Вы находитесь на странице: 1из 2

Page: 1

Settings File Report


Substation: Unit 4
File: orginal.set
Model Number: KBCH13001P15MEL

Printed on: 11/05/2015 09:40:57

SYSTEM DATA
00.02: SYS Password:
****
00.03: SYS Fn. Links:
0000000010000001
00.04: SYS Description: 3 Bias I/P
00.05: SYS Plant Ref.:
NES_TRA4_KBCH130
00.06: SYS Model No.:
KBCH13001P15MEL
00.08: SYS Serial No.:
208354B
00.09: SYS Frequency:
50 Hz
00.0A: SYS Comms Level: 1
00.0B: SYS Rly Address: 3
00.0C: SYS Plant Status: 0000000000000000
00.0D: SYS Ctrl Status: 0000000000000000
00.0E: SYS Setting Grp: 1
00.11: SYS S/W Ref 1:
18 KBCH100 XXE L
00.12: SYS S/W Ref 2:
18KBCH001H
00.20: SYS Logic Stat:
10000000
00.21: SYS Relay Stat:
00000000
00.22: SYS Alarms:
0000000
LOGIC FUNCTIONS
09.02: LOG tAUX0:
0s
09.03: LOG tAUX1:
0s
09.04: LOG tAUX2:
0s
09.05: LOG tAUX3:
0s
09.06: LOG tAUX4:
0s
09.07: LOG tAUX5:
0s
09.08: LOG tAUX6:
0s
09.09: LOG tAUX7:
0s
09.0A: LOG tTEST:
500.0 ms
09.0B: LOG tTapUp:
500.0 ms
09.0C: LOG tTapDown: 500.0 ms
09.0D: LOG DefaultDsply: HVIaIbIc
INPUT MASKS
0A.07: INP Blk V/f Trp: 00000000
0A.08: INP Blk V/f Alm: 00000000
0A.09: INP Aux 0:
00000001
0A.0A: INP Aux 1:
00000010
0A.0B: INP Aux 2:
00000000
0A.0C: INP Aux 3:
00000000
0A.0D: INP Aux 4:
00000000
0A.0E: INP Aux 5:
00000000
0A.0F: INP Aux 6:
00000000
0A.10: INP Aux 7:
00000000
0A.11: INP Set Grp 2:
00000000
RELAY MASKS
0B.01: RLY Id>A:
01011001
0B.02: RLY Id>B:
01011001
0B.03: RLY Id>C:
01011001
0B.04: RLY Id>>A:
01011001
0B.05: RLY Id>>B:
01011001
0B.06: RLY Id>>C:
01011001
0B.07: RLY Io> HV:
00000000
0B.08: RLY Io> LV1:
00000000
0B.0A: RLY Aux0:
01010110
0B.0B: RLY Aux1:
01010110
0B.0C: RLY Aux2:
00000000
0B.0D: RLY Aux3:
00000000
0B.0E: RLY Aux4:
00000000
0B.0F: RLY Aux5:00000000
0B.10: RLY Aux6:00000000
0B.11: RLY Aux7:00000000
0B.12: RLY Tap Up:
00000000

MiCOM S1 Agile

Page: 2
Settings File Report
Substation: Unit 4
File: orginal.set
Model Number: KBCH13001P15MEL

Printed on: 11/05/2015 09:40:58

0B.13: RLY Tap Down:


00000000
0B.15: RLY OF Alarm:
00000000
0B.16: RLY V/f Trip:
00000000
0B.17: RLY V/f Alarm:
00000000
RECORDER
0C.01: REC Control:
Running
0C.02: REC Capture:
Samples
0C.03: REC Post Trigger: 250 samples
0C.04: REC Logic trig:
0000000000000000
0C.05: REC Relay trig:
0000000001011001
TEST/CONTROL
0D.01: TST Logic Stat:
10000000
0D.02: TST Relay Stat:
00000000
0D.03: Select Relays To Test:
11111111
0D.04: Test Relays =[0]:
0D.05: TST Tap Control: No Operation
Group 1
SETTINGS(1)
05.01: S1 Fn. Links:
0000000000000110
05.02: S1 Configuration: HV+LV1+LV2
05.03: S1 HV CT Ratio: 40.00 :1
05.04: S1 LV1 CT Ratio: 500.0 :1
05.05: S1 LV2 CT Ratio: 160.0 :1
05.06: S1 HV Ratio Cor: 230.0e-3
05.07: S1 HV VectorCor: Yd11 (+30 deg)
05.08: S1 LV1 Ratio Cor: 240.0e-3
05.09: S1 LV1 VectorCor: Ydy0 (0 deg)
05.0A: S1 LV2 Ratio Cor: 80.00e-3
05.0B: S1 LV2 VectorCor: Yd11 (+30 deg)
05.0C: S1 Id>: 300.0e-3 PU
05.0D: S1 Id>>: 8.000 PU