Operating instructions

Combined pressure sensor


UK

704828 / 00

06 / 2010

PN20xx

Contents
1 Preliminary note3
1.1 Symbols used3
2 Safety instructions3
3 Function and features4
4 Function5
4.1 Communication, parameter setting and evaluation5
4.2 Switching function6
4.3 Analogue function 6
5 Installation8
6 Electrical connection8
7 Operating and display elements9
8 Menu10
8.1 Menu structure10
8.2 Explanation of the menu 11
9 Parameter setting12
9.1 Parameter setting general12
9.2 Setting the output signal14
9.2.1 Setting the output function14
9.2.2 Setting the switching limits14
9.2.3 Scaling the analogue value14
9.3 User settings (optional)15
9.3.1 Setting the unit of measurement for the system pressure15
9.3.2 Configuring the display15
9.3.3 Zero-point calibration15
9.3.4 Setting the delay time for the switching outputs15
9.3.5 Setting the output polarity16
9.3.6 Setting the damping for the switching outputs16
9.3.7 Setting the damping for the analogue output16
9.4 Service functions16
9.4.1 Reading the min./max. values for the system pressure16
10 Operation17
10.1 Read the set parameter values17
10.2 Fault indication17
2

11 Scale drawing ..................................................................................................18


12 Technical data ..................................................................................................19
12.1 Setting ranges ...........................................................................................21
13 Factory setting .................................................................................................23

1 Preliminary note
1.1 Symbols used

>
[]

Instruction
Reaction, result
Designation of buttons, switches or indications
Cross-reference
Important note
Non-compliance can result in malfunctions or interference.

UK

2 Safety instructions
Read this document before installing the unit. Ensure that the product is suitable for your application without any restrictions.
Non-adherence to the operating instructions or technical data can lead to
personal injury and/or damage to property.
In all applications check compliance of the product materials ( chapter 12
Technical data) with the media to be measured.
Use in gases at pressures > 25 bar only after contacting the manufacturer ifm.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size
Maximum protective device rating
2
Ampere
AWG
(mm )
26
(0.13)
1
24
(0.20)
2
22
(0.32)
3
20
(0.52)
5
18
(0.82)
7
16
(1.3)
10

The Sensor shall be connected only by using any R/C (CYJV2) cord, having suitable ratings.
3

3 Function and features


The pressure sensor detects the system pressure of machines and installations.
Applications
Type of pressure: relative pressure
Order no.
PN2020
PN2021
PN2022
PN2023
PN2024
PN2026
PN2060
PN2009
PN2027
PN2069
PN2028

Measuring range
bar
0...400
0...250
0...100
-1...25
-1...10
-0.13...2.50
0...600
mbar
-1 000...1 000
-50...1 000
-500...500
mbar
-12.5...250.0

PSI
0...5 800
0...3 630
0...1 450
-14.5...362.5
-14.5...145
-1.45...36.25
0...8 700
PSI
-14.5...14.5
-0.74...14.5
-7.25...7.25
inH2O
-5.0...100.4

Permissible
Bursting pressure
overload pressure
bar
PSI
bar
PSI
600
8 700
1 000
14 500
400
5 800
850
12 300
300
4 350
650
9 400
100
1 450
350
5 075
75
1088
150
2 175
20
290
50
725
800
11 600
1 200
17 400
bar
PSI
bar
PSI
20
290
50
725
10
145
30
450
10
145
30
450
bar
inH2O
bar
inH2O
10
4 000
30
12 000
MPa = bar 10 / kPa = bar 100

Static and dynamic overpressures exceeding the indicated overload pressure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the bursting pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
Use in gases at pressures > 25 bar only after contacting the manufacturer
ifm.

4 Function
4.1 Communication, parameter setting and evaluation
The unit shows the current system pressure on its display.
It generates 2 output signals according to the parameter setting.
OUT1
OUT2

switching signal for pressure limit values.


switching signal for pressure limit values.
analogue signal for pressure (4...20mA or 0...10V).

It moreover provides the process data via IO-Link.


The unit is laid out for fully bidirectional communication. So, the following op- UK
tions are possible:
-- Remote display: reading and display of the current system pressure.
-- Remote evaluation: transfer of switching signals (only with PP2001).
-- Remote parameter setting: reading and changing current parameter settings
with PP2001, FDT service program ifm Container or via IO-Link.
-- Using PP2001 and the FDT service program ifm Container, the current parameter settings can be stored and transferred to other units of the same type.
The program library of the available DTM objects can be found at www.ifm.com
Service Download.
Device-specific parameter lists for IO-Link parameter setting are available at:
www.ifm.com Select your country Data sheet direct:

4.2 Switching function


OUTx changes its switching state if it is above or below the set switching limits
(SPx, rPx). The following switching functions can be selected:
Hysteresis function / normally open: [OUx] = [Hno] ( fig. 1).
Hysteresis function / normally closed: [OUx] = [Hnc] ( fig. 1).
First the set point (SPx) is set, then the reset point (rPx) at the requested distance.
Window function / normally open: [OUx] = [Fno] ( fig. 2).
Window function / normally closed: [OUx] = [Fnc] ( fig. 2).
The width of the window can be set by means of the distance between SPx and
rPx. SPx = maximum value, rPx = minimum value.
1































P = system pressure; HY = hysteresis; FE = window

4.3 Analogue function


[OU2] defines whether the set measuring range is provided as a 4...20mA
signal ([OU2] = [I]) or a 0...10V signal ([OU2] = [U]).
The analogue start point [ASP] determines at which measured value the output
signal is 4 mA or 0 V.
The analogue end point [AEP] determines at which measured value the output
signal is 20 mA or 10 V.
Minimum distance between [ASP] and [AEP] = 25 % of the span.

Voltage output 0 ... 10V


Factory setting

Measuring range scaled









UK



 





  

P = system pressure, MEW = final value of the measuring range


In the set measuring range the output signal is between 0 and 10V.
It is also indicated:
System pressure above the measuring range: output signal > 10V.

Current output 4 ... 20mA


Factory setting

Measuring range scaled















 

 

P = system pressure, MEW = final value of the measuring range


In the set measuring range the output signal is between 4 and 20mA.
Also signalled:
System pressure above the measuring range: output signal > 20mA.
System pressure below the measuring range: output signal 4...3.8mA.

5 Installation

Before mounting and removing the sensor, make sure that no pressure is
applied to the system.

Insert the unit in a G process connection.


Tighten firmly.

6 Electrical connection

The unit must be connected by a qualified electrician.


The national and international regulations for the installation of electrical
equipment must be adhered to.
Voltage supply to EN50178, SELV, PELV.
Disconnect power.
Connect the unit as follows:
2 x p-switching
1 BN
2 WH

2 x n-switching
1 BN

L+

2 WH

4 BK
2: OUT2
4: OUT1

3 BU

L+

4 BK
L

2: OUT2
4: OUT1

3 BU

1 x p-switching / 1 x analogue

1 x n-switching / 1 x analogue

1 BN

1 BN

2 WH

L+

2 WH
4 BK

4 BK
2: OUT2
4: OUT1

3 BU

L+

2: OUT2
4: OUT1

3 BU

Pin 4 (OUT1) = Data channel for bidirectional communication. Note: not to be used when
OUT1 = n-switching.
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black).

7 Operating and display elements


     


 


UK


1 to 8: Indicator LEDs
-- LED 1 to LED 6 = system pressure in unit of measurement as indicated on the label.
-- LEDs 4 to 6 not used for units with 3 adjustable units of measurement.
-- LEDs 5 and 6 not used for units with 4 adjustable units of measurement.
-- LED 7, LED 8 = switching state of the respective output.
9: Alphanumeric display, 4 digits
-- Indication of the current system pressure.
-- Indication of the parameters and parameter values.
10: Set pushbutton
-- Setting of the parameter values (scrolling by holding pressed, incremental by pressing
briefly).
11: Mode/Enter pushbutton
-- Selection of the parameters and acknowledgement of the parameter values.

8 Menu
8.1 Menu structure





























































10

















8.2 Explanation of the menu


SP1/rP1

Maximum / minimum value for system pressure, at which output 1 changes


its switching status.

SP2/rP2

Maximum / minimum value for system pressure, at which output 2 changes


its switching status.

OU1

Output function for OUT1:


Switching signal for the limit values: hysteresis function [H ..] or window
function [F ..], normally open [. no] or normally closed [. nc] each.

OU2

Output function for OUT2:


UK
Switching signal for the limit values: hysteresis function [H ..] or window
function [F ..], normally open [. no] or normally closed [. nc] each.
Analogue signal for the current system pressure: 4...20mA [I] or 0...10V
[U].

ASP

Analogue start point for the system pressure: measured value at which
4mA/or 0V are output.

AEP

Analogue end point for the system pressure: measured value at which
20mA/or 10V are output.

EF

Extended functions / Opening menu level 2.


HI Maximum value memory for the system pressure.
LO Minimum value memory for the system pressure.
COF Zero point calibration.
CAr Calibration reset.
dS1/dS2 Switch-on delay for fr OUT1 / OUT2.
dr1/dr2 Reset delay fr OUT1 / OUT2.
P-n Output polarity: pnp / npn
dAP Damping for the switching outputs
dAA Damping for the analogue output
diS Update rate and orientation of the display.
Uni Standard unit of measurement for the system pressure.

11

9 Parameter setting
During the parameter setting process the unit remains in the operating mode. It
continues its monitoring function with the existing parameters until parameter setting has been terminated.
9.1 Parameter setting general
Each parameter setting requires 3 steps:
1

Parameter selection
Press [Mode/Enter] until the
requested parameter is displayed.

 

Setting of the parameter value


Press [Set] and keep it pressed.
>> Current setting value of the param 
eter flashes for 5 s.
>> After 5 s: The setting value is
changed: incremental by pressing briefly or scrolling by holding
pressed.
The numerical values are incremented continuously. If the value is to be reduced: Let
the display move to the maximum setting value. Then the cycle starts again at the
minimum setting value.
3 Acknowledgement of the parameter
value
Press [Mode/Enter] briefly.
 
>> The parameter is displayed again.
The new setting value is stored.
Setting of other parameters:
Start again with step 1.
Finishing the parameter setting:
Press [Mode/Enter] several times until the current measured value is displayed or wait
for 15 s.
>> The unit returns to the operating mode.

If [SLoc] is displayed when attempting a modification of a parameter value, the


sensor is locked via software. This locking can only be removed via a parameter setting software.
In case of parameter setting with the user interface of the ifm Container program, the values can be directly entered in the specified fields.
12

For IO-Link parameter setting device-specific parameter lists at: www.ifm.


com Select your country Data sheet direct:
Changing from menu level 1 to menu level 2:
Press [Mode/Enter] until [EF] is
displayed.
If the submenu is protected with an access code, [Cod1] flashes in the display.
Press [Set] and keep it pressed until
the valid code no. is displayed.
Press [Mode/Enter] briefly.
On delivery by ifm electronic: no access
restriction.
Press [Set] briefly.
>> The first parameter of the sub-menu
is displayed (here: [HI]).

 

UK

 

With the user interface of the ifm Container program:


Activate the [EF] button.
If menu level 2 is protected by an access code, the input field for the code no. is
activated.
Enter valid code no.

Locking / unlocking
The unit can be locked electronically to prevent unintentional wrong settings.
Make sure that the unit is in the
normal operating mode.
Press [Mode/Enter] + [Set] for 10 s.
>> [Loc] is displayed.

 


During operation: [Loc] is briefly displayed if you try to change parameter values.
Press [Mode/Enter] + [Set] for 10 s.
>> [uLoc] is displayed.
 


On delivery: Unlocked.

13

Timeout:
If no button is pressed for 15 s while the parameters are being set, the unit returns to
the operating mode with unchanged values.

9.2 Setting the output signal


9.2.1 Setting the output function
Select [OU1] and set the switching function:
[Hno] = hysteresis function / normally open,
[Hnc] = hysteresis function / normally closed,
[Fno] = window function / normally open,
[Fnc] = window function / normally closed.
Select [OU2] and set the function:
[Hno] = hysteresis function / normally open,
[Hnc] = hysteresis function / normally closed,
[Fno] = window function / normally open,
[Fnc] = window function / normally closed,
[I] = current signal proportional to the pressure 420mA,
[U] = voltage signal proportional to the pressure 0...10V.

9.2.2 Setting the switching limits


Select [SP1] / [SP2] and set the value at which the output switches.

Select [rP1] / [rP2] and set the value at which the output switches back.
rPx is always lower than SPx. The unit only accepts values which are lower
than SPx.

9.2.3 Scaling the analogue value


Select [ASP] and set value at which 4mA / 0V are output.
Select [AEP] and set value at which 20mA / 10V are output.
Minimum distance between ASP and AEP = 25 % of the span (scaling
factor 1:4).

14

9.3 User settings (optional)


9.3.1 Setting the unit of measurement for the system pressure
Select [Uni] and set the unit of measurement:
[bAr], [mbAr]
[MPA], [kPA]
[PSI]
[IH2O] (only PN2009, PN2027, PN2028, PN2069)
[inHG] (only PN2009)
[mmWS] (only PN2028)
UK

9.3.2 Configuring the display


Select [diS] and set update rate and orientation of the display:
[d1]: Update of the measured value every 50 ms.
[d2]: Update of the measured value every 200 ms.
[d3]: Update of the measured value every 600 ms.
[Ph]: Display of the measured peak value remains for a short time (peak
hold).
[rd1], [rd2], [rd3], [rPh]: Display like d1, d2, d3, Ph; rotated by 180.
[OFF]: The display is deactivated in the operating mode.

9.3.3 Zero-point calibration


Select [COF] and set a value between -5 % and 5 % of the final value of
the measuring range (for PN2009 and PN2069 5 % of the span). The
internal measured value 0 is shifted by this amount.
Resets the calibration set by COF to the value set at the factory.
Press [Mode/Enter] until [CAr] is displayed.
Press [Set] and keep it pressed until [----] is displayed.
Press [Mode/Enter] briefly.

9.3.4 Setting the delay time for the switching outputs


[dS1] / [dS2] = switch-on delay for OUT1 / OUT2.
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2.
Select [dS1], [dS2], [dr1] or [dr2], set value between 0.1 und 50s (at 0.0
the delay time is not active).

15

9.3.5 Setting the output polarity


Select [P-n], set [PnP] or [nPn].

9.3.6 Setting the damping for the switching outputs


Select [dAP], set value between 0.01 ... 4.00s; (at 0.00 [dAP] time is
not active).
dAP-value = response time between pressure change and change of the
switching status in seconds (s).
Correlation between switching frequency and [dAP]: fmax = 1 2dAP..

9.3.7 Setting the damping for the analogue output


Select [dAA], set value between 0.01 ... 4.00s; (at 0.00 [dAA] time is
not active).
dAA-value = response time between pressure change and change of the
switching status in seconds (s).
[dAA] affects the IO-Link process data.

9.4 Service functions


9.4.1 Reading the min./max. values for the system pressure
Select [HI] or [LO], press [Set] briefly.
[HI] = maximum value, [LO] = minimum value.
Delete memory:
Select [HI] or [LO].
Press [Set] until [----] is displayed.
Press [Mode/Enter] briefly.

16

10 Operation
After power on of the supply voltage the unit is in the Run mode (= normal operation). It carries out its measurement and evaluation functions and generates output
signals according to the set parameters.
Operating indicators chapter 7 Operating and display elements.
10.1 Read the set parameter values
Press [Mode/Enter] briefly to scroll the parameters.
Press [Set] briefly to indicate the corresponding parameter value for 15s. After
UK
another 15s the unit returns to the Run mode.
10.2 Fault indication
[OL]

overload pressure (measuring range exceeded)

[UL]

underpressure range (measuring range below the minimum value)

[SC1]

short circuit in OUT1*

[SC2]

short circuit in OUT2*

[SC]

short circuit in both switching outputs*

*The output concerned is switched off as long as the short circuit exists.
This faults are indicated even if the display is deactivated.

17

11 Scale drawing





 
















Dimensions are in millimeters
1)
= dimensions for PN2060
1: display; 2: LEDs; 3: programming button

18



 

12 Technical data
Operating voltage [V] ......................................................................................... 18...32 DC1)
Current consumption [mA] ............................................................................................. < 35
Current rating [mA] ................................................................................................... 2 x 250
Protection: short circuit, reverse polarity, overload
Voltage drop [V] .............................................................................................................. < 2
Power-on delay [s] .......................................................................................................... 0.3
Min. response time switching outputs [ms] ..................................................................... 1.5
Switching frequency [Hz] .......................................................................................max. 500
Analogue output ................................................................................ 4 ... 20 mA / 0...10 V
Max. load current output [] .......................................................................... (Ub - 10) x 50 UK
Min. load with voltage output[] .................................................................................. 2000
Min. response time analogue output [ms] .......................................................................... 3
Communication interface ................................................................................... IO-Link 1.0
Baud rate [kBAUD] ........................................................................................................ 38.4
Accuracy / deviations (in % of the span)2)
- Accuracy of switch point ......................................................................................... < 0.4
- Characteristics deviation .................................................... < 0.25 (BFSL) / < 0.5 (LS)
- Hysteresis....................................................................................... < 0.1 (< 1 for PN2060)
- Repeatability (with temperature fluctuations < 10K)................................................ < 0.1
- Long-time stability (in % of the span per year) ........................................................ < 0.1
- Temperature coefficients (TEMPCO) in the compensated
temperature range 0...80C (in % of the span per 10 K)
- greatest TEMPCO of the zero point .................................................................... < 0.2
- greatest TEMPCO of the span ........................................................................... < 0.2

19

Materials (wetted parts) .............................stainless steel (303S22); ceramics; FPM (Viton)


Housing material .........stainless steel (304S15); stainless steel (316S12); PBTP (Pocan);

PEI; FPM (Viton)
in addition PTFE for PN2009, PN2023, PN2024, PN2026, PN2027, PN2028, PN2069
Protection PN2020, PN2021, PN2022, PN2060........................................................... IP 67
Protection PN2009, PN2023, PN2024, PN2026, PN2027, PN2028, PN2069.............. IP 65
Protection class ................................................................................................................. III
Insulation resistance [M]......................................................................... > 100 (500 V DC)
Shock resistance [g] ............................................................... 50 (DIN / IEC 68-2-27, 11ms)
Vibration resistance [g] ................................................ 20 (DIN / IEC 68-2-6, 10 - 2000 Hz)
Switching cycles min. .....................................................100 million (50 million for PN2060)
Operating temperature [C] ................................................................................. -25 ... +80
Storage temperature[C]................................................................................... -40 ... +100
Medium temperature [C]...................................................................................... -25 ... +80
EMC EN 61000-4-2 ESD: ........................................................................................4 / 8 KV

EN 61000-4-3 HF radiated: ............................................................................. 10 V/m

EN 61000-4-4 Burst: ............................................................................................2 KV

EN 61000-4-5 Surge: ...................................................................................0.5 / 1 KV

EN 61000-4-6 HF conducted: ............................................................................. 10 V
to EN50178, SELV, PELV
2)
all indications are referred to a turn down of 1:1
1)

20

12.1 Setting ranges

PN2026

PN2024

PN2023

PN2022

PN2021 PN2020

PN2009

SP1 / SP2

rP1 / rP2

ASP

AEP

min

max

min

max

min

max

min

max

mbar

-988

1000

-996

992

-996

500

-496

1000

PSI

-14.3

14.5

-14.4

14.4

-14.4

7.3

-7.2

14.5

0.1

kPa

-98.8

100

-99.6

99.2

-99.6

50.0

-49.6

100

0.4

inH2O

-396

401

-399

398

-400

201

-199

401

inHg

-29.1

29.5

-29.4

29.3

-29.4

14.8

-14.6

29.5

0.1

bar

400

398

300

100

400

PSI

60

5800

30

5770

4350

1450

5800

10

MPa

0.4

40.0

0.2

39.8

0.0

30.0

10.0

40.0

0.1

bar

2.0

250.0

1.0

249.0

0.0

187.5

62.5

250.0

0.5

PSI

30

3625

15

3610

2720

905

3625

MPa

0.20

25.00

0.10

24.90

0.00

18.57

6.25

25.00

0.05

bar

0.8

100.0

0.4

99.6

0.0

75.0

25.0

100.0

0.2

PSI

12

1450

1444

1088

364

1450

MPa

0.08

10.00

0.04

9.96

0.00

7.50

2.50

10.00

0.02

bar

-0.80

25.00

-0.90

24.90

-1.00

18.75

5.25

25.00

0.05

PSI

-11.5

362.5

-13.0

361.0

-14.5

272.0

76.0

362.5

0.5

MPa

-0.08

2.50

-0.09

2.49

-0.10

1.88

0.53

2.50

0.01

bar

-0.88

10.00

-0.94

9.94

-1.00

7.26

1.50

10.00

0.02

PSI

-12.8

145.0

-13.6

144.2

-14.6

105.2

21.8

145.0

0.2

MPa

-0.088 1.000 -0.094 0.994 -0.100 0.726 0.150 1.000 0.002

bar

-0.11

2.50

-0.12

2.49

-0.13

1.88

0.50

2.50

0.01

PSI

-1.50

36.25

-1.65

36.10

-1.80

27.20

7.25

36.25

0.05

kPa

-10.5

250.0

-11.5

249.0

-12.5

187.5

50.0

250.0

0.5

UK

P = increments

21

PN2069

PN2060

PN2028

PN2027

SP1 / SP2

ASP

AEP

min

max

min

max

min

max

min

max

mbar

-46

1000

-50

996

-50

750

250

1000

PSI

-0.68

14.50

-0.74

14.44

-0.74

10.88

3.64

14.50

0.02

kPa

-4.6

100.0

-5.0

99.6

-5.0

75.0

25.0

100.0

0.2

inH2O

-18.5

401.5

-20.0

400.0

-20.0

301.0 100.5 401.5

0.5

mbar

-10.5

250.0

-11.5

249.0

-12.5

187.5

50.0

250.0

0.5

mmWS

-105

2550

-115

2540

-125

1910

510

2550

kPa

-1.05

25.00

-1.15

24.90

-1.25

18.75

5.00

25.00

0.05

inH2O

-4.2

100.4

-4.6

100.0

-5.0

75.4

20.2

100.4

0.2

bar

600

596

450

150

600

PSI

100

8700

40

8640

6520

2120

8700

20

MPa

0.6

60.0

0.2

59.6

0.0

45.0

15.0

60.0

0,2

mbar

-496

500

-500

496

-500

250

-250

500

PSI

-7.19

7.25

-7.25

7.19

-7.25

3.63

-3.63

7.25

0.01

kPa

-49.6

50.0

-50.0

49.6

-50.0

25.0

-25.0

50.0

0.1

inH2O

-199

201

-201

199

-201

101

-101

201

P = increments

22

rP1 / rP2

13 Factory setting
Factory setting
SP1

25 % VMR*

rP1

23 % VMR*

OU1

Hno

OU2

SP2

75 % VMR*

rP2

73 % VMR*

ASP

0
PN2009: -996 mbar
PN2069: -500 mbar

AEP

100 % VMR*

COF

dS1

0.0

dr1

0.0

dS2

0.0

dr2

0.0

P-n

PnP

dAP

0.06

dAA

0.10

diS

d2

Uni

bAr / mbAr

User setting

UK

* = the indicated percentage of the final value of the measuring range of the corresponding sensor in bar / mbar is set (for PN20x9 the percentage of the span).
VMR = final value of the measuring range
More information at www.ifm.com