Вы находитесь на странице: 1из 1

Amps X 10 Bus1 (Nom. kV=20, Plot Ref.

kV=20)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

I>

500/5

Cable1
Ampacity

500

500

R1-EDLN
CB 1

300

300

Cable1

F0
Chance
Fuse Link (K)
Fast 0 kV
80A

100

50

100

F0
R2 - CARAL

50

I>

100/5
30

30

50/1

10

Cable1 - P
1 - 3/C 50 mm
Copper XLPE
Tc = 90C
Plotted - 1 x 3/C 50 mm

5
3

5
3

R2 - CARAL - P
Merlin Gerin
Sepam 1000
CT Ratio 100:5
Extremely Inverse
Pickup = 0.75 (0.3 - 2.4 xCT Sec)
Time Dial = 0.4
3x = 4.95 s, 5x = 1.65 s, 8x = 0.629 s
Inst = 4.1 (1 - 24 xCT Sec)
Time Delay = 0.05 s

.5
.3

.5

R1-EDLN - 3P
1.772kA @ 20kV
(Asym)

.3

R1-EDLN - P
ABB
RACIC
CT Ratio 500:5
Definite Time
Pickup = 5.12 (2.8 - 12 Sec - 5A)
Time Dial = 0.15
3x = 0.15 s, 5x = 0.15 s, 8x = 0.15 s

.1

.05
.03

.1
F0 - 3P
1.766kA @ 20kV
(Asym)

.05
.03

R2 - CARAL - 3P
1.766kA @ 20kV
(Asym)

.01
.5

10

30

50

100

300

500

1K

Amps X 10 Bus1 (Nom. kV=20, Plot Ref. kV=20)


BARENTS
Project:
Location:
Contract:
Engineer:
Filename: C:\ETAP 1100\CARAL\CARAL.OTI

PROTECCION DE FASE

3K

5K

ETAP Star 11.0.0C

PESQUERA CARAL
Date:
SN:
Rev:
Fault:

19-08-2013
ENERGIAING
Base
Phase

.01
10K

Seconds

Seconds

10

Вам также может понравиться