Вы находитесь на странице: 1из 1

2

Technical data

2.1

Panel type ZX2


Electrical data
Rated voltage

kV

12

17.5

24

36

50 1)

70 1)

Rated power frequency withstand voltage kV

28 1)

38 1)

Rated lightning impulse withstand voltage kV

75

95

125

170

All voltages quoted apply to an insulating


gas pressure, absolute, at 20 C, of
bar 2)

1.0

1.0

1.0

1.0

Rated frequency
Rated current of busbars
Rated current of tee-offs

3)

Hz

50/60

1250/2500

...2000/25004)

Rated peak withstand current 3)

kA

...100

...100

...100

...100

Rated short time current, 3 s 3)

kA

...40

...40

...40

...40

Rated short-circuit breaking current of


the circuit-breaker

kA

...40

...40

...40

...40

Rated short-circuit making current of


the circuit-breaker

kA

...100

...100

...100

...100
5)

Rated operating sequence

O-0.3 sCO-3 minCO

Break time:
manual tripping
protection tripping

ms
ms

4590
4055

4590
4055

4590
4055

4590
4055

Closing time:
manual tripping
protection tripping

ms
ms

6595
60

6595
60

6595
60

6595
60

Insulating gas system2)6)


N2 7)

Insulating gas

SF6 8)

SF6 8)

SF6 8)

Design pressure, absolute

bar

1.36

1.36

1.36

1.36

Operating pressure, absolute, 20 C


(equals filling pressure)

bar

1.3

1.3

1.3

1.3

Rated pressure, absolute, 20 C


(minimum operating pressure)

bar

1.2

1.2

1.2

1.2

Charging motor

<200

<200

<200

<200

Closing coil

250

250

250

250

Opening coil

250

250

250

250

Motor and release data

Rated supply voltage


DC voltage

60, 110, 2209)

Degree of protection (IEC 60529, DIN VDE 0470-1)

1)
2)
3)
4)
5)
6)

Gas-tight enclosure

IP 65

IP 65

IP 65

IP 65

Control cabinet

IP 4X 10)

IP 4X 10)

IP 4X 10)

IP 4X 10)

Higher values in accordance with international standards on request


1 bar = 100 kPa
For details refer to table: "Panel width-classification" section 2.4
Cooling included
Other operating sequences on request
For further details see BA 427 - insulating gas system for ZX switchgear

7)
8)
9)
10)

Insulating gas: nitrogen


Insulating gas: sulphur hexafluoride
Other voltages on request
IP 5X on request