2.1.7. Arrange lifting tools and hooks for Feed Hopper and WF mechanics
installation.
2.1.8. Check availability of all the required fasteners to fix the feed hopper,
WF, drive group, vibrator motor, discharge chute etc.
Axis of the WF must match with the axis of Feed Hopper. Max
permissible offset is 20 mm. Larger mismatch will result into belt sway with
material load and material may touch the side skirt
Check alignment of tacho encoder unit with tail pulley extension shaft.
Check tightness of all fasteners.
Caution: Before connection of any Analog signal to the PLC / DCS system,
ensure that PLC is fully tested and connection is not going into any wrong
terminal. Some of the PLC ports can carry potential.
Note-2:- Correction need more than 2 % upon cross check with material
must be doubted as something is wrong.
Note-3:- Inconsistency of tare result indicate problem in the mechanics, or
load cell assembly or load cell connection.
5. Test data documentation:Test data and parameter to be recorded for future use.
6. Important information for user:6.1. Type SPP or SPTT Load Cells has 4 wire plus shield connection. Color
code:Red = +ve excitation.
Black = -ve excitation.
Green = +ve output.
White = -ve output.
6.2. Type SPP / SPTT Load cell input and output resistance.
Input resistance = 380 ohms +/- 50 ohms,.
Output resistance = 350 ohms +/- 0.5 ohms.
6.3 Load cell connections in parallel.
6.3.1. Series-X WF, i.e. models DABX, DAMX etc, uses 2 nos SPP or SPTT load
cells. Load cells will be connected in parallel.
6.3.2. Combined input and output resistance must be cross checked before
connection to electrical panel.