r Technology and
Protection and Substation Automation
Solutions
BUSBAR
PROTECTION
APPLICATION
BBP_basics_1 / 2002-09-28 / RW
BASICS 1
ABB
Topic Objectives
Objectives
r Measurement
- Differential Current Measurement
- Stabilized Differential Current Measurement
- Fault Conditions
r Differential Current Supervision
BBP_basics_1 / 2002-09-28 / RW
r Intertripping
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
Who knows
Mr. Kirchhoff ?
ABB
Measuring Principle
Kirchhoffs 1st Law: Node Rule
BBP_basics_1 / 2002-09-28 / RW
I1 + I2 + I3 = I = 0
ABB
Measuring Principle
Kirchhoffs 1st Law: Node Rule
If
I1 + I2 + I3 = I
BBP_basics_1 / 2002-09-28 / RW
0
Fault on the busbar
Trip circuit breaker
ABB
Measuring Principle
Differential current measurement
I = I1 + I2 + I3
If
BBP_basics_1 / 2002-09-28 / RW
ABB
Measuring Principle
Stabilised differential current measurement
Trip Busbar
I > Ikmin ; and
Differential current Idiff= | I |
BBP_basics_1 / 2002-09-28 / RW
If
( I / I ) > k
Protection
k= 1
k= 0,85
t
ul
a
lf
a
n
er
t
in
Low impedance
measuring
principle !!!
no fault
Ikmin
0
ABB
Measuring Principle
Stabilised differential current measurement
Advantage:
load depending tripping value
as more (load / fault) current is flowing on the
busbar
as more differential current is required to generate
a tripping signal
BBP_basics_1 / 2002-09-28 / RW
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
load depending tripping value
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
I1 =
1000A
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
= + I1
=+1
= 1 kA
= + + I1
BBP_basics_1 / 2002-09-28 / RW
= + 1 kA
= 1 kA
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
no fault
Ikmin
0
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
I1 =
1000A
I2 =
2500A
I3 =
1500A
I4 =
2000A
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
= + I1 + I2 + I3 + I4
= + 1 kA + 2.5 kA + 1.5 kA + 2 kA
= 7 kA
= + + I1+ + I2 + + I3 + + I4
BBP_basics_1 / 2002-09-28 / RW
= + 1 kA + 2.5 kA + 1.5 kA + 2 kA
= 7 kA
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
no fault
Ikmin
0
ABB
Measuring Principle
I1 =
BBP_basics_1 / 2002-09-28 / RW
6000A
I2 =
I3 =
2500A
1500A
I4 =
2000A
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
= + I1 + I2 + I3 + I4
= - 6 kA + 2.5 kA + 1.5 kA + 2 kA
= 0 kA
= + + I1+ + I2 + + I3 + + I4
BBP_basics_1 / 2002-09-28 / RW
= + 6 kA + 2.5 kA + 1.5 kA + 2 kA
= 12 kA
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
no fault
Ikmin
0
ABB
Measuring Principle
I1 =
CT shorted !!!
BBP_basics_1 / 2002-09-28 / RW
6000A
I2 =
I3 =
2500A
1500A
I4 =
2000A
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
= + I1 + I2 + I3 + I4
=
=
= + + I1+ + I2 + + I3 + + I4
BBP_basics_1 / 2002-09-28 / RW
=
=
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
no fault
Ikmin
0
ABB
Measuring Principle
CT shorted !!!
I1 =
BBP_basics_1 / 2002-09-28 / RW
6000A
I2 =
I3 =
2500A
1500A
I4 =
2000A
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
= + I1 + I2 + I3 + I4
=
=
= + + I1+ + I2 + + I3 + + I4
BBP_basics_1 / 2002-09-28 / RW
=
=
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
no fault
Ikmin
0
ABB
Measuring Principle
CT shorted !!!
I1 =
BBP_basics_1 / 2002-09-28 / RW
600A
I2 =
I3 =
250A
150A
I4 =
200A
ABB
Measuring Principle
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
= + I1 + I2 + I3 + I4
=
=
= + + I1+ + I2 + + I3 + + I4
BBP_basics_1 / 2002-09-28 / RW
=
=
ABB
BBP_basics_1 / 2002-09-28 / RW
Measuring Principle
no fault
Ikmin
0
ABB
BBP_basics_1 / 2002-09-28 / RW
ABB
BBP_basics_1 / 2002-09-28 / RW
ABB
BBP_basics_1 / 2002-09-28 / RW
ABB
a wrong CT ratio
a wrong current direction
ABB
BBP_basics_1 / 2002-09-28 / RW
ABB
Intertripping
Tripping flow chart
Measurement
Intertripping
system
system
TRIP CB
TRIP BBP
BBP_basics_1 / 2002-09-28 / RW
zone x
TRIP CB
TRIP CB
ABB
BBP_basics_1 / 2002-09-28 / RW
ABB
ABB