Вы находитесь на странице: 1из 1

TEXAS FIRM REGISTRAGTION NO.

F-12745
4800 SUGAR GROVE, SUITE 315
STAFFORD. TEXAS 77477
T 713.933.1041
F 713.458.7758
www.ensighthayneswhaley.com
EHW-15-501-A

GENERAL STRUCTURAL NOTES

Issue
No.

Date

2
06.00

SHOP DRAWINGS

05.00

CONCRETE MASONRY

04.00

CONCRETE

03.00

STRUCTURAL STEEL

02.00

FOUNDATION AND SLAB ON GRADE

01.00

GENERAL

06.01

SHOP DRAWINGS SHALL BE PREPARED AND SUBMITTED FOR REVIEW TO THE


STRUCTURAL ENGINEER FOR EACH STRUCTURAL BUILDING MATERIAL AS
INDICATED IN THE STRUCTURAL GENERAL NOTES AND/OR THE CONTRACT
SPECIFICATIONS. SEE THE CONTRACT SPECIFICATIONS, IF PROVIDED, FOR
SUBMITTAL PROCEDURES AND ADDITIONAL INFORMATION.

05.01

MASONRY CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH ACI 531


"BUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY CONSTRUCTION".

04.01

03.01

02.01

THE STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL


BUILDING CODE, 2012 EDITION.

STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.

01.02

THE DESIGN GRAVITY LOADS ARE AS FOLLOWS:

03.02

SHOP DRAWINGS SHALL USE DRAFTING LINE WORK AND LETTERING THAT IS
CLEAR AND LEGIBLE. SHOP DRAWINGS SHALL NOT CONTAIN REPRODUCTION OF
THE CONTRACT PLANS OR DETAILS WITHOUT THE CONSENT OF THE ARCHITECT
OR ENGINEER OF RECORD.

05.03

03.03

STRUCTURAL STEEL PIPE SHALL CONFORM TO ASTM A53, TYPE E OR S GRADE B


OR ASTM A501. MILL TEST REPORTS FOR STEEL PIPE SHALL BE SUBMITTED FOR
REVIEW.

THE SUBSURFACE INFORMATION AND FOUNDATION DESIGN ARE BASED ON A


REPORT PREPARED BY GESSNER ENGINEERING, PROJECT NO. 15-0717, DATED
SEPTEMBER 14, 2015 WITH ADDENDUM LETTERS DATED NOVEMBER 6, 2015 AND
NOVEMBER 24, 2015. THE CONTRACTOR SHALL PERFORM EXCAVATIONS,
FOOTING CONSTRUCTION, AND PREPARATION OF THE SUBGRADE UNDER THE SLAB
ON GRADE IN ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN THE
GEOTECHNICAL REPORT AND THE PROJECT SPECIFICATIONS.

01.01

CONCRETE MASONRY CONSTRUCTION SHALL HAVE A MINIMUM COMPRESSIVE


STRENGTH (F'M) OF 1500 PSI ON THE NET CROSS SECTIONAL AREA AT 28 DAYS.

STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992,


GRADE 50 EXCEPT AS NOTED. OTHER STEEL SHAPES, PLATES, ANGLES AND
CHANNELS SHALL CONFORM TO ASTM A36.

05.02

CONCRETE IN THE FOLLOWING AREAS SHALL HAVE NATURAL SAND FINE


AGGREGATE AND NORMAL WEIGHT COARSE AGGREGATES CONFORMING TO ASTM
C33, TYPE I PORTLAND CEMENT CONFORMING TO ASTM C150, AND SHALL HAVE
THE FOLLOWING COMPRESSIVE STRENGTH (FC') AT 28 DAYS:

06.04

SHOP DRAWINGS SHALL SHOW CLEAR AND COMPLETE INFORMATION FOR THE
FABRICATION (DETAIL SHEETS AND/OR MATERIAL LISTS) AND INSTALLATION.

06.05
06.06
06.07

06.08

06.09

06.10

05.04

ALLOW A MINIMUM OF (2) WEEKS FOR REVIEW OF EACH SET OF SHOP


DRAWINGS.
CONTRACTOR SHALL REVIEW THE SHOP DRAWINGS SUBMITTED BY THE
SUBCONTRACTOR AND COORDINATE SHOP DRAWINGS WITH ALL TRADES.
CONTRACTOR SHALL ANSWER ALL QUESTIONS OR CLARIFICATIONS BY THE
SUBCONTRACTOR BEFORE SUBMITTING TO ENGINEER REVIEW. ANY QUESTIONS
THAT THE CONTRACTOR ANSWER WITH THE INFORMATION ON THE DRAWINGS
SHALL CLEARLY BE MARKED FOR THE ENGINEER FOR REVIEW.
CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL DIMENSIONS, AND SHALL
NOTIFY ARCHITECT OF ANY DISCREPENCIES IN COORDINATION WITH THE
ARCHITECTURAL DOCUMENTS OR THOSE OF OTHER DISCIPLINES.

05.05

GROUT SHALL CONFORM TO ASTM C476 AND SHALL HAVE A COMPRESSIVE


STRENGTH OF 2500 PSI ON THE NET AREA AT 28 DAYS.

05.06

REINFORCEMENT SHALL CONFORM TO THE STANDARDS SPECIFIED IN THE


CONCRETE NOTES. REINFORCEMENT SHALL BE LAP SPLICED A MINIMUM OF 36
BAR DIAMETERS UNLESS NOTED OTHERWISE.

05.07

REVIEW OF THE SHOP DRAWINGS BY THE ENGINEER IS FOR GENERAL


CONFORMANCE TO THE STRUCTURAL DRAWINGS. APPROVAL OF THE SHOP
DRAWINGS BY THE ENGINEER DOES NOT RELIEVE THE CONTRCTOR FOR ANY
ERRORS IN DIMENSIONS OR MATERIALS INDICATED IN THE ON THE SHOP
DRAWINGS.
IF THERE IS ANY DISCREPENCY BETWEEN THE STRUCTURAL DRAWINGS AND
THE SHOP DRAWINGS, THE INFORMATION SHOWN ON THE STRUCTURAL
DOCUMENTS SHALL GOVERN. INFORMATION THAT IS NOT INDICATED ON THE
SHOP DRAWINGS SHALL BE OBTAINED FROM THE STRUCTURAL DRAWINGS.

MORTAR SHALL CONFORM TO THE REQUIREMENTS OF ASTM C270, TYPE M OR S.


TYPE M MORTAR SHALL BE USED IN BELOW GRADE APPLICATIONS AND SHALL
OBTAIN AN AVERAGE COMPRESSIVE STRENGTH OF 2500 PSI AT 28 DAYS. TYPE S
MORTAR MAY BE USED IN ABOVE GRADE APPLICATIONS AND SHALL OBTAIN AN
AVERAGE COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS. THE SAME MORTAR
SHALL BE USED FOR BOTH WYTHES OF CAVITY WALL CONSTRUCTION.

PROVIDE 2-#5 CONTINUOUS IN BOND BEAMS UNLESS INDICATED OTHERWISE.


PROVIDE CORNER BARS OF EQUIVALENT SIZE LAPPED AT CORNERS AND
INTERSECTIONS OF WALLS.

05.08

MASONRY CORES CONTAINING VERTICAL REINFORCEMENT SHALL BE GROUTED


SOLID.

05.09

FOR LIFTS GREATER THAN 4 FEET, HIGH LIFT GROUTING TECHNIQUES SHALL BE
UTILIZED.

05.10

PROVIDE 1-#5 VERTICAL AT ENDS, CORNERS, AND INTERSECTIONS OF WALLS.

05.11

CELLS TO BE GROUTED SHALL BE CLEAN AND FREE OF EXCESS MORTAR AND


FOREIGN MATERIALS.

05.12

IN CONCRETE SUPPORTING MASONRY WALLS, EMBED DOWELS TO MATCH SIZE


AND LOCATION OF VERTICAL MASONRY REINFORCEMENT.

05.13

LINTELS SHALL BEAR ON MASONRY WALLS A MINIMUM OF 8" AT EACH END. FOR
CMU WALLS, PROVIDE TWO GROUTED CORES EACH SIDE OF OPENING FULL
HEIGHT OF WALL AND REINFORCE EACH OF THE TWO GROUTED CORES WITH
1-#5 VERTICAL EXTENDING FROM THE FOUNDATION TO THE POINT OF LATERAL
SUPPORT FOR THE WALL ABOVE THE LINTEL LOCATION. THE FOLLOWING
LINTELS MAY BE USED ONLY WHEN THE HEAD OF THE MASONRY OPENING IS
BELOW FLOOR OR ROOF BEARING ELEMENTS A MINIMUM DISTANCE OF 75% OF
THE LINTEL SPAN:
CLEAR
SPAN PER
WYTHE

STEEL ANGLE
LINTEL FOR 4"
CMU WYTHE

CMU LINTEL
PER CMU WYTHE
(FM'= 1500 PSI)

PRECAST CONC.
LINTEL PER CMU
WYTHE
(FC'= 3000 PSI)

0'-0" - 4'-0"

L3-1/2 x 3-1/2 x 1/4

8" DEEP W/ (2) #4


BOTTOM

8" DEEP W/ (2) #4


TOP & BOTTOM

4'-0" - 6'-0"

L5 x 3-1/2 x 5/16

8" DEEP W/ (2) #5


BOTTOM

8" DEEP W/ (2) #4


TOP & BOTTOM

16" DEEP W/ (2) #4


BOTTOM

8" DEEP W/ (2) #4


TOP & BOTTOM

16" DEEP W/ (2) #5


BOTTOM

8" DEEP W/ (2) #5


TOP & BOTTOM

6'-0" - 8'-0"
8'-0" - 12'-0"

L5 x 3-1/2 x 3/8
L6 x 3-1/2 x 1/2

TEMPORARY SHORING OF LINTELS MUST BE PROVIDED UNTIL MASONRY HAS


CURED. EDGES OF MASONRY OPENINGS SHALL NOT BE LOCATED CLOSER THAN
50% OF THE LINTEL SPAN FROM ENDS OR CORNERS OF WALLS OR MASONRY
CONTROL JOINTS.
05.14

CONTROL JOINTS SHALL BE PLACED IN THE MASONRY CONSTRUCTION SUCH THAT


THE PANEL LENGTH TO HEIGHT RATIO OF THE WALL DOES NOT EXCEED 1.5, AND
THAT THE MAXIMUM PANEL LENGTH OF WALL DOES NOT EXCEED 25 FEET.
ADDITIONAL JOINTS SHALL BE PLACED WHERE ABRUPT CHANGES IN WALL
SECTIONS OCCUR.

04.02

04.03

04.04

04.06

MINIMUM CONCRETE COVER PROTECTION FOR REINFORCEMENT BARS SHALL BE


AS FOLLOWS: (SEE ACI 318 SECTION 7.7 FOR CONDITIONS NOT NOTED)
CONCRETE EXPOSED TO WEATHER
#5 BARS AND SMALLER
1-1/2 INCHES
ALL OTHER BARS
2 INCHES
CONCRETE CAST AGAINST EARTH
3 INCHES
GRADE BEAMS:
TOP
1-1/2 INCHES
BOARD FORMED SIDES
2 INCHES
EARTH FORMED SIDES
3 INCHES
BOTTOM
3 INCHES
SLABS ON GRADE
SINGLE LAYER OR TOP LAYER
2 INCHES
BOTTOM LAYER CAST AGAINST SOIL
3 INCHES
BOTTOM LAYER NOT CAST AGAINST SOIL
2 INCHES
COLUMNS
1-1/2 INCHES
PILASTERS & PLINTHS
2 INCHES
BEAMS
1-1/2 INCHES
WALLS BELOW GRADE (BACKFILLED SIDE)
2 INCHES
WALLS BELOW GRADE (NO BACKFILL)
3/4 INCHES
PROVIDE STANDARD BAR CHAIRS AND SPACERS AS REQUIRED TO MAINTAIN
CONCRETE PROTECTION SPECIFIED.

04.07

04.08

04.09

HORIZONTAL JOINT REINFORCEMENT SHALL BE USED IN THE MASONRY


CONSTRUCTION. SUCH JOINT REINFORCEMENT SHALL BE PLACED AT 8 INCHES
ON CENTER VERTICALLY IN WALLS BELOW GRADE AND AT 16 INCHES ON CENTER
VERTICALLY IN WALLS THAT ARE ABOVE GRADE. HORIZONTAL JOINT
REINFORCEMENT SHALL BE FABRICATED FROM GALVANIZED COLD-DRAWN STEEL
WIRE CONFORMING TO ASTM A82. REINFORCEMENT SHALL CONSIST OF TWO OR
MORE SMOOTH OR DEFORMED LONGITUDINAL WIRES NO. 9 GAGE OR LARGER,
WELD CONNECTED WITH NO. 12 GAGE OR LARGER CROSS WIRES. GALVANIZE
COATING SHALL CONFORM TO ASTM A116 AND SHALL BE APPLIED AT A WEIGHT
OF NOT LESS THAN 1.5 OUNCES PER SQUARE FOOT OF UNCOATED WIRE
SURFACE. THE OUT-TO-OUT SPACING OF THE LONGITUDINAL WIRES SHOULD BE
1-5/8 INCHES LESS THAT THE WIDTH OF THE MASONRY UNITS. THE DISTANCE
BETWEEN THE WELDED CONTACTS OF THE CROSS WIRES WITH EACH
LONGITUDINAL WIRE SHOULD NOT EXCEED 6 INCHES AND 16 INCHES FOR
SMOOTH AND DEFORMED LONGITUDINAL WIRES RESPECTIVELY.

04.10

MASONRY CONSTRUCTION SHALL BE INSPECTED DURING THE VARIOUS WORK


STAGES BY A QUALIFIED SPECIAL INSPECTOR. INSPECTION SHALL INCLUDE
CHECKING FOR COMPLIANCE WITH PROJECT DRAWINGS AND SPECIFICATIONS,
INCLUDING, BUT NOT LIMITED TO RECORDING OF THE FOLLOWING:

04.13

B.

PROPORTIONING, MIXING, AND CONSISTENCY OF MORTAR AND GROUT.

C.

LAYING, MORTARING, AND GROUTING OF MASONRY UNITS AND ELEMENTS.

D.

CONDITION, GRADE, SIZE, SPACING AND PLACEMENT OF REINFORCEMENT.

E.

INSPECTION OF GROUT SPACE IMMEDIATELY PRIOR TO CLOSING OF


CLEANOUTS.

F.

SIGNIFICANT OR UNUSUAL CONSTRUCTION LOADS ON MASONRY


STRUCTURAL ELEMENTS.

G.

WHEN AMBIENT TEMPERATURE FALLS BELOW 40 DEGREES F OR RISES


ABOVE 100 DEGREES F, A COMPLETE RECORD OF WEATHER CONDITIONS
AND OF PRECONDITIONING AND PROTECTION GIVEN TO MASONRY
MATERIALS, AND PROTECTION AND CURING OF COMPLETED WORK,
SHALL BE MAINTAINED.

H.

BARS SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS


INDICATED ON THE CONTRACT DOCUMENTS OR REVIEWED BY THE STRUCTURAL
ENGINEER. CONCRETE REINFORCEMENT BARS SHALL CONFORM TO ASTM A615:
#6 BARS AND SMALLER
#7 BARS AND LARGER

05.16

QUALITY AND TESTING OF MASONRY UNITS AND MATERIALS FOR


MORTAR, GROUT, AND MAKING OF PRISMS WHEN REQUIRED.

DETAILING OF CONCRETE REINFORCEMENT BARS AND ACCESSORIES SHALL


CONFORM TO THE RECOMMENDATIONS OF ACI 315 "DETAILS AND DETAILING OF
CONCRETE REINFORCEMENT" AND ACI SP-66 "DETAILING MANUAL". PLACING OF
REINFORCING BARS SHALL CONFORM TO THE RECOMMENDATIONS OF ACI 315R
"MANUAL OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED
CONCRETE STRUCTURES" AND CRSI "MANUAL OF STANDARD PRACTICE".
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO
ACI 301.

NOTE NOT USED.

A.

GROUT FOR BASE PLATES SHALL BE NONSHRINKABLE, NONMETALLIC


CONFORMING TO ASTM C827, AND SHALL HAVE A SPECIFIED COMPRESSIVE
STRENGTH AT 28 DAYS OF 5000 PSI. PREGROUTING OF BASE PLATES WILL NOT
BE PERMITTED.

04.05

05.15

05.17

FLY ASH MAY BE USED AS A POZZOLAN TO REPLACE A PORTION OF THE


PORTLAND CEMENT IN A CONCRETE MIX, SUBJECT TO THE APPROVAL OF THE
GENERAL CONTRACTOR AND THE STRUCTURAL ENGINEER. FLY ASH, WHEN USED,
SHALL CONFORM TO ASTM C618, TYPE C OR F. CONCRETE MIXES USING FLY ASH
SHALL BE PROPORTIONED TO ACCOUNT FOR THE PROPERTIES OF THE SPECIFIC
FLY ASH USED AND TO ACCOUNT FOR THE SPECIFIC PROPERTIES OF THE FLY
ASH CONCRETE THUS RESULTING. THE RATIO OF THE AMOUNT OF THE FLY ASH
TO THE TOTAL AMOUNT OF FLY ASH AND CEMENT IN THE MIX SHALL NOT EXCEED
25 PERCENT.

04.11

04.12

04.14

04.15

04.16

03.04

03.05

03.06

03.07

03.08

CONNECTION BOLTS FOR STRUCTURAL STEEL MEMBERS SHALL BE HIGH


STRENGTH BOLTS WHICH MEET OR EXCEED THE REQUIREMENTS OF ASTM A325,
TYPE N, X, OR SC CLASS A. BOLTS SHALL BE DESIGNED AS BEARING TYPE
BOLTS, EXCEPT AS NOTED. BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH
THE "SNUG TIGHT" CONDITION AS OUTLINED IN THE "RCSC'S SPECIFICATION FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS". BOLTS SHALL HAVE A
HARDENED WASHER PLACED UNDER THE ELEMENT TO BE TIGHTENED.
CONNECTIONS WITH OVERSIZES ROUND HOLES AND CONNECTIONS WITH HOLES
SLOTTED IN THE DIRECTION OF LOAD, AND CONNECTIONS NOTED ON THE
DRAWINGS TO BE "SLIP CRITICAL" (SC CLASS A) BOLTS, AND SHALL BE
DESIGNED AS SUCH. BOLTS FOR SLIP-CRITICAL CONNECTIONS SHALL BE
TIGHTENED BY THE USE OF THE TURN-OF-THE-NUT METHOD OR THE USE OF
LOAD-INDICATING TYPE BOLTS, OR LOAD-INDICATING WASHERS, INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

CONTRACTOR SHALL FABRICATE AND ERECT STEEL IN ACCORDANCE WITH


OSHA'S SAFETY REQUIREMENTS, INCLUDING 29 CFR PART 1926 SAFETY
STANDARDS FOR STEEL ERECTION.
TYPICAL BEAM CONNECTION DETAILS ARE DETAILED ON THE DRAWINGS. FOR
NON-COMPOSITE BEAMS, THE END REACTION OF THE CONNECTED BEAM SHALL
BE DETERMINED FROM AISC "MANUAL OF STEEL CONSTRUCTION - ALLOWABLE
STRESS DESIGN," NINTH EDITION, PART 2 "ALLOWABLE LOADS ON BEAMS",
UNLESS A DESIGN REACTION IS INDICATED ON THE PLANS. IN NO CASE SHALL
THE END REACTION BE TAKEN AS LESS THAN 12.0 KIPS. IF ALTERNATE BEAM
CONNECTION DESIGNS ARE USED AND FOR ALL OTHER CONNECTIONS NOT
DETAILED ON THE DRAWINGS, THE FABRICATOR SHALL HAVE A REGISTERED
PROFESSIONAL ENGINEER PREPARE THE CONNECTION DESIGNS IN
ACCORDANCE WITH AISC "MANUAL OF STEEL CONSTRUCTION - VOLUME II
CONNECTIONS" AND "HOLLOW STRUCTURAL SECTIONS-CONNECTIONS MANUAL."
SUCH DESIGNS SHALL BE SUBMITTED PRIOR TO PREPARATION OF THE SHOP
DRAWINGS AND SHALL BEAR THE SEAL OF THIS RESPONSIBLE PROFESSIONAL
ENGINEER.
PRIOR TO DETAILING CONNECTIONS FOR STRUCTURAL STEEL, THE STEEL
FABRICATOR SHALL SUBMIT FOR APPROVAL REPRESENTATIVE DETAILS AND
CALCULATIONS FOR EACH TYPE OF STRUCTURAL STEEL CONNECTION TO BE
UTILIZED. AFTER APPROVAL, THE CONNECTIONS MAY BE INCORPORATED INTO
THE SHOP DRAWINGS, ALONG WITH A TABLE OF DESIGN CAPACITIES FOR THE
RANGE OF CONNECTIONS TO BE USED.
WELDING SHALL CONFORM TO THE AMERICAN WELDING SOCIETY STANDARD
D1.1. ELECTRODES FOR SHOP AND FIELD WELDS SHALL CONFORM TO AWS
A5.1 OR AWS A5.5, CLASS E70XX, LOW HYDROGEN.

03.10

ALL FILLET WELDS SHALL BE MINIMUM AS REQUIRED BY AISC TABLE J2.4, BUT
NOT LESS THAN 3/16". UNLESS OTHERWISE NOTED WELDS SHALL BE WELDED
ALL AROUND ON ALL ACCESSIBLE SIDES.

03.11

ALL FULL PENETRATION WELDS AT MOMENT CONNECTIONS SHALL BE TESTED


AND CERTIFIED BY AN INDEPENDENT TESTING LAB USING NON-DESTRUCTIVE
TESTING METHOD. CERTIFICATIONS SHALL BE SUBMITTED PRIOR TO COVERING
CONNECTIONS WITH ARCHITECTURAL FINISHES.

03.12

SPLICING OF STRUCTURAL STEEL MEMBERS WHERE NOT DETAILED ON THE


CONTRACT DOCUMENTS IS PROHIBITED WITHOUT THE PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER AS TO LOCATION, TYPE OF SPLICE AND CONNECTION TO
BE MADE.

REINFORCEMENT DESIGNATED AS "CONTINUOUS" SHALL HAVE A CLASS B LAP


SPLICE UNLESS NOTED OTHERWISE. REINFORCEMENT BAR SPLICES IN GRADE
BEAMS SHALL BE LOCATED AT THE CENTERLINE OF SUPPORTS FOR BOTTOM
BARS AND AT MIDSPAN FOR TOP BARS. PROVIDE STANDARD ACI HOOKS FOR TOP
AND BOTTOM BARS AT DISCONTINUOUS ENDS OF ALL GRADE BEAMS.

03.13
03.14

PENETRATIONS SHALL NOT BE CUT IN STRUCTURAL STEEL MEMBERS UNLESS SO


INDICATED IN THE DRAWINGS OR AS REVIEWED BY THE ENGINEER.

HORIZONTAL FOOTING AND HORIZONTAL WALL REINFORCEMENT SHALL BE


CONTINUOUS AND SHALL HAVE 90-DEGREE BENDS AND EXTENSIONS, OR CORNER
BARS OF EQUIVALENT SIZE LAPPED WITH CLASS B LAP SPLICES, AT CORNERS
AND INTERSECTIONS.

03.15

BEAMS SHALL BE CAMBERED UPWARD WHERE SHOWN ON THE CONTRACT


DOCUMENTS. WHERE NO UPWARD CAMBER IS INDICATED, ANY MILL CAMBER
SHALL BE DETAILED UPWARD IN THE BEAMS.

HORIZONTAL JOINTS WILL NOT BE PERMITTED IN CONCRETE CONSTRUCTION


EXCEPT AS SHOWN ON THE CONTRACT DOCUMENTS. VERTICAL JOINTS SHALL
OCCUR AT CENTER OF SPANS AT LOCATIONS REVIEWED BY THE STRUCTURAL
ENGINEER.
CONSTRUCTION JOINTS BETWEEN PIERS AND PIER CAPS, FOOTINGS AND WALLS
OR COLUMNS, OR WALLS, COLUMNS, BEAMS AND THE FLOOR SYSTEM THEY
SUPPORT SHALL BE PREPARED BY ROUGHENING THE CONTACT SURFACE TO A
FULL AMPLITUDE OF APPROXIMATELY 1/4 INCH LEAVING THE CONTACT SURFACE
CLEAN AND FREE OF LAITANCE.
PROVIDE (2) NO. 4 REINFORCEMENT BARS X 4'-0" AT REENTRANT CORNERS OF
SLAB ON GRADE AT POUR STRIPS AND COLUMN BLOCKOUTS. PLACE BARS
CENTERED IN THE SLAB AND DIAGONAL TO THE CORNER WITH 1" CLEARANCE
FROM THE SLAB AT THE CORNER.
CONDUIT, PIPES, AND SLEEVES EMBEDDED IN CONCRETE SHALL CONFORM TO
THE REQUIREMENTS OF ACI 318, CHAPTER 6.3.

03.16

02.03

THE CONTRACTOR SHALL NOTIFY STRUCTURAL ENGINEER OF ANY MISFABRICATED


STRUCTURAL STEEL PRIOR TO ERECTION OF SAME.

WHERE INDICATED ON THE DRAWINGS, STRUCTURAL STEEL MEMBERS,


FABRICATIONS, AND WELDED ASSEMBLIES SHALL BE GALVANIZED AFTER
FABRICATION BY HOT DIP PROCESS IN ACCORDANCE WITH ASTM A123. WEIGHT
OF ZINC COATING SHALL CONFORM TO THE REQUIREMENTS SPECIFIED UNDER
"WEIGHT OF COATING" IN ASTM A123 OR ASTM A386, AS APPLICABLE. THE
AFFECTED PORTIONS OF FIELD WELDED GALVANIZED ASSEMBLIES SHALL BE
FIELD PAINTED WITH ZINC RICH CORROSION RESISTANT PAINT.
STRUCTURAL STEEL MEMBERS TO RECEIVE FIREPROOFING SHALL NOT BE
PRIMED NOR PAINTED. FIREPROOFING MATERIAL THICKNESS SHALL BE
INCREASED AS REQUIRED FOR STEEL MEMBERS NOT CONFORMING TO THE
MINIMUM SIZES INDICATED IN THE U.L. FIRE RESISTANCE DIRECTORY VOLUME 1 AND FOR STEEL MEMBERS DETERMINED UNRESTRAINED.

03.18

ERECTION OF THE STRUCTURAL FRAME SHALL NOT PROCEED MORE THAN FOUR
LEVELS ABOVE A LEVEL CONTAINING A COMPLETED CONCRETE SLAB.

03.19

ARCHITECTURALLY EXPOSED STRUCTURAL STEEL MEMBERS AND CONNECTIONS


SHALL CONFORM WITH THE REQUIREMENTS OF THE AISC "CODE OF STANDARD
PRACTICE FOR STEEL BUILDINGS AND BRIDGES" FOR ARCHITECTURALLY
EXPOSED STRUCTURAL STEEL (AESS), SECTION 10, UNLESS MORE STRINGENT
REQUIRMENTS ARE SHOWN OR SPECIFIED ELSEWHERE.

THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW A MIX DESIGN FOR THE
PROPOSED CONCRETE. MIX DESIGNS SHALL BE IN ACCORDANCE WITH ACI 318
CHAPTER 5 AND SHOW WEIGHT PROPORTIONS FOR ALL COMPONENTS OF THE
MIX. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGN WITHOUT THE
APPROVAL OF STRUCTURAL ENGINEER
THE FIRE PROTECTION RATING FOR THIS PROJECT IS BASED UPON THE USE
OF NORMAL WEIGHT AGGREGATE CONCRETE MADE WITH CARBONATE
AGGREGATES. CARBONATE AGGREGATES CONSIST MAINLY OF CALCIUM OR
MAGNESIUM CARBONATE, E.G., LIMESTONE OR DOLOMITE, AND CONTAIN 40
PERCENT OR LESS QUARTZ, CHERT AND FLINT.

02.04

02.05

02.06

02.07

02.08

FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER


FROM THOSE DESCRIBED IN THE GEOTECHNICAL REPORT SHALL BE
REPORTED TO THE ARCHITECT, STRUCTURAL ENGINEER AND GEOTECHNICAL
ENGINEER BEFORE FURTHER CONSTRUCTION IS ATTEMPTED.

02.09

WALLS RETAINING BACKFILL HAVE BEEN DESIGNED FOR IN SERVICE LOADS


ONLY. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING DURING
CONSTRUCTION. THE SHORING SHALL NOT BE REMOVED UNTIL THE
SUPPORTING ELEMENTS ARE IN PLACE, THE CONCRETE IN THE WALLS AND
SUPPORTING ELEMENTS HAS ATTAINED THE SPECIFIED 28 DAY COMPRESSIVE
STRENGTH (FC') AND COMPACTION OF THE BACKFILL HAS BEEN COMPLETED.

02.10

DURING CONSTRUCTION, THE CONTRACTOR SHALL PROVIDE TEMPORARY


SHORING OF WALLS WHICH ARE ULTIMATELY SUPPORTED TOP AND BOTTOM.
SUCH SHORING SHALL NOT BE REMOVED UNTIL THE SUPPORTING ELEMENTS
ARE IN PLACE, THE CONCRETE IN THE WALLS AND SUPPORTING ELEMENTS
HAS ATTAINED THE SPECIFIED 28 DAY COMPRESSIVE STRENGTH (FC') AND
COMPACTION OF THE BACKFILL AGAINST THE WALL HAS BEEN COMPLETED.

02.11

A GRAVITY DRAINAGE SYSTEM IS REQUIRED TO PREVENT THE BUILD-UP OF


HYDROSTATIC PRESSURE BEHIND THE WALLS.

02.12

GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT AND STRUCTURAL


ENGINEER, 24 HOURS PRIOR TO PLACEMENT OF CONCRETE IN THE FOOTINGS.

02.13

REINFORCEMENT PLACEMENT SEQUENCE FOR FOOTINGS IS NOTED ONLY FOR


MAJOR REINFORCEMENT BAR LAYERS. IN SPREAD FOOTINGS AND MATS THE
CONTRACTOR SHALL SEQUENCE ALL OTHER BAR PLACEMENTS AS REQUIRED
TO CONFORM TO THE CONTRACT DOCUMENTS.

02.14

02.15

02.17

BASIC WIND SPEED


ENCLOSURE
BUILDING CATEGORY
WIND EXPOSURE
INTERNAL PRESSURE COEFFICIENT

70 PCF
90 PCF

TEMPORARY STEEL CASING MAY BE REQUIRED DURING THE INSTALLATION OF


DRILLED PIERS (SEE GEOTECHNICAL REPORT). THE CONTRACTOR SHALL
PROVIDE A UNIT PRICE FOR THE USE OF STEEL CASING AS A SEPARATE ITEM
IN THE CONTRACT.

SUBGRADE UNDER SLABS ON FILL SHALL HAVE A MAXIMUM PLASTICITY INDEX


OF 15 AND SHALL BE PREPARED, PLACED AND COMPACTED IN STRICT
ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN THE
GEOTECHNICAL REPORT.

SLABS ON GRADE SHALL HAVE CONSTRUCTION JOINTS OR CRACK CONTROL


JOINTS AT EACH COLUMN LINE IN EACH DIRECTION. ADDITIONAL CRACK
CONTROL JOINTS SHALL BE PROVIDED, SUCH THAT THE SPACING OF THE
JOINTS DOES NOT EXCEED 36 TIMES THE SLAB THICKNESS, AND THE RESULTING
ASPECT RATIO OF THE DIMENSIONS OF SLAB AREA DOES NOT EXCEED 1.5 TO 1.
CRACK CONTROL JOINTS SHALL BE MADE USING A "SOFT-CUT" CONCRETE SAW AS
SOON AS THE SLAB WILL SUPPORT THE WEIGHT OF THE SAW AND OPERATOR
WITHOUT DISTRUBING THE FINAL FINISH. REFER TO STANDARD FOUNDATION
DETAILS FOR INFORMATION ON CONTROL JOINTS, CONSTRUCTION JOINTS,
REINFORCEMENT DETAILS AND JOINT SEALANT DETAILS. FOR SLABS
REINFORCED WITH REINFORCING BARS OR WELDED WIRE FABRIC SUPPLIED
IN FLAT SHEETS PROVIDE STANDARD CORROSION RESISTANT HIGH-CHAIRS
WITH SAND BEARING PLATES TO MAINTAIN THE REINFORCEMENT AT OR ABOVE
THE MID-DEPTH OF THE SLAB.
GRADE BEAMS SHALL BE CAST ON 8 INCH DEEP x BEAM WIDTH CORRUGATED
CARDBOARD CARTON FORMS. CARTON FORMS SHALL BE SUREVOID WAX
COATED VERTICAL CELL RECTANGULAR BOXES (OR EQUIVALENT).
TRAPEZOIDAL VOID BOXES SHALL NOT BE USED. DIAGONAL CELL BOXES
SHALL NOT BE USED. BOXES SHALL NOT BE WRAPPED IN POLYETHYLENE. SOIL
RETAINERS SHALL BE USED ON EACH SIDE OF THE GRADE BEAM TO PREVENT SOIL
FROM SLOUGHING OFF INTO THE VOID. RETAINERS SHALL BE PLASTIC
MOTZBLOCK OR OTHER MATERIAL PROVIDED TO THE STRUCTURAL ENGINEER.

DEC 09, 2015 ISSUE FOR SITE ROUGH GRADING / GARAGE


FONDATION PERMIT
01-18-2016 FOUNDATION REVISIONS

120 MPH
ENCLOSED
III
B
0.18

BASIC WIND SPEED IS 3-SECOND GUST SPEED AT A REFERENCE ELEVATION


OF 33 FEET ABOVE THE GROUND.
01.05

ALL EXTERIOR COMPONENT AND CLADDING MATERIALS SHALL BE DESIGNED TO


WITHSTAND THE WIND PRESSURES SPECIFIED IN COMPONENTS AND CLADDING
LOAD TABLE, THIS SHEET.

01.06

ALL EXTERIOR PARAPET COMPONENT AND CLADDING MATERIALS SHALL BE


DESIGNED TO WITHSTAND THE WIND PRESSURES SPECIFIED IN PARAPET
COMPONENTS AND CLADDING LOAD TABLE, THIS SHEET.

01.07

THE GROUND SNOW LOAD 'Pg' FOR THIS AREA IS 5 PSF OR LESS.

01.08

THE STRUCTURE HAS BEEN DESIGNED TO WITHSTAND THE SEISMIC FORCES


SPECIFIED IN CHAPTER 16, SECTION 1613, OF THE INTERNATIONAL BUILDING
CODE, USING THE FOLLOWING PARAMETERS:
SEISMIC IMPORTANCE FACTOR
Ss
S1
SITE CLASS
SDS
SD1
OCCUPANCY CATEGORY
SEISMIC DESIGN CATEGORY

1.25
0.074g
0.040g
D
0.079g
0.065g
III
A

01.09

STRUCTURAL MEMBERS HAVE BEEN LOCATED AND DESIGNED TO


ACCOMMODATE THE MECHANICAL EQUIPMENT AND OPENINGS SPECIFIED BY
THE MECHANICAL CONSULTANT. ANY SUBSTITUTIONS RESULTING IN
REVISIONS TO THE STRUCTURE SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO COORDINATE WITH STRUCTURAL ENGINEER.

01.10

THE LIVE LOADS ARE NOT REDUCED IN PASSENGER CAR GARAGES EXCEPT
THE LIVE LOADS FOR MEMBERS SUPPORTING TWO OR MORE FLOORS ARE
REDUCED UP TO A MAXIMUM OF 20 PERCENT.

01.11

THE PARKING DECK FLOOR SYSTEM HAS BEEN DESIGNED TO WITHSTAND A


CONCENTRATED WHEEL LOAD OF 3000 POUNDS PLACED UPON ANY SPACE 20
SQUARE INCHES, IN ACCORDANCE WITH SECTION 1607 OF THE BUILDING
CODE.

01.12

GARAGE GUARDRAILS HAVE BEEN DESIGNED TO WITHSTAND A SERVICE LOAD


FORCE OF 6000 POUNDS APPLIED HORIZONTALLY AT 1'-6" ABOVE THE PARKING
LEVEL, IN COMPLIANCE WITH SECTION 1607.7.3 OF THE INTERNATIONAL
BUILDING CODE. THE FORCE MAY BE DISTRIBUTED OVER A 1 FT SQUARE
AREA.

01.13

THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE
METHODS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE
RESPONSIBILITY OF THE CONTRACTOR. SUPPORTING FORMWORK FOR THE
CONCRETE CONSTRUCTION SHALL NOT BE REMOVED BEFORE THE CONCRETE
HAS GAINED SUFFICIENT STRENGTH TO SAFELY STRESS THE POSTTENSIONING TENDONS IN BOTH DIRECTIONS AND THE STRUCTURE HAS GAINED
SUFFICIENT STRENGTH TO SAFELY SUPPORT THE DEAD AND SUPERIMPOSED
LOADS WHICH WOULD BE SUBSEQUENTLY APPLIED. THE CONTRACTOR SHALL
TAKE ALLNECESSARY PRECAUTIONS TO MAINTAIN AND INSURE THE INTEGRITY
OF THE TRUCTURE AT ALL STAGES OF CONSTRUCTION.

SLAB ON GRADE SHALL BE UNDERLAID BY A MAXIMUM OF 2 INCHES OF SAND.


PRIOR TO PLACING THE SAND, THE FLOOR SUBGRADE SHALL BE PROPERLY
COMPACTED, PROOFROLLED, FREE OF STANDING WATER, MUD AND FROZEN
SOIL. BEFORE PLACEMENT OF THE CONCRETE, A VAPOR BARRIER SHALL BE
PLACED ON TOP OF THE GRANULAR MATERIAL.
VAPOR BARRIER SHALL CONFORM TO ASTM E1745, CLASS C OR BETTER AND
SHALL HAVE A MAXIMUM VAPOR PERMEANCE OF 0.04 PERMS WHEN TESTED IN
ACCORDANCE WITH ASTM E96. VAPOR BARRIER SHALL BE NO LESS THAN
10 MILS THICK IN ACCORDANCE WITH ACI 301.1R-96.

20 PSF
80 PSF
125 PSF
125 PSF
AS REQUIRED
40 PSF
ACTUAL WTS

AS PER SECTION 1609.1.1 OF THE INTERNATIONAL BUILDING CODE, THE


STRUCTURE HAS BEEN DESIGNED TO WITHSTAND THE WIND PRESSURES
SPECIFIED IN CHAPTER 6 OF ASCE 7, USING THE FOLLOWING INFORMATION:

WALLS RETAINING BACKFILL HAVE BEEN DESIGNED FOR THE FOLLOWING


LATERAL EARTH PRESSURES:

DRILLED PIERS SHALL BE EXCAVATED, CLEANED, REINFORCED AND


CONCRETE PLACED ON THE SAME DAY. DRILLED PIERS WITH LESS THAN 2'-0"
CLEAR BETWEEN BELLS OR SHAFTS SHALL BE EXCAVATED AND CONCRETE
PLACED A MINIMUM OF 24 HOURS APART. IF PIERS CAN NOT BE FORMED
WITHOUT CAVING OF THE SOIL, THE ARCHITECT, STRUCTURAL ENGINEER AND
GEOTECHNICAL ENGINEER SHALL BE NOTIFIED BEFORE FURTHER
CONSTRUCTION IS ATTEMPTED.

LIVE LOADS
ROOF
OFFICE
MECHANICAL SPACE
LIGHT STORAGE
MECHANICAL & PIPING LOADS
PARKING
MECHANICAL EQUIPMENT AND PADS

01.04
10,000 PSF

CANTILEVER RETAINING WALLS


WALLS SUPPORTED TOP AND BOTTOM

10 PSF
10 PSF

FIRE SPRINKLER PIPING SUPPORTED BY THE STRUCTURAL SYSTEM IS TO BE


DISTRIBUTED SO THAT THE WEIGHT OF THE WATER-FILLED PIPE DIVIDED BY
THE TRIBUTARY AREA OF THE SUPPORTING MEMBER DOES NOT EXCEED
5 POUNDS PER SQUARE FOOT, AND THE LOAD IMPARTED TO ANY ONE
STRUCTURAL MEMBER DOES NOT EXCEED 50 POUNDS PER LINEAR FOOT.
EACH STRUCTURAL SUPPORT OF THE PIPING SHALL BE DESIGNED TO SUPPORT
A LOAD EQUAL TO THE WEIGHT OF THE WATER-FILLED PIPE PLUS 250 POUNDS.

THE FOUNDATION FOR THE STRUCTURE HAS BEEN DESIGNED FOR THE
FOLLOWING ALLOWABLE SOIL BEARING PRESSURES AT A DEPTH OF 50 FT
BELOW EXISTING GRADE:

TOTAL LOAD

SUPERIMPOSED DEAD LOADS


CEILING + MECHANICAL
BUILT-UP ROOF

01.03
4,500 PSF

DRILLED AND UNDERREAMED PIERS

02.18

THE COMPRESSIVE STRENGTH OF CONCRETE IN POST-TENSIONED SLAB


SYSTEM AT TIME OF TRANSFER (FCI') SHALL BE CAPABLE OF DEVELOPING
ULTIMATE TENDON ANCHORAGE STRENGTH.

THE FOUNDATION FOR THE STRUCTURE HAS BEEN DESIGNED FOR THE
FOLLOWING ALLOWABLE SOIL BEARING PRESSURES AT A DEPTH OF 25 FT
BELOW EXISTING GRADE:

TOTAL LOAD

02.16
03.17

STRUCTURE HAS BEEN DESIGNED BASED ON A MAXIMUM POTENTIAL VERTICAL


RISE (PVR) OF 1 INCH. PER THE PROJECT GEOTECHNICAL REPORT, THE SLABS
ON GRADE WILL REQUIRE A MINIMUM OF 8 FT OF SELECT NON-EXPANSIVE
MATERIAL BELOW THE SLAB EXTENDING THROUGHOUT THE BUILDING LIMITS
AND UNDER THE ADJOINING FLATWORK. REFER TO THE GEOTECHNICAL REPORT
FOR ADDITIONAL REQUIREMENTS.

DRILLED AND UNDERREAMED PIERS

STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM


TO THE AISC "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" AND THE
MARCH 2000 VERSION OF THE AISC "CODE OF STANDARD PRACTICE FOR STEEL
BUILDINGS AND BRIDGES".

03.09

GRADE 60
GRADE 75

02.02

01.14

01.15

01.16

ELEVATOR SHAFT AND SUPPORT BEAMS HAVE BEEN DESIGNED AND DETAILED
BASED ON A(N) KONE ECOSPACE 3500 LB CAPACITY ELEVATOR. THE ELEVATOR
CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONNECTION OF THE MACHINE
BEAMS AND/OR SECONDARY BEAMS TO THE STRUCTURE. SHOP DRAWINGS FOR
THE ELEVATORS SHOWING CONNECTION DETAILS, LOCATION AND MAGNITUDE OF
LOADS APPLIED TO THE STRUCTURE, ETC. SHALL BE SUBMITTED TO STRUCTURAL
ENGINEER FOR VERIFICATION OF DESIGN ASSUMPTIONS.
THE GENERAL CONTRACTOR AND SUBCONTRACTORS SHALL DETERMINE THE
SCOPE OF THE STRUCTURAL WORK FROM THE CONTRACT DOCUMENTS TAKEN AS
A WHOLE. THE STRUCTURAL DRAWINGS SHALL NOT BE CONSIDERED
SEPARATELY FOR PURPOSES OF BIDDING THE STRUCTURAL WORK. DUE
CONSIDERATION SHALL BE GIVEN TO OTHER STRUCTURAL WORK OR WORK
RELATED TO THE STRUCTURE, INCLUDING NECESSARY COORDINATION
DESCRIBED OR IMPLIED BY THE ARCHITECTURAL AND MECHANICAL DRAWINGS.
METHODS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL TAKE ALL
NECESSARY PRECAUTIONS TO MAINTAIN AND INSURE THE INTEGRITY OF THE
STRUCTURE AT ALL STAGES OF CONSTRUCTION.

01.17

THE REPRODUCTIVE USE OF THE STRUCTURAL CONTRACT DOCUMENTS OR


ELECTRONIC FILES AS STRUCTURAL SHOP DRAWING DOCUMENTS BY THE
CONTRACTOR OR SUB-CONTRACTORS IS AT THEIR OWN RISK. STRUCTURAL
ENGINEER ASSUMES NO LIABILITY AS THE RESULT OF THE REPRODUCTIVE USE
OF THE STRUCTURAL CONTRACT DOCUMENTS FOR SHOP DRAWINGS.

01.18

SCALES NOTED ON THE DRAWINGS ARE FOR GENERAL INFORMATION ONLY. NO


DIMENSIONAL INFORMATION SHALL BE OBTAINED BY DIRECT SCALING OF THE
DRAWINGS.

01.29

THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL


RESULTING REVISIONS TO THE STRUCTURAL SYSTEM AS A RESULT OF
ACCEPTANCE OF CONTRACTOR PROPOSED ALTERNATIVES OR SUBSTITUTIONS.

01.20

PRINCIPAL OPENINGS IN THE STRUCTURE ARE INDICATED ON THE CONTRACT


DOCUMENTS. REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND
PLUMBING DRAWINGS FOR SLEEVES, CURBS, INSERTS, ETC. NOT HEREIN
INDICATED. OPENINGS IN SLABS WITH A MAXIMUM SIDE DIMENSION OR DIAMETER
OF 12 INCHES OR LESS SHALL NOT REQUIRE ADDITIONAL FRAMING OR
REINFORCEMENT, UNLESS NOTED OTHERWISE.THE LOCATION OF SLEEVES OR
OPENINGS IN STRUCTURAL MEMBERS SHALL BE SUBMITTED TO THE STRUCTURAL
ENGINEER FOR REVIEW.

GENERAL PROGRESS OF WORK.

1001 Fannin Street, Suite 4040 | Houston, Texas 77002 USA


Phone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
Project Team

STONEHENGE HOLDINGS LLC


OWNER

MORRIS
ARCHITECT

HUITT-ZOLLARS, INC.
CIVIL ENGINEER

ENSIGHT HAYNES WHALEY, LLC


STRUCTURAL ENGINEER

BLUM CONSUTLING ENGINEER, INC.


MEP ENGINEER

THE OFFICE OF JAMES BURNETT


LANDSCAPE CONSULTANT

FERGUSON CONSULTING, INC.


TECHNOLOGY / SECURITY CONSULTANT

DESIGN LOAD (psf)


ZONE

0-10 sq ft

>100 sq ft

12.1, -29.6

10, -27.1

12.1, -49.5

10, -32.1

12.1, -74.8

10, -32.1

2 (O.H.)

-47.2

-44.7

3 (O.H.)

-74.8

-24.6

ZONE

0-10 sq ft

>500 sq ft

22.6, -22.6

15.1, -17.6

22.6, -25.1

15.1, -25.1

SHOP DRAWINGS SHALL NOT SHOW MATERIALS FOR MORE THAN ONE LEVEL OF
THE SAME PLAN.

3000 PSI
4000 PSI
4000 PSI
4000 PSI
4000 PSI
3500 PSI
4000 PSI
SEE SCHEDULE
SEE SCHEDULE
5000 PSI
3750 PSI

PARAPET DESIGN LOAD (psf)


INTERIOR ZONE
h

0-30

40

50

60

CORNER ZONE

FRONT SURFACE

BACK SURFACE

FRONT SURFACE

BACK SURFACE

0-10 sf

>500 sf

0-10 sf

>500 sf

0-10 sf

>500 sf

0-10 sf

>500 sf

+22.0

+15.4

+22.0

+15.4

+22.0

+15.4

+22.0

+15.4

-19.8

-15.4

-39.5

-24.1

-39.5

-22.0

-61.5

-24.1

+23.8

+16.7

+23.8

+16.7

+23.8

+16.7

+23.8

+16.7

-21.4

-16.7

-42.9

-26.2

-42.9

-23.8

-66.7

-26.2

+25.4

+17.8

+25.4

+17.8

+25.4

+17.8

+25.4

+17.8

-22.9

-17.8

-45.7

-27.9

-45.7

-25.4

-71.1

-27.9

+26.8

+18.7

+26.8

+18.7

+26.8

+18.7

+26.8

+18.7

-24.1

-18.7

-48.2

-29.4

-48.2

-26.8

-74.9

-29.4

(BUILDING CATEGORY III, EXPOSURE B, V = 120 MPH, GABLE/HIP ROOF <7 DEGREES)

COMPONENTS & CLADDING WIND LOAD - PARAPETS

01-18-2016
Project Name

TEXAS A&M CAIN HALL SITE


4
REDEVELOPMENT - VOLUME 4
500 GENE STALLINGS BOULEVARD,
COLLEGE STATION, TEXAS 77840

06.03

DRILLED PIERS
PIER CAPS
PLINTHS
FOOTINGS
GRADE BEAMS
SLABS ON GRADE
WALLS
COLUMNS
SHEAR WALLS
POST TENSIONED SLAB SYSTEMS
MINIMUM AT TRANSFER (FCI')

MASONRY UNITS SHALL BE GRADE N, TYPE I LIGHT WEIGHT OR MEDIUM WEIGHT


HOLLOW CONCRETE UNITS MEETING FIRE RATING REQUIREMENTS AND
CONFORMING TO THE REQUIREMENTS OF ASTM C90. MASONRY UNITS SHALL
HAVE A MINIMUM COMPRESSIVE STRENGTH OF 1900 PSI ON THE NET AREA AT 28
DAYS, BUT NOT LESS THAN THE REQUIRED STRENGTH TO PRODUCE THE MINIMUM
MASONRY STRENGTH (F'M). MASONRY UNITS SHALL NOT BE INSTALLED PRIOR TO
ATTAINING THE REQUIRED 28 DAY STRENGTH.

h = 57 ft

a = 15 ft

JANUARY 18, 2016


Project Number

R303928.03
Drawing Name

NOTES
a

06.02

Description

1.

(0-10 sq ft) EXAMPLE DENOTES EFFECTIVE WIND AREA.

2.

+ AND - SIGNS SIGNIFY PRESSURES ACTING TOWARD OR AWAY


FROM THE SUFACES, RESPECTIVELY.

3.

WIND PRESSURES MAY BE INTERPOLATED FOR EFFECTIVE WIND


AREAS BETWEEN THE SPECIFIED RANGES.

4.

(O.H.) REFERS TO ROOF OVERHANG.

GENERAL
STRUCTURAL NOTES

Scale:

(BUILDING CATEGORY III, EXPOSURE B, V = 120 MPH, GABLE/HIP ROOF <7 DEGREES)

COMPONENTS & CLADDING WIND LOAD

12" = 1'-0"

Drawing Number

S-0.00

Вам также может понравиться