Protection
Manish Dhruw
Asst Manager
14843
Cpp-540
To
To
To
To
avoid
avoid
avoid
avoid
operational faults
equipments damage.
accidents to individuals.
system disturbances
In case of
MFT Trip
Master Fuel Trip - it produces trip signal for fuel
systems from operation , then trip the boiler out of
service away from danger. this relay needs many
will failure.
be found
9. Unit flame
conditions
1. Both ID to
fanoperate
trip. , these conditions
at the following points.
10. Loss of fuel.
2. Both FD fans trip.
11. Loss of scanner
3. Emergency manual
cooling air (Scanner air
trip.
pressure<2 KPa with 5
4. Turbine tripped and
min time delay).
HPLP bypass not
12. Both APH tripped.
opened (RH protection
13. Oil burner light off
act).
5. Drum level low low
failed.
low (<-325mm with 5
sec delay).
Other than MFT 6. Total air flow<30%.
1. MS
Boiler
1. If one ID fan trips, one FD fan will trip in the same sequence.
2. If one FD fan trips, one ID fan will trip in the same sequence.
3. If one APH trips, one ID fan, one FD fan and one PA fan will trip in
the same sequence.
4. In case of GCB opening, top elevation mill or non adjacent mill
will trip.
5. If drum level200 mm, EBD will open.
6. If drum level150 mm, EBD will close.
7. Feed water flow<50 TPH, Economiser recirculation MOV will
open.
8. Feed water flow>80 TPH, Economiser recirculation MOV will
close.
9. If superheated steam pressure is higher than 14.86 MPa ERV will
open and if pressure is lower than the value ERV will close (if kept
in service).
Other
Protections
1. Boiler drum pressurea) Higher than 17.24 MPa LHS safety valve will lift
and it will reset @ 16.35 MPa.
b) Higher than 16.74 MPa RHS safety valve will lift
and it will reset @ 16.21 MPa.
2. Superheated steam pressurea) Higher than 15.29 MPa, LHS safety valve will lift
and it will reset @ 14.765 MPa.
b) Higher than 15.2 MPa, RHS safety valve will lift
and it will reset @ 14.747 MPa.
3. CRH steam pressurea) Higher than 3.058 MPa, LHS safety valve will lift
and it will reset @ 2.947 MPa.
b) Higher than 2.963 MPa, RHS safety valve will lift
Alarm
Drum level
1. Level>125 mm: high
priority alarm.
2. Level>-125 mm: high
priority alarm.
3. Level>250 mm:
emergency priority alarm.
4. Level>-250 mm:
emergency priority alarm.
Furnace pressure
1. Pressure>30 mm of
H2O: high priority alarm.
2. Pressure>-30 mm of
H2O: high priority alarm.
3. Pressure>50 mm of
H2O: emergency priority
alarm.
4. Pressure>-50 mm of
MS & RH Temperature
1. MS temperature>5450C:
high priority alarm.
2. MS temperature>5500C:
emergency priority alarm.
3. RH temperature>5450C:
high priority alarm.
4. RH temperature>5500C:
emergency priority alarm.
Others
1. APH flue gas inlet
temperature<3000C: high
priority alarm.
2. O2<1: high priority
alarm.
3. O2 zero: emergency
priority alarm.
4. Furnace DP90 mm of
e
Interl
ock:
TRIP
enabl
e
Interl
ock:
ALARM
1. Fan/ motor bearing temperature750C: high
priority alarm.
2. Fan/ motor bearing temperature800C:
emergency priority alarm.
3. Fan bearing vibration6.3 mm/sec: high
priority alarm.
4. Fan bearing vibration11mm/sec:
emergency priority alarm.
5. Motor winding temperature1100C: high
priority alarm.
6. Motor winding temperature1200C:
emergency priority alarm
TRIP
1. Motor winding temperature1300C (2 out of
6 temperatures with 60sec time delay).
2. Fan/ motor bearing temperature900C (with
60 sec time delay).
TRIP
enable
Interlo
ck:
ALARM
1. Fan/ motor bearing temperature750C: high
priority alarm.
2. Fan/ motor bearing temperature800C: emergency
priority alarm.
3. Fan bearing vibration6.3 mm/sec: high priority
alarm.
4. Fan bearing vibration11mm/sec: emergency
priority alarm.
5. Motor winding temperature1100C: high priority
alarm.
6. Motor winding temperature1200C: emergency
priority alarm.
TRIP
1. Motor winding temperature1300C (2 out of 6
temperatures with 60sec time delay).
2. Fan/ motor bearing temperature900C with 60 sec
OR
Interl
ock
Trip
enabl
e
Interl
ock:
ALARM
1. Fan/ motor bearing temperature75 0C: high priority alarm.
2. Fan/ motor bearing temperature80 0C: emergency priority
alarm.
3. Fan bearing vibration6.3 mm/sec: high priority alarm.
4. Fan bearing vibration11mm/sec: emergency priority alarm.
5. Motor winding temperature110 0C: high priority alarm.
6. Motor winding temperature120 0C: emergency priority alarm.
TRIP
1. Motor winding temperature130 0C (2 out of 6 temperatures
with 60 sec time delay).
2. Fan/ motor bearing temperature90 0C with 60 sec time delay.
3. Fan bearing vibration11mm/sec with 60 sec time delay.
4. PA fan motor protection (over current, earth fault, negative
sequence, phase fault etc) acted.
5. MFT trip PA fan.
6. ID fan/ FD fan A/B trip to PA fan A/B trip.
7. PA fan running and fan discharge damper closed.
e
interl
ock:
AND
OR
ALARM
TRIP
1.
No
motor
or
breaker
protection acted.
2. Fan is in remote.
3. In case of one fan is running
and the other is in stopped
conditiona) By interlock input if one fan
is stopped/ tripped, standby fan
will start in auto.
b) If scanner air header
pressure<2 KPa for 5 sec, then
standby fan will start in auto by
interlock input.
1. Scanner air header pressure<
low switch acting: emergency
AND
Start
Enable
Interlo
ck
Alarm
Trip
1. No breaker/ motor
protection acted.
2. Lube oil pressure normal
for > 5 minutes.
3. No MFT acted.
AND
4. Boiler drum pressure>3.4
kg/cm2.
5. Secondary air
temperature>1770C.
6. Total air flow<40%
(230TPH).
7. MDVs are open.
8. Mill outlet
temperature<1150C.
Start
Enable
Interlock
AND
Alarm
Trip
Start
Enable
AN
D
1.
2.
3.
4.
OR
Interlo
ck
Stop/Trip
Enable
Interlo
ck:
Alar
m
Trip
1. No breaker or motor
protection acted.
2. LOP is in remote.
3. Oil pool temperature of lube
oil>600C.
Start
enable
Interlo
ck
AND
OR
Stop/tri
p
enable
Interlo
ck
Ala
rm
Trip
AND
Interl
ock
Stop/tr
ip
enabl
e
Interl
ock:
a
h
T s
nk