BUSBAR
PROTECTION
APPLICATION

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 1

BASICS 1

ABB

Topic Objectives
Objectives
r Measurement
- Differential Current Measurement
- Stabilized Differential Current Measurement
- Fault Conditions
r Differential Current Supervision

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 2

r Intertripping

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 3

Measuring Principle

Who knows
Mr. Kirchhoff ?

ABB

Measuring Principle
Kirchhoffs 1st Law: Node Rule

The summe of all

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 4

currents must be zero

I1 + I2 + I3 = I = 0

ABB

Measuring Principle
Kirchhoffs 1st Law: Node Rule

If

I1 + I2 + I3 = I

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 5

0
Fault on the busbar
Trip circuit breaker

ABB

Measuring Principle
Differential current measurement

I = I1 + I2 + I3
If

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 6

I > differential current setting


Trip Busbar Protection

ABB

Measuring Principle
Stabilised differential current measurement
Trip Busbar
I > Ikmin ; and
Differential current Idiff= | I |

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 7

If

( I / I ) > k

Protection
k= 1
k= 0,85

t
ul
a
lf
a
n
er
t
in

Low impedance
measuring
principle !!!

no fault

Ikmin
0

Restraint current IRest = | I |

ABB

Measuring Principle
Stabilised differential current measurement
Advantage:
load depending tripping value
as more (load / fault) current is flowing on the
busbar
as more differential current is required to generate
a tripping signal
BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 8

system is very stable in case of


CT failure
CT saturation

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 9

Measuring Principle
load depending tripping value

ABB

Measuring Principle

load depending tripping value

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 10

Busbar fault condition single injection

I1 =
1000A

ABB

Measuring Principle

load depending tripping value

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 11

What would be the


differential and
restrained current in that
situation
???
ABB

Measuring Principle

load depending tripping value

Stabilised differential current measurement

= + I1
=+1
= 1 kA

= + + I1

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 12

= + 1 kA
= 1 kA

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 13

Differential current Idiff= | I |

Measuring Principle

load depending tripping value


k= 1
k= 0,85
lt
u
l fa
a
n
er
t
in

no fault

Ikmin
0

Restraint current IRest = | I |

trip measurement system !!!


( if I > Ikmin)

ABB

Measuring Principle

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 14

Busbar fault condition

load depending tripping value


multiple injection

I1 =
1000A

I2 =
2500A

I3 =
1500A

I4 =
2000A

ABB

Measuring Principle

load depending tripping value

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 15

What would be the


differential and
restrained current in that
situation
???
ABB

Measuring Principle

load depending tripping value

Stabilised differential current measurement

= + I1 + I2 + I3 + I4
= + 1 kA + 2.5 kA + 1.5 kA + 2 kA
= 7 kA

= + + I1+ + I2 + + I3 + + I4

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 16

= + 1 kA + 2.5 kA + 1.5 kA + 2 kA
= 7 kA

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 17

Differential current Idiff= | I |

Measuring Principle

load depending tripping value


k= 1
k= 0,85
lt
u
l fa
a
n
er
t
in

no fault

Ikmin
0

Restraint current IRest = | I |

trip measurement system !!!

ABB

Measuring Principle

External fault condition


e.g. line fault

I1 =

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 18

6000A

I2 =

I3 =

2500A

1500A

I4 =
2000A

ABB

Measuring Principle

External fault condition

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 19

What would be the


differential and
restrained current in that
situation
???
ABB

Measuring Principle

External fault condition

Stabilised differential current measurement

= + I1 + I2 + I3 + I4
= - 6 kA + 2.5 kA + 1.5 kA + 2 kA
= 0 kA

= + + I1+ + I2 + + I3 + + I4

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 20

= + 6 kA + 2.5 kA + 1.5 kA + 2 kA
= 12 kA

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 21

Differential current Idiff= | I |

Measuring Principle

External fault condition


k= 1
k= 0,85
lt
u
l fa
a
n
er
t
in

no fault

Ikmin
0

Restraint current IRest = | I |

measurement system stable !!!

ABB

Measuring Principle

Current transformer failure

during fault condition ()

I1 =

CT shorted !!!

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 22

6000A

I2 =

I3 =

2500A

1500A

I4 =
2000A

ABB

Measuring Principle

Current transformer failure

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 23

What would be the


differential and
restrained current in that
situation
???
ABB

Measuring Principle

Current transformer failure

Stabilised differential current measurement

= + I1 + I2 + I3 + I4
=
=

= + + I1+ + I2 + + I3 + + I4

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 24

=
=

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 25

Differential current Idiff= | I |

Measuring Principle

Current transformer failure


k= 1
k= 0,85
lt
u
l fa
a
n
er
t
in

no fault

Ikmin
0

Restraint current IRest = | I |

ABB

Measuring Principle

Current transformer failure

during fault condition ()

CT shorted !!!
I1 =

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 26

6000A

I2 =

I3 =

2500A

1500A

I4 =
2000A

ABB

Measuring Principle

Current transformer failure

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 27

What would be the


differential and
restrained current in that
situation
???
ABB

Measuring Principle

Current transformer failure

Stabilised differential current measurement

= + I1 + I2 + I3 + I4
=
=

= + + I1+ + I2 + + I3 + + I4

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 28

=
=

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 29

Differential current Idiff= | I |

Measuring Principle

Current transformer failure


k= 1
k= 0,85
lt
u
l fa
a
n
er
t
in

no fault

Ikmin
0

Restraint current IRest = | I |

ABB

Measuring Principle

Current transformer failure

during load condition

CT shorted !!!
I1 =

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 30

600A

I2 =

I3 =

250A

150A

I4 =
200A

ABB

Measuring Principle

Current transformer failure

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 31

What would be the


differential and
restrained current in that
situation
???
ABB

Measuring Principle

Current transformer failure

Stabilised differential current measurement

= + I1 + I2 + I3 + I4
=
=

= + + I1+ + I2 + + I3 + + I4

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 32

=
=

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 33

Differential current Idiff= | I |

Measuring Principle

Current transformer failure


k= 1
k= 0,85
lt
u
l fa
a
n
er
t
in

no fault

Ikmin
0

Restraint current IRest = | I |

ABB

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 34

How is it possible to detect


failures in the CT circuits
???

ABB

Differential Current Supervision


Differential Current Alarm

A differential current for a longer time is


the consequence of a failure in the
system (intern / extern)

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 35

Differential current alarm


Option to block the system

ABB

Differential Current Supervision

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 36

Which failures in the CT circuits


can the Differential current
supervision detect
???

ABB

Differential Current Supervision

The differential current


supervision can detect
a missing CT input (e.g. CT circuit
not connected to the system)
BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 37

a wrong CT ratio
a wrong current direction

ABB

Differential Current Supervision


the differential current supervision is able
to detect a missing / wrong CT input
therefore the differential current alarm is
very important and must not be ignored by the
operating personal

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 38

If not, there is a risk of maloperation !!!

ABB

Intertripping
Tripping flow chart
Measurement

Intertripping

system

system
TRIP CB

TRIP BBP

BBP_basics_1 / 2002-09-28 / RW

ABB Switzerland Ltd. - 39

zone x

trip all CBs


connected
to zone x

just the Intertripping system can send a tripping


signal to the CB because it knows which CB
to trip (the measurement systems are only
responsible for measuring !)

TRIP CB
TRIP CB

ABB