704828 / 00
06 / 2010
PN20xx
Contents
1 Preliminary note3
1.1 Symbols used3
2 Safety instructions3
3 Function and features4
4 Function5
4.1 Communication, parameter setting and evaluation5
4.2 Switching function6
4.3 Analogue function 6
5 Installation8
6 Electrical connection8
7 Operating and display elements9
8 Menu10
8.1 Menu structure10
8.2 Explanation of the menu 11
9 Parameter setting12
9.1 Parameter setting general12
9.2 Setting the output signal14
9.2.1 Setting the output function14
9.2.2 Setting the switching limits14
9.2.3 Scaling the analogue value14
9.3 User settings (optional)15
9.3.1 Setting the unit of measurement for the system pressure15
9.3.2 Configuring the display15
9.3.3 Zero-point calibration15
9.3.4 Setting the delay time for the switching outputs15
9.3.5 Setting the output polarity16
9.3.6 Setting the damping for the switching outputs16
9.3.7 Setting the damping for the analogue output16
9.4 Service functions16
9.4.1 Reading the min./max. values for the system pressure16
10 Operation17
10.1 Read the set parameter values17
10.2 Fault indication17
2
1 Preliminary note
1.1 Symbols used
>
[]
Instruction
Reaction, result
Designation of buttons, switches or indications
Cross-reference
Important note
Non-compliance can result in malfunctions or interference.
UK
2 Safety instructions
Read this document before installing the unit. Ensure that the product is suitable for your application without any restrictions.
Non-adherence to the operating instructions or technical data can lead to
personal injury and/or damage to property.
In all applications check compliance of the product materials ( chapter 12
Technical data) with the media to be measured.
Use in gases at pressures > 25 bar only after contacting the manufacturer ifm.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size
Maximum protective device rating
2
Ampere
AWG
(mm )
26
(0.13)
1
24
(0.20)
2
22
(0.32)
3
20
(0.52)
5
18
(0.82)
7
16
(1.3)
10
The Sensor shall be connected only by using any R/C (CYJV2) cord, having suitable ratings.
3
Measuring range
bar
0...400
0...250
0...100
-1...25
-1...10
-0.13...2.50
0...600
mbar
-1 000...1 000
-50...1 000
-500...500
mbar
-12.5...250.0
PSI
0...5 800
0...3 630
0...1 450
-14.5...362.5
-14.5...145
-1.45...36.25
0...8 700
PSI
-14.5...14.5
-0.74...14.5
-7.25...7.25
inH2O
-5.0...100.4
Permissible
Bursting pressure
overload pressure
bar
PSI
bar
PSI
600
8 700
1 000
14 500
400
5 800
850
12 300
300
4 350
650
9 400
100
1 450
350
5 075
75
1088
150
2 175
20
290
50
725
800
11 600
1 200
17 400
bar
PSI
bar
PSI
20
290
50
725
10
145
30
450
10
145
30
450
bar
inH2O
bar
inH2O
10
4 000
30
12 000
MPa = bar 10 / kPa = bar 100
Static and dynamic overpressures exceeding the indicated overload pressure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the bursting pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
Use in gases at pressures > 25 bar only after contacting the manufacturer
ifm.
4 Function
4.1 Communication, parameter setting and evaluation
The unit shows the current system pressure on its display.
It generates 2 output signals according to the parameter setting.
OUT1
OUT2
UK
5 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
6 Electrical connection
2 x n-switching
1 BN
L+
2 WH
4 BK
2: OUT2
4: OUT1
3 BU
L+
4 BK
L
2: OUT2
4: OUT1
3 BU
1 x p-switching / 1 x analogue
1 x n-switching / 1 x analogue
1 BN
1 BN
2 WH
L+
2 WH
4 BK
4 BK
2: OUT2
4: OUT1
3 BU
L+
2: OUT2
4: OUT1
3 BU
Pin 4 (OUT1) = Data channel for bidirectional communication. Note: not to be used when
OUT1 = n-switching.
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black).
UK
1 to 8: Indicator LEDs
-- LED 1 to LED 6 = system pressure in unit of measurement as indicated on the label.
-- LEDs 4 to 6 not used for units with 3 adjustable units of measurement.
-- LEDs 5 and 6 not used for units with 4 adjustable units of measurement.
-- LED 7, LED 8 = switching state of the respective output.
9: Alphanumeric display, 4 digits
-- Indication of the current system pressure.
-- Indication of the parameters and parameter values.
10: Set pushbutton
-- Setting of the parameter values (scrolling by holding pressed, incremental by pressing
briefly).
11: Mode/Enter pushbutton
-- Selection of the parameters and acknowledgement of the parameter values.
8 Menu
8.1 Menu structure
10
SP2/rP2
OU1
OU2
ASP
Analogue start point for the system pressure: measured value at which
4mA/or 0V are output.
AEP
Analogue end point for the system pressure: measured value at which
20mA/or 10V are output.
EF
11
9 Parameter setting
During the parameter setting process the unit remains in the operating mode. It
continues its monitoring function with the existing parameters until parameter setting has been terminated.
9.1 Parameter setting general
Each parameter setting requires 3 steps:
1
Parameter selection
Press [Mode/Enter] until the
requested parameter is displayed.
UK
Locking / unlocking
The unit can be locked electronically to prevent unintentional wrong settings.
Make sure that the unit is in the
normal operating mode.
Press [Mode/Enter] + [Set] for 10 s.
>> [Loc] is displayed.
During operation: [Loc] is briefly displayed if you try to change parameter values.
Press [Mode/Enter] + [Set] for 10 s.
>> [uLoc] is displayed.
On delivery: Unlocked.
13
Timeout:
If no button is pressed for 15 s while the parameters are being set, the unit returns to
the operating mode with unchanged values.
Select [rP1] / [rP2] and set the value at which the output switches back.
rPx is always lower than SPx. The unit only accepts values which are lower
than SPx.
14
15
16
10 Operation
After power on of the supply voltage the unit is in the Run mode (= normal operation). It carries out its measurement and evaluation functions and generates output
signals according to the set parameters.
Operating indicators chapter 7 Operating and display elements.
10.1 Read the set parameter values
Press [Mode/Enter] briefly to scroll the parameters.
Press [Set] briefly to indicate the corresponding parameter value for 15s. After
UK
another 15s the unit returns to the Run mode.
10.2 Fault indication
[OL]
[UL]
[SC1]
[SC2]
[SC]
*The output concerned is switched off as long as the short circuit exists.
This faults are indicated even if the display is deactivated.
17
11 Scale drawing
Dimensions are in millimeters
1)
= dimensions for PN2060
1: display; 2: LEDs; 3: programming button
18
12 Technical data
Operating voltage [V] ......................................................................................... 18...32 DC1)
Current consumption [mA] ............................................................................................. < 35
Current rating [mA] ................................................................................................... 2 x 250
Protection: short circuit, reverse polarity, overload
Voltage drop [V] .............................................................................................................. < 2
Power-on delay [s] .......................................................................................................... 0.3
Min. response time switching outputs [ms] ..................................................................... 1.5
Switching frequency [Hz] .......................................................................................max. 500
Analogue output ................................................................................ 4 ... 20 mA / 0...10 V
Max. load current output [] .......................................................................... (Ub - 10) x 50 UK
Min. load with voltage output[] .................................................................................. 2000
Min. response time analogue output [ms] .......................................................................... 3
Communication interface ................................................................................... IO-Link 1.0
Baud rate [kBAUD] ........................................................................................................ 38.4
Accuracy / deviations (in % of the span)2)
- Accuracy of switch point ......................................................................................... < 0.4
- Characteristics deviation .................................................... < 0.25 (BFSL) / < 0.5 (LS)
- Hysteresis....................................................................................... < 0.1 (< 1 for PN2060)
- Repeatability (with temperature fluctuations < 10K)................................................ < 0.1
- Long-time stability (in % of the span per year) ........................................................ < 0.1
- Temperature coefficients (TEMPCO) in the compensated
temperature range 0...80C (in % of the span per 10 K)
- greatest TEMPCO of the zero point .................................................................... < 0.2
- greatest TEMPCO of the span ........................................................................... < 0.2
19
20
PN2026
PN2024
PN2023
PN2022
PN2021 PN2020
PN2009
SP1 / SP2
rP1 / rP2
ASP
AEP
min
max
min
max
min
max
min
max
mbar
-988
1000
-996
992
-996
500
-496
1000
PSI
-14.3
14.5
-14.4
14.4
-14.4
7.3
-7.2
14.5
0.1
kPa
-98.8
100
-99.6
99.2
-99.6
50.0
-49.6
100
0.4
inH2O
-396
401
-399
398
-400
201
-199
401
inHg
-29.1
29.5
-29.4
29.3
-29.4
14.8
-14.6
29.5
0.1
bar
400
398
300
100
400
PSI
60
5800
30
5770
4350
1450
5800
10
MPa
0.4
40.0
0.2
39.8
0.0
30.0
10.0
40.0
0.1
bar
2.0
250.0
1.0
249.0
0.0
187.5
62.5
250.0
0.5
PSI
30
3625
15
3610
2720
905
3625
MPa
0.20
25.00
0.10
24.90
0.00
18.57
6.25
25.00
0.05
bar
0.8
100.0
0.4
99.6
0.0
75.0
25.0
100.0
0.2
PSI
12
1450
1444
1088
364
1450
MPa
0.08
10.00
0.04
9.96
0.00
7.50
2.50
10.00
0.02
bar
-0.80
25.00
-0.90
24.90
-1.00
18.75
5.25
25.00
0.05
PSI
-11.5
362.5
-13.0
361.0
-14.5
272.0
76.0
362.5
0.5
MPa
-0.08
2.50
-0.09
2.49
-0.10
1.88
0.53
2.50
0.01
bar
-0.88
10.00
-0.94
9.94
-1.00
7.26
1.50
10.00
0.02
PSI
-12.8
145.0
-13.6
144.2
-14.6
105.2
21.8
145.0
0.2
MPa
bar
-0.11
2.50
-0.12
2.49
-0.13
1.88
0.50
2.50
0.01
PSI
-1.50
36.25
-1.65
36.10
-1.80
27.20
7.25
36.25
0.05
kPa
-10.5
250.0
-11.5
249.0
-12.5
187.5
50.0
250.0
0.5
UK
P = increments
21
PN2069
PN2060
PN2028
PN2027
SP1 / SP2
ASP
AEP
min
max
min
max
min
max
min
max
mbar
-46
1000
-50
996
-50
750
250
1000
PSI
-0.68
14.50
-0.74
14.44
-0.74
10.88
3.64
14.50
0.02
kPa
-4.6
100.0
-5.0
99.6
-5.0
75.0
25.0
100.0
0.2
inH2O
-18.5
401.5
-20.0
400.0
-20.0
0.5
mbar
-10.5
250.0
-11.5
249.0
-12.5
187.5
50.0
250.0
0.5
mmWS
-105
2550
-115
2540
-125
1910
510
2550
kPa
-1.05
25.00
-1.15
24.90
-1.25
18.75
5.00
25.00
0.05
inH2O
-4.2
100.4
-4.6
100.0
-5.0
75.4
20.2
100.4
0.2
bar
600
596
450
150
600
PSI
100
8700
40
8640
6520
2120
8700
20
MPa
0.6
60.0
0.2
59.6
0.0
45.0
15.0
60.0
0,2
mbar
-496
500
-500
496
-500
250
-250
500
PSI
-7.19
7.25
-7.25
7.19
-7.25
3.63
-3.63
7.25
0.01
kPa
-49.6
50.0
-50.0
49.6
-50.0
25.0
-25.0
50.0
0.1
inH2O
-199
201
-201
199
-201
101
-101
201
P = increments
22
rP1 / rP2
13 Factory setting
Factory setting
SP1
25 % VMR*
rP1
23 % VMR*
OU1
Hno
OU2
SP2
75 % VMR*
rP2
73 % VMR*
ASP
0
PN2009: -996 mbar
PN2069: -500 mbar
AEP
100 % VMR*
COF
dS1
0.0
dr1
0.0
dS2
0.0
dr2
0.0
P-n
PnP
dAP
0.06
dAA
0.10
diS
d2
Uni
bAr / mbAr
User setting
UK
* = the indicated percentage of the final value of the measuring range of the corresponding sensor in bar / mbar is set (for PN20x9 the percentage of the span).
VMR = final value of the measuring range
More information at www.ifm.com