SRNO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
DISCRIPTION
1000 KVA 11000/415 V ON LOAD DISTRIBUTION TRANSFORMERS
INDOOR TYPE 11 KV VCB PANEL [ ICOG ], INCLUDING SUITABLE SIMENS MAKE VCB,
NUMEICAL 3 O/C + 1E/F RELAY, MASTER TRIP RELAY, TRAFO FAULT RELAY, ANNUNCIATOR
WITH INBUILT PUSH BOTTON
600 KVAR APFC PANEL WITH 800 A ON/OFF SWITCH
DESCRIPTION
Specifications reference
Rating in kva
No load voltage ratio
Primary amps
Secondary amps
No of phase
Frequency
Method of cooling
Vector group
Tapping mode
Taping range
Losses
A, no load loss
B, full load loss(copper loss)
Impedance (%)
Insulation class
Insulation level
A, power frequency test voltage(kVrms)(hv/lv)
B, impulse test voltage (kvp)(hv/Lv)
Material
winding
Terminal of
arrangement
HV LV
Core
Maximum temperature rise over an ambient of 45 c
Pam connector at LV
Buchholz Relay
Aluminum Bus bar for LV side suitable for cable
EXTRA ACCESSORIES
Oil temperature indicator
Winding temperature indicator
Marshaling box
Magnetic oil level gauge
PRICE BASE ON
TAXES
WARANTEE
VALIDITY
DELIVERY
PAYMENT
UNLODING
ERECTION & COMMISSIONING
INSPECTION
QTY.
1 NO.
1 NO.
1 NO.
PARTICULARS
1000
11000/415
52.5
1391
3
50 HZ
ONAN
Dyn11
OLTC (ON LOAD TAP CHANGER ) WITH RTCC + AVR PANEL
NORMAL + 10% IN STEP OF 1.25% ( 17 NOS )
A - 1.55 KW , B - 13 KW (SUBJECT TO IS TOL)
4.75% (SUBJECT TO IS TOL)
A' CLASS
A - 28 / 3 , B - 95
COPPER
HV WINDING- BARE BUSHING , LV WINDING - CABLE BOX , ORIENTATION - 180 C
CRGO , STAKED
OIL - 50 C ,WINDING - 55C
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES