ImportanceofTransformerInrushCurrent

ImportanceofTransformerInrushCurrent(onphoto:DataCenterPowerTransformerbydigitalrealtytrust@Flickr)

ResidualFlux
Whenatransformeristakenoffline,therewillbeacertainamountofresidualfluxthatcanremain
inthecoreduetothepropertiesofthemagneticcorematerial.
Theresidualfluxcanbeasmuchas50to90%ofthemaximumoperatingflux,dependingon
thetypeofcoresteel.Whenvoltageisreappliedtothetransformer,thefluxintroducedbythis
sourcevoltagewillbuilduponthatwhichalreadyexistsinthecore.
Inordertomaintainthisleveloffluxinthecore,whichcanbewellintothesaturationrangeof
thecoresteel,thetransformercandrawcurrentwellinexcessofthetransformersratedfullload
current.
Dependingonthetransformerdesign,themagnitudeofthiscurrentinrushcanbeanywhere
from3.5to40timestheratedfullloadcurrent.Thewaveformoftheinrushcurrentwillbe
similartoasinewave,butlargelyskewedtowardsthepositiveornegativedirection.Thisinrush
currentwillexperienceadecay,partiallyduetotransformerlosses,whichwillprovidea
dampeningeffecthowever,thecurrentcanremainwellaboveratedcurrentformanycycles.

Thisinrushcurrentcanhaveaneffectontheoperationofrelaysandfuseslocated
inthesystemnearthetransformer.

Decentapproximationsoftheinrushcurrentrequiredetailedinformationregardingthetransformer
designwhichmaybeavailablefromthemanufacturerbutisnottypicallyavailabletotheuser.
Actualinrushcurrentswillalsodependuponwhereinthesourcevoltagewavetheswitching
operationsoccur,themomentofopeningeffectingtheresidualfluxmagnitude,andthemomentof
closingeffectingthenewflux.