PLUMBING FIXTURE SCHEDULE

DESIGNATION FIXTURE TYPE C.W. H.W. WASTE MANUFACTURER MODEL NO. FAUCET / FLUSH VALVE ACCESSORIES REMARKS
WC-1 WATER CLOSET- FLUSH VALVE
WALL MOUNTED BARRIER-FREE
1" - 4" TOTO CT708 SLOAN- DUAL FLUSH
ECOS-8111-SF ( 1.6 GPF /1.1 GPF )
TOLIET SEAT- TOTO SC534 1, 2, 3, 4
Mt. Pleasant
WC-2 WATER CLOSET- FLUSH VALVE
WALL MOUNTED- CHILDREN'S
1" - 4" TOTO CT708 SLOAN- DUAL FLUSH
ECOS-8111-SF ( 1.6 GPF /1.1 GPF )
TOLIET SEAT- TOTO SC534 1, 2, 3, 4 Library
L-1 LAVATORY- 1/2" 1/2" 1 1/2" KOHLER SOHO SLOAN- OPTIMA SLOAN EAF-12 1, 2, 3, 5 3160 16th Street, NW
WALL MOUNTED BARRIER-FREE K-2084-L EAF-200-P-ISM ( 0.5 GPM ) PROVIDE PLUG-IN TRANSFORMER (T2) Washington, DC 20010
L-2 LAVATORY- 1/2" 1/2" 1 1/2" TOTO VERNICA SLOAN- OPTIMA SLOAN EAF-12 1, 2, 3, 5
UNDERCOUNTER BARRIER-FREE LT156 EAF-200-P-ISM ( 0.5 GPM ) PROVIDE PLUG-IN TRANSFORMER (T2)
SK-1 SINGLE COMPARTMENT SINK- 1/2" 1/2" 1 1/2" ELKAY DAYTON DELTA- TECK VANDAL RESISTANT FLOW CONTROL 1, 2, 3, 5
SELF RIMMING BARRIER-FREE GE12521L 29C2801 AERATOR ( 1.5 GPM )
U-1 URINAL- 3/4" - 2" SLOAN WEUS-1000.1301 SLOAN- OPTIMA TRANSFORMER (T1) SLOAN EL-154 1, 2, 4
ULTRA LOW FLOW -0.13 ES-S 186-0.13 ES-S (0.13 GPF)
U-2 URINAL- 3/4" - 2" SLOAN WEUS-1000.1301 SLOAN- OPTIMA TRANSFORMER (T1) SLOAN EL-154 1, 2, 3, 4
ULTRA LOW FLOW -0.13 ES-S 186-0.13 ES-S (0.13 GPF) 901 G Street, NW
MS-1 MOP SINK 3/4" 3/4" 3" ACORN TERRAZZO-WARE DELTA- TECK - 1, 2 Washington, DC 20001
TSH-24-KF24 29C2801 ( 2.2 GPM )
Architect
DF-1 DRINKING FOUNTAIN- 1/2" - 1 1/2" ELKAY EDFP217RAC 1, 2, 3
BARRIER-FREE
REMARKS:
1. PROVIDE ALL REQUIRED COMPONENTS FOR COMPLETE FIXTURE ROUGH-IN, I.E., SUPPLIES, STOPS, TRAPS, CARRIERS, GRID DRAINS, TAILPIECES, ETC. NOT ALL REQUIRED COMPONENTS ARE SPECIFIED ABOVE.
2. SEE PLANS & RISERS FOR VENT SIZES AND CONNECTIONS
3. FIXTURES SHALL BE ADA COMPLIANT. PROVIDED WITH ADA COMPLIANT ACCESSORIES. MOUNT ADA COMPLIANT. SEE ARCHITECTURAL PLAN FOR ELEVATIONS.
4. COORDINATE VALVE INSTALLATION WITH ADA GRAB BAR. VALVE SHALL BE LOCATED SO THAT GRAB BAR DOES NOT INTERFERE WITH USE OF VALVE. PROVIDE EXTENSION AS REQUIRED. 1010 wisconsin avenue, nw
suite 405
5. PROVIDE SKAL + GUARD INSULATING DEVICES ON EXPOSED UNDERCOUNTER PLUMBING. washington, dc 20007
T 202.466.6116
PUMP SCHEDULE F 202.466.6235

SYMBOL DESCRIPTION LOCATION BASIS OF DESIGN GPM FT OF HD HP RPM REMARKS

SP-1 ELEVATOR ELEVATOR PIT STANCOR 50 28 1 3600 1, 2


SUMP PUMPS ROOM 009 SE100A
3 East 28th Street, 6th Floor
SP-2 DUPLEX MECH 1, 2 New York, NY 10016
SUMP PUMPS ROOM 007
T 212.696.0414
DOMESTIC WATER DUPLEX MINI DOMESTIC FIRE PUMP BELL & GOSSET 40 GPM EA 40 2HP 3500 1, 2, 3
BOOSTER SYSTEM WATER BOOSTER PACKAGE ROOM EA20 EA Structural Engineer

FIRE IN-LINE FIRE PUMP FIRE PUMP PEERLESS 500 54 25 1450 1, 2 ReStl Designers, Inc.
PUMP ROOM 5PVF7 1001 Connecticut Ave, NW, Suite 320
Washington, DC 20036
JOCKEY REGENERATIVE FIRE PUMP MTH 5 60 1/2 3450 1, 2
PUMP JOCKEY PUMP ROOM T 202.452.1103
F 202.452.1133
REMARKS:
1. REFER TO ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS. MEP Engineer

2. FOR ADDITIONAL INFORMATION REFER TO PLUMBING DETAIL SHEET.


3. SET PRESSURE REDUCING VALVE AT PUMP DISCHARGE TO MAXIMUM 75 PSI.
7061 Deepage Drive
WATER HEATER SCHEDULE Columbia, MD 21045

SYMBOL DESCRIPTION LOCATION MAKE/MODEL SIZE KW TEMPERATURE RISE REMARKS T 410.381.7100


F 410.381.7110
EWH-1 SINGLE POINT ELECTRIC TANKLESS MOUNT UNDER EEMAX - 4.1 56°F @ 0.5 GPM 1 Civil Engineer

WATER HEATER LAVATORY MODEL SP4208 AMT


EWH-2 THERMOSTATIC ELECTRIC TANKLESS MOUNT UNDER EEMAX - 8.3 57°F @ 1.0 GPM 1 12750 Twinbrook Parkway
Rockville, MD 20852
WATER HEATER LAVATORY MODEL EX8208T-ML
EWH-3 ELECTRIC TANK TYPE ABV. MOP AO. SMITH 20 GAL 4.5 18 GPH RECOVERY 1, 2 T 301.881.2545
WATER HEATER SINK MODEL DEL-20 NON-SIMULTANEAUS @ 100ºF RISE F 301.881.0814
REMARKS: Landscape Architect
1. REFER TO DETAIL SHEET FOR MORE INFORMATION.
2. PROVIDE EXPANSION TANK (ET-1) AMTROL MODEL ST-5. 2410 17th Street, NW, Suite 201
Washington, DC 20009

DRAIN SCHEDULE T 202.588.5454


F 202.588.5449
DESIGNATION FIXTURE TYPE MANUFACTURER MODEL NO. ACCESSORIES REMARKS
REV DT ISSUED
FD-1 FLOOR DRAIN- GENERAL MIFAB F1100 ~ 1 5-29-09 SCHEMATIC DESIGN
FD-2 FLOOR DRAIN- MECH. RMS. MIFAB F1100-X ~ 1
7-17-09 DESIGN DEVELOPMENT
OSD OPEN SITE DRAIN MIFAB F1100-DD - 1
12-4-09 ISSUED FOR PERMIT
AD AREA WAY DRAIN MIFAB R1100 - 1
TD TRENCH DRAIN MIFAB T1320-FL ~ 1 1 2-24-10 ISSUED FOR BID ADDENDUM 1
PD PROMENADE DRAIN MIFAB R1100-PJ ~ 1
RD-1 ROOF DRAIN- VEGETATED ROOF AREAS MIFAB F1830-P ~ 1
RD-2 ROOF DRAIN- GENERAL MIFAB R1200 ~ 1
OFD-1 OVERFLOW DRAIN- VEGETATED ROOF AREAS MIFAB F1840 ~ 1
OFD-2 OVERFLOW DRAIN- GENERAL MIFAB R1200-W ~ 1
SD SCUPPER DRAIN MIFAB R1320 ~ 1
REMARKS:
1. SEE PLANS & RISERS FOR VENT SIZES AND CONNECTIONS.
2. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS.
3. REFER TO PLUMBING PLANS FOR SIZES.

EQUIPMENT SCHEDULE
1 SYMBOL DESCRIPTION LOCATION MAKE/MODEL SIZE ELECTRICAL ACCESSORIES REMARKS
BFP-1 BACKFLOW PREVENTER (ASSE 1013)- ROOM 023 WATTS 2" - - 1
REDUCED PRESSURE ZONE ASSEMBLY TERRACE LEVEL 009M2QT
BFP-2 BACKFLOW PREVENTER (ASSE 1048)- ROOM 023 WILKINS 6" - - 2
DOUBLE CHECK DETECTOR ASSEMBLY TERRACE LEVEL 350DA
BFP-3 BACKFLOW PREVENTER- REFER TO PLANS WATTS 1" - - -
REDUCED PRESSURE ZONE ASSEMBLY (AT MECH EQUIP) SERIES 009
BFP-4 BACKFLOW PREVENTER- AT ICEMAKER WATTS 1/2" - - -
IN-LINE DUAL CHECK CONNECTION SERIES 7
WH-1 NON-FREEZE VARIOUS ZURN 3/4" - COVER, VACUUM BREAKER - I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
WALL HYDRANT REFER TO PLANS Z1300 BRONZE FINISH DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA
GPB-1 NATURAL GAS PRESSURE MECH SPENCER TURBINE - 1 HP - 3
BOOSTER SYSTEM ROOM 007 GL-050-3/4-R
GPR-1 GAS PRESSURE REGULATOR MECH RM 007 MAXITROL 210E 2x2 - 1/2" VENT TO EXTERIOR -
1 REMARKS:
1. MEETS REQUIREMENTS OF ASSE 1013 AND SHALL BE INSTALLED IN THE HORIZONTAL CONFIGURATION. Project No. 08002.10
2. MEETS REQUIREMENTS OF ASSE 1048.
3. REFER TO DETAIL 8 ON THIS DRAWING FOR MORE INFORMATION. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL REQUIREMENTS.

COMMERCIAL - MINIMUM PIPE INSULATION THICKNESS (PER IPC & IECC) [1]
SERVICE WATER PIPE SIZES
HEATING NONCIRCULATING PIPING [2] CIRCULATING MAINS AND RUNOUTS Plumbing Schedules
TEMPERATURES ALL SIZES - 1ST 8 FEET UP TO 1 1/4" 1 1/2" TO 2" OVER 2"
170-180 ºF
140-169 ºF
100-139 ºF
1/2"
1/2"
1/2"
1"
1"
1"
1"
1"
1"
1"
1"
1"
P0.02
Printed: 11/11/08
NOTES:
© core group, pc 2008
1. CONDUCTIVITY OF INSULATION k = 0.27 BTU PER INCH/HxSQ.FTxºF - TABLE ADAPTED FROM IECC 2003 SECTION 804.5.
ASE JOB# 0811_179
2. NONCIRCULATING PIPING SERVED BY EQUIPMENT WITHOUT INTEGRAL HEAT TRAPS.
eF
1 2 2.3 3 3.9 4 5 5.7 6 GENERAL NOTES:
A. REFER TO DATA SHEET FOR PLUMBING SYMBOLS AND ABBREVIATIONS.
B. REFER TO RISER DIAGRAMS FOR ADDITIONAL SIZES OF UTILITIES AND PIPING. Mt. Pleasant
C. FOR PLUMBING FIXTURES AND EQUIPMENT REFER TO SCHEDULES ON DATA SHEET.
Library
DRAWING NOTES: #
3160 16th Street, NW
eE 1.
PIPING BELOW SLAB. Washington, DC 20010
2.
PIPING ABOVE CEILING OR TIGHT TO UNDER SIDE OF STRUCTURE.
MAINTAIN MINIMUM 18" CLEARANCE 3.
PIPING ABOVE FLOOR SLAB IN PIPE CHASE OR WALL.
1 1/2" G 4.
FOR CONTINUATION REFER TO CIVIL DRAWINGS.
11
5.
RPZ- BACKFLOW PREVENTER BFP-3 FOR MECHANICAL EQUIPMENT. EXTEND FULL SIZE
(500 CFH) (TYP) GPB-1 eD DISCHARGE TO 4" OPEN SITE DRAIN.
P3.01 SP-2
MECH BOILERS 1/2" GPR-1 6. 4" FOUNDATION DRAINAGE CONNECTION BELOW SLAB. REFER TO STRUCTURAL
G 7 DRAWINGS FOR CONTINUATION. INVERT AT 3' BELOW FINISHED FLOOR.
7. 1" NON-POTABLE WATER SERVICE FOR MECHANICAL EQUIPMENT.
2" (1,000 CFH) 2" 8. PROVIDE ACCESS PANEL IN WALL OR PROVIDE ACCESS BELOW CABINET. 901 G Street, NW
9 eC 9. 1/2" GAS PRESSURE REGULATOR VENT THROUGH EXTERIOR WALL TO OUTSIDE.
1 6 Washington, DC 20001
7 10. NON-FREEZE WALL HYDRANT.
Elec. 11. OVERFLOW DRAIN THROUGH EXTERIOR WALL AND SPILL TO GRADE. Architect
4 12 G 3" V- UP 008 eB
4" FD-2 W 1 1/4" CW- UP 12. GAS METER BY LOCAL GAS COMPANY.

TP
2

M
5 BFP-3 13. CONTRACTOR SHALL PROVIDE ADD-ALTERNATIVE PRICE TO REPLACE EXISTING STORM

ST/PD
1" 2 2" 1 1/4"
Mech. 3" W 1" NP WATER- UP RISER WITH NEW CAST IRON NO-HUB RISER FROM THE ROOM DOWN TO THE POINT OF
007 G PD 2 2 TO COOLING TOWER TERMINATION.
F

PD
SP-1 eA 14. 1" RPZ DISCHARGE AND 2" SUMP PUMP DISCHARGE TO 4" OPEN SITE DRAIN. PROVIDE
14 L-2 TAILPIECE AND TERMINATE PIPE AT 45° SAW CUT ANGLE.
4" OSD L-2 WC-2 Elev.
E 11 MS-1 WC-2 009 15. SPRINKLER FLOOR CONTROL VALVE ASSEMBLY.
EWH-3 1010 wisconsin avenue, nw
L-2 2 16. EXTEND TO AUTOMATIC HYDRAULICALLY CALCULATED FULLY SPRINKLERED SYSTEM. suite 405
P3.01
WC-1 washington, dc 20007
Mop
3/4" Women's U-1 Men's L-2
D Sink
011 010 T 202.466.6116
4" WC-1 Garden F 202.466.6235
3" U-2
and Entry
Storage
C.5 1 6" ST- UP & DN 014
Trash
006 (4,315 SQ. FT.) 1
CO
Conf.
C 2" 4" 2" CW
012
2 3 East 28th Street, 6th Floor
3/4" 1 New York, NY 10016
B 6" ST 4 CW- UP ST/PD P1.01
T 212.696.0414
Hallway 1 4" SAN- UP 1 1/2" Lobby
005 1" CO 2" 013 3/4" Structural Engineer
4"

ST
CO 1/2" ReStl Designers, Inc.
A.7 ST 3/4"
1001 Connecticut Ave, NW, Suite 320
Stair
4" CO DF-1 2"
004 Washington, DC 20036
A 16 15 T 202.452.1103
1
2 F 202.452.1133
SP

eF CO 4" SAN- UP 2 MEP Engineer


Stair 4"
003 3/4" Info1
F 016 Adult Non-Fiction
1 015 EX 4" ST 3
(E) 7061 Deepage Drive
CO 13
(E) 4" ST 13 (E) 4" POWER CONVERTER POWER CONVERTER Columbia, MD 21045
2 8 8
F FOR (2) FAUCETS FOR (2) FAUCETS
4" F- UP T 410.381.7100
1
F 410.381.7110
CO 3"
Mech. T2 4" T2 1 1/4" Civil Engineer
2" L-2
002
(E) WH TO BE EWH-2
WC-2 WC-2
1 1/4" L-2 Elev.
AMT
12750 Twinbrook Parkway
eE REMOVED & 3 3" FD-1 Rockville, MD 20852
4" Stacks 10 REPLACED EWH-2 2"

TP
017 3/4" 2 4"
2" 3" T 301.881.2545
W 1" CW- UP 1" WITH NEW H-1 3 L-2
L-2 3" TP 3" FD-1 3" 3" 3 F 301.881.0814
1 3"
Landscape Architect

U-1
eD
Study
021 1
D
2 Women's WC-1 TP Men's3" CO
3"
2410 17th Street, NW, Suite 201
Young Adult e10 011
001
WC-1 4" 2" 010 1 Washington, DC 20009
U-2 3" FD-1 T 202.588.5454
2" 2 2"
Study C.53 3" 2" F 202.588.5449
eE.5 018
Study 4" T1 POWER CONVERTER
022 Comp./ 3/4" 8
(E) 4" ST 13 2" FOR (2) URINAL FV'S
eC Conf. REV DT ISSUED
020 e9 5-29-09 SCHEMATIC DESIGN
e10 4" 4" 4" 1 1/4"
F

2 2" CW- DN 7-17-09 DESIGN DEVELOPMENT


1 1 2"
CO (E) 4" SANITARY 12-4-09 ISSUED FOR PERMIT
eB Pump 1
Room 2 1 1/2" 4" 1-13-10 BID SET
4" 019
Study 1 2-24-10 ISSUED FOR BID ADDENDUM 1
024 2" Study
023
e8
TO BE FIELD VERIFIED
F 1 I.E. 185.6'
BY CIVIL ENGINEER e9
F
4
2 PART PLAN- TOILET ROOMS
eA P1.01 SCALE: 1/4" = 1'-0"
EX 4" ST
3" V- UP e7
13 6" FIRE TO FIRE PUMP
2" INCOMING DOMESTIC WATER 1 TEST HEADER, ROUTE
SERVICE, REFER TO CIVIL FOR FIRE PUMP ROOM e8 PIPING THROUGH CHASE
CONT. SET CENTERLINE OF 4 BELOW GRADE P1.01
INCOMING PIPE AT 195.90' IN STUDY ROOM
022 Comp./
F

6" INCOMING FIRE SERVICE


4
Conf.
F

REFER TO CIVIL FOR CONT. 4" FIRE TO FREE STANDING


SET CENTERLINE OF INCOMING FIRE DEPT SIAMESE CONNECTION,
2"
FIRE SERVICE PIPE AT 195.96'
e7
ROUTE PIPING THROUGH 020 4"
CHASE IN STUDY ROOM 4"
eC.1 6" F- UP TO FIRE DEPARTMENT
SIAMESE CONNECTION RAISED THRESHOLD TO PREVENT F
POSSIBLE WATER DAMAGE F
8" F- UP TO FIRE PUMP DOMESTIC WATER

TP
TEST HEADER BOOSTER PACKAGE BP-1 F 4"
4" Pump
PLUMBING CHASE
WITH FULL SIZE
Room
F
F 3" FD-2
019
I CERTIFY THAT THESE DOCUMENTS WERE
eA.5 ACCESS DOOR 3" FD-2 4" OS&Y WITH TAMPER SWITCH (TYP) PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
4" JOCKEY PUMP JP-1
Study 2" Study IN-LINE ELECTRIC FIRE PUMP FP-1
DISTRICT OF COLUMBIA

TP
e6
024 3" FD-2 023
F
e5.8
e5.7 F 08002.10
F FIRE PUMP & JOCK PUMP CONTROLLERS Project No.

e5.3
e5.2 eA.5 TP
e5 3" V- UP 6" BFP-2

e1 e2 e3 e4 2" BFP-1 Terrace Floor Plan


2" INCOMING DOMESTIC
1 PART PLAN- PUMP ROOM - Plumbing
WATER SERVICE 1 4"OSD P1.01 SCALE: 1/4" = 1'-0"
3 TERRACE FLOOR PLAN- PLUMBING
P1.01 SCALE: 1/8" = 1'-0"
6" INCOMING FIRE SERVICE

e5.2
e5.3
1' 0 2' 4' 6' 8' 1' 0 4' 8' 12' 16'
N P1.01
e5 Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/4" = 1'-0" GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
3" VTR 3" VTR 3" VTR
ROOF ROOF

3" 3" 3"

Mt. Pleasant
3"
1 1/2" L-1
3"
3"
L-1 1 1/2" SK-1 1 1/2" Library
1 1/2" 3160 16th Street, NW
1 1/2" 2"
2" WC-2 WC-2 Washington, DC 20010

SECOND FLOOR 4" FD-2 CO SECOND FLOOR


TP 4" 1 1/2"
4" 4"
4" (2 DFU) 1 1/2"
4" (7 DFU) CO
CO 4" (7 DFU) 4" 1 1/2"
4" SK-1 901 G Street, NW
4"
Washington, DC 20001
2" ELEVATOR PD FROM SP-1 Architect
TO 4" OPEN SITE DRAIN 2" VENT 2" (2 DFU)
3" 3" FROM SP-2
FIRST FLOOR 2" FIRST FLOOR
PD
4"
2"
3" 3"
3" 1 1/2" 1 1/2" 1010 wisconsin avenue, nw
FIELD VERIFY PRIOR TO START 1 1/2" 1 1/2" 2" suite 405
2" 1 1/2"

PD
OF ANY INSIDE SANITARY 2" 3" 3" 3" washington, dc 20007
DF-1 L-1 L-1 3" L-1 L-1 U-2 U-1 4"
PIPING. REPORT TO ARCH/ T 202.466.6116
ENGINEER IF INV. EL. INSTALLED 3" (6 DFU) 1 1/2" 1 1/2" 2" (4 DFU) F 202.466.6235
4" (12 DFU) 4" CO 1 1/2" WC-1 WC-1 WC-2 WC-2
LOWER THAN ANTICIPATED. I.E. 185.6' 2" (2 DFU) 2" 4" (20 DFU) CO
(E) CO 4" OSD CO 1 1/2" (0.5 DFU) 3" 4" OSD MS-2 CO CO
TERRACE FLOOR (E) CO 3" FD-2 3" FD-2 3" FD-2 3" FD-1 3" FD-1 4" FD-2 2" (2 DFU) 3" FD-1 CO TERRACE FLOOR
EXISTING 4" SANITARY 4" TP TP TP CO 2" TP 4" (10 DFU) TP 4" (16 DFU) 2" 2" 4" 4"
TP 4" 2" TP
SEWER LATERAL. REFER 4"
TO CIVIL DWG FOR CONT. 2" 4"
3 East 28th Street, 6th Floor
(E) 4" (49.5 DFU) 4" (49 DFU) 4" (40 DFU) 4" (9 DFU) 4" (34 DFU) 3" (2 DFU) 4" (6 DFU) 4" (2 DFU) 4" (9 DFU) 3" (2 DFU) 4" (14 DFU) 4" (9 DFU) New York, NY 10016
(E) 4" W 1" NON POTABLE WATER 4" (56.5 DFU) 4" (2 DFU) 4" (34 DFU)
(68.5 DFU) 3 TO MECH COOLING TOWER 5 SANITARY RISER DIAGRAM T 212.696.0414
NO SCALE W 1 1/4" (16 WSFU) W 1" (12 WSFU) Structural Engineer
P2.01 1 2
NP AIR CHAMBER AIR CHAMBER ReStl Designers, Inc.
ROOF ROOF 1001 Connecticut Ave, NW, Suite 320
1" NON POTABLE WATER Washington, DC 20036
TO MECH COOLING TOWER, T 202.452.1103
REFER TO MECH DWGS. 1" (12 WSFU) F 202.452.1133
1" 1 1/4" (16 WSFU) 3/4" (2 WSFU) 1" (12 WSFU)
PROVIDE HEAT TRACING ON
NON POTABLE WATER LINE MEP Engineer
1/2"
ON ROOF AND 2' FEET BELOW ROOF
EWH-2 EWH-1 WC-2 L-1 EWH-1
L-1 WC-2 L-1
TO ICE
MAKER 7061 Deepage Drive
Columbia, MD 21045
1/2" 1" 1/2" 1" 1/2" 1"
SECOND FLOOR BFP-4 SECOND FLOOR T 410.381.7100
F 410.381.7110
Civil Engineer
AMT
12750 Twinbrook Parkway
Rockville, MD 20852
T 301.881.2545
SK-1 EWH-2 F 301.881.0814
VACUUM RELIEF VALVE 1" (12 WSFU) Landscape Architect
COMPLY WITH ANZI Z21.22 2" (54 WSFU) 1 1/4" (16 WSFU) 1/2" 2" (69.25 WSFU) 2" (81.25 WSFU)
FIRST FLOOR 1" 1" 1" 2" (50 WSFU) FIRST FLOOR
2410 17th Street, NW, Suite 201
Washington, DC 20009
ET-1 1
1" NON POTABLE WATER T 202.588.5454
3/4" (2 WSFU) 2" (64 WSFU) 3/4" 2"
TO MECH BOILERS, REFER TO 3/4" (4 WSFU) 2" (50 WSFU) F 202.588.5449
3/4" (3 WSFU) 1 1/4" (20 WSFU) 2" (64 WSFU) 2"
MECH DWGS FOR CONT. 1/2" (0.25 WSFU)
EWH-3 3/4" 3/4"
1" WC-1 2"
1" NON POTABLE WATER 11 (4 WSFU) EWH-2 (4 WSFU) EWH-2 3/4" REV DT
WC-2 DF-1 2" BFP-1 ISSUED
TO MECH CHILLER, REFER TO L-2 L-2 U-2 L-2 L-2
MECH DWGS FOR CONT. BFP-3 P3.01 SA 3/4" 5-29-09 SCHEMATIC DESIGN
MS-1 WC-2 U-1 WC-1 WH-1 7-17-09 DESIGN DEVELOPMENT
NP 2"
NP 1/2" 1/2" 1/2" 1/2" 12-4-09 ISSUED FOR PERMIT
TERRACE FLOOR 3" FD-2 2" TERRACE FLOOR
1 2-24-10 ISSUED FOR BID ADDENDUM 1
FULL SIZE DISCHARGE TO 1" 1 1/4" 1 1/2" 2"
4" OPEN SITE DRAIN 4 DOMESTIC WATER RISER DIAGRAM DOMESTIC WATER 2
3"
P2.01 NO SCALE 2" INCOMING DOMESTIC
BOOSTER PACKAGE P3.01 WATER SERVICE, REFER
EXTEND TO HYDRAULIC SP (DRY)
F CALCULATED FULLY TO CIVIL DRAWINGS FOR
1 SPRINKLERED WET PIPE SYSTEM CONTINUATION
ROOF ROOF
EXTEND TO HYDRAULIC
SP DESIGNED SPRINKLER EXISTING DOWNSPOUT TO
DRY- PIPE SYSTEM IN ATTIC REMAIN REFER NOTE #13 DWG
F
P1.01.
DRY- PIPE VALVE AND COMPLETE
SYSTEM IN FACTORY MADE CABINET
F

DS
BY VICTAULIC OR APPROVED EQUAL 2
F

P3.01 (E) 4"


SECOND FLOOR SECOND FLOOR
EXTEND TO HYDRAULIC
SP CALCULATED FULLY
SPRINKLERED WET PIPE SYSTEM
FREE STANDING FIRE
DEPARTMENT
FREE STANDING SIAMESE CONNECTION
FIRE PUMP TEST HEADER 8 NATURAL GAS BOOSTER
F

FLANGED EXPANSION JOINT ON INLET AND


SYSTEM (GBP-1), REFER TO
DISCHARGE PIPING IN ACCORDANCE WITH P3.01
I CERTIFY THAT THESE DOCUMENTS WERE
RISER CONTROL VALVE DETAIL FOR MORE INFORMATION PREPARED OR APPROVED BY ME, AND THAT I AM A

2" ST/ PUMP DISCHARGE 2" VENT TO 1/2" GAS PRESSURE REDUCING SPECIFICATION. MANUAL BY-PASS PACKAGED DULY LICENSED ARCHITECT UNDER THE LAWS OF
AT THE BASE OF STAIR 003 JOCKEY PUMP JP-1 8" 6" 1/2" DISTRICT OF COLUMBIA
FIRST FLOOR TO 4" OPEN SITE DRAIN 3" VENT RISER VALVE VENT TO EXTERIOR AS PART OF GAS BOOSTER SYSTEM FIRST FLOOR
SP F F
2" (1,000 CFH) G G
F 3/4" AUTO BALL DRIP 2" 2" 1 1/2" (500 CFH)
EXTEND TO HYDRAULIC CALCULATED FULLY GAS METER, MAIN SHUT-OFF Project No. 08002.10

G
SPRINKLERED WET PIPE SYSTEM GUARDIAN MODEL 6432 AND PRESSURE REGULATOR 1 1/2" (500 CFH)
F

G
GAS COCK
ST/PD

BY LOCAL GAS COMPANY G


(E) 4" PROVIDE GAS BOOSTER SYSTEM
6" BFP-2 TO B-1 TO B-1 TO BOOST TO 14" W.C.
Plumbing
G
DS

MECH BOILER MECH BOILER MAINTAIN 18" CLEARANCE


4" BACK WATER VALVE
(500 CFH) (500 CFH) GPR-1
TERRACE FLOOR
1 3" FD-2 3" FD-2
4" M
TERRACE FLOOR
Riser Diagrams

F
3"
CONCENTRIC REDUCER
IN-LINE FIRE PUMP FP-1
ECCENTRIC REDUCER 6" TO FOUNDATION
G
INCOMING LOW PRESSURE GAS
SERVICE BY LOCAL GAS COMPANY REFER
NATURAL GAS CALCULATIONS BASED ON INTERNATIONAL FUEL GAS CODE:
SCHEDULE 40 METALLIC PIPING
P2.01
6" INLET PRESSURE = LESS THAN 2.0 PSI PRESSURE DROP = 0.3" W.C. Printed: 11/11/08
6" INCOMING FIRE DRAIN (BY OTHERS) TO CIVIL DRAWINGS FOR CONTINUATION EQUIVALENT LENGTH = 40' SPECIFIC GRAVITY= 0.60
SERVICE, REFER TO 3 FIRE PROTECTION RISER DIAGRAM 2 STORM WATER RISER DIAGRAM SP-2, DUPLEX SUMP (E) DOWNSPOUT CONNECTION TO TOTAL LOAD = 1,000 CFH
1 GAS RISER DIAGRAM © core group, pc 2008

CIVIL DRAWINGS FOR ASE JOB# 0811_179


P2.01 NO SCALE P2.01 NO SCALE PUMP PACKAGE REMAIN, REFER TO CIVIL DRAWINGS P2.01 NO SCALE
CONTINUATION FOR CONTINUATION