INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42

VOLTAGE DROP CALCULATION


REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.


1

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

MLTP1A
1.1

CHILLER-1

MLTP1A

1001.000

3 PHASE

3000A B.B

55

415.00

1740.80

0.00

2.24

2.24

0.54%

1.2

COOLING TOWER-1

MLTP1A

37.500

3 PHASE

50

115

415.00

65.21

0.87

0.00

6.52

6.52

1.57%

1.3

SECONDERY CHW PUMP-1

MLTP1A

94.000

3 PHASE

185

66

415.00

163.47

0.26

0.00

2.81

2.81

0.68%

1.4

PRIMARY CHW PUMP-1

MLTP1A

40.000

3 PHASE

50

60

415.00

69.56

0.87

0.00

3.63

3.63

0.87%

1.5

CONDENSING-1

MLTP1A

90.000

3 PHASE

150

68

415.00

156.52

0.3

0.00

3.19

3.19

0.77%

1.6

BOILER-1

MLTP1A

150.000

3 PHASE

240

90

415.00

260.86

0.21

0.00

4.93

4.93

1.19%

MLTP1B
2.1

TVSS

MLTP1B

2.200

3 PHASE

415.00

3.83

6.8

0.00

0.16

0.16

0.04%

2.2

CHILLER-2

MLTP1B

1001.000

3 PHASE

3000A B.B

60

415.00

1740.80

0.00

2.44

2.44

0.59%

2.3

COOLING TOWER-2

MLTP1B

37.500

3 PHASE

50

116

415.00

65.21

0.87

0.00

6.58

6.58

1.59%

2.4

SECONDERY CHW PUMP-2

MLTP1B

94.000

3 PHASE

185

68

415.00

163.47

0.26

0.00

2.89

2.89

0.70%

2.5

PRIMARY CHW PUMP-2

MLTP1B

40.000

3 PHASE

50

61

415.00

69.56

0.87

0.00

3.69

3.69

0.89%

2.6

CONDENSING-2

MLTP1B

90.000

3 PHASE

150

69

415.00

156.52

0.3

0.00

3.24

3.24

0.78%

2.7

BOILER-2

MLTP1B

150.000

3 PHASE

240

92

415.00

260.86

0.21

0.00

5.04

5.04

1.21%

MLTP 2A
3.1

CHILLER-3

MLTP 2A

1001.000

3 PHASE

3000A B.B

65

415.00

1740.80

0.00

2.65

2.65

0.64%

3.2

COOLING TOWER-3

MLTP 2A

37.500

3 PHASE

50

117

415.00

65.21

0.87

0.00

6.64

6.64

1.60%

3.3

SECONDERY CHW PUMP-3

MLTP 2A

94.000

3 PHASE

185

69

415.00

163.47

0.26

0.00

2.93

2.93

0.71%

3.4

PRIMARY CHW PUMP-3

MLTP 2A

40.000

3 PHASE

50

57

415.00

69.56

0.87

0.00

3.45

3.45

0.83%

3.5

CONDENSING-3

MLTP 2A

90.000

3 PHASE

150

69

411.55

157.83

0.3

0.00

3.27

3.27

0.79%

3.6

BOILER-3

MLTP 2A

150.000

3 PHASE

240

93

411.55

263.05

0.21

0.00

5.14

5.14

1.24%

MLTP 2B
4.1

CHILLER-4 (STAND BY)

MLTP 2B

1001.000

3 PHASE

3000A B.B

70

415.00

1740.80

0.00

2.85

2.85

0.69%

4.2

COOLING TOWER-4 (STAND BY)

MLTP 2B

37.500

3 PHASE

50

118

415.00

65.21

0.87

0.00

6.69

6.69

1.61%

4.3

SECONDERY CHW PUMP-4 (STAND BY)

MLTP 2B

94.000

3 PHASE

185

70

415.00

163.47

0.26

0.00

2.98

2.98

0.72%

4.4

PRIMARY CHW PUMP-4 (STAND BY)

MLTP 2B

40.000

3 PHASE

50

58

415.00

69.56

0.87

0.00

3.51

3.51

0.85%

Infousectious diseases Hospital

1 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

4.5

CONDENSING-4 (STAND BY)

MLTP 2B

90.000

3 PHASE

150

70

415.00

156.52

0.3

0.00

3.29

3.29

0.79%

4.6

BOILER-4 (STAND BY)

MLTP 2B

150.000

3 PHASE

240

95

415.00

260.86

0.21

0.00

5.20

5.20

1.25%

4.7

FIRE PUMP 1

MLTP 2B

120.000

3 PHASE

240

70

415.00

208.69

0.21

0.00

3.07

3.07

0.74%

4.8

FIRE PUMP 2

MLTP 2B

120.000

3 PHASE

240

72

415.00

208.69

0.21

0.00

3.16

3.16

0.76%

4.9

JOCKEY PUMP

MLTP 2B

7.500

3 PHASE

16

70

415.00

13.04

2.5

0.00

2.28

2.28

0.55%

4.1

SAND FILTER

MLTP 2B

4.500

3 PHASE

16

45

415.00

7.83

2.5

0.00

0.88

0.88

0.21%

4.11

BOOSTER PUMP

MLTP 2B

45.000

3 PHASE

70

65

415.00

78.26

0.6

0.00

3.05

3.05

0.74%

4.12

HEAT EXCHANGER-1

MLTP 2B

122.000

3 PHASE

240

65

415.00

212.17

0.21

0.00

2.90

2.90

0.70%

B.B-1

MLTP 5A

866.000

3 PHASE

2500A B.B

115

415.00

1506.02

0.00

4.47

4.47

1.08%

5.1.1

MSB-BF-1(LIGHT & POWER)

B.B-1

78.000

3 PHASE

120

410.53

137.12

0.37

4.47

0.36

4.83

1.16%

5.1.2

MSB-BF-2(LIGHT & POWER)

B.B-1

26.000

3 PHASE

35

75

410.53

45.71

1.15

4.47

3.94

8.41

2.03%

5.1.3

MSB-GF-1(LIGHT & POWER)

B.B-1

72.000

3 PHASE

120

410.53

126.58

0.37

4.47

0.33

4.80

1.16%

5.1.4

MSB-GF-2(LIGHT & POWER)

B.B-1

54.000

3 PHASE

120

100

410.53

94.93

0.37

4.47

3.51

7.98

1.92%

5.1.5

MSB-GF-4

B.B-1

234.000

3 PHASE

3 X 150

100

410.53

411.37

0.1

4.47

4.11

8.58

2.07%

5.1.6

MSB-1F-1(LIGHT & POWER)

B.B-1

60.000

3 PHASE

70

410.53

105.48

0.6

4.47

0.44

4.91

1.18%

5.1.7

MSB-1F-2(LIGHT & POWER)

B.B-1

45.000

3 PHASE

95

100

410.53

79.11

0.45

4.47

3.56

8.03

1.93%

5.1.8

MSB-1F-4

B.B-1

120.000

3 PHASE

240

100

410.53

210.96

0.21

4.47

4.43

8.90

2.14%

5.1.9

MSB-2F-1(LIGHT & POWER)

B.B-1

45.000

3 PHASE

50

410.53

79.11

0.87

4.47

0.48

4.95

1.19%

5.1.10

MSB-3F-1(LIGHT & POWER)

B.B-1

38.000

3 PHASE

50

410.53

66.80

0.87

4.47

0.41

4.88

1.18%

5.1.11

MSB-4F-1(LIGHT & POWER)

B.B-1

38.000

3 PHASE

50

410.53

66.80

0.87

4.47

0.41

4.88

1.18%

5.1.12

MSB-5F-1(LIGHT & POWER)

B.B-1

38.000

3 PHASE

25

410.53

66.80

0.87

2.28

0.41

2.69

0.65%

5.1.13

MSB-RF-1(LIGHT & POWER)

B.B-1

18.000

3 PHASE

16

410.53

31.64

2.5

2.28

0.55

2.84

0.68%

MLTP 3A
5.1

MLTP 3B
6.1

B.B-2

MLTP 5B

455.740

3 PHASE

1350A B.B

110

415.00

792.56

0.00

4.63

4.63

1.12%

6.2

B.B-10

MLTP 5B

535.000

3 PHASE

1600A B.B

55

415.00

930.40

0.00

2.20

2.20

0.53%

MCC-BF-1 (FOR A/C's)

B.B-2

27.260

3 PHASE

35

410.37

47.94

1.15

4.63

0.39

5.02

1.21%

6.1.1

Infousectious diseases Hospital

2 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

6.1.2

MCC-BF-2 (FOR A/C's)

B.B-2

27.260

3 PHASE

50

75

410.37

47.94

0.87

4.63

3.13

7.76

1.87%

6.1.3

MCC-GF-1 (FOR A/C's)

B.B-2

18.250

3 PHASE

25

410.37

32.10

1.65

4.63

0.37

5.00

1.20%

6.1.4

MCC-GF-2 (FOR A/C's)

B.B-2

18.250

3 PHASE

35

100

410.37

32.10

1.15

4.63

3.69

8.32

2.01%

6.1.5

MCC-1F-1 (FOR A/C's)

B.B-2

19.460

3 PHASE

25

410.37

34.22

1.65

4.63

0.40

5.03

1.21%

6.1.6

MCC-1F-2 (FOR A/C's)

B.B-2

19.460

3 PHASE

35

100

410.37

34.22

1.15

4.63

3.94

8.57

2.06%

6.1.7

MCC-2F-1 (FOR A/C's)

B.B-2

4.300

3 PHASE

16

410.37

7.56

2.5

4.63

0.13

4.76

1.15%

6.1.8

MCC-3F-1 (FOR A/C's)

B.B-2

4.300

3 PHASE

16

410.37

7.56

2.5

4.63

0.13

4.76

1.15%

6.1.9

MCC-4F-1 (FOR A/C's)

B.B-2

3.700

3 PHASE

16

410.37

6.51

2.5

4.63

0.11

4.74

1.14%

6.1.10

MCC-5F-1 (FOR A/C's)

B.B-2

5.000

3 PHASE

16

410.37

8.79

2.5

4.63

0.15

4.78

1.15%

6.1.11

MCC-RF-1 (FOR A/C's)

B.B-2

308.500

3 PHASE

3 X 240

410.37

542.55

0.07

4.63

0.27

4.90

1.18%

6.2.1

MSB-KIT-1

B.B-10

179.000

3 PHASE

2 X 150

10

412.80

312.95

0.15

2.20

0.47

2.67

0.64%

6.2.2

MSB-KIT-2

B.B-10

179.000

3 PHASE

2 X 150

11

412.80

312.95

0.15

2.20

0.52

2.72

0.65%

6.2.3

MSB-KIT-3

B.B-10

179.000

3 PHASE

2 X 150

12

412.80

312.95

0.15

2.20

0.56

2.76

0.67%

1042.000

3 PHASE

3000A B.B

110

415.00

1812.10

0.00

4.66

4.66

1.12%

MLTP 4A
7.1

B.B-3

MLTP 4A

7.1.1

MSB-BF-3

B.B-3

27.000

3 PHASE

25

410.34

47.49

1.65

4.66

0.55

5.21

1.26%

7.1.2

MSB-BF-4

B.B-3

18.000

3 PHASE

25

75

410.34

31.66

1.65

4.66

3.92

8.58

2.07%

7.1.3

MSB-GF-3

B.B-3

312.000

3 PHASE

4 X 120

410.34

548.75

0.0925

4.66

0.36

5.02

1.21%

7.1.4

MSB-1F-3

B.B-3

80.000

3 PHASE

120

410.34

140.70

0.37

4.66

0.36

5.02

1.21%

7.1.5

MSB-1F-11(LAB)

B.B-3

80.000

3 PHASE

120

410.34

140.70

0.37

4.66

0.36

5.02

1.21%

7.1.6

MSB-2F-2

B.B-3

125.000

3 PHASE

240

410.34

219.85

0.21

4.66

0.32

4.98

1.20%

7.1.7

MSB-3F-2

B.B-3

125.000

3 PHASE

240

410.34

219.85

0.21

4.66

0.32

4.98

1.20%

7.1.8

MSB-4F-2

B.B-3

125.000

3 PHASE

240

28

410.34

219.85

0.21

4.66

1.29

5.95

1.43%

7.1.9

MSB-5F-2

B.B-3

170.000

3 PHASE

2 X 150

31

410.34

299.00

0.15

4.66

1.39

6.05

1.46%

1054.000

3 PHASE

3200A B.B

65

415.00

1832.97

0.00

2.17

2.17

0.52%

58.500

3 PHASE

95

412.83

102.27

0.45

2.17

0.32

2.49

0.60%

MLTP 4B
8.1
8.1.1

Infousectious diseases Hospital

B.B-4

MLTP 4B

MSB-BF-5(LIGHT & POWER)

B.B-4

3 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

8.1.2

MSB-BF-6(LIGHT & POWER)

B.B-4

58.500

3 PHASE

95

80

412.83

102.27

0.45

2.17

3.68

5.85

1.41%

8.1.3

MSB-GF-5(LIGHT & POWER)

B.B-4

36.000

3 PHASE

50

412.83

62.94

0.87

2.17

0.38

2.55

0.62%

8.1.4

MSB-GF-6(LIGHT & POWER)

B.B-4

36.000

3 PHASE

50

100

412.83

62.94

0.87

2.17

5.48

7.65

1.84%

8.1.5

MSB-GF-8

B.B-4

156.000

3 PHASE

2 X 120

412.83

272.72

0.185

2.17

0.35

2.52

0.61%

8.1.6

MSB-1F-5(LIGHT & POWER)

B.B-4

30.000

3 PHASE

50

412.83

52.45

0.87

2.17

0.32

2.49

0.60%

8.1.7

MSB-1F-6(LIGHT & POWER)

B.B-4

30.000

3 PHASE

50

100

412.83

52.45

0.87

2.17

4.56

6.73

1.62%

8.1.8

MSB-2F-3(LIGHT & POWER)

B.B-4

45.000

3 PHASE

50

412.83

78.67

0.87

2.17

0.48

2.65

0.64%

8.1.9

MSB-3F-3(LIGHT & POWER)

B.B-4

38.000

3 PHASE

50

412.83

66.43

0.87

2.17

0.40

2.57

0.62%

8.1.10

MSB-4F-3(LIGHT & POWER)

B.B-4

38.000

3 PHASE

50

412.83

66.43

0.87

2.17

0.40

2.57

0.62%

8.1.11

MSB-4F-6 (ICU)

B.B-4

100.000

3 PHASE

185

412.83

174.82

0.26

2.17

0.32

2.49

0.60%

8.1.12

MSB-4F-7 (ICU)

B.B-4

100.000

3 PHASE

185

412.83

174.82

0.26

2.17

0.32

2.49

0.60%

8.1.13

MSB-5F-3(LIGHT & POWER)

B.B-4

38.000

3 PHASE

50

412.83

66.43

0.87

2.17

0.40

2.57

0.62%

8.1.14

MSB-5F-6 (ICU)

B.B-4

136.000

3 PHASE

300

412.83

237.76

0.19

2.17

0.32

2.49

0.60%

8.1.15

MSB-5F-7 (ICU)

B.B-4

136.000

3 PHASE

300

412.83

237.76

0.19

2.17

0.32

2.49

0.60%

8.1.16

MSB-RF-2(LIGHT & POWER)

B.B-4

18.000

3 PHASE

25

412.83

31.47

1.65

2.17

0.36

2.53

0.61%

555.800

3 PHASE

2000A B.B

65

415.00

966.57

0.00

2.26

2.26

0.54%

MLTP 5A
9.1

B.B-5

MLTP 5A

9.1.1

MCC-BF-3(FOR A/C's)

B.B-5

27.260

3 PHASE

35

412.74

47.67

1.15

2.26

0.38

2.64

0.64%

9.1.2

MCC-BF-4(FOR A/C's)

B.B-5

27.260

3 PHASE

35

80

412.74

47.67

1.15

2.26

4.39

6.65

1.60%

9.1.3

MCC-GF-3(FOR A/C's)

B.B-5

18.280

3 PHASE

25

412.74

31.96

1.65

2.26

0.37

2.63

0.63%

9.1.4

MCC-GF-4(FOR A/C's)

B.B-5

18.280

3 PHASE

25

100

412.74

31.96

1.65

2.26

5.27

7.53

1.82%

9.1.5

MCC-1F-3(FOR A/C's)

B.B-5

19.460

3 PHASE

25

412.74

34.03

1.65

2.26

0.39

2.65

0.64%

9.1.6

MCC-1F-4(FOR A/C's)

B.B-5

19.460

3 PHASE

25

100

412.74

34.03

1.65

2.26

5.61

7.87

1.90%

9.1.7

MCC-2F-2(FOR A/C's)

B.B-5

4.300

3 PHASE

16

412.74

7.52

2.5

2.26

0.13

2.39

0.58%

9.1.8

MCC-3F-2(FOR A/C's)

B.B-5

4.300

3 PHASE

16

412.74

7.52

2.5

2.26

0.13

2.39

0.58%

9.1.9

MSB-3F-5 (ICU)

B.B-5

100.000

3 PHASE

185

412.74

174.86

0.26

2.26

0.32

2.58

0.62%

9.1.10

MCC-4F-2(FOR A/C's)

B.B-5

3.700

3 PHASE

16

412.74

6.47

2.5

2.26

0.11

2.37

0.57%

Infousectious diseases Hospital

4 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

9.1.11

MCC-5F-2(FOR A/C's)

B.B-5

5.000

3 PHASE

16

412.74

8.74

2.5

2.26

0.15

2.41

0.58%

9.1.12

MCC-RF-2(FOR A/C's)

B.B-5

308.500

3 PHASE

3 X 240

412.74

539.44

0.07

2.26

0.26

2.52

0.61%

1088.000

3 PHASE

3200A B.B

60

415.00

1892.09

0.00

2.09

2.09

0.50%

10

MLTP 5B
10.1

B.B-6

MLTP 5B

10.1.1

MSB-BF-7

B.B-6

18.000

3 PHASE

25

412.91

31.46

1.65

2.09

0.36

2.45

0.59%

10.1.2

MSB-BF-8

B.B-6

18.000

3 PHASE

25

412.91

31.46

1.65

2.09

0.36

2.45

0.59%

10.1.3

MSB-GF-7

B.B-6

156.000

3 PHASE

2 X 120

412.91

272.67

0.185

2.09

0.35

2.44

0.59%

10.1.4

MSB-1F-7

B.B-6

80.000

3 PHASE

120

412.91

139.83

0.37

2.09

0.36

2.45

0.59%

10.1.5

MSB-1F-8

B.B-6

80.000

3 PHASE

120

412.91

139.83

0.37

2.09

0.36

2.45

0.59%

10.1.6

MSB-2F-5 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.7

MSB-2F-6 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.8

MSB-2F-7 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.9

MSB-3F-6 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.10

MSB-3F-7 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.11

MSB-4F-5 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.12

MSB-5F-5 (ICU)

B.B-6

136.000

3 PHASE

300

412.91

237.71

0.19

2.09

0.32

2.41

0.58%

11

MLTB 6A
11.1

B.B-7

MLTB 6A

390.800

3 PHASE

1250A B.B

120

415.00

679.62

0.00

4.74

4.74

1.14%

11.2

B.B-8

MLTB 6A

607.500

3 PHASE

2000A B.B

120

415.00

1056.48

0.00

4.56

4.56

1.10%

11.2.1

MSB-BF-9(LIGHT & POWER)

B.B-8

58.500

3 PHASE

95

410.44

102.87

0.45

4.56

0.32

4.88

1.18%

11.2.2

MSB-GF-9(LIGHT & POWER)

B.B-8

72.000

3 PHASE

120

410.44

126.60

0.37

4.56

0.33

4.89

1.18%

11.2.3

MSB-LAUNDRY

B.B-8

240.000

3 PHASE

2 X 240

20

410.44

422.01

0.105

4.56

0.89

5.45

1.31%

11.2.4

MSB-1F-9(LIGHT & POWER)

B.B-8

60.000

3 PHASE

95

410.44

105.50

0.45

4.56

0.33

4.89

1.18%

11.2.5

MSB-2F-5(LIGHT & POWER)

B.B-8

45.000

3 PHASE

70

410.44

79.13

0.6

4.56

0.33

4.89

1.18%

11.2.6

MSB-3F-5(LIGHT & POWER)

B.B-8

38.000

3 PHASE

50

410.44

66.82

0.87

4.56

0.41

4.97

1.20%

11.2.7

MSB-4F-5(LIGHT & POWER)

B.B-8

38.000

3 PHASE

50

410.44

66.82

0.87

4.56

0.41

4.97

1.20%

11.2.8

MSB-5F-5(LIGHT & POWER)

B.B-8

38.000

3 PHASE

50

410.44

66.82

0.87

4.56

0.41

4.97

1.20%

Infousectious diseases Hospital

5 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

11.2.9

MSB-RF-5(LIGHT & POWER)

B.B-8

18.000

3 PHASE

25

410.44

31.65

1.65

4.56

0.37

4.93

1.19%

11.1.1

MCC-BF-5(FOR A/C's)

B.B-7

27.260

3 PHASE

35

410.26

47.95

1.15

4.74

0.39

5.13

1.24%

11.1.2

MCC-GF-5(FOR A/C's)

B.B-7

18.280

3 PHASE

35

100

410.26

32.16

1.15

4.74

3.70

8.44

2.03%

11.1.3

MCC-1F-5(FOR A/C's)

B.B-7

19.460

3 PHASE

25

410.26

34.23

1.65

4.74

0.40

5.14

1.24%

11.1.4

MCC-2F-3(FOR A/C's)

B.B-7

4.300

3 PHASE

16

410.26

7.56

2.5

4.74

0.13

4.87

1.17%

11.1.5

MCC-3F-3(FOR A/C's)

B.B-7

4.300

3 PHASE

16

410.26

7.56

2.5

4.74

0.13

4.87

1.17%

11.1.6

MCC-4F-3(FOR A/C's)

B.B-7

3.700

3 PHASE

16

410.26

6.51

2.5

4.74

0.11

4.85

1.17%

11.1.7

MCC-5F-3(FOR A/C's)

B.B-7

5.000

3 PHASE

16

410.26

8.80

2.5

4.74

0.15

4.89

1.18%

11.1.8

MCC-RF-2(FOR A/C's)

B.B-7

308.500

3 PHASE

3 X 240

410.26

542.70

0.07

4.74

0.27

5.01

1.21%

1035.000

3 PHASE

3200A B.B

115

415.00

1799.92

0.00

3.81

3.81

0.92%

12

MLTP 6B
12.1

B.B-9

MLTP 6B

12.1.1

MSB-BF-10

B.B-9

18.000

3 PHASE

25

411.19

31.59

1.65

3.81

0.36

4.17

1.01%

12.1.2

MSB-GF-10

B.B-9

312.000

3 PHASE

3 X 185

411.19

547.61

0.0867

3.81

0.33

4.14

1.00%

12.1.3

MSB-1F-10

B.B-9

160.000

3 PHASE

2 X 120

411.19

280.83

0.185

3.81

0.36

4.17

1.01%

12.1.4

MSB-2F-6 (MEDICAL EQUIPMENTS)

B.B-9

125.000

3 PHASE

240

411.19

219.40

0.21

3.81

0.32

4.13

1.00%

12.1.5

MSB-3F-6

B.B-9

125.000

3 PHASE

240

411.19

219.40

0.21

3.81

0.32

4.13

1.00%

12.1.6

MSB-4F-6

B.B-9

125.000

3 PHASE

240

411.19

219.40

0.21

3.81

0.32

4.13

1.00%

12.1.7

MSB-5F-6

B.B-9

170.000

3 PHASE

2 X 120

411.19

298.38

0.185

3.81

0.39

4.20

1.01%

Infousectious diseases Hospital

6 OF 6

REM.