NMI-MS

RECTIFIERS SETTINGS
Emerson & Delta system
B.A.Kasun Chamikara

MS-Project

Emerson system
Amararaja battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:54.0V
:55.2V
:44.0 V (If it hub site this can be 45.0V)
:43.2V ( Never change this value below this)
:0.15c10

Settings----Battery settings---Charge

HBL battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:54.0V
:56.0V
:45.0 V (If it hub site this can be 46.0V)
:44.4V ( Never change this value below this)
:0.15c10

Settings----Battery settings---Charge

Shoto/Huawei battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

Kasun Chamikara

:53.5V
:55.2V
:44.0 V (If it hub site this can be 45.0V)
:43.2V ( Never change this value below this)
:0.10c10

Settings----Battery settings---Charge

Page 2

NED battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:54.0V
:56.0V
:44.8 V (If it hub site this can be 45.8V)
:44 V ( Never change this value below this)
:0.15c10

Settings----Battery settings---Charge

Coslight battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:53.5V
:56.4V
:44.0 V (If it hub site this can be 45.0V)
:43.2V ( Never change this value below this)
:0.10c10

Settings----Battery settings---Charge

Other common settings

Under voltage alarm point


Low voltage alarm point
Test End voltage
Battery capacity
Cyclic boost interval
Cyclic boost duration

Boost limit
Battery fuse

Set system time and Date


Kasun Chamikara

:49V (This value shoud be at least 2V higher


than LLVD point)
:49V
:47V (This value shoud be at least 1V higher
than LLVD point)
:Actual installed capacity
:720hrs
:1500 min
:1500min
:Actual installed number of banks
Set current

(settingsDc settings under voltage alarm)


( settingsDc settings low voltage alarm)
Settingbattery settingsBatt test
(Settings-- battery settings--charge)
(Settings--battery settings--charge--Boost limit)

Settings---Battery settings----Batt. selection


Settings---System

Page 3

Alarm settings

Relay

Alarm

Load fuse Alarm


Batt discharge
Mains failure
Multi rect Alarm
Rect. Not respond
Rect. failure
Rect. Fan fails
Rect. Lost
DC low voltage
DC Under voltage
All other alarms

4
5
3
1
1
1
1
1
2
2
NC

Settings----Alarm settings---Alarm type

How to give manual boost and battery test mode


Battery Mode

:Manual

(Settings----Battery settings---Battery selection----Battery mode)


Start
(Maintenance---Start---Boost).
:Boost
Start
:Test
* Since this has to do under "Manual mode", it is necessary to visit the site to change the system to "Auto" mode

Kasun Chamikara

Page 4

Delta system
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

Amararaja battery
:54.0V
set parameter- Charge para set--Set FL/EQU V--FL set
:55.2V
set parameter- Charge para set--Set FL/EQU V--EQU set
:44.0 V (If it hub site this can be 45.0V)
set parameter--BAT set--LVDs set--LLVDs functions--DISC V
:43.2V ( Never change this value below this)
:0.15c10

HBL battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:54.0V
:56.0V
:45.0 V (If it hub site this can be 46.0V)
:44.4V ( Never change this value below this)
:0.15c10

set parameter- Charge para set--Set FL/EQU V--FL set


set parameter- Charge para set--Set FL/EQU V--EQU set
set parameter--BAT set--LVDs set--LLVDs functions--DISC V

Shoto/Huawei battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

Kasun Chamikara

:53.5V
:55.2V
:44.0 V (If it hub site this can be 45.0V)
:43.2V ( Never change this value below this)
:0.10c10

set parameter- Charge para set--Set FL/EQU V--FL set


set parameter- Charge para set--Set FL/EQU V--EQU set
set parameter--BAT set--LVDs set--LLVDs functions--DISC V

Page 5

NED battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:54.0V
:56.0V
:44.8 V (If it hub site this can be 45.8V)
:44 V ( Never change this value below this)
:0.15c10

set parameter- Charge para set--Set FL/EQU V--FL set


set parameter- Charge para set--Set FL/EQU V--EQU set
set parameter--BAT set--LVDs set--LLVDs functions--DISC V

Coslight battery
Floating Charge
Equalizing (Boost) charge
LLVD voltage
BLVD voltage
Charge current limit

:53.5V
:56.4V
:44.0 V (If it hub site this can be 45.0V)
:43.2V ( Never change this value below this)
:0.10c10

set parameter- Charge para set--Set FL/EQU V--FL set


set parameter- Charge para set--Set FL/EQU V--EQU set
set parameter--BAT set--LVDs set--LLVDs functions--DISC V

Other common settings

LV alarm
No of BAT
Battery capacity

Current limit
EQU period

49V (This value shoud be at least 2V higher


than LLVD point)
:Actual installed quantity
:Actual installed capacity
:0.10c10
:1 month

(Set parameters--Alarm parameters)


(Set parameters-- BAT set)
(Set parameters--Charge para set--CL value)
(Set Parameters-- Charge para set--Start equ-- Equ period
2 set parameter-- SMR set--No. of SMR

Rectiers quantity
Battery install date

actual installed date

set parameter--BAT set--BAT install date

Set system time and Date

Set current

set parameter--other--system time

Kasun Chamikara

Page 6

Alarm settings

Alarm
LLVD disc
BLVD disc
Discharge
DCV low
All other alarms

Required relay

Set parameters- Relay para set- Alarm relay set

None
None
7
Relay 4
Default (No need to change)

Get current time and Date


EQU enable

How to give manual boost charge


HH.MM.SS and YY.MM.DD
(Set parameters--Others--System time)
ON )
(Set parameters--Charge para set--Start equ para

Next EQU time

HH:MM:SS yy-mm-dd (Set this value as


Current time + 5 mins)

Get current time and Date


Max test time
BAT test Enable
Bat test mode
Next BDT time
BAT test Enable

Kasun Chamikara

(Set parameters--Charge para set-- Start equ para)

How to do battery test


HH.MM.SS and YY.MM.DD
250 min
On
Auto
HH:MM:SS and YY:MM:DD (Set this value as current
time + 5 min)
Off (Before leaving the site this shoud set as "Off")

(Set parameters--Others--System time)


(Set parameters--Bat set--Bat test set)
(Set parameters--Bat set-- Bat test enable)
(Set parameters--Bat set--Bat test enable)
(Set parameters- Bat set--Bat test enable)