design maintains a luminance level


of no more than specified in MS1525:2007 for 90% of NLA as measured at the
working plane measured from floor level

7 Strategy and Implementation


Design approach by use of Philips TBS424 2xTLS-28W HFP O light fittings completed
with high frequency electronic ballast with automatic dimming function for office
space.
Location

Office
Space

Fitting Selection
MS1525
T8 fitting c/w
magnetic
ballast

Gold
TL5 fitting c/w high
frequency electronic
ballast and auto
dimmer function

Minimum Required
Luminance (Lux)
MS1525
300-400

Gold
300

As for a gold building, the office lighting should not be over designed, therefore the
introduction of the LuxSense Automatic dimmer for all fittings to ensure control of
the lux levels within the 300 Lux range.
(Refer to Supporting documents for Gold Building Typical office floor
design simulation)

8 Cost Implication
9 Supporting Documents