Академический Документы
Профессиональный Документы
Культура Документы
IEEE - IEC
PROVE DEAD THE PLACE OF WORK
MODULE STRUCTURE
THE ROUTINE / TIMINGS
PRE & POST COURSE ASSESSMENT
LAYOUT AND GENERAL SAFETY IN THE PREMISES AND THE high
voltage ELECTRICAL LAB
DURATION OF THE COURSE
ATTENDANCE
BRIEF ABOUT IMTC
IMTC COMPLIMANTRY BUS
Inspection
Operation
Maintenance
Repair
Replacement
MODULE : 1
COURSE OBJECTIVES
ON COMPLETION OF THE COURSE THE PARTICIPANTS WILL HAVE SUFFICIENT KNOWLEDGE AND ENABLE THEM
TO UNDERSTAND :
High Voltage safety, precaution and procedures during maintenance and operations
Understand and demonstrate the functional, operational and safety requirements for a Marine High Voltage system
Assist suitably qualified personnel to carry out the inspection, operation, maintenance and limited repairs on High
Voltage apparatus
Devise a switching strategy for isolating HV system / Apparatus in accordance with specified safety procedures
documented and a thorough risk assessment
Perform 5k V insulation resistance (IR) and Polarization Index ( P I ) on High Voltage equipment
Work permits and company specific High Voltage Safety related documents
Trapped key system for sequential isolation and procedures to PROVE DEAD the place of work
2 Situational Awareness: Know your surroundings and working environment and the risk
involved and tackle the problems
3 Knowhow and Training: Correct operating knowledge of different equipment tools and
systems on board, including safety procedures and emergency plans through proper training
4 Use of PPE: Every person on board ships must know what PPE is to be used and when and
donning and checking. Maintain your PPE so as it is fit for use all the time as and when required
5 Help Yourself First: When you and your colleagues are trapped in dangerous situation,
help your self first to get out of the situation and then help others
6 Know Your Ship Inside - Out: On joining a ship be familiar and know every nook and
corner of the ship including location of fire fighting appliances, life saving appliances, alarms ,
escape routes, life boats and every thing needed in an emergency
7 Know Your Emergency Duties: Every crew member should know his emergency
duties
8 Avoid Panic Attacks: It is human to get tensed or nervous in case of an accident. Try to
control emotions to maintain mental peace and to act in a quick and smart manner under the
pressure of an emergency situation
DIE
Disconnect Isolate Earth
PROCEDURES
No Electrical conductors should be regarded as being safe unless it has been
isolated earthed, secured and proved dead
Precautions should be taken to ensure that isolated equipment can not be re
energized. Lock out . Tag out. Put up Warning and Caution notices
Voltage indicators should always to be tested before and after use
When not attended the barriers should be placed around live conductors
If isolation is done by other than competent person then it should be
demonstrated to the competent person
SAFETY PRECAUTIONS
MODULE :- 2
Brief revision of Power system on board
AC / DC
SERIES OR PARALLEL
INTRODUCTION
The Management of Health and Safety at
Work, regulation :
Risk Assessment.
Every employer (Senior personnel, Manager, Superintendent) shall
make a suitable and sufficient assessment of :1.
Risk to the health and safety of his employees (subordinates)
to which they are exposed whilst they are at work: and
2.
In making or reviewing the assessment the employer shall
take particular account of ; a)
The experience, lack of awareness of risk and immaturity of
New joiners, Trainees and Apprentices
b) The fitting out and lay out of the work place
c)
The nature, degree and duration of exposure to physical
biological, chemical agents and radiation ( very high Voltage)
d) The form, range and the use of the work equipment and the
way it is handled
Contd.
e)
f)
Capabilities of training:1.
2.
a)
THE TRAINING REFERED ABOVE SHALL :a) Be repeated periodically where applicable
b) Be adapted to take account of any new or
changed risk to the health and safety of the
employees concerned
c) Take place during working hours
7.
8.
Avoiding risk
Evaluate the risk which can not be avoided
Combating the risk at source
Adapting to technical progress
Replacing dangerous by non dangerous or by less
dangerous
Developing a coherent overall prevention policy which
covers technology, organization of work , working
conditions, social relationships and influence of factors
relating to the working environment
Giving collective protection measure priority over individual
protective measures
Giving appropriate instructions to employees (subordinates)
ENERGY TRANSMISSION
Energy can be transmitted by various means:
Mechanically
Hydraulically
Electrically
By Radiation and other means
Electricity is the most common energy transmission mean
ADVANTAGES OF ELECTRICAL MEANS:
Most efficient
Pollution free
Flexible
Instant availability over any distance
Comparatively less maintenance
Low weight to high power ratio for a given capacity
Low Voltage
:
Medium Voltage :
High Voltage
:
Extra High Voltage
Up to 1000 volts
1000 to 6600 volts
6600 to 11000 volts
Above 11000 volts
Illustration:
1000 volts RMS = 1414 volts peak &
6600 volts RMS = 9335 volts peak
9000 volts RMS = ? volts peak
MODULE :- 3
SAFETY BOOK / MANUAL
AN OVERVIEW
IEC
ANSI
EAW
See:
1)
ESR 1(company
specific)
2)
Code of safe working
practice for merchant
Seamen
Integrity
Modifications,
adjustments,
approvals, records,
maintenance
See:
1)
ESR 1(company
specific)
Access
Rooms, locks,
duties
See:
1)
ESR 1 (Company
specific rules)
Work
Electrical
distribution,
operating positions,
permits, planning,
risk assessment,
preparation,
completion, testing
See:
1)
ESR 1( company
specific)
2)
Safety Management
System (SMS)
3)
Hazardous Area Guide
Competence
Competence
assessment
training
See:
1)
ESR 1
2)
ESR 3
Responsibilities
Authorization
and
EMERGENCY CONDITIONS
When does an emergency condition arise?
How would you define an emergency condition?
Fire, flood, gas leak, trapped person, etc.
First preference should be the safety of personnel
Immediate steps to be taken to remove the danger and inform
the people/person
Do not enter an area which is prohibited to you
Switch off the power supply.
MODULE - 4
ADVANTAGES OF
HIGH VOLTAGE (3.3/ 4.4 / 6.6 / 11K.v. etc.
TRANSMISSION OF POWER TO LONG DISTANCES
FOR A GIVEN ENERGY LEVEL THE ARC INTENSITY IS
LOW (The current is low hence I x I x t is low)
LOW WEIGHT / POWER RATIO. ( COMPACT SYSTEM )
LOW / NO MAINTENANCE ON METAL ENCLOSED
SWITCH GEAR
High Voltage work carried out close to a person who is not familiar with
High Voltage hazards
High Voltage insulation testing
Equipment using water as part of High Voltage plant
Using test instruments when taking High Voltage measurements
High Voltage equipment stores energy even after disconnection
If the High Voltage circuit main earth is removed while carrying out any
maintenance
1.2 1.6 mA
1.6 2.2 mA
2.2 2.8 mA
2.8 3.5 mA
3.4 4.5 mA
4.0 5.0 mA
4.5 5.0 mA
5.0 7.0 mA
6.0 mA
9.0 mA
15 20 mA
20 40 mA
Serious and very painful contractions of the muscles, breathing stops, but
normally resumes if current is interrupted within
5 seconds
50 100 mA
AT HIGH
VOLTAGES
The recipient can be thrown off and may survive but with severe burns
AT LOW
VOLTAGE
time is important
Importance of Earthing
MODULE 5
440 volts
LOW
HIGH
VCB,SF6,OIL,Air Blast
ACB
ACB/VCB MAINTENANCE
VACUUM CHECKER/GAP
VISUAL CHECK
SEPARATE PROTECTION
DC 110V
DC 24 V
BUS BAR
SMALL
LARGE
WIDER
NARROW
MSB PROTECTION
SEGREGATED
COMPARTMENTS
WITHOUT COMPARTMENTS
EXPLOSION
NO EXPLOSION
NO SAFETY SHUTTERS
EARTHING DEVICE
NO EARTHING SWITCH
MSB DOORS
MECHANICAL INTERLOCK
SYSTEM
NO NEED
MODULE - 6
High voltage switch gear
NFPA
OSHA
BIS
IEC
Incident energy < 1.5 calories / cm2 will cause a burn just curable
The guide lines from NFPA- 70 provide guidance on appropriate level of
Personal Protective Equipment (PPE) as follows
Fault
current
Fault
Clearing
Time
Arc Safe
Distance
Incidence
Energy at
455 mm
Risk
Category
20 kA
0.5 sec
3375 mm
24 cal / cm2
5.8 kA
0.2 sec
850 mm
20 kA
0.2 SEC.
1811 mm
10 kA
0.2 sec.
1186 mm
8 kA
0.2 sec
457 mm
Risk
Energy level
Category
Cal / cm2
PPE
NOTE ; More PPE related details are available with MCA on request for a
particular plant and activity.
Arcs & Sparks that take place when the contacts are making and
breaking with normal load currents
Under fault currents
ARC depends on the following factors:
The nature and pressure of the medium of arc
The external ionizing and de-ionizing agents present
The voltage across the electrodes and variation of time
The material and configuration of the electrodes
The nature and configuration of the arcing chamber
Techniques to reduce
the Arc fault hazard
Design
Preferred Methods
Non Preferred
Methods
Reduce the
Prospective Fault
Current Level
Increase transformer
impedance
Techniques to reduce
the Arc fault hazard
Operation
Increase the
working
distance for
personnel
Preferred Methods
Operate the switch gear from
a remote position. Use local
electrical control desks away
from switch gear
Non Preferred
Methods
Increase the length of
tools used for
withdrawing functional
devices, e.g.circuit
breaker racking handle
MODULE 6 (a)
Safety and use of portable tools
Hazardous area:
All electric tools, including battery operated, and test equipment are
to be certified for the area (Zones) in which they are to be used
Non-Certified equipment may be used when the vessel is in gas free
condition
Pneumatic tools are to be used in restricted, conductive locations,
eg; tanks, crankcase, bilges etc.
Regular inspection and maintenance is recommended for damaged
insulation, overheating, proper plug socket contacts
User/Informal checks
Physical Condition/ Function
check before each use
Physical Condition/ Function
check before each use
Physical Condition/ Function
check before each use
Comment
Refer Note 1
9-12 months
Refer Note 2
Refer Note 3
6-9 months
Refer Note 2
Refer Note 3
MODULE - 7
Energy Levels
ENERGY
Energy in electrical system is measured
in;-
ARC ENERGY
When a fault occurs, the Energy at the fault = Current
squired. x time
FAULT LEVELS AT DIFFERENT VOLTAGES:
Fault level @ 11,000 volts = 1.732. x k V. x Fault current
Therefore Fault current = Fault level (MVA ) / 1.732. x
Voltage (Kv)
Typical Fault level in HV (11,000 /6600 v) system is
measured in MVA. Standard 250 MVA
Calculate the fault current for the above fault at 11,000
and 6600 volts
MODULE:- 8
SAFETY AND PROTECTION SYSTEM
MODULE 8
MEDIUM VOLTAGE SWITCH GEAR
PROTECTION;
Current transformers and associated relays placed as
close as possible with special features
SECURITY;
Unauthorized entry to switch rooms is restricted
Special key safe / trapped key system is
incorporated. Doors are secured
SWITCH GEAR
CLASSIFICATION OF CIRCUIT BREAKERS:
Based on Voltage
Low Less than 1kV
Medium 1kV to 52 kV
High/extra high 66kV to 765 kV
Ultra high above 765 kV
Based on location
In door
Out door
SWITCH GEAR
Based on interrupting Media
Air break
Air blast
Bulk oil
Minimum Oil
SF6 Gas Insulated
Vacuum
SWITCH GEAR
SWITCHES: Load break- fault make devices.
Not capable of handling the fault currents
EARTHING SWITCHES: Normally not designed
to break fault current
Features;
a) Independent manual operation. May have
stored energy
b) Inter lock is provided when connected to
circuit main earth
c) Some switches are fitted with anti - flex
handles
SWITCH GEAR
CONTACTORS ; Mechanical switching devices operated other than by
hand. Not capable of breaking the fault current hence fitted with
fuses
Features;
a)
Frequent operations with vacuum interrupter
b)
Are dependent power operated
c)
Withdrawal not possible with contactor ON
d)
Can not be closed until the isolating contacts are fully engaged
e)
Automatic shutters cover the exposed live contacts when
withdrawn
f)
The contactor opens on failure of a single fuse to prevent the single
phasing
g)
In some cases the earthing switch automatically closes on
withdrawal
SWITCH GEAR
Features;
a)
b)
c)
CIRCUIT BREAKERS
SAFETY FEATURES ;
a)
b)
c)
d)
e)
ENCLOSURES
VACUUM TECHNOLOGY
Another media used in metal enclosed
switch gear is vacuum for dielectric
between contacts and cooling the
arcing chamber
NOTE :Vacuum switch gear is the most
commonly used switch gear in systems
up to 65 kV .
VACCUM ARC
General characteristics :
The vacuum arc is really a metal vapor discharge
The vacuum arc is different from general low or high
pressure arcs since the arc forming particles are the
electrons, ions and neutral atoms , derived from the
electrodes itself. ( Contact material )
The base gas pressure here is very low ( vacuum).
Therefore conduction process role is not significant
Vacuum Interrupter
Design aspects;
Interrupter length ( 8-20 mm) depending upon voltage
Contact travel (contact gap) 6 10 mm for 6.6 k.V.
Contact shape
Contact size
Time of travel
Contact Gap
8 to 12 mm
Contact speed
Opening
Closing
Interrupter
Vacuum interrupter
Vacuum testing
Checking VACUUM.
1. Check the pull on moving contact
2.
Demerits
The vacuum interrupter is more expensive
Restriction on rated voltage
High technology involved in designing the
interrupter
Loss of vacuum will render the switch gear
useless
Surge suppresser are required for certain
switching operations
Vacuum Contactor
Capable of millions of operations on load
and overload
Short circuit interruption capability is limited
Back up fuses give the short circuit
protection
Strikers are provided to take care of single
phasing and short circuits
Sustaining power is required ( 110 volt DC on
board )
OPERATING MECHANISM
SPRING MECHANISM
PNEUMATIC MECHANISM
HYDRAULIC MECHANISM
SF6 DYNANAMIC MECHANISM
MOTOR DRIVEN MECHANISM
SYSTEM REQUIREMENTS OF
CIRCUIT BREAKERS
The main function of the circuit breaker is to interrupt short
circuit currents and protect their loads against the effects of
such faults.
This function must be carried out with a high degree of safety
and reliability
Terminal faults
Short line faults
Transformer magnetizing and reactor
currents
Switching of unloaded capacitor banks
Out of phase switching
ROUTINE TESTS
1. Di electric test on the main circuit
2. Di electric test on the auxiliary and control
circuits
3. Measurement of the resistance of the main
circuit
4. Tightness test
5. Design and visual checks.( name plate
details and values )
6. Mechanical operation tests.
( minimum/maximum operating test. At
least five closing opening time and
pressure where applicable)
MODULE 9
REMEDIAL ACTION SCHEME
WHAT IS A FAULT?
WHAT IS FAULT LEVEL?
FAULT ENERGY?
FAULT ENERGY IS MEASURED AS ( I x I x t )
Consequently, the FAULT ENERGY is to be
kept to a minimum level to limit the damage
to plant and more importantly, to
FAULT LEVELS
400
35000
50
275
15000
31.4
132
7500
32
66
2500
21.8
33
1500
26.2
11
500
26.2
6.6
150
13.1
3.3
50
8.8
.415
31
43.0
a)
b)
c)
d)
e)
FAULTS CONTD.
SOLID FAULTS:- These faults occur due
to suddenly the complete break down of
insulation due to external damage
resulting in very high fault currents and an
explosion. Such faults also must be
cleared as rapidly as possible otherwise it
will result in any of the following
consequences;
FAULTS CONTD.
Increased damage at location of the fault
since fault energy = (current)2 x time
Danger to personnel ( arcs and flashes)
Enhanced probability of earth faults
spreading to healthy phases
Higher mechanical and thermal stressing
in all items of the plant carrying the fault
current, particularly in transformers
Sustained voltage dips
FAULTS CONTD.
The incipient faults:- The small faults developing into catastrophic
failure
Passive Faults :- Not really direct faults but may result into
active faults if not attended to:-
FAULTS CONTD.
TRANSIENT AND PERMANENT
FAULTS :- These faults occur mostly
PROTECTION SYSTEM
Protection system provides protection
to the complete electrical system;
From source to the consumers
Maintainer and the operator.
The system also activates alarms and
indicates the cause of the faults and
abnormalities
PROTECTION SCHEME
5-S principles
;-
PROTECTION SYSTEM
Protection System includes the : Generator Protection
Switch Board Protection
Feeder Protection
Transformer Protection
Motor protection
The CT performance can be improved by Using a core of very high permeability and low
hysteresis loss
Maintaining the rated burden (load)
Ensuring a minimum length of flux path
Lowering the internal secondary burden
Use of wound type primary
Keeping the secondary burden to minimum
possible value
PARAMETERS OF INSTRUMENT
TRANSFORMERS
CURRENT RATING
RATED BURDEN
ACCUEACY CLASS FOR PROTECTION CT,s ( 5P,10P,15P.)
INSTRUMENT SECURITY FACTOR (In case of short circuit)
KNEE POINT VOLTAGE
Knee point; The point on the magnetization curve at which 10%
increase in flux density causes a 50% increase in exciting
ampere turns
Sequence Components:
1. Positive sequence, caused by locked rotor
2. Negative sequence, caused by current imbalance
3. Zero sequence, caused by earth faults
SURGE PROTECTION
FUSES
PRACTICAL EXAMPLE OF
HRC FUSE SELECTION AND
DISCRIMINATION
SURGE PROTECTION
SURGE; A transient over voltage steeply rising
followed by slowly decaying voltage wave
SURGE PROTECTION
TYPES OF SURGE PROTECTION CONNECTED TO ANY SYSTEM
DEPENDS UPON THE VOLTAGE AND THE INSULATION OF
THE SYSTEM
OIL INSULATED SYSTEM; - This type generally doesnt require
protection due to inherent properties of the oil used.
DRY INSULATED SYSTEM; - Rotating machines, dry core
transformers can not withstand large switching surges. This
type of apparatus requires surge protection
NOTE- SURGE ARRESTER/SUPPRESSORS ARE CONNECTED ON
THE ON LOAD SIDE ,FROM ALL THE THREE PHASES TO
GROUND
SURGE PROTECTION
S0URCE OF
SURGE
TYPE OF
SURGE
PROTECTION
DEVICE
MOUNTING
EXTERNAL
LIGHTNING
INTERNAL
SWITCHING
SURGE ARRESTERS
SUPRESSORS
SURGE PROTECTION
DEVICES USED FOR SURGE PROTECTION;-
1.
2.
FUSES
Simple construction and consistency
Last resort against faults if the protection
system fails
Selecting a right fuse will meet the discrimination
requirement
Excursions of currents can affect the safety factor of a
fuse
TYPES OF FUSES
Semi enclosed or rewire able type
Totally enclosed cartridge
Drop out fuse
HRC fuse ( Used on Medium Voltage )
Striker Fuse ( used with High Voltage contactors)
OPERATION OF A FUSE
There are two distinct periods in blowing of a fuse
RELAYS
MODULE -10
Detect
Discriminate
Disconnect
PROTECTION RELAYS
The most vital component in power safety
system is the PROTECTION RELAY. Senses
the current and voltage
A protective relay is an electrically operated
device designed to :
Sense the identified circuit parameters and
To initiate the disconnection with or without a
warning signal, of the intended part of an
electrical section in case of any abnormal
condition in the installation
Discrimination
Discrimination can be achieved by
one of three methods
Comparison: - The basic principle of such protection is the
zone protection. Incorporates the differential relays
TYPES OF RELAYS
Electromechanical Relays
1 Attracted Armature
2 Moving Coil
3 Induction
4 Thermal
5 Motor operated
6 Mechanical
RELAYS
Most commonly used relays are the
IDMTL relays
Relays may be non directional or
bidirectional and directional
The relays may be typically 1A or 5A
IDMTL characteristics can be adjusted
according to criticality of system
involved like: -
Current setting
For a given current setting as the current
increases the operating time decreases.
British and most of the other standards
require that the relay does not operate below
the 110% setting
For electromechanical over current relays of
1A, the typical settings range as0.5A (50%) to 2A (200%)
1.
2.
3.
4.
Thermal protection
Unbalance protection
Under-current protection
Over-current and earth fault
protection and temperature protection
(RTD)
5. Number of starts
6. Hour run meter
7. Ampere meter
The system on board usually has features as ;1 Data which is required to be viewed/logged
2 Trend graphs ( spread sheets)
3 Define lower and upper limits. Deviation will initiate
alarms/standby system readily available
4 Mimic representation of the system with data and status
5 Archiving of the collected data for reference
6 Comparison
7 Data exchange to/from other units and many more features
including SCADA
APPLICATION OF NUMERICAL
PROGRAMMABLE RELAYS
Functions available
Remote computer/HMI capability
Sequence quantity (positive, negative, zero)
Power ( active, reactive, power factor)
Average, RMS, Peak values
Harmonic quantities
Frequency
Temperature (RTD)
Motor start/stop
Numerical Relay for Motor ProtectionFeature: Self check feature Ability to detect
and correct a failure before the
protection system operate
Data Acquisition System
Memory Testing
Set Point Testing
Watch Dog Timer
HI - MAP RELAYS
Hyundai- Intelligent Measurement and
Protection Relays
PROTECTION FUNCTION
24
25/A
Automatic Synchronizing
27
27B
32
37
40Q
Loss of excitation
46
Reverse phase
47
49
Thermal overload
50BF
Breaker failure
50GN
51LR
Locked rotor
59
59B
59N
64
66
Start inhibit
Protection function
67
67GS/GD
78
78 S
79
Auto Reclosing
81
Frequency supervision
81 B
86
Lock out
87M
Motor differential
87T
Transformer differential
87G
Generator differential
87LD
Line differential
87N
94
95 i
Inrush blocking
- FF
Fuse failure
TRANSFORMERS
INSULATION
Oil, Fluorogas, Nitrogen,
On ships, dry type resin encased transformers are
common
COOLING
Marine transformers are air cooled and placed in
separate well ventilated rooms ( In some cases in
A/C rooms. ( Avoid moisture ingress)
Special protection against surges is integral part of
safety system associated with transformers
Precautions are also taken against shock and vibration
due to heavy seas
TRANSFORMER PROTECTION
High set Over Current :- HSOC [50/51] I >>or inst.-To provide
operation for high levels of fault current associated with primary
side phase /phase faults. Set to be stable for phase to phase faults
on the secondary side. Trip primary and inter trip the secondary
circuit breaker
IDMTL OVER CURRENT:- To provide non directional IDMTL
protection for over current discrimination external to the
transformer as a back up
IDMTL DIRECTIONAL OVER CURRENT:- DOC [67] I > To provide
directional discrimination protection for over current external to
the transformer in the opposite direction to the normal current
flow.
INTER TRIP:- INT. [94] To inter trip another circuit breaker which
could possibly feed into the fault
DIFFERENTIAL RELAYING (87) Measured difference between the
input and output current initiates the tripping of the breaker
MOTOR PROTECTION
Sequence Components and supply unbalance
Three sequence Components
1.
2.
3.
MOTOR PROTECTION
Although environment and load may affect the life and integrity of the motor by
and large all motors are liable to the same types of failure, namely:Primary cause of motor failure is the EXCESSIVE HEATING
Phase failure
Insulation failure
Motor protection
GENERATOR PROTECTION
INSULATION : Corona in the Armature of generators generating voltages in
excess of 5000 Volts
Insulation failure: a) Excessive temperature
b) Excessive voltage
c) Contamination
d) Physical damage
Inspection:a) Swelling
b) cracking
GENERATOR PROTECTION
STATOR SIDE
The protection installed on generators circuits varies with :The size of the generators
a)
types of prim movers.
Note : -Tripping of the generator circuit breaker should be
accompanied by a complete shut down of the generatorsthat includes the disconnection of field excitation circuit,
shutting of fuel/steam etc.
GENERATOR PROTECTION
ROTOR SIDE :The generator of MVA capacity need rotor protection
as follows :- Rotor Excitation Under Current [ UBC/A/37 ]
Rotor Excitation Under Voltage[ UV 80 ]
Diode Failure Relay
Rotor Earth fault Relay [ 64R ]
Purpose:
Evaluate the condition of the insulation
between the ground and the conductor
IR value measured with Meggar may not be
the actual reliable I/R value.
To obtain the reliable I/R value, P/I and I/R
values are needed
What does the Meggar actually measure ?
Capacitive Current - ic
2.
Conduction Current - il
3.
4.
Polarization current - ip
Capacitive current: ic
Any insulation behaves like a capacitor when
subjected to D. C. voltage
A high charging current will flow through the
capacitor and then it will decay
In case of generators, motors and
transformers the decay time of the current is
less than 10 seconds, however the IR value
is taken for 1 minute
Conduction Current: il
This current is galvanic current which
flows between copper and core
This can happen if the moisture is
absorbed by the insulating material like
thermoplastic or crack in the insulation
or some contamination
This current is constant with time
Polarization Current : ip
Electrical insulation is hygroscopic in nature and
absorbs moisture in low quantity or in excess
Applying D.C. potential (Electric Field) from Meggar
results in the absorption of electrons from the
hydrogen molecules resulting in the ionization of
Hydrogen
The energy (current) required for this to happen
comes from Meggar D.C. voltage
This current is called POLARIZATION CURRENT
Total current It
It = ic + ir + il + ip
After 1 Min. ic = 0 (As analyzed earlier)
So, It after 1 min. it = ir + il + ip
After 10 min. ip is zero ( seen earlier )
So, it after 10 min. = ir + il
Therefore, PI = ir + il + ip / ir + il, = R10/R1
That is .Resistance after 10 min. / Resistance after
1 min
Note : Minimum IR value acceptable = 100 M Ohms with
2500/ 5000 volt Meggar for 1 min.
Interpretation of PI value
PI
Condition of winding
Measure to be taken
< 1.0
Hazardous
Dry winding
1-1.5
Bad
Dry winding
1.5-2
Doubtful
Drying recommended
2.0-3.0
Adequate
3.0-4.0
Good
>4.0
Excellent
Discharge Stick
2.
3.
4.
6.
7.
8.
9.
10.
11.
on the ship and the Electrical power system under his control. The C/E
should have sufficient Electro technical knowledge and experience to
recognize and avoid danger and fully familiar with STASCO SMS
Chief engineers may delegate part or the whole of their electrical role,
including authority for issuing electrical safety document, to others at
their discretion but in doing so retains personal responsibility
Definitions contd.
Definitions contd.
B.
C.
PMS
An overview and salient features
Power management is a group of functions
Design of power management system and power
plants installed on ship types
Black out prevention system
Minimization of fuel consumption and operation
Power redistribution control
Integrated net work power control
Speed control of generators and motors
PMS
Functions
Generator allocation. Compare the total demand with
the available power
Auto start / stop of generators to consider with the
load changes as per pre calculated load dependent
start /stop table
Transient frequency deviation limit
Under frequency limit will trip the circuit breaker of
an on line generator resulting in a black out
PMS
Load limiting features
Types of consumers
Sheddable loads; All non essential loads can be
regarded as sheddable loads
Non sheddable loads; Consumers with high
importance of supplying the energy eg; Nav. aids
and control net work etc.
Controllable consumers; thrusters, compressors etc.
Non controllable loads; switch ON /OFF
PMS
There are consumers that rely on power rather than
Energy. These can operate with reduced power for
limited time ( HVAC, HEATERS)
There are consumers which rely on POWER. These
consumers need full power all the time ( controllers,
control equipment, Nav. aids)
PMS
Black out prevention control
Electrical Causes of black out
Short circuit
Earth fault
Overload
Sharing of KW and KVAR load
PMS
SUMMARY
The plant definition phase: Tighter dimensioning and thus reduced
costs
Plant start up: The PMS will ensure the power system capacity is not
violated at any time by holding load start command until the system
can provide the required power. This helps the plant safety
All phases of plant operation: The PMS will control all generators,
transformers and motors to ensure stable power system operation as
well as monitoring and controlling active and reactive power with
other generators running in parallel
Maintenance planning: Comprehensive data are recorded and
aggregated on the conditions of the electrical power plant. The data
can be monitored automatically and responsible person can be
notified
PMS
Non Electrical causes
Temperature
Pressure
Level
Rpm
Criterion
Without exceeding the safety limits.. means;
Healthy elements should remain in operation
Available generator on line
Available standby generator
Available fuel supply
The reserve or standby power should be able to
accommodate the new operational situation
Situation? The fault has happened to a particular
section or part of a plant
Criterion
Situation
Active power available
Alert state System operating normally but a
contingency is detected
Section control. Frequency
Black out state
Exceptional contingency. Fault on generator /
transformer or DC line failure
Short circuit / Open circuit
Components of RAS;
Load shedding
Harmonic domain analysis in
case of electronic switching
devices
Thermal problems caused
harmonic frequency leakage
Components of RAS
EXERCISES