IEC608705104InterfacetoNPCC
Equipment
NPPC
Nomenclature
Status
Indications
Double+
SOE
Single+SOE
AnalogValues
MW
Amp
Mvar
Volt
Commands
hz
P.F
Tap
Position
Other
Open/
Close
Raise/
Lower
Setpoint
ASDU
CASDU1
CASDU2
Analogmeasured
Information(AMI)
Value
InformationObject
Address
IOA1
IOA2
IOA3
Complete
Address
Max.
Min
960
Comments
132kVoverheadTransmissionLineE01*
Breakerposition
Busbardisconnectorposition
Linedisconnectorposition
Lineearthswitchposition
Breakerremotecommand
Local/remotepermit
Forexample(E1Q1)
x
x
x
x
x
x
x
CurrentphaseY
LinevoltagephaseRY
Busbar1voltagephaseRY
Busbar1frequency
Activepower
Reactivepower
Powerfactor
Differentialprotectiontrip
Distanceprotectiontrip
Breakerfailureprotectiontrip
Breakerfailureprotectiondirectintertripsent
Directintertripreceived
Powerswingblockingpickup
Switchontofaulttrip
Autoreclose
Autorecloseblocked
Autorecloseoperated
Differentialprotectioncommunicationfailure
Protectionrelayfailure
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
22kV/132kVTransformerBay(E03)**
Breakerposition
Busbardisconnectorposition
Linedisconnectorposition
Lineearthswitchposition
Breakerposition
Breakerremotecommand
Local/remotepermit
CurrentphaseY
BayvoltagephaseRY
BayvoltagephaseBR
Activepower
Reactivepower
Differentialprotectiontrip
Restrictedearthfaultprotectiontrip
Overcurrentprotectiontrip
Breakerfailureprotectiontrip
Lockoutrelayoperated
Protectionrelayfailure
CurrentphaseY
Activepower
Reactivepower
Powerfactor
Windingtemperaturetrip
Buchholzalarm
Buchholzmaintanktrip
OLTCposition
OLTCremotecommand
Local/remotepermit
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
132kVBusCouplerBay(E05)
Breakerposition
Busbar1disconnectorposition
Busbar2disconnectorposition
Breakerremotecommand
Local/remotepermit
CurrentphaseY
Busbarprotectiontripbusbar1
Busbarprotectiontripbusbar2
Busbarprotectiondifferentialcurrent
Breakerfailureprotectiontrip
Protectionrelayfailure
x
x
x
x
x
x
x
x
x
x
x
BusSection22kV
Breakerposition
Busbar1voltagephaseRY
Busbar1frequency
Busbar2voltagephaseRY
Busbar2frequency
x
x
x
x
x
NetElectricalOutput
Totalactivepowerdelivered
Totalreactivepowerdelivered
x
x
Telecom
Telecomlinkfaulty
Directtripoperated/received
Datalinkalarm
PLChardwarealarm
x
x
x
x
Auxiliary/Miscellaneous
Alarm1
Alarm2
Alarm3
Alarm4
Alarm5
Temperature
Humidity
Windspeed
Winddirection
Notes:
*IdenticalsignalstobeincludedforE02bay
**IdenticalsignalstobeincludedforE04bay
x
x
x
x
x
x
x
x
x
960=960A(120%ofratedvalue)asanexample