Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

SettingGroup1

SettingGroup1

CoarseSyncSrc

Off

Off

FineSyncSource

Off

Off

SyncMaster

Off

Off

TimeAdjustRate

Fast

Fast

ModulePosition

BinaryInput
BinDetection

Unit

Min

Max

16

16

PositiveEdge

PositiveEdge

MonthInYear

March

March

DayInWeek

Sunday

Sunday

WeekInMonth

Last

Last

UTCTimeOfDay

3600

3600

86400

MonthInYear

October

October

DayInWeek

Sunday

Sunday

WeekInMonth

Last

Last

UTCTimeOfDay

3600

3600

86400

SynchType

Opto

Opto

TimeDomain

LocalTime

LocalTime

Encoding

IRIG-B

IRIG-B

TimeZoneAs1344

PlusTZ

PlusTZ

ServerIP-Add

0.0.0.0

0.0.0.0

18 character(s)

RedServIP-Add

0.0.0.0

0.0.0.0

18 character(s)

Settings
Activate setting group
ActiveSetGrp
Time
Synchronisation
TimeSynch

TimeSynchBIN

TimeSynchDSTBegin

TimeSynchDSTEnd

TimeSynchIRIG-B

TimeSynchSNTP

TimeSynchTimeZone
NoHalfHourUTC

-24

24

General settings

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

StationName

Station name

Station name

StationNumber

ObjectName

A31

A31

ObjectNumber

UnitName

Unit name

Unit name

UnitNumber

50,0

50,0

SubNetAddr

NodeAddr
NeuronID

Unit

Min

Max

Power system
Identifiers
18 character(s)
0

99999
18 character(s)

99999
18 character(s)

99999

50,0

60,0

-1

255

12

12

-1

255

002002886300

002002886300

Operation

Off

Off

TimerClass

Slow

Slow

Operation

Off

Off

SlaveAddress

30

30

Primary values
Frequency

Hz

Communication
SLM configuration
Rear optical LON port
General

18 character(s)

ADE

SPA

899

899

255

Horizontal communication
Operation

Off

Off

Rear optical SPA-IEC port


Protocol selection SPA or IEC103
Off

Off

SlaveAddress

30

30

BaudRate

9600 Bd

9600 Bd

SlaveAddress

30

30

BaudRate

9600 Bd

9600 Bd

RevPolarity

On

On

Operation
SPA

IEC60870-5-103

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

CycMeasRepTime 5,0

PC Value
5,0

Unit

Min

Max

1,0

3600,0

Station communication
IEC61850-8-1
Operation

Off

Off

IEDName

GOOSE

OEM311_AB

OEM311_AB

Off

Off

Operation

Off

Off

BaudRate

9600 Bd

9600 Bd

WireMode

Two-wire

Two-wire

Operation

Off

Off

SlaveAddress

65519

MasterAddres

65519

Obj1DefVar

1:BISingleBit

1:BISingleBit

Obj2DefVar

3:BIChWithRelTime

3:BIChWithRelTime

Obj4DefVar

3:DIChWithRelTime

3:DIChWithRelTime

Obj10DefVar

2:BOStatus

2:BOStatus

Obj20DefVar

5:BinCnt32WoutF

5:BinCnt32WoutF

Obj22DefVar

1:BinCnt32EvWoutT

1:BinCnt32EvWoutT

Obj30DefVar

3:AI32IntWithoutF

3:AI32IntWithoutF

Obj32DefVar

1:AI32IntEvWoutF

1:AI32IntEvWoutF

Operation

Off

Off

TCPIPLisPort

20000

20000

65535

UDPPortAccData 20000

20000

65535

UDPPortInitNUL 20000

20000

65535

65535

Operation

Off

Off

SlaveAddress

65519

MasterAddres

65519

18 character(s)

DNP3.0
DNP3.0
Operation
Serial channel 1

Serial master 1

TCPIP channel 2

UDPPortCliMast
TCPIP master 2

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

ValMasterAddr

Yes

Yes

MasterIP-Addr

0.0.0.0

0.0.0.0

18 character(s)

255.255.255.255

18 character(s)

MasterIPNetMsk 255.255.255.255

Unit

Min

Max

Obj1DefVar

1:BISingleBit

1:BISingleBit

Obj2DefVar

3:BIChWithRelTime

3:BIChWithRelTime

Obj4DefVar

3:DIChWithRelTime

3:DIChWithRelTime

Obj10DefVar

2:BOStatus

2:BOStatus

Obj20DefVar

5:BinCnt32WoutF

5:BinCnt32WoutF

Obj22DefVar

1:BinCnt32EvWoutT

1:BinCnt32EvWoutT

Obj30DefVar

3:AI32IntWithoutF

3:AI32IntWithoutF

Obj32DefVar

1:AI32IntEvWoutF

1:AI32IntEvWoutF

Operation

Off

Off

TCPIPLisPort

20000

20000

65535

UDPPortAccData 20000

20000

65535

UDPPortInitNUL 20000

20000

65535

65535

Operation

Off

Off

SlaveAddress

65519

MasterAddres

65519

ValMasterAddr

Yes

Yes

MasterIP-Addr

0.0.0.0

0.0.0.0

18 character(s)

255.255.255.255

18 character(s)

TCPIP channel 3

UDPPortCliMast
TCPIP master 3

MasterIPNetMsk 255.255.255.255
Obj1DefVar

1:BISingleBit

1:BISingleBit

Obj2DefVar

3:BIChWithRelTime

3:BIChWithRelTime

Obj4DefVar

3:DIChWithRelTime

3:DIChWithRelTime

Obj10DefVar

2:BOStatus

2:BOStatus

Obj20DefVar

5:BinCnt32WoutF

5:BinCnt32WoutF

Obj22DefVar

1:BinCnt32EvWoutT

1:BinCnt32EvWoutT

Obj30DefVar

3:AI32IntWithoutF

3:AI32IntWithoutF

Obj32DefVar

1:AI32IntEvWoutF

1:AI32IntEvWoutF

Operation

Off

Off

TCPIPLisPort

20000

20000

TCPIP channel 4

65535

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

UDPPortAccData 20000

20000

65535

UDPPortInitNUL 20000

20000

65535

65535

Operation

Off

Off

SlaveAddress

65519

MasterAddres

65519

ValMasterAddr

Yes

Yes

MasterIP-Addr

0.0.0.0

0.0.0.0

18 character(s)

255.255.255.255

18 character(s)

UDPPortCliMast
TCPIP master 4

MasterIPNetMsk 255.255.255.255
Obj1DefVar

1:BISingleBit

1:BISingleBit

Obj2DefVar

3:BIChWithRelTime

3:BIChWithRelTime

Obj4DefVar

3:DIChWithRelTime

3:DIChWithRelTime

Obj10DefVar

2:BOStatus

2:BOStatus

Obj20DefVar

5:BinCnt32WoutF

5:BinCnt32WoutF

Obj22DefVar

1:BinCnt32EvWoutT

1:BinCnt32EvWoutT

Obj30DefVar

3:AI32IntWithoutF

3:AI32IntWithoutF

Obj32DefVar

1:AI32IntEvWoutF

1:AI32IntEvWoutF

Operation

Off

Off

TCPIPLisPort

20000

20000

65535

UDPPortAccData 20000

20000

65535

UDPPortInitNUL 20000

20000

65535

65535

Operation

Off

Off

SlaveAddress

65519

MasterAddres

65519

ValMasterAddr

Yes

Yes

MasterIP-Addr

0.0.0.0

0.0.0.0

18 character(s)

255.255.255.255

18 character(s)

TCPIP channel 5

UDPPortCliMast
TCPIP master 5

MasterIPNetMsk 255.255.255.255
Obj1DefVar

1:BISingleBit

1:BISingleBit

Obj2DefVar

3:BIChWithRelTime

3:BIChWithRelTime

Obj4DefVar

3:DIChWithRelTime

3:DIChWithRelTime

Obj10DefVar

2:BOStatus

2:BOStatus

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Obj20DefVar

5:BinCnt32WoutF

5:BinCnt32WoutF

Obj22DefVar

1:BinCnt32EvWoutT

1:BinCnt32EvWoutT

Obj30DefVar

3:AI32IntWithoutF

3:AI32IntWithoutF

Obj32DefVar

1:AI32IntEvWoutF

1:AI32IntEvWoutF

IPAddress

10.1.150.3

10.1.150.3

18 character(s)

IPMask

255.255.255.0

255.255.255.0

18 character(s)

Link

Off

Off

IPAddress

192.168.1.10

192.168.1.10

18 character(s)

IPMask

255.255.255.0

255.255.255.0

18 character(s)

Link

Off

Off

IPAddress

192.168.2.10

192.168.2.10

18 character(s)

IPMask

255.255.255.0

255.255.255.0

18 character(s)

10.1.150.1

10.1.150.1

18 character(s)

NAMECH1

TRM40-CH1

TRM40-CH1

13 character(s)

RatedTrans1

1,0

1,0

CTStarPoint1

ToObject

ToObject

CTsec1

CTprim1

Unit

Min

Max

TCP-IP configuration
Front port

Rear OEM - port AB

Rear OEM - port CD

Gateway
GWAddress
Analog modules
AnalogInputs6Iand6U 1

0,1

300,0

10

600

600

99999

NAMECH2

TRM40-CH2

TRM40-CH2

RatedTrans2

1,0

1,0

CTStarPoint2

ToObject

ToObject

CTsec2

CTprim2

13 character(s)
A

0,1

300,0

10

600

600

99999

NAMECH3

TRM40-CH3

TRM40-CH3

RatedTrans3

1,0

1,0

CTStarPoint3

ToObject

ToObject

CTsec3

CTprim3

600

13 character(s)
A

0,1

300,0

10

600

99999

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAMECH4

TRM40-CH4

TRM40-CH4

RatedTrans4

1,0

1,0

CTStarPoint4

ToObject

ToObject

CTsec4

CTprim4

Unit

Min

Max
13 character(s)

0,1

300,0

10

600

600

99999

NAMECH5

TRM40-CH5

TRM40-CH5

RatedTrans5

1,0

1,0

CTStarPoint5

ToObject

ToObject

CTsec5

CTprim5

13 character(s)
A

0,1

300,0

10

600

600

99999

NAMECH6

TRM40-CH6

TRM40-CH6

RatedTrans6

1,0

1,0

CTStarPoint6

ToObject

ToObject

CTsec6

CTprim6

13 character(s)
A

0,1

300,0

10

600

600

99999

NAMECH7

TRM40-CH7

TRM40-CH7

RatedTrans7

110,0

110,0

0,1

300,0

VTsec7

110,000

110,000

0,001

999,999

VTprim7

132,00

132,00

kV

0,05

2000,00

NAMECH8

TRM40-CH8

TRM40-CH8

RatedTrans8

110,0

110,0

0,1

300,0

VTsec8

110,000

110,000

0,001

999,999

VTprim8

132,00

132,00

kV

0,05

2000,00

NAMECH9

TRM40-CH9

TRM40-CH9

RatedTrans9

110,0

110,0

0,1

300,0

VTsec9

110,000

110,000

0,001

999,999

VTprim9

132,00

132,00

kV

0,05

2000,00

NAMECH10

TRM40-CH10

TRM40-CH10

RatedTrans10

110,0

110,0

0,1

300,0

VTsec10

110,000

110,000

0,001

999,999

VTprim10

132,00

132,00

kV

0,05

2000,00

NAMECH11

TRM40-CH11

TRM40-CH11

RatedTrans11

110,0

110,0

0,1

300,0

VTsec11

110,000

110,000

0,001

999,999

VTprim11

132,00

132,00

kV

0,05

2000,00

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAMECH12

TRM40-CH12

TRM40-CH12

RatedTrans12

110,0

110,0

0,1

300,0

VTsec12

110,000

110,000

0,001

999,999

VTprim12

132,00

132,00

kV

0,05

2000,00

Unit

Min

Max
13 character(s)

Reference channel service values


TRM40-Ch1

TRM40-Ch1

GRPNAME

LINE VT A

LINE VT A

13 character(s)

AI1NAME

UL1

UL1

13 character(s)

AI2NAME

UL2

UL2

13 character(s)

AI3NAME

UL3

UL3

13 character(s)

AI4NAME

UN optional

UN optional

13 character(s)

DFTRefExtOut

InternalDFTRef

InternalDFTRef

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

LINE CT A

LINE CT A

13 character(s)

AI1NAME

IL1

IL1

13 character(s)

AI2NAME

IL2

IL2

13 character(s)

AI3NAME

IL3

IL3

13 character(s)

AI4NAME

IN optional

IN optional

13 character(s)

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

MUTUAL COMP

MUTUAL COMP

13 character(s)

AI1NAME

Not used

Not used

13 character(s)

AI2NAME

Not used

Not used

13 character(s)

AI3NAME

Not used

Not used

13 character(s)

AI4NAME

PLineCT_IN

PLineCT_IN

13 character(s)

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

LINE VT B

LINE VT B

13 character(s)

AI1NAME

UL1

UL1

13 character(s)

PhaseAngleRef
3PhaseAnalogGroup
PR01

PR07

PR09

PR13

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

AI2NAME

UL2

UL2

13 character(s)

AI3NAME

UL3

UL3

13 character(s)

AI4NAME

Not used

Not used

13 character(s)

DFTRefExtOut

InternalDFTRef

InternalDFTRef

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

BusA_1PhVT

BusA_1PhVT

13 character(s)

AI1NAME

UL1

UL1

13 character(s)

AI2NAME

UL2

UL2

13 character(s)

AI3NAME

UL3

UL3

13 character(s)

AI4NAME

Not used

Not used

13 character(s)

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

BusB_1PhVT

BusB_1PhVT

13 character(s)

AI1NAME

UL1

UL1

13 character(s)

AI2NAME

UL2

UL2

13 character(s)

AI3NAME

UL3

UL3

13 character(s)

AI4NAME

Not used

Not used

13 character(s)

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

LINE CT B

LINE CT B

13 character(s)

AI1NAME

IL1

IL1

13 character(s)

AI2NAME

IL2

IL2

13 character(s)

AI3NAME

IL3

IL3

13 character(s)

AI4NAME

IN optional

IN optional

13 character(s)

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

LineCTMeasure

LineCTMeasure

13 character(s)

AI1NAME

IL1

IL1

13 character(s)

AI2NAME

IL2

IL2

13 character(s)

AI3NAME

IL3

IL3

13 character(s)

Unit

Min

Max

PR14

PR16

PR17

PR19

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

AI4NAME

IN optional

IN optional

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

GRPNAME

MeasurementVT

MeasurementVT

13 character(s)

AI1NAME

UL1

UL1

13 character(s)

AI2NAME

UL2

UL2

13 character(s)

AI3NAME

UL3

UL3

13 character(s)

AI4NAME

Not used

Not used

13 character(s)

DFTReference

InternalDFTRef

InternalDFTRef

ConnectionType

Ph-N

Ph-N

BINAME1

BIM03-BI1

BIM03-BI1

13 character(s)

BINAME2

BIM03-BI2

BIM03-BI2

13 character(s)

BINAME3

BIM03-BI3

BIM03-BI3

13 character(s)

BINAME4

BIM03-BI4

BIM03-BI4

13 character(s)

BINAME5

BIM03-BI5

BIM03-BI5

13 character(s)

BINAME6

BIM03-BI6

BIM03-BI6

13 character(s)

BINAME7

BIM03-BI7

BIM03-BI7

13 character(s)

BINAME8

BIM03-BI8

BIM03-BI8

13 character(s)

BINAME9

BIM03-BI9

BIM03-BI9

13 character(s)

BINAME10

BIM03-BI10

BIM03-BI10

13 character(s)

BINAME11

BIM03-BI11

BIM03-BI11

13 character(s)

BINAME12

BIM03-BI12

BIM03-BI12

13 character(s)

BINAME13

BIM03-BI13

BIM03-BI13

13 character(s)

BINAME14

BIM03-BI14

BIM03-BI14

13 character(s)

BINAME15

BIM03-BI15

BIM03-BI15

13 character(s)

BINAME16

BIM03-BI16

BIM03-BI16

13 character(s)

Operation

On

On

OscRelease

30

30

Hz

30

OscBlock

40

40

Hz

40

BONAME1

BOM04-BO1

BOM04-BO1

13 character(s)

BONAME2

BOM04-BO2

BOM04-BO2

13 character(s)

Unit

Min

Max
13 character(s)

PR21

I/O modules
BIM3

BOM4

10

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

BONAME3

BOM04-BO3

BOM04-BO3

13 character(s)

BONAME4

BOM04-BO4

BOM04-BO4

13 character(s)

BONAME5

BOM04-BO5

BOM04-BO5

13 character(s)

BONAME6

BOM04-BO6

BOM04-BO6

13 character(s)

BONAME7

BOM04-BO7

BOM04-BO7

13 character(s)

BONAME8

BOM04-BO8

BOM04-BO8

13 character(s)

BONAME9

BOM04-BO9

BOM04-BO9

13 character(s)

BONAME10

BOM04-BO10

BOM04-BO10

13 character(s)

BONAME11

BOM04-BO11

BOM04-BO11

13 character(s)

BONAME12

BOM04-BO12

BOM04-BO12

13 character(s)

BONAME13

BOM04-BO13

BOM04-BO13

13 character(s)

BONAME14

BOM04-BO14

BOM04-BO14

13 character(s)

BONAME15

BOM04-BO15

BOM04-BO15

13 character(s)

BONAME16

BOM04-BO16

BOM04-BO16

13 character(s)

BONAME17

BOM04-BO17

BOM04-BO17

13 character(s)

BONAME18

BOM04-BO18

BOM04-BO18

13 character(s)

BONAME19

BOM04-BO19

BOM04-BO19

13 character(s)

BONAME20

BOM04-BO20

BOM04-BO20

13 character(s)

BONAME21

BOM04-BO21

BOM04-BO21

13 character(s)

BONAME22

BOM04-BO22

BOM04-BO22

13 character(s)

BONAME23

BOM04-BO23

BOM04-BO23

13 character(s)

BONAME24

BOM04-BO24

BOM04-BO24

13 character(s)

Operation

On

On

Operation

On

On

tRestart

0,0

0,0

0,0

100,0

tMax

0,0

0,0

0,0

100,0

SeqTypeLED1

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED2

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED3

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED4

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED5

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED6

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED7

LatchedAck-F-S

LatchedAck-F-S

Unit

Min

Max

HMI
LEDs

11

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

SeqTypeLED8

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED9

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED10

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED11

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED12

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED13

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED14

LatchedAck-F-S

LatchedAck-F-S

SeqTypeLED15

LatchedAck-F-S

LatchedAck-F-S

DisplayTimeout

60

60

AutoRepeat

On

On

ContrastLevel

SymbolFont

IEC

IEC

Latest on top

Latest on top

Unit

Min

Max

Min

10

120

-10

20

Screen

Functions
EvListSrtOrder
Current protection
PhaseOverCurrent4Step(PTOC,51/67)
TOC1
MeasType

DFT

DFT

Voltage protection
OverVoltage2Step(PTOV,59)
TOV1
ConnType

PhN DFT

PhN DFT

UnderVoltage2Step(PTUV,27)
TUV1
PhN DFT

PhN DFT

Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

Mode

L1, L2, L3

L1, L2, L3

PowAmpFact

1,000

1,000

0,000

6,000

ConnType
Monitoring
ServiceValues(MMXU)
SVR1
General

12

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

PowAngComp

0,0

0,0

Deg

-180,0

180,0

0,00

0,00

0,00

1,00

SLowLim

0,000

0,000

VA

0,000

10000000000,000

SLowLowLim

0,000

0,000

VA

0,000

10000000000,000

SMin

0,000

0,000

VA

0,000

10000000000,000

SMax

1000000000,000

1000000000,000

VA

0,000

10000000000,000

SRepTyp

Cyclic

Cyclic

PMin

-1000000000,000

-1000000000,000

-10000000000,000
10000000000,000

PMax

1000000000,000

1000000000,000

-10000000000,000
10000000000,000

PRepTyp

Cyclic

Cyclic

QMin

-1000000000,000

-1000000000,000

VAr

-10000000000,000
10000000000,000

QMax

1000000000,000

1000000000,000

VAr

-10000000000,000
10000000000,000

QRepTyp

Cyclic

Cyclic

PFMin

-1,000

-1,000

-1,000

0,000

PFMax

1,000

1,000

0,000

1,000

PFRepTyp

Cyclic

Cyclic

UMin

0,000

0,000

-10000000000,000
10000000000,000

UMax

400000,000

400000,000

-10000000000,000
10000000000,000

URepTyp

Cyclic

Cyclic

IMin

0,000

0,000

-10000000000,000
10000000000,000

IMax

1000,000

1000,000

-10000000000,000
10000000000,000

IRepTyp

Cyclic

Cyclic

FrMin

0,000

0,000

Hz

-10000000000,000
10000000000,000

FrMax

70,000

70,000

Hz

-10000000000,000
10000000000,000

FrRepTyp

Cyclic

Cyclic

Apparent power S

Active power P

Reactive power Q

Power factor PF

Voltage U

Current I

Frequency Fr

CurrentPhasors(MMXU)
CP01
General

13

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Operation

On

On

IBase

3000

IL1DbRepInt

Unit

Min

Max

3000

99999

10

10

Type

300

IL1Max

1000,000

1000,000

0,000

10000000000,000

IL1RepTyp

Cyclic

Cyclic

10

Type

300

IL1 Amplitude

IL1 Angle
IL1AngDbRepInt 10
IL2 Amplitude
IL2DbRepInt

10

10

Type

300

IL2Max

1000,000

1000,000

0,000

10000000000,000

IL2RepTyp

Cyclic

Cyclic

10

Type

300

IL2 Angle
IL2AngDbRepInt 10
IL3 Amplitude
IL3DbRepInt

10

10

Type

300

IL3Max

1000,000

1000,000

0,000

10000000000,000

IL3RepTyp

Cyclic

Cyclic

Type

300

IL3 Angle
IL3AngDbRepInt 10

10

VoltagePhasors(MMXU)
Phase - Phase
VP01
General
Operation

On

On

UBase

400,00

400,00

kV

0,05

2000,00

10

Type

300

500000,000

0,000

10000000000,000

10

Type

300

10

Type

300

500000,000

0,000

10000000000,000

UL12 Amplitude
UL12DbRepInt 10
UL12Max

500000,000

UL12RepTyp Cyclic

Cyclic

UL12 Angle
10
UL12AnDbRepInt
UL23 Amplitude
UL23DbRepInt 10
UL23Max

500000,000

14

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

UL23RepTyp Cyclic

PC Value

Unit

Min

Max

10

Type

300

10

Type

300

500000,000

0,000

10000000000,000

Type

300

Cyclic

UL23 Angle
10
UL23AnDbRepInt
UL31 Amplitude
UL31DbRepInt 10
UL31Max

500000,000

UL31RepTyp Cyclic

Cyclic

UL31 Angle
10
UL31AnDbRepInt

10

Phase - Earth
VN01
General
Operation

On

On

UBase

400,00

400,00

kV

0,05

2000,00

10

Type

300

0,000

10000000000,000

UL1 Amplitude
UL1DbRepInt 10
UL1Max

300000,000

300000,000

UL1RepTyp

Cyclic

Cyclic

UL1LimHys

5,000

5,000

0,000

100,000

10

Type

300

10

Type

300

0,000

10000000000,000

UL1 Angle
UL1AnDbRepInt10
UL2 Amplitude
UL2DbRepInt 10
UL2Max

300000,000

300000,000

UL2RepTyp

Cyclic

Cyclic

UL2LimHys

5,000

5,000

0,000

100,000

10

Type

300

10

Type

300

0,000

10000000000,000

UL2 Angle
UL2AnDbRepInt10
UL3 Amplitude
UL3DbRepInt 10
UL3Max

300000,000

300000,000

UL3RepTyp

Cyclic

Cyclic

UL3LimHys

5,000

5,000

0,000

100,000

10

Type

300

UL3 Angle
UL3AnDbRepInt10

15

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

CurrentSequenceComponents(MSQI)
CSQ1
General
On

On

3I0DbRepInt

10

10

Type

300

3I0Min

0,000

0,000

0,000

10000000000,000

3I0Max

1000,000

1000,000

0,000

10000000000,000

3I0RepTyp

Cyclic

Cyclic

3I0LimHys

5,000

5,000

0,000

100,000

10

Type

300

Operation
3I0 Amplitude

3I0 Angle
3I0AngDbRepInt 10
3I0AngMin

-180,000

-180,000

Deg

-180,000

180,000

3I0AngMax

180,000

180,000

Deg

-180,000

180,000

3I0AngRepTyp

Cyclic

Cyclic

I1DbRepInt

10

10

Type

300

I1Min

0,000

0,000

0,000

10000000000,000

I1Max

1000,000

1000,000

0,000

10000000000,000

I1RepTyp

Cyclic

Cyclic

10

Type

300

Deg

-180,000

180,000

I1 Amplitude

I1 Angle
I1AngDbRepInt 10
I1AngMax

180,000

180,000

I1AngRepTyp

Cyclic

Cyclic

I2DbRepInt

10

10

Type

300

I2Min

0,000

0,000

0,000

10000000000,000

I2Max

1000,000

1000,000

0,000

10000000000,000

I2RepTyp

Cyclic

Cyclic

I2LimHys

5,000

5,000

0,000

100,000

10

Type

300

Deg

-180,000

180,000

I2 Amplitude

I2 Angle
I2AngDbRepInt 10
I2AngMin

-180,000

-180,000

I2AngRepTyp

Cyclic

Cyclic

VoltageSequenceComponents(MSQI)

16

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

On

On

3U0DbRepInt

10

3U0Min

Unit

Min

Max

10

Type

300

0,000

0,000

0,000

10000000000,000

3U0Max

300000,000

300000,000

0,000

10000000000,000

3U0RepTyp

Cyclic

Cyclic

3U0LimHys

5,000

5,000

0,000

100,000

10

Type

300

VSQ1
General
Operation
3U0 Amplitude

3U0 Angle
3U0AngDbRepInt 10
3U0AngZeroDb

m%

100000

3U0AngMin

-180,000

-180,000

Deg

-180,000

180,000

3U0AngMax

180,000

180,000

Deg

-180,000

180,000

3U0AngRepTyp Cyclic

Cyclic

U1 Amplitude
U1DbRepInt

10

10

Type

300

U1Min

0,000

0,000

0,000

10000000000,000

U1Max

300000,000

300000,000

0,000

10000000000,000

U1RepTyp

Cyclic

Cyclic

U1LimHys

5,000

5,000

0,000

100,000

10

Type

300

U1 Angle
U1AngDbRepInt 10
U2 Amplitude
U2DbRepInt

10

10

Type

300

U2Min

0,000

0,000

0,000

10000000000,000

U2Max

300000,000

300000,000

0,000

10000000000,000

U2RepTyp

Cyclic

Cyclic

U2LimHys

5,000

5,000

0,000

100,000

10

Type

300

U2 Angle
U2AngDbRepInt 10
U2AngMin

-180,000

-180,000

Deg

-180,000

180,000

U2AngMax

180,000

180,000

Deg

-180,000

180,000

U2AngRepTyp

Cyclic

Cyclic

DisturbanceReport

17

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

DisturbanceReport(RDRE)
Operation

On

On

PreFaultRecT

0,10

0,10

0,05

1,00

PostFaultRecT

0,5

0,5

0,1

10,0

TimeLimit

1,0

1,0

0,5

10,0

PostRetrig

Off

Off

ZeroAngleRef

Ch

30

OpModeTest

Off

Off

NAME1

TRIP

TRIP

Operation01

On

On

TrigLevel01

Trig on 1

Trig on 1

IndicationMa01

Hide

Hide

SetLED01

On

On

NAME2

DRB01-INPUT2

DRB01-INPUT2

Operation02

Off

Off

TrigLevel02

Trig on 1

Trig on 1

IndicationMa02

Hide

Hide

SetLED02

Off

Off

NAME3

DRB01-INPUT3

DRB01-INPUT3

Operation03

Off

Off

TrigLevel03

Trig on 1

Trig on 1

IndicationMa03

Hide

Hide

SetLED03

Off

Off

NAME4

DRB01-INPUT4

DRB01-INPUT4

Operation04

Off

Off

TrigLevel04

Trig on 1

Trig on 1

IndicationMa04

Hide

Hide

SetLED04

Off

Off

NAME5

DRB01-INPUT5

DRB01-INPUT5

Operation05

Off

Off

TrigLevel05

Trig on 1

Trig on 1

IndicationMa05

Hide

Hide

SetLED05

Off

Off

BinarySignals(RBDR)
Channel 1-16
13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

18

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME6

DRB01-INPUT6

DRB01-INPUT6

Operation06

Off

Off

TrigLevel06

Trig on 1

Trig on 1

IndicationMa06

Hide

Hide

SetLED06

Off

Off

NAME7

ZM01-TRIP

ZM01-TRIP

Operation07

Off

Off

TrigLevel07

Trig on 1

Trig on 1

IndicationMa07

Hide

Hide

SetLED07

Off

Off

NAME8

ZM01-START

ZM01-START

Operation08

Off

Off

TrigLevel08

Trig on 1

Trig on 1

IndicationMa08

Hide

Hide

SetLED08

Off

Off

NAME9

ZM02-TRIP

ZM02-TRIP

Operation09

Off

Off

TrigLevel09

Trig on 1

Trig on 1

IndicationMa09

Hide

Hide

SetLED09

Off

Off

NAME10

ZM02-START

ZM02-START

Operation10

Off

Off

TrigLevel10

Trig on 1

Trig on 1

IndicationMa10

Hide

Hide

SetLED10

Off

Off

NAME11

ZM03-TRIP

ZM03-TRIP

Operation11

Off

Off

TrigLevel11

Trig on 1

Trig on 1

IndicationMa11

Hide

Hide

SetLED11

Off

Off

NAME12

ZM03-START

ZM03-START

Operation12

Off

Off

TrigLevel12

Trig on 1

Trig on 1

IndicationMa12

Hide

Hide

SetLED12

Off

Off

Unit

Min

Max
13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

19

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME13

ZM04-TRIP

ZM04-TRIP

Operation13

Off

Off

TrigLevel13

Trig on 1

Trig on 1

IndicationMa13

Hide

Hide

SetLED13

Off

Off

NAME14

ZM04-START

ZM04-START

Operation14

Off

Off

TrigLevel14

Trig on 1

Trig on 1

IndicationMa14

Hide

Hide

SetLED14

Off

Off

NAME15

ZM05-TRIP

ZM05-TRIP

Operation15

Off

Off

TrigLevel15

Trig on 1

Trig on 1

IndicationMa15

Hide

Hide

SetLED15

Off

Off

NAME16

ZM05-START

ZM05-START

Operation16

Off

Off

TrigLevel16

Trig on 1

Trig on 1

IndicationMa16

Hide

Hide

SetLED16

Off

Off

NAME17

SOTF-TRIP

SOTF-TRIP

Operation17

Off

Off

TrigLevel17

Trig on 1

Trig on 1

IndicationMa17

Hide

Hide

SetLED17

Off

Off

NAME18

ZCOM-TRIP

ZCOM-TRIP

Operation18

Off

Off

TrigLevel18

Trig on 1

Trig on 1

IndicationMa18

Hide

Hide

SetLED18

Off

Off

NAME19

BI_ZCOM-CR

BI_ZCOM-CR

Operation19

Off

Off

TrigLevel19

Trig on 1

Trig on 1

IndicationMa19

Hide

Hide

Unit

Min

Max
13 character(s)

13 character(s)

13 character(s)

13 character(s)

Channel 17-32
13 character(s)

13 character(s)

13 character(s)

20

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

SetLED19

Off

Off

NAME20

ZCAL-TRWEI

ZCAL-TRWEI

Operation20

Off

Off

TrigLevel20

Trig on 1

Trig on 1

IndicationMa20

Hide

Hide

SetLED20

Off

Off

NAME21

ZCAL_IREVBL

ZCAL_IREVBL

Operation21

Off

Off

TrigLevel21

Trig on 1

Trig on 1

IndicationMa21

Hide

Hide

SetLED21

Off

Off

NAME22

PHS-STFWL1

PHS-STFWL1

Operation22

Off

Off

TrigLevel22

Trig on 1

Trig on 1

IndicationMa22

Hide

Hide

SetLED22

Off

Off

NAME23

PHS-STFWL2

PHS-STFWL2

Operation23

Off

Off

TrigLevel23

Trig on 1

Trig on 1

IndicationMa23

Hide

Hide

SetLED23

Off

Off

NAME24

PHS-STFWL3

PHS-STFWL3

Operation24

Off

Off

TrigLevel24

Trig on 1

Trig on 1

IndicationMa24

Hide

Hide

SetLED24

Off

Off

NAME25

PHS-STFWPE

PHS-STFWPE

Operation25

Off

Off

TrigLevel25

Trig on 1

Trig on 1

IndicationMa25

Hide

Hide

SetLED25

Off

Off

NAME26

PSD1-START

PSD1-START

Operation26

Off

Off

TrigLevel26

Trig on 1

Trig on 1

IndicationMa26

Hide

Hide

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

21

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

SetLED26

Off

Off

NAME27

IEF-TRIP

IEF-TRIP

Operation27

Off

Off

TrigLevel27

Trig on 1

Trig on 1

IndicationMa27

Hide

Hide

SetLED27

Off

Off

NAME28

IOC1-TRIP

IOC1-TRIP

Operation28

Off

Off

TrigLevel28

Trig on 1

Trig on 1

IndicationMa28

Hide

Hide

SetLED28

Off

Off

NAME29

DTTR

DTTR

Operation29

Off

Off

TrigLevel29

Trig on 1

Trig on 1

IndicationMa29

Hide

Hide

SetLED29

Off

Off

NAME30

DRB02-INPUT30

DRB02-INPUT30

Operation30

Off

Off

TrigLevel30

Trig on 1

Trig on 1

IndicationMa30

Hide

Hide

SetLED30

Off

Off

NAME31

DRB02-INPUT31

DRB02-INPUT31

Operation31

Off

Off

TrigLevel31

Trig on 1

Trig on 1

IndicationMa31

Hide

Hide

SetLED31

Off

Off

NAME32

L1 FUSE FAIL

L1 FUSE FAIL

Operation32

Off

Off

TrigLevel32

Trig on 1

Trig on 1

IndicationMa32

Hide

Hide

SetLED32

Off

Off

NAME33

BI EXT TRIP3P

BI EXT TRIP3P

Operation33

Off

Off

TrigLevel33

Trig on 1

Trig on 1

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

Channel 33-48
13 character(s)

22

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

IndicationMa33

Hide

Hide

SetLED33

Off

Off

NAME34

DRB03-INPUT34

DRB03-INPUT34

Operation34

Off

Off

TrigLevel34

Trig on 1

Trig on 1

IndicationMa34

Hide

Hide

SetLED34

Off

Off

NAME35

DRB03-INPUT35

DRB03-INPUT35

Operation35

Off

Off

TrigLevel35

Trig on 1

Trig on 1

IndicationMa35

Hide

Hide

SetLED35

Off

Off

NAME36

DRB03-INPUT36

DRB03-INPUT36

Operation36

Off

Off

TrigLevel36

Trig on 1

Trig on 1

IndicationMa36

Hide

Hide

SetLED36

Off

Off

NAME37

BFP BUTR

BFP BUTR

Operation37

Off

Off

TrigLevel37

Trig on 1

Trig on 1

IndicationMa37

Hide

Hide

SetLED37

Off

Off

NAME38

BFP TRRET

BFP TRRET

Operation38

Off

Off

TrigLevel38

Trig on 1

Trig on 1

IndicationMa38

Hide

Hide

SetLED38

Off

Off

NAME39

BI BFP ST3P

BI BFP ST3P

Operation39

Off

Off

TrigLevel39

Trig on 1

Trig on 1

IndicationMa39

Hide

Hide

SetLED39

Off

Off

NAME40

DRB03-INPUT40

DRB03-INPUT40

Operation40

Off

Off

TrigLevel40

Trig on 1

Trig on 1

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

23

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

IndicationMa40

Hide

Hide

SetLED40

Off

Off

NAME41

DRB03-INPUT41

DRB03-INPUT41

Operation41

Off

Off

TrigLevel41

Trig on 1

Trig on 1

IndicationMa41

Hide

Hide

SetLED41

Off

Off

NAME42

DRB03-INPUT42

DRB03-INPUT42

Operation42

Off

Off

TrigLevel42

Trig on 1

Trig on 1

IndicationMa42

Hide

Hide

SetLED42

Off

Off

NAME43

DRB03-INPUT43

DRB03-INPUT43

Operation43

Off

Off

TrigLevel43

Trig on 1

Trig on 1

IndicationMa43

Hide

Hide

SetLED43

Off

Off

NAME44

DRB03-INPUT44

DRB03-INPUT44

Operation44

Off

Off

TrigLevel44

Trig on 1

Trig on 1

IndicationMa44

Hide

Hide

SetLED44

Off

Off

NAME45

DRB03-INPUT45

DRB03-INPUT45

Operation45

Off

Off

TrigLevel45

Trig on 1

Trig on 1

IndicationMa45

Hide

Hide

SetLED45

Off

Off

NAME46

CB CLOSED

CB CLOSED

Operation46

Off

Off

TrigLevel46

Trig on 1

Trig on 1

IndicationMa46

Hide

Hide

SetLED46

Off

Off

NAME47

DRB03-INPUT47

DRB03-INPUT47

Operation47

Off

Off

TrigLevel47

Trig on 1

Trig on 1

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

24

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

IndicationMa47

Hide

Hide

SetLED47

Off

Off

NAME48

TEST MODE ON

TEST MODE ON

Operation48

Off

Off

TrigLevel48

Trig on 1

Trig on 1

IndicationMa48

Hide

Hide

SetLED48

Off

Off

NAME49

CB_CLOSE

CB_CLOSE

Operation49

Off

Off

TrigLevel49

Trig on 1

Trig on 1

IndicationMa49

Hide

Hide

SetLED49

Off

Off

NAME50

CB READY

CB READY

Operation50

Off

Off

TrigLevel50

Trig on 1

Trig on 1

IndicationMa50

Hide

Hide

SetLED50

Off

Off

NAME51

AR UNSUCCL

AR UNSUCCL

Operation51

Off

Off

TrigLevel51

Trig on 1

Trig on 1

IndicationMa51

Hide

Hide

SetLED51

Off

Off

NAME52

AR INPROGR

AR INPROGR

Operation52

Off

Off

TrigLevel52

Trig on 1

Trig on 1

IndicationMa52

Hide

Hide

SetLED52

Off

Off

NAME53

DRB04-INPUT53

DRB04-INPUT53

Operation53

Off

Off

TrigLevel53

Trig on 1

Trig on 1

IndicationMa53

Hide

Hide

SetLED53

Off

Off

NAME54

BI AR START

BI AR START

Operation54

Off

Off

Unit

Min

Max

13 character(s)

Channel 49-64
13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

25

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

TrigLevel54

Trig on 1

Trig on 1

IndicationMa54

Hide

Hide

SetLED54

Off

Off

NAME55

BI AR INHIBIT

BI AR INHIBIT

Operation55

Off

Off

TrigLevel55

Trig on 1

Trig on 1

IndicationMa55

Hide

Hide

SetLED55

Off

Off

NAME56

CB EXTPDIN

CB EXTPDIN

Operation56

Off

Off

TrigLevel56

Trig on 1

Trig on 1

IndicationMa56

Hide

Hide

SetLED56

Off

Off

NAME57

PD TRIP

PD TRIP

Operation57

Off

Off

TrigLevel57

Trig on 1

Trig on 1

IndicationMa57

Hide

Hide

SetLED57

Off

Off

NAME58

DRB04-INPUT58

DRB04-INPUT58

Operation58

Off

Off

TrigLevel58

Trig on 1

Trig on 1

IndicationMa58

Hide

Hide

SetLED58

Off

Off

NAME59

DRB04-INPUT59

DRB04-INPUT59

Operation59

Off

Off

TrigLevel59

Trig on 1

Trig on 1

IndicationMa59

Hide

Hide

SetLED59

Off

Off

NAME60

DRB04-INPUT60

DRB04-INPUT60

Operation60

Off

Off

TrigLevel60

Trig on 1

Trig on 1

IndicationMa60

Hide

Hide

SetLED60

Off

Off

NAME61

DRB04-INPUT61

DRB04-INPUT61

Operation61

Off

Off

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

26

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

TrigLevel61

Trig on 1

Trig on 1

IndicationMa61

Hide

Hide

SetLED61

Off

Off

NAME62

DRB04-INPUT62

DRB04-INPUT62

Operation62

Off

Off

TrigLevel62

Trig on 1

Trig on 1

IndicationMa62

Hide

Hide

SetLED62

Off

Off

NAME63

DRB04-INPUT63

DRB04-INPUT63

Operation63

Off

Off

TrigLevel63

Trig on 1

Trig on 1

IndicationMa63

Hide

Hide

SetLED63

Off

Off

NAME64

DRB04-INPUT64

DRB04-INPUT64

Operation64

Off

Off

TrigLevel64

Trig on 1

Trig on 1

IndicationMa64

Hide

Hide

SetLED64

Off

Off

NAME65

DRB05-INPUT65

DRB05-INPUT65

Operation65

Off

Off

TrigLevel65

Trig on 1

Trig on 1

IndicationMa65

Hide

Hide

SetLED65

Off

Off

NAME66

DRB05-INPUT66

DRB05-INPUT66

Operation66

Off

Off

TrigLevel66

Trig on 1

Trig on 1

IndicationMa66

Hide

Hide

SetLED66

Off

Off

NAME67

DRB05-INPUT67

DRB05-INPUT67

Operation67

Off

Off

TrigLevel67

Trig on 1

Trig on 1

IndicationMa67

Hide

Hide

SetLED67

Off

Off

NAME68

TEF1-TRIP

TEF1-TRIP

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

Channel 65-80
13 character(s)

13 character(s)

13 character(s)

13 character(s)

27

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Operation68

Off

Off

TrigLevel68

Trig on 1

Trig on 1

IndicationMa68

Hide

Hide

SetLED68

Off

Off

NAME69

TEF1-START

TEF1-START

Operation69

Off

Off

TrigLevel69

Trig on 1

Trig on 1

IndicationMa69

Hide

Hide

SetLED69

Off

Off

NAME70

TEF1-STFW

TEF1-STFW

Operation70

Off

Off

TrigLevel70

Trig on 1

Trig on 1

IndicationMa70

Hide

Hide

SetLED70

Off

Off

NAME71

TEF1-STRV

TEF1-STRV

Operation71

Off

Off

TrigLevel71

Trig on 1

Trig on 1

IndicationMa71

Hide

Hide

SetLED71

Off

Off

NAME72

TEF1-2NDHARMD

TEF1-2NDHARMD

Operation72

Off

Off

TrigLevel72

Trig on 1

Trig on 1

IndicationMa72

Hide

Hide

SetLED72

Off

Off

NAME73

EFC1-TRIP

EFC1-TRIP

Operation73

Off

Off

TrigLevel73

Trig on 1

Trig on 1

IndicationMa73

Hide

Hide

SetLED73

Off

Off

NAME74

BI_EFC_CR

BI_EFC_CR

Operation74

Off

Off

TrigLevel74

Trig on 1

Trig on 1

IndicationMa74

Hide

Hide

SetLED74

Off

Off

NAME75

EFCA-TRWEI

EFCA-TRWEI

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

28

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Operation75

Off

Off

TrigLevel75

Trig on 1

Trig on 1

IndicationMa75

Hide

Hide

SetLED75

Off

Off

NAME76

EFC_IREVBL

EFC_IREVBL

Operation76

Off

Off

TrigLevel76

Trig on 1

Trig on 1

IndicationMa76

Hide

Hide

SetLED76

Off

Off

NAME77

TUV1-TRIP

TUV1-TRIP

Operation77

Off

Off

TrigLevel77

Trig on 1

Trig on 1

IndicationMa77

Hide

Hide

SetLED77

Off

Off

NAME78

TUV1-START

TUV1-START

Operation78

Off

Off

TrigLevel78

Trig on 1

Trig on 1

IndicationMa78

Hide

Hide

SetLED78

Off

Off

NAME79

TOV1-TRIP

TOV1-TRIP

Operation79

Off

Off

TrigLevel79

Trig on 1

Trig on 1

IndicationMa79

Hide

Hide

SetLED79

Off

Off

NAME80

TOV1-START

TOV1-START

Operation80

Off

Off

TrigLevel80

Trig on 1

Trig on 1

IndicationMa80

Hide

Hide

SetLED80

Off

Off

NAME81

TOC1-TRIP

TOC1-TRIP

Operation81

Off

Off

TrigLevel81

Trig on 1

Trig on 1

IndicationMa81

Hide

Hide

SetLED81

Off

Off

Unit

Min

Max

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

Channel 81-96
13 character(s)

29

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME82

TOC1-START

TOC1-START

Operation82

Off

Off

TrigLevel82

Trig on 1

Trig on 1

IndicationMa82

Hide

Hide

SetLED82

Off

Off

NAME83

THL1-TRIP

THL1-TRIP

Operation83

Off

Off

TrigLevel83

Trig on 1

Trig on 1

IndicationMa83

Hide

Hide

SetLED83

Off

Off

NAME84

THL1-START

THL1-START

Operation84

Off

Off

TrigLevel84

Trig on 1

Trig on 1

IndicationMa84

Hide

Hide

SetLED84

Off

Off

NAME85

THL1-ALARM

THL1-ALARM

Operation85

Off

Off

TrigLevel85

Trig on 1

Trig on 1

IndicationMa85

Hide

Hide

SetLED85

Off

Off

NAME86

BRC1-TRIP

BRC1-TRIP

Operation86

Off

Off

TrigLevel86

Trig on 1

Trig on 1

IndicationMa86

Hide

Hide

SetLED86

Off

Off

NAME87

BRC1-START

BRC1-START

Operation87

Off

Off

TrigLevel87

Trig on 1

Trig on 1

IndicationMa87

Hide

Hide

SetLED87

Off

Off

NAME88

LOV-TRIP

LOV-TRIP

Operation88

Off

Off

TrigLevel88

Trig on 1

Trig on 1

IndicationMa88

Hide

Hide

SetLED88

Off

Off

Unit

Min

Max
13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

30

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME89

LOV-START

LOV-START

Operation89

Off

Off

TrigLevel89

Trig on 1

Trig on 1

IndicationMa89

Hide

Hide

SetLED89

Off

Off

NAME90

PHS-TRIP

PHS-TRIP

Operation90

Off

Off

TrigLevel90

Trig on 1

Trig on 1

IndicationMa90

Hide

Hide

SetLED90

Off

Off

NAME91

PHS-START

PHS-START

Operation91

Off

Off

TrigLevel91

Trig on 1

Trig on 1

IndicationMa91

Hide

Hide

SetLED91

Off

Off

NAME92

DRB06-INPUT92

DRB06-INPUT92

Operation92

Off

Off

TrigLevel92

Trig on 1

Trig on 1

IndicationMa92

Hide

Hide

SetLED92

Off

Off

NAME93

DISC OPEN

DISC OPEN

Operation93

Off

Off

TrigLevel93

Trig on 1

Trig on 1

IndicationMa93

Hide

Hide

SetLED93

Off

Off

NAME94

DRB06-INPUT94

DRB06-INPUT94

Operation94

Off

Off

TrigLevel94

Trig on 1

Trig on 1

IndicationMa94

Hide

Hide

SetLED94

Off

Off

NAME95

SetGR1 ACTIVE

SetGR1 ACTIVE

Operation95

Off

Off

TrigLevel95

Trig on 1

Trig on 1

IndicationMa95

Hide

Hide

SetLED95

Off

Off

Unit

Min

Max
13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

13 character(s)

31

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME96

SetGR2 ACTIVE

SetGR2 ACTIVE

Operation96

Off

Off

TrigLevel96

Trig on 1

Trig on 1

IndicationMa96

Hide

Hide

SetLED96

Off

Off

NAME1

LINE_A_IL1

LINE_A_IL1

Operation01

On

On

NomValue01

0,0

0,0

UnderTrigOp01

Off

Off

UnderTrigLe01

50

50

OverTrigOp01

Off

Off

OverTrigLe01

200

200

NAME2

LINE_A_IL2

LINE_A_IL2

Operation02

On

On

NomValue02

0,0

0,0

UnderTrigOp02

Off

Off

UnderTrigLe02

50

50

OverTrigOp02

Off

Off

OverTrigLe02

200

200

NAME3

LINE_A_IL3

LINE_A_IL3

Operation03

On

On

NomValue03

0,0

0,0

UnderTrigOp03

Off

Off

UnderTrigLe03

50

50

OverTrigOp03

Off

Off

OverTrigLe03

200

200

NAME4

LINE_A_IN

LINE_A_IN

Operation04

On

On

NomValue04

0,0

0,0

UnderTrigOp04

Off

Off

UnderTrigLe04

50

50

OverTrigOp04

Off

Off

OverTrigLe04

200

200

Unit

Min

Max
13 character(s)

AnalogSignals(RADR)
Channel 1-10
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000

32

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME5

LINE_UL1

LINE_UL1

Operation05

On

On

NomValue05

0,0

0,0

UnderTrigOp05

Off

Off

UnderTrigLe05

50

50

OverTrigOp05

Off

Off

OverTrigLe05

200

200

NAME6

LINE_UL2

LINE_UL2

Operation06

On

On

NomValue06

0,0

0,0

UnderTrigOp06

Off

Off

UnderTrigLe06

50

50

OverTrigOp06

Off

Off

OverTrigLe06

200

200

NAME7

LINE_UL3

LINE_UL3

Operation07

On

On

NomValue07

0,0

0,0

UnderTrigOp07

Off

Off

UnderTrigLe07

50

50

OverTrigOp07

Off

Off

OverTrigLe07

200

200

NAME8

LINE_UN

LINE_UN

Operation08

On

On

NomValue08

0,0

0,0

UnderTrigOp08

Off

Off

UnderTrigLe08

50

50

OverTrigOp08

Off

Off

OverTrigLe08

200

200

NAME9

//LINE M CTN

//LINE M CTN

Operation09

On

On

NomValue09

0,0

0,0

UnderTrigOp09

Off

Off

UnderTrigLe09

50

50

OverTrigOp09

Off

Off

OverTrigLe09

200

200

Unit

Min

Max
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000
13 character(s)

0,0

999999,9

200

5000

33

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

NAME10

NotUsed

NotUsed

Operation10

Off

Off

NomValue10

0,0

0,0

UnderTrigOp10

Off

Off

UnderTrigLe10

50

50

OverTrigOp10

Off

Off

OverTrigLe10

200

DrepChNoIL1

Unit

Min

Max
13 character(s)

0,0

999999,9

200

200

5000

Ch

30

DrepChNoIL2

Ch

30

DrepChNoIL3

Ch

30

DrepChNoIN

Ch

30

DrepChNoIP

Ch

30

DrepChNoUL1

Ch

30

DrepChNoUL2

Ch

30

DrepChNoUL3

Ch

30

RatedMeasur1

1000,00

1000,00

0,05

10000000000,00

RatedMeasur2

1000,00

1000,00

0,05

10000000000,00

RatedMeasur3

1000,00

1000,00

0,05

10000000000,00

RatedMeasur4

1000,00

1000,00

0,05

10000000000,00

RatedMeasur5

1000,00

1000,00

0,05

10000000000,00

RatedMeasur6

1000,00

1000,00

0,05

10000000000,00

RatedMeasur7

1000,00

1000,00

0,05

10000000000,00

RatedMeasur8

1000,00

1000,00

0,05

10000000000,00

RatedMeasur9

1000,00

1000,00

0,05

10000000000,00

RatedMeasur1

1000,00

1000,00

0,05

10000000000,00

RatedMeasur2

1000,00

1000,00

0,05

10000000000,00

RatedMeasur3

1000,00

1000,00

0,05

10000000000,00

RatedMeasur4

1000,00

1000,00

0,05

10000000000,00

RatedMeasur5

1000,00

1000,00

0,05

10000000000,00

FaultLocator(RFLO)
FLO1

IEC60870-5-103
Measurements
UserDefined1

UserDefined2

34

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

RatedMeasur6

1000,00

RatedMeasur7

Unit

Min

Max

1000,00

0,05

10000000000,00

1000,00

1000,00

0,05

10000000000,00

RatedMeasur8

1000,00

1000,00

0,05

10000000000,00

RatedMeasur9

1000,00

1000,00

0,05

10000000000,00

RatedMeasur1

1000,00

1000,00

0,05

10000000000,00

RatedMeasur2

1000,00

1000,00

0,05

10000000000,00

RatedMeasur3

1000,00

1000,00

0,05

10000000000,00

RatedMeasur4

1000,00

1000,00

0,05

10000000000,00

RatedMeasur5

1000,00

1000,00

0,05

10000000000,00

RatedMeasur6

1000,00

1000,00

0,05

10000000000,00

RatedMeasur7

1000,00

1000,00

0,05

10000000000,00

RatedMeasur8

1000,00

1000,00

0,05

10000000000,00

RatedMeasur9

1000,00

1000,00

0,05

10000000000,00

UserDefined3

DisturbanceReport
BinarySignals(RBDR)
Channel 1-16
FUNT1

FunT

255

FUNT2

FunT

255

FUNT3

FunT

255

FUNT4

FunT

255

FUNT5

FunT

255

FUNT6

FunT

255

FUNT7

FunT

255

FUNT8

FunT

255

FUNT9

FunT

255

FUNT10

FunT

255

FUNT11

FunT

255

FUNT12

FunT

255

FUNT13

FunT

255

FUNT14

FunT

255

FUNT15

FunT

255

FUNT16

FunT

255

INFNO1

InfNo

255

INFNO2

InfNo

255

35

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

INFNO3

InfNo

255

INFNO4

InfNo

255

INFNO5

InfNo

255

INFNO6

InfNo

255

INFNO7

InfNo

255

INFNO8

InfNo

255

INFNO9

InfNo

255

INFNO10

InfNo

255

INFNO11

InfNo

255

INFNO12

InfNo

255

INFNO13

InfNo

255

INFNO14

InfNo

255

INFNO15

InfNo

255

INFNO16

InfNo

255

FUNCT17

FunT

255

FUNCT18

FunT

255

FUNCT19

FunT

255

FUNCT20

FunT

255

FUNCT21

FunT

255

FUNCT22

FunT

255

FUNCT23

FunT

255

FUNCT24

FunT

255

FUNCT25

FunT

255

FUNCT26

FunT

255

FUNCT27

FunT

255

FUNCT28

FunT

255

FUNCT29

FunT

255

FUNCT30

FunT

255

FUNCT31

FunT

255

FUNCT32

FunT

255

INFONO17

InfNo

255

INFONO18

InfNo

255

INFONO19

InfNo

255

INFONO20

InfNo

255

Channel 17-32

36

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

INFONO21

InfNo

255

INFONO22

InfNo

255

INFONO23

InfNo

255

INFONO24

InfNo

255

INFONO25

InfNo

255

INFONO26

InfNo

255

INFONO27

InfNo

255

INFONO28

InfNo

255

INFONO29

InfNo

255

INFONO30

InfNo

255

INFONO31

InfNo

255

INFONO32

InfNo

255

FUNCT33

FunT

255

FUNCT34

FunT

255

FUNCT35

FunT

255

FUNCT36

FunT

255

FUNCT37

FunT

255

FUNCT38

FunT

255

FUNCT39

FunT

255

FUNCT40

FunT

255

FUNCT41

FunT

255

FUNCT42

FunT

255

FUNCT43

FunT

255

FUNCT44

FunT

255

FUNCT45

FunT

255

FUNCT46

FunT

255

FUNCT47

FunT

255

FUNCT48

FunT

255

INFONO33

InfNo

255

INFONO34

InfNo

255

INFONO35

InfNo

255

INFONO36

InfNo

255

INFONO37

InfNo

255

INFONO38

InfNo

255

Channel 33-48

37

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

INFONO39

InfNo

255

INFONO40

InfNo

255

INFONO41

InfNo

255

INFONO42

InfNo

255

INFONO43

InfNo

255

INFONO44

InfNo

255

INFONO45

InfNo

255

INFONO46

InfNo

255

INFONO47

InfNo

255

INFONO48

InfNo

255

FUNCT49

FunT

255

FUNCT50

FunT

255

FUNCT51

FunT

255

FUNCT52

FunT

255

FUNCT53

FunT

255

FUNCT54

FunT

255

FUNCT55

FunT

255

FUNCT56

FunT

255

FUNCT57

FunT

255

FUNCT58

FunT

255

FUNCT59

FunT

255

FUNCT60

FunT

255

FUNCT61

FunT

255

FUNCT62

FunT

255

FUNCT63

FunT

255

FUNCT64

FunT

255

INFONO49

InfNo

255

INFONO50

InfNo

255

INFONO51

InfNo

255

INFONO52

InfNo

255

INFONO53

InfNo

255

INFONO54

InfNo

255

INFONO55

InfNo

255

INFONO56

InfNo

255

Channel 49-64

38

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

INFONO57

InfNo

255

INFONO58

InfNo

255

INFONO59

InfNo

255

INFONO60

InfNo

255

INFONO61

InfNo

255

INFONO62

InfNo

255

INFONO63

InfNo

255

INFONO64

InfNo

255

FUNCT65

FunT

255

FUNCT66

FunT

255

FUNCT67

FunT

255

FUNCT68

FunT

255

FUNCT69

FunT

255

FUNCT70

FunT

255

FUNCT71

FunT

255

FUNCT72

FunT

255

FUNCT73

FunT

255

FUNCT74

FunT

255

FUNCT75

FunT

255

FUNCT76

FunT

255

FUNCT77

FunT

255

FUNCT78

FunT

255

FUNCT79

FunT

255

FUNCT80

FunT

255

INFONO65

InfNo

255

INFONO66

InfNo

255

INFONO67

InfNo

255

INFONO68

InfNo

255

INFONO69

InfNo

255

INFONO70

InfNo

255

INFONO71

InfNo

255

INFONO72

InfNo

255

INFONO73

InfNo

255

INFONO74

InfNo

255

Channel 65-80

39

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

INFONO75

InfNo

255

INFONO76

InfNo

255

INFONO77

InfNo

255

INFONO78

InfNo

255

INFONO79

InfNo

255

INFONO80

InfNo

255

FUNCT81

FunT

255

FUNCT82

FunT

255

FUNCT83

FunT

255

FUNCT84

FunT

255

FUNCT85

FunT

255

FUNCT86

FunT

255

FUNCT87

FunT

255

FUNCT88

FunT

255

FUNCT89

FunT

255

FUNCT90

FunT

255

FUNCT91

FunT

255

FUNCT92

FunT

255

FUNCT93

FunT

255

FUNCT94

FunT

255

FUNCT95

FunT

255

FUNCT96

FunT

255

INFONO81

InfNo

255

INFONO82

InfNo

255

INFONO83

InfNo

255

INFONO84

InfNo

255

INFONO85

InfNo

255

INFONO86

InfNo

255

INFONO87

InfNo

255

INFONO88

InfNo

255

INFONO89

InfNo

255

INFONO90

InfNo

255

INFONO91

InfNo

255

INFONO92

InfNo

255

Channel 81-96

40

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

INFONO93

InfNo

255

INFONO94

InfNo

255

INFONO95

InfNo

255

INFONO96

InfNo

255

Metering
ThreePhEnergMeas(MMTR)
ETP1
Operation

On

On

StartAcc

Off

Off

tEnergy

1 Minute

1 Minute

tEnergyOnPls

1,000

1,000

0,000

60,000

tEnergyOffPls

0,500

0,500

0,000

60,000

EAFAccPlsQty

100,000

100,000

MWh

0,001

10000,000

EARAccPlsQty

100,000

100,000

MWh

0,001

10000,000

ERFAccPlsQty

100,000

100,000

MVArh

0,001

10000,000

ERVAccPlsQty

100,000

100,000

MVArh

0,001

10000,000

Operation

On

On

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

3,48

3,48

ohm/p

0,10

3000,00

R1

1,37

1,37

ohm/p

0,10

1000,00

X0

10,66

10,66

ohm/p

0,10

9000,00

R0

2,82

2,82

ohm/p

0,50

3000,00

RFPP

25,42

25,42

ohm/l

1,00

3000,00

RFPE

38,62

38,62

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

Setting group N1
Impedance Protection
DistanceZones(PDIS,21)
ZM01

41

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

IMinOpIN

%IB

30

Operation

On

On

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

6,69

6,69

ohm/p

0,50

3000,00

R1

2,65

2,65

ohm/p

0,10

1000,00

X0

20,52

20,52

ohm/p

0,50

9000,00

R0

5,42

5,42

ohm/p

0,50

3000,00

RFPP

35,07

35,07

ohm/l

1,00

3000,00

RFPE

53,11

53,11

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,350

0,350

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,350

0,350

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

Operation

On

On

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

11,30

11,30

ohm/p

0,50

3000,00

R1

4,47

4,47

ohm/p

0,10

1000,00

X0

36,64

36,64

ohm/p

0,50

9000,00

R0

9,16

9,16

ohm/p

0,50

3000,00

RFPP

48,88

48,88

ohm/l

1,00

3000,00

RFPE

73,82

73,82

ohm/l

1,00

9000,00

OperationPP

On

On

ZM02

ZM03

42

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Timer tPP

On

On

tPP

0,700

0,700

OperationPE

On

On

Timer tPE

On

On

tPE

0,700

IMinOpPP
IMinOpPE

Unit

Min

Max

0,000

60,000

0,700

0,000

60,000

20

20

%IB

10

30

20

20

%IB

10

30

Operation

Off

Off

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

OperationDir

Non-directional

Non-directional

X1

6,69

6,69

ohm/p

0,50

3000,00

R1

2,65

2,65

ohm/p

0,10

1000,00

X0

20,52

20,52

ohm/p

0,50

9000,00

R0

5,42

5,42

ohm/p

0,50

3000,00

RFPP

35,07

35,07

ohm/l

1,00

3000,00

RFPE

53,11

53,11

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

Operation

Off

Off

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

OperationDir

Reverse

Reverse

X1

40,00

40,00

ohm/p

0,50

3000,00

R1

5,00

5,00

ohm/p

0,10

1000,00

X0

120,00

120,00

ohm/p

0,50

9000,00

R0

15,00

15,00

ohm/p

0,50

3000,00

ZM04

ZM05

43

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

RFPP

30,00

30,00

ohm/l

1,00

3000,00

RFPE

100,00

100,00

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,300

0,300

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,300

0,300

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

INBlockPP

40

40

%IPh

10

100

INReleasePE

20

20

%IPh

10

100

RLdFw

76,20

76,20

ohm/p

1,00

3000,00

RLdRv

76,20

76,20

ohm/p

1,00

3000,00

ArgLd

30

30

Deg

70

X1

16,26

16,26

ohm/p

0,50

3000,00

X0

49,88

49,88

ohm/p

0,50

9000,00

RFFwPP

63,55

63,55

ohm/l

0,50

3000,00

RFRvPP

63,55

63,55

ohm/l

0,50

3000,00

RFFwPE

73,00

73,00

ohm/l

1,00

9000,00

RFRvPE

73,00

73,00

ohm/l

1,00

9000,00

IMinOpPP

10

10

%IB

30

IMinOpPE

%IB

30

PhaseSelection(PDIS,21)
PHS1

DirectionalImpedance(RDIR)
ZD01
ArgNegRes

115

115

Deg

90

175

ArgDir

15

15

Deg

45

IMinOp

10

10

%IB

99999

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

AutomaticSOTF(PSOF)

44

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Operation

Off

Off

IBase

600

UBase

Unit

Min

Max

600

99999

132,00

132,00

kV

0,05

2000,00

Mode

Impedance

Impedance

AutoInit

Off

Off

IPh<

20

20

%IB

100

UPh<

70

70

%UB

100

tDuration

0,020

0,020

0,000

60,000

tSOTF

0,000

0,000

0,000

60,000

tDLD

0,200

0,200

0,000

60,000

SFV1

PowerSwingDetection(RPSB,78)
PSD1
Operation

On

On

X1InFw

13,55

13,55

ohm

0,10

3000,00

R1LIn

5,35

5,35

ohm

0,10

1000,00

R1FInFw

58,66

58,66

ohm

0,10

1000,00

X1InRv

13,55

13,55

ohm

0,10

3000,00

R1FInRv

58,66

58,66

ohm

0,10

1000,00

OperationLdCh

On

On

RLdOutFw

66,29

66,29

ohm

0,10

3000,00

ArgLd

30

30

Deg

70

RLdOutRv

66,29

66,29

ohm

0,10

3000,00

kLdRFw

0,75

0,75

Mult

0,50

0,90

kLdRRv

0,75

0,75

Mult

0,50

0,90

tEF

2,000

2,000

0,000

60,000

IMinOpPE

10

10

%IB

30

IBase

600

600

99999

99999

Current protection
BreakerFailure(RBRF,50BF)
BFP1
Operation

Off

Off

IBase

3000

3000

FunctionMode

Current

Current

BuTripMode

1 out of 3

1 out of 3

45

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

RetripMode

Retrip Off

Retrip Off

IP>

10

IN>

Unit

Min

Max

10

%IB

200

10

10

%IB

200

t1

0,000

0,000

0,000

60,000

t2

0,150

0,150

0,000

60,000

t2MPh

0,150

0,150

0,000

60,000

tPulse

0,200

0,200

0,000

60,000

BrokenCondCheck(PTOC,46)
BRC1
Operation

Off

Off

IBase

3000

3000

99999

Iub>

50

50

%IM

50

90

IP>

20

20

%IB

100

tOper

5,000

5,000

0,000

60,000

99999

%IB

2500

InstPhaseOverCurrent(PIOC,50)
IOC1
Operation

Off

Off

IBase

3000

3000

OpMode

1 out of 3

1 out of 3

IP>>

200

200

InstResidualOverCurrent(PIOC,50N)
IEF1
Operation

Off

Off

IBase

3000

3000

99999

IN>>

200

200

%IB

2500

PhaseOverCurrent4Step(PTOC,51/67)
TOC1
General
Operation

Off

Off

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

AngleRCA

55

55

Deg

40

65

AngleROA

80

80

Deg

40

89

StartPhSel

1 out of 3

1 out of 3

Step 1

46

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

DirMode1

Non-directional

Non-directional

Characterist1

ANSI Def. Time

ANSI Def. Time

I1>

1000

t1

Unit

Min

Max

1000

%IB

2500

0,000

0,000

0,000

60,000

k1

0,05

0,05

0,05

999,00

t1Min

0,000

0,000

0,000

60,000

I1Mult

2,0

2,0

1,0

10,0

DirMode2

Non-directional

Non-directional

Characterist2

ANSI Def. Time

ANSI Def. Time

I2>

500

500

%IB

2500

t2

0,400

0,400

0,000

60,000

k2

0,05

0,05

0,05

999,00

I2Mult

2,0

2,0

1,0

10,0

t2Min

0,000

0,000

0,000

60,000

DirMode3

Non-directional

Non-directional

Characterist3

ANSI Def. Time

ANSI Def. Time

I3>

250

250

%IB

2500

t3

0,800

0,800

0,000

60,000

k3

0,05

0,05

0,05

999,00

t3Min

0,000

0,000

0,000

60,000

I3Mult

2,0

2,0

1,0

10,0

DirMode4

Non-directional

Non-directional

Characterist4

ANSI Def. Time

ANSI Def. Time

I4>

175

175

%IB

2500

t4

2,000

2,000

0,000

60,000

k4

0,05

0,05

0,05

999,00

t4Min

0,000

0,000

0,000

60,000

I4Mult

2,0

2,0

1,0

10,0

Step 2

Step 3

Step 4

ResidualOverCurr4Step(PTOC,51N/67N)
TEF1
General
Operation

Off

Off

47

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

AngleRCA

65

65

Deg

-180

180

polMethod

Voltage

Voltage

UPolMin

%UB

100

IPolMin

%IB

100

RNPol

5,00

5,00

ohm

0,50

1000,00

XNPol

40,00

40,00

ohm

0,50

3000,00

IN>Dir

10

10

%IB

100

2ndHarmStab

20

20

100

BlkParTransf

Off

Off

UseStartValue

IN4>

IN4>

SOTF

Off

Off

ActivationSOTF

Open

Open

StepForSOTF

Step 2

Step 2

HarmResSOTF

Off

Off

tSOTF

0,200

0,200

0,000

60,000

t4U

1,000

1,000

0,000

60,000

DirMode1

Non-directional

Non-directional

Characterist1

ANSI Def. Time

ANSI Def. Time

IN1>

100

100

%IB

2500

t1

0,000

0,000

0,000

60,000

k1

0,05

0,05

0,05

999,00

IN1Mult

2,0

2,0

1,0

10,0

t1Min

0,000

0,000

0,000

60,000

HarmRestrain1

On

On

DirMode2

Non-directional

Non-directional

Characterist2

ANSI Def. Time

ANSI Def. Time

IN2>

50

50

%IB

2500

t2

0,400

0,400

0,000

60,000

k2

0,05

0,05

0,05

999,00

IN2Mult

2,0

2,0

1,0

10,0

t2Min

0,000

0,000

0,000

60,000

Step 1

Step 2

48

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

On

On

DirMode3

Non-directional

Non-directional

Characterist3

ANSI Def. Time

ANSI Def. Time

IN3>

33

t3

Unit

Min

Max

33

%IB

2500

0,800

0,800

0,000

60,000

k3

0,05

0,05

0,05

999,00

IN3Mult

2,0

2,0

1,0

10,0

t3Min

0,000

0,000

0,000

60,000

HarmRestrain3

On

On

DirMode4

Non-directional

Non-directional

Characterist4

ANSI Def. Time

ANSI Def. Time

IN4>

17

17

%IB

2500

t4

1,200

1,200

0,000

60,000

k4

0,05

0,05

0,05

999,00

IN4Mult

2,0

2,0

1,0

10,0

t4Min

0,000

0,000

0,000

60,000

HarmRestrain4

On

On

HarmRestrain2
Step 3

Step 4

ThermalOverload1TimeConst(PTTR,26)
THL1
Operation

Off

Off

IBase

3000

3000

99999

TRef

90

90

Deg

600

IRef

100

100

%IB

400

IMult

Tau

45

45

Min

1000

AlarmTemp

80

80

Deg

200

TripTemp

90

90

Deg

600

ReclTemp

75

75

Deg

600

tPulse

0,10

0,10

0,05

0,30

AmbiSens

Off

Off

DefaultAmbTemp

20

20

Deg

-50

250

DefaultTemp

50

50

Deg

-50

600

Voltage protection

49

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Operation

Off

Off

UBase

400,0

UPE
tTrip

Unit

Min

Max

400,0

kV

0,1

9999,9

70

70

%UB

100

7,000

7,000

0,000

60,000

kV

0,05

2000,00

LossOfVoltage(PTUV,27)
LOV1

OverVoltage2Step(PTOV,59)
TOV1
General
Operation

Off

Off

UBase

400,00

400,00

Step 1
OperationStep1 On

On

Characterist1

Definite time

Definite time

OpMode1

1 out of 3

1 out of 3

U1>

120

120

%UB

200

t1

5,00

5,00

0,00

6000,00

t1Min

5,000

5,000

0,000

60,000

k1

0,05

0,05

0,05

1,10

HystAbs1

0,5

0,5

%UB

0,0

100,0

OperationStep2 On

On

Step 2

Characterist2

Definite time

Definite time

OpMode2

1 out of 3

1 out of 3

U2>

150

150

%UB

200

t2

5,000

5,000

0,000

60,000

t2Min

5,000

5,000

0,000

60,000

k2

0,05

0,05

0,05

1,10

HystAbs2

0,5

0,5

%UB

0,0

100,0

kV

0,05

2000,00

UnderVoltage2Step(PTUV,27)
TUV1
General
Operation

Off

Off

UBase

400,00

400,00

Step 1

50

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

OperationStep1 On

PC Value

Unit

Min

Max

On

Characterist1

Definite time

Definite time

OpMode1

1 out of 3

1 out of 3

U1<

70

70

%UB

100

t1

5,00

5,00

0,00

6000,00

t1Min

5,000

5,000

0,000

60,000

k1

0,05

0,05

0,05

1,10

IntBlkSel1

Off

Off

IntBlkStVal1

20

20

%UB

100

tBlkUV1

0,000

0,000

0,000

60,000

HystAbs1

0,5

0,5

%UB

0,0

100,0

OperationStep2 On

On

Step 2

Characterist2

Definite time

Definite time

OpMode2

1 out of 3

1 out of 3

U2<

50

50

%UB

100

t2

5,000

5,000

0,000

60,000

t2Min

5,000

5,000

0,000

60,000

k2

0,05

0,05

0,05

1,10

IntBlkSel2

Off

Off

IntBlkStVal2

20

20

%UB

100

tBlkUV2

0,000

0,000

0,000

60,000

HystAbs2

0,5

0,5

%UB

0,0

100,0

Scheme communication
ZSchemeCommunication(PSCH,85)
ZCOM
Operation

Off

Off

SchemeType

Permissive OR

Permissive OR

tCoord

0,035

0,035

0,000

60,000

tSendMin

0,100

0,100

0,000

60,000

ZCurrentReversalWEI(PSCH,85)
ZCAL
CurrRev

Off

Off

tPickUpRev

0,020

0,020

0,000

60,000

tDelayRev

0,060

0,060

0,000

60,000

51

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

WEI

Off

Off

tPickUpWEI

0,010

UBase

Unit

Min

Max

0,010

0,000

60,000

400,00

400,00

kV

0,05

2000,00

UPP<

70

70

%UB

10

90

UPN<

70

70

%UB

10

90

EFCurrentReversalWEI(PSCH,85)
EFCA
CurrRev

Off

Off

tPickUpRev

0,020

0,020

0,000

60,000

tDelayRev

0,060

0,060

0,000

60,000

WEI

Off

Off

tPickUpWEI

0,000

0,000

0,000

60,000

UBase

400,00

400,00

kV

0,05

2000,00

3U0>

25

25

%UB

70

EFSchemeCommunication(PSCH,85)
EFC1
Operation

Off

Off

SchemeType

Permissive UR

Permissive UR

tCoord

0,035

0,035

0,000

60,000

tSendMin

0,100

0,100

0,000

60,000

Secondary system supervision


FuseFailure(RFUF)
FSD1
Operation

On

On

IBase

600

600

99999

UBase

132,00

132,00

kV

0,05

2000,00

OpMode

UNsINs

UNsINs

3U0>

30

30

%UB

100

3I0<

10

10

%IB

100

3U2>

30

30

%UB

100

3I2<

10

10

%IB

100

OpDUDI

Off

Off

DU>

60

60

%UB

100

DI<

15

15

%IB

100

UPh>

70

70

%UB

100

52

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

IPh>

10

10

%IB

100

SealIn

Off

Off

USealln<

70

70

%UB

100

IDLD<

%IB

100

UDLD<

60

60

%UB

100

Operation

Off

Off

ARMode

1/2/3ph

1/2/3ph

t1 1Ph

1,000

1,000

0,000

60,000

t1 3Ph

6,000

6,000

0,000

60,000

t1 3PhHS

0,400

0,400

0,000

60,000

tReclaim

60,00

60,00

0,00

6000,00

tSync

30,00

30,00

0,00

6000,00

tTrip

0,200

0,200

0,000

60,000

tPulse

0,200

0,200

0,000

60,000

tCBClosedMin

5,00

5,00

0,00

6000,00

tUnsucCl

30,00

30,00

0,00

6000,00

Priority

None

None

tWaitForMaster

60,00

60,00

0,00

6000,00

Operation

Off

Off

SelPhaseBus1

phase2

phase2

SelPhaseBus2

phase2

phase2

SelPhaseLine1

phase2

phase2

SelPhaseLine2

phase2

phase2

CBConfig

No voltage sel.

No voltage sel.

UBase

400,000

400,000

kV

0,001

9999,999

PhaseShift

Deg

-180

180

URatio

1,000

1,000

0,040

25,000

OperationSynch

Off

Off

UHighBusSynch

80,0

80,0

%UB

50,0

120,0

UHighLineSynch

80,0

80,0

%UB

50,0

120,0

Control
AutoRecloser(RREC,79)
AR01

Synchronizing(RSYN,25)
SYN1

53

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

UDiffSynch

10,0

10,0

%UB

2,0

50,0

FreqDiffMin

0,010

0,010

Hz

0,003

0,250

FreqDiffMax

0,200

0,200

Hz

0,050

0,250

FreqRateChange

0,300

0,300

Hz/s

0,000

0,500

tBreaker

0,080

0,080

0,000

60,000

tClosePulse

0,200

0,200

0,050

60,000

tMaxSynch

600,00

600,00

0,00

6000,00

tMinSynch

2,000

2,000

0,000

60,000

OperationSC

On

On

UHighBusSC

80,0

80,0

%UB

50,0

120,0

UHighLineSC

80,0

80,0

%UB

50,0

120,0

UDiffSC

15,0

15,0

%UB

2,0

50,0

FreqDiffA

0,010

0,010

Hz

0,003

1,000

FreqDiffM

0,010

0,010

Hz

0,003

1,000

PhaseDiffA

25,0

25,0

Deg

5,0

90,0

PhaseDiffM

25,0

25,0

Deg

5,0

90,0

tSCA

0,100

0,100

0,000

60,000

tSCM

0,100

0,100

0,000

60,000

AutoEnerg

DBLL

DBLL

ManEnerg

Both

Both

ManEnergDBDL

Off

Off

UHighBusEnerg

80,0

80,0

%UB

50,0

120,0

UHighLineEnerg

80,0

80,0

%UB

50,0

120,0

ULowBusEnerg

40,0

40,0

%UB

10,0

80,0

ULowLineEnerg

40,0

40,0

%UB

10,0

80,0

UMaxEnerg

115,0

115,0

%UB

50,0

180,0

tAutoEnerg

0,100

0,100

0,000

60,000

tManEnerg

0,100

0,100

0,000

60,000

R1A

15,000

15,000

ohm/p

0,001

1500,000

X1A

39,000

39,000

ohm/p

0,001

1500,000

R1B

2,150

2,150

ohm/p

0,001

1500,000

X1B

5,430

5,430

ohm/p

0,001

1500,000

Monitoring
FaultLocator(RFLO)
FLO1

54

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

R1L

1,616

1,616

ohm/p

0,001

1500,000

X1L

4,088

4,088

ohm/p

0,001

1500,000

R0L

3,314

3,314

ohm/p

0,001

1500,000

X0L

12,540

12,540

ohm/p

0,001

1500,000

R0M

0,000

0,000

ohm/p

0,000

1500,000

X0M

0,000

0,000

ohm/p

0,000

1500,000

LineLength

10,2

10,2

0,0

10000,0

Operation

On

On

Program

3 phase

3 phase

tTripMin

0,150

0,150

0,000

60,000

Operation

On

On

PulseTime

0,150

0,150

0,050

60,000

OnDelay

0,000

0,000

0,000

60,000

OffDelay

0,000

0,000

0,000

60,000

ModeOutput1

Steady

Steady

ModeOutput2

Steady

Steady

ModeOutput3

Steady

Steady

Operation

On

On

PulseTime

0,150

0,150

0,050

60,000

OnDelay

0,000

0,000

0,000

60,000

OffDelay

0,000

0,000

0,000

60,000

ModeOutput1

Steady

Steady

ModeOutput2

Steady

Steady

ModeOutput3

Steady

Steady

On

On

Off

Off

Logic
TripLogic(PTRC,94)
TRP1

TripMatrix(GGIO)
TR01

TR07

LogicGate
GT01
Operation
GT13
Operation

55

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Off

Off

Off

Off

Operation

On

On

IBase

3000

UBase

Unit

Min

Max

3000

99999

400,00

400,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

30,00

30,00

ohm/p

0,10

3000,00

R1

5,00

5,00

ohm/p

0,10

1000,00

X0

100,00

100,00

ohm/p

0,10

9000,00

R0

15,00

15,00

ohm/p

0,50

3000,00

RFPP

30,00

30,00

ohm/l

1,00

3000,00

RFPE

100,00

100,00

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

IMinOpIN

%IB

30

Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

40,00

40,00

ohm/p

0,50

3000,00

R1

5,00

5,00

ohm/p

0,10

1000,00

X0

120,00

120,00

ohm/p

0,50

9000,00

GT16
Operation
GT21
Operation
Setting group N2
Impedance Protection
DistanceZones(PDIS,21)
ZM01

ZM02

56

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

R0

15,00

15,00

ohm/p

0,50

3000,00

RFPP

30,00

30,00

ohm/l

1,00

3000,00

RFPE

100,00

100,00

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

40,00

40,00

ohm/p

0,50

3000,00

R1

5,00

5,00

ohm/p

0,10

1000,00

X0

120,00

120,00

ohm/p

0,50

9000,00

R0

15,00

15,00

ohm/p

0,50

3000,00

RFPP

30,00

30,00

ohm/l

1,00

3000,00

RFPE

100,00

100,00

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

OperationDir

Forward

Forward

ZM03

ZM04

57

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

X1

40,00

40,00

ohm/p

0,50

3000,00

R1

5,00

5,00

ohm/p

0,10

1000,00

X0

120,00

120,00

ohm/p

0,50

9000,00

R0

15,00

15,00

ohm/p

0,50

3000,00

RFPP

30,00

30,00

ohm/l

1,00

3000,00

RFPE

100,00

100,00

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

OperationDir

Forward

Forward

X1

40,00

40,00

ohm/p

0,50

3000,00

R1

5,00

5,00

ohm/p

0,10

1000,00

X0

120,00

120,00

ohm/p

0,50

9000,00

R0

15,00

15,00

ohm/p

0,50

3000,00

RFPP

30,00

30,00

ohm/l

1,00

3000,00

RFPE

100,00

100,00

ohm/l

1,00

9000,00

OperationPP

On

On

Timer tPP

On

On

tPP

0,000

0,000

0,000

60,000

OperationPE

On

On

Timer tPE

On

On

tPE

0,000

0,000

0,000

60,000

IMinOpPP

20

20

%IB

10

30

IMinOpPE

20

20

%IB

10

30

ZM05

PhaseSelection(PDIS,21)
PHS1

58

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

INBlockPP

40

40

%IPh

10

100

INReleasePE

20

20

%IPh

10

100

RLdFw

80,00

80,00

ohm/p

1,00

3000,00

RLdRv

80,00

80,00

ohm/p

1,00

3000,00

ArgLd

30

30

Deg

70

X1

40,00

40,00

ohm/p

0,50

3000,00

X0

120,00

120,00

ohm/p

0,50

9000,00

RFFwPP

30,00

30,00

ohm/l

0,50

3000,00

RFRvPP

30,00

30,00

ohm/l

0,50

3000,00

RFFwPE

100,00

100,00

ohm/l

1,00

9000,00

RFRvPE

100,00

100,00

ohm/l

1,00

9000,00

IMinOpPP

10

10

%IB

30

IMinOpPE

%IB

30

DirectionalImpedance(RDIR)
ZD01
ArgNegRes

115

115

Deg

90

175

ArgDir

15

15

Deg

45

IMinOp

10

10

%IB

99999

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

Mode

UILevel

UILevel

AutoInit

Off

Off

IPh<

20

20

%IB

100

UPh<

70

70

%UB

100

tDuration

0,020

0,020

0,000

60,000

tSOTF

1,000

1,000

0,000

60,000

tDLD

0,200

0,200

0,000

60,000

AutomaticSOTF(PSOF)
SFV1

PowerSwingDetection(RPSB,78)

59

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Operation

Off

Off

X1InFw

30,00

R1LIn

Unit

Min

Max

30,00

ohm

0,10

3000,00

30,00

30,00

ohm

0,10

1000,00

R1FInFw

30,00

30,00

ohm

0,10

1000,00

X1InRv

30,00

30,00

ohm

0,10

3000,00

R1FInRv

30,00

30,00

ohm

0,10

1000,00

OperationLdCh

On

On

RLdOutFw

30,00

30,00

ohm

0,10

3000,00

ArgLd

25

25

Deg

70

RLdOutRv

30,00

30,00

ohm

0,10

3000,00

kLdRFw

0,75

0,75

Mult

0,50

0,90

kLdRRv

0,75

0,75

Mult

0,50

0,90

tEF

3,000

3,000

0,000

60,000

IMinOpPE

10

10

%IB

30

IBase

3000

3000

99999

99999

PSD1

Current protection
BreakerFailure(RBRF,50BF)
BFP1
Operation

Off

Off

IBase

3000

3000

FunctionMode

Current

Current

BuTripMode

1 out of 3

1 out of 3

RetripMode

Retrip Off

Retrip Off

IP>

10

10

%IB

200

IN>

10

10

%IB

200

t1

0,000

0,000

0,000

60,000

t2

0,150

0,150

0,000

60,000

t2MPh

0,150

0,150

0,000

60,000

tPulse

0,200

0,200

0,000

60,000

BrokenCondCheck(PTOC,46)
BRC1
Operation

Off

Off

IBase

3000

3000

99999

Iub>

50

50

%IM

50

90

60

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

IP>

20

20

%IB

100

tOper

5,000

5,000

0,000

60,000

99999

%IB

2500

InstPhaseOverCurrent(PIOC,50)
IOC1
Operation

Off

Off

IBase

3000

3000

OpMode

1 out of 3

1 out of 3

IP>>

200

200

InstResidualOverCurrent(PIOC,50N)
IEF1
Operation

Off

Off

IBase

3000

3000

99999

IN>>

200

200

%IB

2500

PhaseOverCurrent4Step(PTOC,51/67)
TOC1
General
Operation

Off

Off

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

AngleRCA

55

55

Deg

40

65

AngleROA

80

80

Deg

40

89

StartPhSel

1 out of 3

1 out of 3

DirMode1

Non-directional

Non-directional

Characterist1

ANSI Def. Time

ANSI Def. Time

I1>

1000

1000

%IB

2500

t1

0,000

0,000

0,000

60,000

k1

0,05

0,05

0,05

999,00

t1Min

0,000

0,000

0,000

60,000

I1Mult

2,0

2,0

1,0

10,0

DirMode2

Non-directional

Non-directional

Characterist2

ANSI Def. Time

ANSI Def. Time

I2>

500

500

%IB

2500

t2

0,400

0,400

0,000

60,000

Step 1

Step 2

61

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

k2

0,05

I2Mult
t2Min

Unit

Min

Max

0,05

0,05

999,00

2,0

2,0

1,0

10,0

0,000

0,000

0,000

60,000

DirMode3

Non-directional

Non-directional

Characterist3

ANSI Def. Time

ANSI Def. Time

I3>

250

250

%IB

2500

t3

0,800

0,800

0,000

60,000

k3

0,05

0,05

0,05

999,00

t3Min

0,000

0,000

0,000

60,000

I3Mult

2,0

2,0

1,0

10,0

DirMode4

Non-directional

Non-directional

Characterist4

ANSI Def. Time

ANSI Def. Time

I4>

175

175

%IB

2500

t4

2,000

2,000

0,000

60,000

k4

0,05

0,05

0,05

999,00

t4Min

0,000

0,000

0,000

60,000

I4Mult

2,0

2,0

1,0

10,0

Step 3

Step 4

ResidualOverCurr4Step(PTOC,51N/67N)
TEF1
General
Operation

Off

Off

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

AngleRCA

65

65

Deg

-180

180

polMethod

Voltage

Voltage

UPolMin

%UB

100

IPolMin

%IB

100

RNPol

5,00

5,00

ohm

0,50

1000,00

XNPol

40,00

40,00

ohm

0,50

3000,00

IN>Dir

10

10

%IB

100

2ndHarmStab

20

20

100

BlkParTransf

Off

Off

UseStartValue

IN4>

IN4>

62

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

SOTF

Off

Off

ActivationSOTF

Open

Open

StepForSOTF

Step 2

Step 2

HarmResSOTF

Off

Off

tSOTF

0,200

t4U

Unit

Min

Max

0,200

0,000

60,000

1,000

1,000

0,000

60,000

DirMode1

Non-directional

Non-directional

Characterist1

ANSI Def. Time

ANSI Def. Time

IN1>

100

100

%IB

2500

t1

0,000

0,000

0,000

60,000

k1

0,05

0,05

0,05

999,00

IN1Mult

2,0

2,0

1,0

10,0

t1Min

0,000

0,000

0,000

60,000

HarmRestrain1

On

On

DirMode2

Non-directional

Non-directional

Characterist2

ANSI Def. Time

ANSI Def. Time

IN2>

50

50

%IB

2500

t2

0,400

0,400

0,000

60,000

k2

0,05

0,05

0,05

999,00

IN2Mult

2,0

2,0

1,0

10,0

t2Min

0,000

0,000

0,000

60,000

HarmRestrain2

On

On

DirMode3

Non-directional

Non-directional

Characterist3

ANSI Def. Time

ANSI Def. Time

IN3>

33

33

%IB

2500

t3

0,800

0,800

0,000

60,000

k3

0,05

0,05

0,05

999,00

IN3Mult

2,0

2,0

1,0

10,0

t3Min

0,000

0,000

0,000

60,000

HarmRestrain3

On

On

Non-directional

Non-directional

Step 1

Step 2

Step 3

Step 4
DirMode4

63

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Characterist4

ANSI Def. Time

ANSI Def. Time

IN4>

17

t4

Unit

Min

Max

17

%IB

2500

1,200

1,200

0,000

60,000

k4

0,05

0,05

0,05

999,00

IN4Mult

2,0

2,0

1,0

10,0

t4Min

0,000

0,000

0,000

60,000

HarmRestrain4

On

On

ThermalOverload1TimeConst(PTTR,26)
THL1
Operation

Off

Off

IBase

3000

3000

99999

TRef

90

90

Deg

600

IRef

100

100

%IB

400

IMult

Tau

45

45

Min

1000

AlarmTemp

80

80

Deg

200

TripTemp

90

90

Deg

600

ReclTemp

75

75

Deg

600

tPulse

0,10

0,10

0,05

0,30

AmbiSens

Off

Off

DefaultAmbTemp

20

20

Deg

-50

250

DefaultTemp

50

50

Deg

-50

600

Operation

Off

Off

UBase

400,0

400,0

kV

0,1

9999,9

UPE

70

70

%UB

100

tTrip

7,000

7,000

0,000

60,000

kV

0,05

2000,00

Voltage protection
LossOfVoltage(PTUV,27)
LOV1

OverVoltage2Step(PTOV,59)
TOV1
General
Operation

Off

Off

UBase

400,00

400,00

Step 1

64

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

OperationStep1 On

PC Value

Unit

Min

Max

On

Characterist1

Definite time

Definite time

OpMode1

1 out of 3

1 out of 3

U1>

120

120

%UB

200

t1

5,00

5,00

0,00

6000,00

t1Min

5,000

5,000

0,000

60,000

k1

0,05

0,05

0,05

1,10

HystAbs1

0,5

0,5

%UB

0,0

100,0

OperationStep2 On

On

Step 2

Characterist2

Definite time

Definite time

OpMode2

1 out of 3

1 out of 3

U2>

150

150

%UB

200

t2

5,000

5,000

0,000

60,000

t2Min

5,000

5,000

0,000

60,000

k2

0,05

0,05

0,05

1,10

HystAbs2

0,5

0,5

%UB

0,0

100,0

kV

0,05

2000,00

UnderVoltage2Step(PTUV,27)
TUV1
General
Operation

Off

Off

UBase

400,00

400,00

Step 1
OperationStep1 On

On

Characterist1

Definite time

Definite time

OpMode1

1 out of 3

1 out of 3

U1<

70

70

%UB

100

t1

5,00

5,00

0,00

6000,00

t1Min

5,000

5,000

0,000

60,000

k1

0,05

0,05

0,05

1,10

IntBlkSel1

Off

Off

IntBlkStVal1

20

20

%UB

100

tBlkUV1

0,000

0,000

0,000

60,000

HystAbs1

0,5

0,5

%UB

0,0

100,0

Step 2

65

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

OperationStep2 On

PC Value

Unit

Min

Max

On

Characterist2

Definite time

Definite time

OpMode2

1 out of 3

1 out of 3

U2<

50

50

%UB

100

t2

5,000

5,000

0,000

60,000

t2Min

5,000

5,000

0,000

60,000

k2

0,05

0,05

0,05

1,10

IntBlkSel2

Off

Off

IntBlkStVal2

20

20

%UB

100

tBlkUV2

0,000

0,000

0,000

60,000

HystAbs2

0,5

0,5

%UB

0,0

100,0

Scheme communication
ZSchemeCommunication(PSCH,85)
ZCOM
Operation

Off

Off

SchemeType

Permissive UR

Permissive UR

tCoord

0,035

0,035

0,000

60,000

tSendMin

0,100

0,100

0,000

60,000

ZCurrentReversalWEI(PSCH,85)
ZCAL
CurrRev

Off

Off

tPickUpRev

0,020

0,020

0,000

60,000

tDelayRev

0,060

0,060

0,000

60,000

WEI

Off

Off

tPickUpWEI

0,010

0,010

0,000

60,000

UBase

400,00

400,00

kV

0,05

2000,00

UPP<

70

70

%UB

10

90

UPN<

70

70

%UB

10

90

EFCurrentReversalWEI(PSCH,85)
EFCA
CurrRev

Off

Off

tPickUpRev

0,020

0,020

0,000

60,000

tDelayRev

0,060

0,060

0,000

60,000

WEI

Off

Off

tPickUpWEI

0,000

0,000

0,000

60,000

66

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

UBase

400,00

400,00

kV

0,05

2000,00

3U0>

25

25

%UB

70

EFSchemeCommunication(PSCH,85)
EFC1
Operation

Off

Off

SchemeType

Permissive UR

Permissive UR

tCoord

0,035

0,035

0,000

60,000

tSendMin

0,100

0,100

0,000

60,000

Secondary system supervision


FuseFailure(RFUF)
FSD1
Operation

On

On

IBase

3000

3000

99999

UBase

400,00

400,00

kV

0,05

2000,00

OpMode

UZsIZs

UZsIZs

3U0>

30

30

%UB

100

3I0<

10

10

%IB

100

3U2>

30

30

%UB

100

3I2<

10

10

%IB

100

OpDUDI

Off

Off

DU>

60

60

%UB

100

DI<

15

15

%IB

100

UPh>

70

70

%UB

100

IPh>

10

10

%IB

100

SealIn

On

On

USealln<

70

70

%UB

100

IDLD<

%IB

100

UDLD<

60

60

%UB

100

Operation

External ctrl

External ctrl

ARMode

1/2/3ph

1/2/3ph

t1 1Ph

1,000

1,000

0,000

60,000

t1 3Ph

6,000

6,000

0,000

60,000

Control
AutoRecloser(RREC,79)
AR01

67

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

t1 3PhHS

0,400

0,400

0,000

60,000

tReclaim

60,00

60,00

0,00

6000,00

tSync

30,00

30,00

0,00

6000,00

tTrip

0,200

0,200

0,000

60,000

tPulse

0,200

0,200

0,000

60,000

tCBClosedMin

5,00

5,00

0,00

6000,00

tUnsucCl

30,00

30,00

0,00

6000,00

Priority

None

None

tWaitForMaster

60,00

60,00

0,00

6000,00

Operation

Off

Off

SelPhaseBus1

phase2

phase2

SelPhaseBus2

phase2

phase2

SelPhaseLine1

phase2

phase2

SelPhaseLine2

phase2

phase2

CBConfig

No voltage sel.

No voltage sel.

UBase

400,000

400,000

kV

0,001

9999,999

PhaseShift

Deg

-180

180

URatio

1,000

1,000

0,040

25,000

OperationSynch

Off

Off

UHighBusSynch

80,0

80,0

%UB

50,0

120,0

UHighLineSynch

80,0

80,0

%UB

50,0

120,0

UDiffSynch

10,0

10,0

%UB

2,0

50,0

FreqDiffMin

0,010

0,010

Hz

0,003

0,250

FreqDiffMax

0,200

0,200

Hz

0,050

0,250

FreqRateChange

0,300

0,300

Hz/s

0,000

0,500

tBreaker

0,080

0,080

0,000

60,000

tClosePulse

0,200

0,200

0,050

60,000

tMaxSynch

600,00

600,00

0,00

6000,00

tMinSynch

2,000

2,000

0,000

60,000

OperationSC

On

On

UHighBusSC

80,0

80,0

%UB

50,0

120,0

UHighLineSC

80,0

80,0

%UB

50,0

120,0

UDiffSC

15,0

15,0

%UB

2,0

50,0

Synchronizing(RSYN,25)
SYN1

68

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

FreqDiffA

0,010

0,010

Hz

0,003

1,000

FreqDiffM

0,010

0,010

Hz

0,003

1,000

PhaseDiffA

25,0

25,0

Deg

5,0

90,0

PhaseDiffM

25,0

25,0

Deg

5,0

90,0

tSCA

0,100

0,100

0,000

60,000

tSCM

0,100

0,100

0,000

60,000

AutoEnerg

DBLL

DBLL

ManEnerg

Both

Both

ManEnergDBDL

Off

Off

UHighBusEnerg

80,0

80,0

%UB

50,0

120,0

UHighLineEnerg

80,0

80,0

%UB

50,0

120,0

ULowBusEnerg

40,0

40,0

%UB

10,0

80,0

ULowLineEnerg

40,0

40,0

%UB

10,0

80,0

UMaxEnerg

115,0

115,0

%UB

50,0

180,0

tAutoEnerg

0,100

0,100

0,000

60,000

tManEnerg

0,100

0,100

0,000

60,000

R1A

2,000

2,000

ohm/p

0,001

1500,000

X1A

12,000

12,000

ohm/p

0,001

1500,000

R1B

2,000

2,000

ohm/p

0,001

1500,000

X1B

12,000

12,000

ohm/p

0,001

1500,000

R1L

2,000

2,000

ohm/p

0,001

1500,000

X1L

12,500

12,500

ohm/p

0,001

1500,000

R0L

8,750

8,750

ohm/p

0,001

1500,000

X0L

50,000

50,000

ohm/p

0,001

1500,000

R0M

0,000

0,000

ohm/p

0,000

1500,000

X0M

0,000

0,000

ohm/p

0,000

1500,000

LineLength

40,0

40,0

0,0

10000,0

Operation

On

On

Program

1ph/3ph

1ph/3ph

Monitoring
FaultLocator(RFLO)
FLO1

Logic
TripLogic(PTRC,94)
TRP1

69

20/04/2015

Bhikki2/Substation/Voltage Level/Bay/REL 670 IEC


Parameter Name

IED Value

PC Value

Unit

Min

Max

0,150

0,150

0,000

60,000

Operation

On

On

PulseTime

0,150

0,150

0,050

60,000

OnDelay

0,000

0,000

0,000

60,000

OffDelay

0,000

0,000

0,000

60,000

ModeOutput1

Steady

Steady

ModeOutput2

Steady

Steady

ModeOutput3

Steady

Steady

Operation

On

On

PulseTime

0,150

0,150

0,050

60,000

OnDelay

0,000

0,000

0,000

60,000

OffDelay

0,000

0,000

0,000

60,000

ModeOutput1

Steady

Steady

ModeOutput2

Steady

Steady

ModeOutput3

Steady

Steady

Off

Off

Off

Off

Off

Off

Off

Off

tTripMin
TripMatrix(GGIO)
TR01

TR07

LogicGate
GT01
Operation
GT13
Operation
GT16
Operation
GT21
Operation

70