Вы находитесь на странице: 1из 28

General Information

Building Name
Building Address
Building Type
PE(Mech)
PE(Mech) Address
Chiller Configuration
Operating Cooling Load
Design Chilled Water Supply Temperature
Design Chilled Water Delta T
Design Condenser Supply Water Temperature
Design Condenser Delta T
Design Chilled Water Flow Rate
Design Condenser Water Flow Rate

al Information
e.g. Building ABC
e.g. Blk 25 Jurong Street Singapore 123456
e.g Mix development (Hotel/Retail)
e.g Vince Tan
e.g blk 22 Bishan Street, #04-15, Singapore
654321
e.g 2 x 550RT, 1 x 300RT
e.g 810 RT
e.g 6.67 C
e.g 5.5C
e.g 29.7C
FIX/VARIABLE <please choose one>
e.g 60 L/s
e.g 70 L/s

CHILLER 1
% Load

Capacity
(RT)

Chiller Input
Power
(kW)

Chiller
Efficiency
kW/RT

Evaporator
Flow
(L/s)

example

100

700

363

0.519

106.00

example

90

630

329

0.522

95.41

80

560

70

490

60

420

50

350

40

280

30

210

20

140

10

70

CHILLER 3
% Load

Capacity
(RT)

100

500

90

450

80

400

70

350

60

300

50

250

40

200

30

150

Chiller Input
Power
(kW)

Chiller
Efficiency
kW/RT

Evaporator
Flow
(L/s)

20

100

10

50

CHILLER 1
Evaporator

Condenser

CHWST
(C)

CHWRT
(C)

Flow
(L/s)

CWST
(C)

CWRT
(C)

6.67

12.22

132.00

29.44

34.53

6.67

12.22

119.26

29.44

34.53

CHILLER 3
Evaporator
CHWST
(C)

Condenser
CHWRT
(C)

Flow
(L/s)

CWST
(C)

CWRT
(C)

CHILLER 2
% Load

Chiller
Input
Capacity
Power
(RT)

Chiller
Efficiency
kW/RT

(kW)
100

700

90

630

80

560

70

490

60

420

50

350

40

280

30

210

20

140

10

70

Evaporator
Flow
(L/s)

CHWST
(C)

CHILLER 4
% Load

Chiller
Input
Capacity
Power
(RT)
(kW)

100

500

90

450

80

400

70

350

60

300

50

250

40

200

30

150

Chiller
Efficiency
kW/RT

Evaporator
Flow
(L/s)

CHWST
(C)

20

100

10

50

LLER 2

aporator

Condenser
CHWRT
(C)

Flow
(L/s)

CWST
(C)

CWRT
(C)

LLER 4

aporator

Condenser
CHWRT
(C)

Flow
(L/s)

CWST
(C)

CWRT
(C)

Chilled Water Pump 1

% Load

example

100
90
80
70
60
50
40
30
20
10

A
Rated
Flow
(L/s)
106.01
95.41
84.81
74.21
63.61
N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)
28
22.68
17.92
13.72
10.08
N.A.
N.A.
N.A.
N.A.
N.A.

C
Motor
Efficiency
(%)
90
94.2
90
90
90
N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)
80
86.8
80
80
80
N.A.
N.A.
N.A.
N.A.
N.A.

Chilled Water Pump 3


% Load

A
Rated
Flow
(L/s)

100
90
80
70
60
50
40
30
20
10

N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)

N.A.
N.A.
N.A.
N.A.
N.A.

C
Motor
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

r Pump 1

Chilled W
E = (A x 1000 x 9.81 x B)
/ (106 x C x D)

% Load

Rated
Flow
(L/s)

Motor Absorbed Power


(kW)
40.44
25.96
20.71
13.87
8.74
N.A.
N.A.
N.A.
N.A.
N.A.

100
90
80
70
60
50
40
30
20
10

N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)

N.A.
N.A.
N.A.
N.A.
N.A.

r Pump 3

Chilled W
E = (A x 1000 x 9.81 x B)
/ (106 x C x D)

% Load

Rated
Flow
(L/s)

Motor Absorbed Power


(kW)

N.A.
N.A.
N.A.
N.A.
N.A.

100
90
80
70
60
50
40
30
20
10

N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)

N.A.
N.A.
N.A.
N.A.
N.A.

Chilled Water Pump 2


C
Motor
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

E = (A x 1000 x 9.81 x B)
/ (106 x C x D)
Motor Absorbed Power
(kW)

N.A.
N.A.
N.A.
N.A.
N.A.

Chilled Water Pump 4


C
Motor
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

E = (A x 1000 x 9.81 x B)
/ (106 x C x D)
Motor Absorbed Power
(kW)

N.A.
N.A.
N.A.
N.A.
N.A.

Condenser Water Pump 1

% Load

example

100
90
80
70
60
50
40
30
20
10

A
Rated
Flow
(L/s)
132.51
119.26
106.01
92.76
79.51
N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)
32
25.92
20.48
15.68
11.52
N.A.
N.A.
N.A.
N.A.
N.A.

C
Motor
Efficiency
(%)
90
90
90
90
90
N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)
80
80
80
80
80
N.A.
N.A.
N.A.
N.A.
N.A.

Condenser Water Pump 3


% Load

A
Rated
Flow
(L/s)

100
90
80
70
60
50
40
30
20
10

N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)

N.A.
N.A.
N.A.
N.A.
N.A.

C
Motor
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

ter Pump 1

Condens

E = (A x 1000 x 9.81 x B)
/ (106 x C x D)

% Load

Rated
Flow
(L/s)

Motor Absorbed Power


(kW)
57.77
42.12
29.58
19.82
12.48
N.A.
N.A.
N.A.
N.A.
N.A.

100
90
80
70
60
50
40
30
20
10

N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)

N.A.
N.A.
N.A.
N.A.
N.A.

ter Pump 3

Condens

E = (A x 1000 x 9.81 x B)
/ (106 x C x D)

% Load

Rated
Flow
(L/s)

Motor Absorbed Power


(kW)

N.A.
N.A.
N.A.
N.A.
N.A.

100
90
80
70
60
50
40
30
20
10

N.A.
N.A.
N.A.
N.A.
N.A.

B
Rated
Head
(m)

N.A.
N.A.
N.A.
N.A.
N.A.

Condenser Water Pump 2


C
Motor
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)

E = (A x 1000 x 9.81 x B)
/ (106 x C x D)
Motor Absorbed Power
(kW)

N.A.
N.A.
N.A.
N.A.
N.A.

N.A.
N.A.
N.A.
N.A.
N.A.

Condenser Water Pump 4


C
Motor
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

D
Pump
Efficiency
(%)

N.A.
N.A.
N.A.
N.A.
N.A.

E = (A x 1000 x 9.81 x B)
/ (106 x C x D)
Motor Absorbed Power
(kW)

N.A.
N.A.
N.A.
N.A.
N.A.

Cooling Towers
* Based on an ambient DBT 32 C WBT of 27.5C
Parameters
Tower Capacity (RT)
Tower Capacity (kW)
Number of Fan
Airflow Rate (m3/min)
Absorbed Fan Power (kW)
Total Each Fan Power (kW)
Cooling Tower (Peak Load) - For 341RT chillers
Operating CT1 + CT2
Total Capacity (kW)
Heat Rejected Load Requred (kW)
Number of Tower Operating
Total Full Fan Power (kW)
Required Capacity for Each Tower
Total Airflow Rate (m3/min)
Required Airflow Rate (m3/min)
Total Fan Power Required (kW)

Cooling Tower 1
203.7
715
1
1164
10.82
10.82
Percentage of Load
100% (407 RT)
1430
1394
2
21.64
98%
2328
2270
20.3

Cooling Tower 2
203.3
715
1
1164
10.82
10.82

Cooling Tower 3
203.3
715
1
1164
10.82
10.82

Percentage of Load
90% (366RT)
1430
1249
2
24.04
87%
2328
2034
17.2

80% (326RT)
1430
1107
2
27.05
77%
2328
1803
14.3

Forced-draft, blow-thru type

Motor power rating = 15 kW

In the absent of detail data, assume fan efficiency drop

Provision of VSD set at min of 60% speed

assume fan efficiency drops accordingly to % Load.

of 60% speed

Office

Time

example

0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
Total
(highlighted,
0900-1800hrs)

Cooling Load
RT

1200

Operating
chiller(s)

Chiller(s)
power input
(kW)

700 RT x 2 x 90%

626.67

1200

626.67

0.52

Individual equipment efficiency (kW/RT) =

Retail

Time

Cooling Load
RT

Operating
chiller(S)

Chiller(s)
power input
(kW)

0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
Total
(Highlighted,
1000-2200hrs)

0.00

0.00

#DIV/0!

Individual equipment efficiency (kW/RT) =

Hotel

Time

0000
0100
0200

Cooling Load
RT

Operating
chiller(S)

Chiller(s)
power input
(kW)

0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
Total
(Highlighted)

0.00

Individual equipment efficiency (kW/RT) =

0.00
#DIV/0!

D
Operating
Chilled Water
Pump(s)

45kW x 2 x 90%

Condenser
Chilled water
Operating
water pump(s) Operating Cooling
pump(s) power Condenser Water
power input
Tower(s)
input
(kW)
Pump(s)
(kW)

51.92

55kW x 2 x 90%

84.24

51.92

84.24

0.04

0.07

22.5kW x 3

Operating
Chilled Water
Pump(s)

D
Operating
Chilled Water
Pump(s)

Condenser
Chilled water
Operating
water pump(s) Operating Cooling
pump(s) power Condenser Water
power input
Tower(s)
input
(kW)
Pump(s)
(kW)

0.00

0.00

#DIV/0!

#DIV/0!

Condenser
Chilled water
Operating
water pump(s) Operating Cooling
pump(s) power Condenser Water
power input
Tower(s)
input
(kW)
Pump(s)
(kW)

0.00

0.00

#DIV/0!

#DIV/0!

I
Cooling
Tower(s)
power input
(kW)

14.58

14.58

J=C+E+G+I

Total Power Input


(kW)

Chiller Plant
Efficiency

0
0
0
0
0
0
0
0
0
777.40
0
0
0
0
0
0
0
0
0
0
0
0
0
0

#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
0.65
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!

777.40

0.65

0.01

J/A

0.65

J=C+E+G+I

J/A

Cooling
Tower(s)
power input
(kW)

Total Power Input


(kW)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0.00

0.00

#DIV/0!

I
Cooling
Tower(s)
power input
(kW)

Chiller Plant
Efficiency
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!

#DIV/0!

J=C+E+G+I

Total Power Input


(kW)
0
0
0

J/A

Chiller Plant
Efficiency
#DIV/0!
#DIV/0!
#DIV/0!

0.00
#DIV/0!

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!

0.00

#DIV/0!
#DIV/0!

Вам также может понравиться