REFLECTED CEILING PLAN SYMBOLS KEY

GENERAL REFLECTING CEILING PLAN NOTES

REFLECTING CEILING PLAN NOTES

A. ALL FIXTURES UNLESS NOTED OTHERWISE SHALL BE


LOCATED WITHIN THE CETNER OF THE APPROPRIATE
CEILING TILE, OR SHALL BE SPREAD EVENLY AND
SYMMETRICALLY WITHIN THE GYPSUM BOARD CEILING
UNLESS NOTED OTHERWISE.
B. CEILING TILES WITHIN EACH ROOM SHALL BE CENTERED
WITHIN THE MAJOR RECTANGULAR SPACE, UNLESS NOTED
OTHERWISE. DO NOT CUT CEILING TILES LESS THAN 4"
WIDE.
C. ALL SPRINKLER HEADS SHALL BE WITHIN THE
APPROPRIATE CEILING TILES OR SHALL BE IN A
SYMMETRIC PATTERN IN A DRYWALL CEILING.
D. PARTIAL REMOVAL/DEMOLITION OF EXISTING
CEILINGS TO REMAIN NECESSARY AS A RESULT OF MEP
INSTALLATION SHALL BE COORDINATED WITH THE MEP
DRAWINGS. CONTRACTOR TO REPLACE ALL CEILINGS
DAMAGED AS A RESULT OF REQUIRED MEP INSTALLATION.

GWB
11' - 4" A.F.F.

NO FINISHED CEILING - OPEN TO


STRUCTURE ABOVE

RC2

WALL MOUNTED LIGHT FIXTURE PER


ELECTRICAL PLANS.

RC3

OPEN TO ABOVE - SEE SECOND FLOOR


REFLECTED CEILING PLAN FOR MORE
INFORMATION.

RC4

EXTERIOR WALL MOUNTED LIGHT


FIXTURE PER ELECTRICAL PLANS.

RC5

INGORUND LIGHT FIXTURE PER


ELECTRICAL DRAWINGS.

RC6

GROUND MOUNTED SPOTLIGHT FIXTURE


PER ELECTRICAL DRAWINGS.

DESCRIPTION
2'x2' ACOUSTIC CEILING TILE. ALL CEILING GRIDS ARE CENTERED IN ROOM UNLESS
OTHERWISE DIMENSIONED IN PLAN

2'x4' ACOUSTIC CEILING TILE. ALL CEILING GRIDS ARE CENTERED IN ROOM UNLESS
OTHERWISE DIMENSIONED IN PLAN

g
GYPSUM WALLBOARD CEILING - ALIGN WITH ADJACENT PARTITION UNLESS
OTHERWISE DIRECTED IN PLAN

GWB
8' - 0" A.F.F.

DENOTES CEILING HEIGHT ABOVE FINISHED FLOOR. ALL CEILING HEIGHTS ARE
8'-0" UNLESS OTHERWISE NOTED IN PLAN.

F. ALL CEILING HEIGHTS TO BE 8'-0" UNLESS NOTED


OTHERWISE.

1'x4' FLUORESCENT LIGHT FIXTURE

STATE OF MARYLAND LICENSE NUMBER:14696

NOT USED

2008 CR GOODMAN ASSOCIATES, LLC


THESE DRAWINGS ARE THE PROPERTY OF THE ARCHITECT,
CR GOODMAN ASSOCIATES, LLC. UNAUTHORIZED
REPRODUCTION FOR ANY PURPOSE IS AN INFRINGEMENT
UPON COPYRIGHT LAWS. VIOLATORS WILL BE SUBJECT TO
PROSECUTION TO THE FULLEST EXTENT OF THE LAW.

RC6

RC4

G. DRAWING LOCATES CEILING MOUNTED LIGHTS. OTHER


CEILING MOUNTED ITEMS OTHER THAN LIGHTS SHALL BE
LOCATED 12" FROM BOTH ADJACENT EDGES OF A CEILING
TILE TO THE CENTER OF THE ITEM, UNLESS OTHERWISE
NOTED. CEILING MOUNTED ITEMS TO BE CENTERED ON
SHORT DIMENSION OF MAIN CORRIDOR, UNLESS NOTED
OTHERWISE.

RC4

2' - 3"

RC4

2'x4' FLUORESCENT LIGHT FIXTURE

CONSULTANTS

H. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL CEILING


MOUNTED ITEMS.
2' x 2' ACT
9' - 0" A.F.F.

SB

SB

2'x2' FLUORESCENT LIGHT FIXTURE

RECESSED INCANDESCENT OR FLUORESCENT CAN LIGHT FIXTURE

I. ALL GYPSUM BULKHEADS AND CEILINGS TO BE P-5 UNLESS


NOTED OTHERWISE.
WALL MOUNTED LIGHT FIXTURE - SEE INTERIOR ELEVATIONS FOR MORE INFORMATION

2' - 0"

SB
TYPE B
8' - 8" A.F.F.

SB

WIRE HANGER
BEYOND

FIN. WALL

RC4

'1x4' 'BASKET' FLUORESCENT INDIRECT LIGHT FIXTURE

SITE ENGINEER
N.G & O ENGINEERING INC.
23725 THREE NOTCH ROAD, SUITE 200
HOLYWOOD, MARYLAND 20636
PHONE: 301-475-8700
FAX: 301-475-8705
STRUCTURAL ENGINEER
MORABITO CONSULTANTS, INC
952 RIDGEBROOK ROAD, SUITE 1700
SPARKS, MARYLAND 21152
PHONE: 410-467-2377
FAX: 410-467-4132

EXPOSED MAIN
TEE

EXPOSED CROSS
TEE

METAL WALL
MOULDING

2' - 3"

2' x 2' ACT


9' - 0" A.F.F.
RC4

V - 410-841-2570
F - 410-841-2575

MECHANICAL SYSTEMS PER ENGINEERING DRAWINGS

RC6

2' - 0"

912 COMMERCE ROAD


ANNAPOLIS, MD 21401
SEAL

E. DO NOT CUT TILES IN A "U" SHAPE TO FIT AROUND


PARTITION EDN CAPS AND OTHER PROTRUSIONS. CUT
TILES ON AN "L" AND PROVIDE AN ADDITIONAL SUPPORT
BAR AS NECESSARY.
3

RC4

RC1

SYMBOL

2'x2' 'BASKET' FLUORESCENT LIGHT FIXTURE.

SB

FLUORESCENT COVE LIGHT FIXTURE

MECHANICAL & ELECTRICAL ENGINEER


LEACH WALLACE ASSOCIATES, INC
6522 MEADOWRIDGE ROAD
ELKRIDGE, MARYLAND 21075
PHONE: 410-579-8100
FAX: 410-540-9041

RC1
LAY-IN ACOUST.

SB

TILE UNITS

SURFACE MOUNTED DECORATIVE FIXTURE

SB

PER SCHEDULE

TYPICAL
ACOUSTICAL TILE CEILING
SCALE: 3" = 1'-0"

E5

2' x 4' ACT


9' - 0" A.F.F.

RC4

A151

WALL MOUNTED LIGHT FIXURE PER ELECTRICAL DRAWINGS

RC2

RC1

1-1/2" METAL CHANNELS

HANGERS AT

METAL RUNNER
CHANNEL

RC1

RC2

INGROUND LIGHT FIXTURE PER ELECTRICAL DRAWINGS

@ 4'-0" O.C. MAX.

4'-0" O.C. MAX.

WALL MOUNTED FLUORESCENT LIGHT FIXTURE

RC1
RC3

RC3
RC4

SECURITY CAMERA

C
CONTROL
JOINT

METAL TRIM

SB

TYPE B
8' - 8" A.F.F.

5/8" GYP. BD.

FURRING CHANNELS
@ 24" O.C. MAX.

RC2
FIN. WALL

FURRING CHANNEL

RC2

DECORATIVE PENDANT LIGHT FIXTURE PER ELECTRICAL DRAWINGS

SB

A151

TYPICAL GWB BULKHEAD DETAILS - SCALE: 1-1/2" = 1'-0"

2' - 0"

d
3 5/8" X 25 GA
METAL STUD BRACING
@ 48" O.C.

2' - 0"

RC4

RC4

GWB, 5/8"

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.

6"

NUMBER
DATE
12/09/08
1
12/22/08
2
01/09/09
3

FIN. CLG., SEE ROOM

GWB, 5/8"

SEE FLOOR PLAN &


PARTITION SCHED.

3 5/8" X 25 GA
METAL STUDS
@ 16" O.C.

RC4

FIN. CLG., SEE


FINISH SCHEDULE

FINISH SCHEDULE
GWB, 5/8"

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.
TO STRUCT. ABOVE

ALIGN WITH ADJACENT PART.

SEE REFLECTED CEILING PLAN

RC6

ISSUE
PERMIT SET
BID ISSUE
ADDENDUM #1

SEE REFLECTED CLG. PLAN

2' - 0"

TYPE B
8' - 8" A.F.F.

RC6

6"

6"

FIN. CLG., SEE


FINISH SCHEDULE

CLG. PLAN

RC1

PROJECT KEY PLAN

TO STRUCT. ABOVE

SEE REFLECTED CLG. PLAN

SB

2' x 2' ACT


9' - 0" A.F.F.

2' - 0"

3 5/8" X 25 GA MTL.
STUDS @ 16" O.C.

TYPE A
8' - 8" A.F.F.

2' - 0"

2' - 0"

2' x 2' ACT


9' - 0" A.F.F.

RC4

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.
TO STRUCTURE ABOVE

SEE REFLECTED CLG. PLAN

SB

TYPE B
8' - 8" A.F.F.

2' - 0"

2' - 0"

RC4

RC4

2' x 2' ACT


9' - 0" A.F.F.

2' x 2' ACT


9' - 0" A.F.F.

SEE REFL.

SB

SEE REFLECTED CLG. PLAN

SB

SB

6"

RC1

SEE REFLECTED CLG. PLAN

SB

CLIPS OR WIRE

TYPICAL
SUSPENDED GYP. BD. CEILING
SCALE: 3" = 1'-0"

D5

2' x 2' ACT


9' - 0" A.F.F.

GROUND MOUNTED SPOTLIGHT FIXTURE PER ELECTRICAL DRAWINGS

UNLESS DIMENSIONED IN PLAN

4'

8'

16'

NOTE: FOR EMERGENCY ELECTRICAL CLOSET, ELECTRICAL


ROOM, IT CLOSET, WATER ROOM AND SHELL SPACES SEE
ELECTRICAL PLANS.

RC5

3 5/8" X 25 GA
METAL STUDS
@ 16" O.C.

SEE FLOOR PLAN &


PARTITION SCHED.

RC5

TYPE

RC5

6"
5"

TYPE

5"

SEE REFLECTED CEILING


PLAN
FOR HEIGHT ABOVE
FINISHED
FLOOR

TYPE

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.
TO STRUCTURE ABOVE
WITH 5/8" GWB, PTD

6"
6"

6"

FLUORESCENT
COVE LIGHT

TYPE

9"

6"
4"

TYPE

08.056.A

FIRST FLOOR
REFLECTED
CEILING PLAN &
DETAILS

5"
SEE REFELCTED CLG. PLAN

SCHEDULED ACT

5/8" PAINTED GYP. BD.


ON 2 1/2" METAL STUD (22 GA)

8'-8" AFF

4"

SEE REFLECTED CLG. PLAN

5/8" PAINTED GYP. BD.


ON METAL STUD (22 GA)

7'-4" A.F.F.

3"

5"

8"

SEE REFELCTED CLG. PLAN


FLUORESCENT STRIP
LIGHT FIXTURE

12/09/2008

DRAWING TITLE

5"

6"

MEDICAL OFFICE
BUILDING
CRGA PROJECT NUMBER

SCHEDULED
PARTITION

SCHEDULED ACT

SCHEDULED ACT

PROJECT TITLE

DATE

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.
TO STRUCTURE ABOVE
WITH 5/8" GWB, PTD

NOT USED

SCHEDULED
ACT

DECORATIVE FIXTURE
AS SCHEDULED

5"

3'-2"

1" MINIMUM UNLESS


DIMENSIONED
OTHERWISE IN PLAN

FACE OF WALL CABINET

RC5

FIN. CLG.

8'-0" A.F.F.

2'

6"

0'

ST. MARY'S
HOSPITAL

4"

1/8" = 1'-0"

CLIENT

6"

5/8" GYP. BD.

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.
TO STRUCTURE ABOVE
WITH 5/8" GWB, PTD

3 5/8" X 25 GA
METAL STUDS @ 16" O.C.
TO STRUCTURE ABOVE
WITH 5/8" GWB, PTD

SEE REFLECTED CLG. PLAN

FIRST FLOOR
REFLECTED CEILING PLAN
SCALE: 1/8" = 1'-0"

SEE REFLECTED CLG. PLAN

A151

TYPE

6"

3 5/8" X 25 GA MTL.
STUDS @ 16" O.C.
TO STRUCT. ABOVE

C1

RC5

2"

GWB
11' - 4" A.F.F.

TYPE

8'-0" A.F.F.

RC5

8'-0" A.F.F.

TYPE

DRAWING NUMBER

A151