DAYTON VAMC

PLAN NOTES
1.- REMOVE EXISTING RECESSED MOUNTED STEAM CONVECTOR AND
ASSOCIATED PIPING. PATCH FLOORS TO MATCH EXISTING THROUGHOUT.
2.- REMOVE EXISTING AIR HANDLING UNIT AND ASSOCIATED CONTROLS.
3.- REMOVE ALL EXISTING DUCTWORK ASSOCIATED WITH AIR HANDLER TO RISER.
4.- REMOVE EXISTING LOUVER AND DAMPER. OUTSIDE AIR DUCT SIZE 12"X12".
5.- REMOVE EXISTING STEAM AND CONDENSATE PIPING BACK TO MAIN. PIPING
TO BE REPLACED FROM MAIN DISTRIBUTION LINE.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

6.- EXISTING LOW AND MEDIUM PRESSURE PRESSURE REDUCING (PRV) STATION
SHALL BE REMOVED AND REPLACED WITH NEW. MEDIUM PRESSURE PRV
STATION IS NOT PRESENT, ALTHOUGH THE ASSOCIATED PIPING FOR THIS
SYSTEM SHALL BE REMOVED BACK TO THE MAIN LINE AND CAPPED AND
SEALED. THE EXISTING LOW PRESSURE PRV'S SHALL BE DISCONNECTED BACK
TO A POINT AT WHICH THE NEW PRV STATION CAN BE INSTALLED AND
REPIPED TO THE EXISTING LOW PRESSURE SYSTEMS.
7.- REMOVE VISIBLE SURFACE CONTAMINANTS AND DEPOSITS FROM WITHIN THE
HVAC SYSTEM. SYSTEM AND COMPONENTS TO BE CLEANED: AIR DEVICES SUPPLY AND RETURN, SUPPLY AIR DUCTWORK, RETURN AIR DUCTWORK.
DUCTWORK FROM MECHANICAL ROOM LEVEL UP TO THE CONNECTING
CORRIDOR BETWEEN BUILDING 409 AND 305. ASSUME APPROXIMATELY 150
FEET OF SUPPLY AIR DUCTWORK AND 45 FEET OF RETURN AIR DUCTWORK.
DUCTWORK IS TO BE CLEANED IN ACCORDANCE WITH THE NATIONAL AIR
DUCT CLEANERS ASSOCIATION DOCUMENT (NADCA) ACR 2006. UTILIZE
MECHANICAL CLEANING METHODOLOGY WHICH INCLUDES CONTINUOUS
NEGATIVE PRESSURE HEPA FILTRATION COLLECTION EQUIPMENT ON THE
DUCTWORK TO COLLECT DEBRIS, AND MECHANICAL AGITATION DEVICES TO
DISLODGE DEBRIS THAT IS ADHERED TO THE INTERIOR SURFACES OF THE HVAC
SYSTEM COMPONENTS. ENSURE CLEANING METHODS SHALL NOT DAMAGE
THE INTEGRITY OF HVAC SYSTEM COMPONENTS. ALL SYSTEM COMPONENTS
SHALL BE VISIBLY CLEAN.

IC

DS

556-4098

BASEMENT
HVAC
DEMOLITION PLAN

HVAC DEMOLITION PLAN BASEMENT


SCALE: 1/8"=1'-0"
NORTH

M100
02-21-2011

1/8" = 1'-0"

TECHNICIAN
OFFICE
101

TECHNICIAN
OFFICE
148

5
3

103

104

104A

105

106

107

109

CORRIDOR
.

138

139

140

141

142

C-1-3

4
149
150

103A

109A

142A

SOLARIUM

110
CORRIDOR

CORRIDOR

CORRIDOR

C-1-2

thinkchamplin.com

C-1-4

EXISTING SPACE TO REMAIN

C-1-3

H.A.C.

H.A.C.

H.A.C.

130

.
127

114

118
.

3 4

126

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

117

118

.
131

STAIR
SW3

119

TOILET
116

WASH ROOM

115

113

112

111

SHOWER &
BATH
115A
.

117A

110A

(CONV)E

CORRIDOR

C-1-3

120

S
6 7
.
.

123

121

DAYTON VAMC

8
.

137

137

PLAN NOTES

122A

1.- REMOVE EXISTING WALL MOUNTED STEAM CONVECTOR AND ASSOCIATED


PIPING. PIPING TO BE REMOVED BACK TO THE MAINS FROM EACH
CONVECTOR UNIT. CAP AND SEAL LINES AT MAIN. PATCH FLOORS TO MATCH
EXISTING THROUGHOUT.

138

2.- REMOVE EXISTING ELECTRIC BASEBOARD HEATER AND ASSOCIATED


CONTROLS. ELECTRIC SERVING HEATER TO BE REMOVED, SEE ELECTRICAL
DRAWINGS FOR FURTHER INFORMATION.

3.- REMOVE EXISTING DUCTWORK.

135A

4.- REMOVE EXISTING GRILLES AND DIFFUSERS.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

CORR

5.- REMOVE ENTIRE BRANCH DUCT FROM FIRST TO THIRD FLOOR.

C-1

6.- REMOVE EXISTING EXHAUST FAN AND ASSOCIATED CONTROLS.

DINING ROOM

8
7.- PATCH WALL TO MATCH EXISTING.

122
SOLARIUM

8.- REMOVE EXISTING RECESSED MOUNTED STEAM CONVECTOR AND


ASSOCIATED PIPING. PIPING TO BE REMOVED BACK TO THE MAINS FROM
EACH CONVECTOR UNIT. CAP AND SEAL LINES AT MAIN. PATCH FLOORS TO
MATCH EXISTING THROUGHOUT.

134

133

132

131

9.- REMOVE ENTIRE BRANCH DUCT AND ASSOCIATED GRILLES ON THIS LEVEL.
BRANCH DUCT TO BE REMOVED FROM FIRST FLOOR TO THIRD FLOOR.

H.A.C.
122B

IC

STOR.
122C

DS

556-4098

LEVEL 1
HVAC
DEMOLITION PLAN

HVAC DEMOLITION PLAN LEVEL 1


SCALE: 1/8"=1'-0"
NORTH

M101
02-21-2011

1/8" = 1'-0"

2
2

244

245

246

247

247A

248

202

202A

203

204

205

206

201

CORRIDOR

CORRIDOR

C-2-3

C-2-1

236

STAIR

201A

202B

SW2

208A

.
216

234

232

SHOWER AND
BATH
235a

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

213
TOILET
215

233A

WASH ROOM
SHOWER &
BATH
214A

212

211

216A

SHOWER &
BATH
218

214

217

STAIR

thinkchamplin.com

TOILET

209

C-2-4

233

235

SOLARIUM

CORRIDOR

231

.
WASH ROOM

237

H.A.C.

2
2

218A

SW3
2

.
TOILET

229

219
2

DAYTON VAMC
.
228

.
220

PLAN NOTES

.
.

241

243

244

1.-REMOVE ENTIRE BRANCH DUCT FROM FIRST TO THIRD FLOOR.

226

2.- EXISTING SUPPLY AND RETURN STEAM RISERS SERVING FLOOR ABOVE. RISERS
AND ASSOCIATED PIPING THAT SERVES THE THIRD FLOOR SHALL BE REMOVED
ENTIRELY. RISERS SHALL BE REMOVED BACK DOWN TO THE FLOOR BELOW IF
NO ADDITIONAL STEAM CONNECTIONS SERVING THIS FLOOR EXISTS ABOVE
THE SECOND FLOOR LEVEL.

STAIR

SW1

248AA
SOLARIUM

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

240
.
225

239

238

.
221

23
DAYROOM
222

STAIR
SW4

KITCHEN
NOURISHMENT
223

IC

DS

556-4098

LEVEL 2
HVAC
DEMOLITION PLAN

HVAC DEMOLITION PLAN LEVEL 2


SCALE: 1/8"=1'-0"
NORTH

M102
02-21-2011

1/8" = 1'-0"

(CONV)E

(CONV)E

301B

301D

301E

(CONV)E

1
1

1
(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

344

345

346

347

347A

302

302A

303

304

305

306

308

309

1
.

STORAGE

347AA

301

301A

(CONV)E

.
STAIR

302B

2.

SW2
.

308A
(EF)E

301E

(EF)E
1

CORRIDOR

CORRIDOR
CORRIDOR

C-3-3

C-3-4

309A

C-3-1
.

332A

336

STOR.

H.A.C.

(EF)E
317A

331

313

TOILET
315

337

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

H.A.C.

thinkchamplin.com

.
(CONV)E

WASH ROOM

TOILET

B.P.S.

335

334

333

332

317

316

(CONV)E

WASH ROOM
314
SHOWER &
BATH
314A

SHOWER &
BATH
335A

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

(CONV)E

312

311A

311

310

309B

(CONV)E

(CONV)E
(CONV)E

(CONV)E
.

BATH

317

318

(CONV)E

TOILET

(CONV)E

328

319

(CONV)E

(EF)E

1
4

(EF)E

(EF)E

2 3

1
4

(CONV)E

1
1

1
2 3

CORRIDOR

(EF)E

C-3-2

DAYTON VAMC
(CONV)E

327
.
320

PLAN NOTES

.
.

340B

343

326

1.- REMOVE EXISTING WALL MOUNTED STEAM CONVECTOR AND ASSOCIATED


PIPING. PIPING TO BE REMOVED BACK TO THE MAINS FROM EACH
CONVECTOR UNIT. CAP AND SEAL LINES AT MAIN. PATCH FLOORS TO MATCH
EXISTING THROUGHOUT.
2.- REMOVE EXISTING EXHAUST SYSTEM (INCLUDING DUCTWORK, FANS, GRILLES,
CONTROLS) ASSOCIATED WITH THIS ROOM.

STAIR

SW1

341A

325

321

3.- REMOVE EXISTING EXHAUST FAN AND PATCH WALL TO MATCH EXISTING.
4.- REMOVE EXISTING EXHAUST FAN AND REPAIR WINDOW TO MATCH EXISTING.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

.
340A

.
324
.

340

338A

338

337

DAYROOM
322

STAIR
SW4

.
323

IC

DS

556-4098

LEVEL 3
HVAC
DEMOLITION PLAN

HVAC DEMOLITION PLAN LEVEL 3


SCALE: 1/8"=1'-0"
NORTH

M103
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

4
6"x8"

6"x8"

8.2
8

12"x28"

7.5
12"x20"

12"x28"

12"x20"

7
6.8

10"x8"

4
4

thinkchamplin.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

5
2
3

5
6"x6"

4
6

A
T

6"x8"

DAYTON VAMC

9
5

PLAN NOTES
1.- REMOVE EXISTING DUCTWORK.
2.- PATCH WALL OPENING TO MATCH EXISTING.

3.- REMOVE EXISTING EXHAUST FAN AND ASSOCIATED DUCTWORK.


4.- REMOVE EXISTING EXHAUST DUCT RISER FROM ATTIC TO FIRST FLOOR. PATCH
ALL OPENINGS DUE TO EXISTING DUCTWORK REMOVAL TO MATCH EXISTING.
5.- REMOVE EXISTING LOUVER AND PREPARE EXISTING OPENING FOR
INSTALLATION OF NEW LOUVER.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

6.-REMOVE EXISTING WINDOW-MOUNTED EXHAUST FAN AND ASSOCIATED


CONTROLS.
5
7.- PATCH FLOOR OPENING TO MATCH EXISTING.

IC

DS

556-4098

HVAC DEMOLITION PLAN LEVEL 4


SCALE: 1/8"=1'-0"
NORTH

LEVEL 4
HVAC
DEMOLITION PLAN

M104
02-21-2011

1/8" = 1'-0"

DN

M.1

8.3

UP

DN

UP

FC-1

041

DN

H.9

9
001

CUH-1
3
C-B-1

SW2

040B

040A

UP

8.2
8

12

thinkchamplin.com
8"x8"
10"x8"

7.5

C-B-4

C-B-7

C-B-6

7
DN

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

6.8

22"x10"
C-B-2

11

B
B

5
18"x10"

AH-1

UP

15

B
6

13

12

SW3

6.1

L-10
9 24"x42"

10
028

1
C-B-8

18"x14"

UP

14

A
M200
7

D
D

R
R

A
D

R
4

DAYTON VAMC

5
SW1B

GENERAL NOTES

10'-1"

A.- CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING AND CONDUIT AS


NECESSARY TO ALLOW FOR INSTALLATION OF NEW DUCTWORK.

18"X14"

8"x10"

PLAN NOTES

SW1

4
UP

SOUTH WING A-SECTION DETAIL


SCALE: 1/8"=1'-0"
C-B-5

C-B-4

8'-312"

7'-112"

1.- 18" X 14" EXHAUST DUCT UP TO FLOOR ABOVE.


8'-312"

6'-1112"

10"

10"x14"

2.- 18" X 14" SUPPLY DUCT UP TO FLOOR ABOVE.


3.- DUCT FOR FUTURE EXHAUST FOR GENERAL OFFICE SHELL SPACE, CAP AND
SEAL AIRTIGHT.
4.- DUCTWORK SHALL BE ROUTED BENEATH BEAM. KEEP DUCTS TIGHT TO
STRUCTURE ABOVE ALONG BEAM SECTION AND THROUGHOUT CORRIDOR
SECTION.
5.- UNIT TO BE MOUNTED IN MECHANICAL SPACE. SUSPEND UNIT FROM
STRUCTURE ABOVE. UNIT SHALL BE ASSEMBLED IN MECHANICAL SPACE.
CONTRACTOR SHALL INCLUDE IN HIS PRICE ALL LABOR AND EQUIPMENT TO
DISASSEMBLE, TRANSPORT, AND RE-ASSEMBLE UNIT IN MECHANICAL SPACE.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

6.- FURNISH AND INSTALL MOTORIZED DAMPER AND WIRE TO OPEN WHEN AH-1
FAN OPERATES.
7.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 900 CFM FRESH AIR FUTURE
CAPACITY.
8.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 855 CFM EXHAUST AIR FUTURE
CAPACITY.

9.- LOUVER SIZE SHOWN FOR BIDDING PURPOSES ONLY . VERIFY EXISTING
WINDOW OPENING SIZE AND SIZE NEW LOUVER TO FIT IN OPENING.
10.- BALANCE MANUAL DAMPER TO 1,400 CFM.
11.- DUCTWORK TO BE COORDINATED WITH EXISTING PIPING AND CONDUITS
WITHIN SPACE. RUN DUCTWORK AS HIGH AS POSSIBLE IN THIS AREA. WHERE
DUCTWORK DROPS DOWN AGAINST NORTH WALL, KEEP TIGHT TO NORTH
WALL.
12.- DUCTWORK TO BE ROUTED ACROSS PIPING CHASE BELOW BASEMENT LEVEL
IN CRAWLSPACE. COORDINATE DUCT WORK WITH EXISTING PIPING
THROUGH THIS CHASE. KEEP DUCTWORK AS TIGHT TO BASEMENT FLOOR
LEVEL AS POSSIBLE TO MAXIMIZE HEAD ROOM IN CRAWL SPACE.

13.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 1250 CFM FRESH AIR FUTURE
CAPACITY.
2

14.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 1180 CFM EXHAUST AIR
FUTURE CAPACITY.
15.- PROVIDE AND INSTALL FIRE DAMPERS AT FLOOR LEVEL OF EXISTING SHAFT.

IC

DS
DN

556-4098

ROOM SCHEDULE
NO.

NAME

VA NO.

VA NAME

001

UNOCCUPIED

028

STORAGE

001CW

STORAGE

040A

ELECT RM

000WW

ELECTRICAL

040B

COMM RM

001WW

COMMUNICATIONS

041

ENTRY

000CW

VESTIBULE

BASEMENT
HVAC DUCT PLAN

HVAC DUCT PLAN BASEMENT


SCALE: 1/8"=1'-0"
NORTH

M200
02-21-2011

1/8" = 1'-0"

M.1

8.3

DN

Prntr

Camera
FC-2

H.9

DN

CUH-2

Copy

101
TV

144
9
DN

Files

135 CFM
6"

102

C-1-1

FC-4

FC-1
Brochures

14"X10"

UP

SW2

8.2

FC-4

143
8
102A

14"X10"

NOT IN SCOPE

24"X8"

thinkchamplin.com
7.5

C-1-3

C-1-2

7
125

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

6.8

102B

WHITEBOARD

10"X8"

125A

80 CFM
8"

E2
45

4
DN

120A
118

UP

E2
345

6
6.1

SW3

120

14"X10"
1
B

WHITEBOARD
B

305 Connector

FC-5

A
M201

OVERHEAD
PROJECTOR

E2
380

630 CFM

A.- CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING AND CONDUIT AS


NECESSARY TO ALLOW FOR INSTALLATION OF NEW DUCTWORK.

8"

123

FC-7

202 CFM

122G

9
DN

GENERAL NOTES

C-1-4

DN
PROJ
SCREEN

121

16"X12"

20"X12"

190 CFM

20"X10"

12"
20"X15"

FC-8

24"X10"

DAYTON VAMC

8"

114 CFM

PLAN NOTES
1.- 36" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 18" X 14" EXHAUST DUCT
DOWN TO 1ST FLOOR.
2.- 36" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 18" X 14" SUPPLY DUCT DOWN
TO 1ST FLOOR.

MOUNT FAN COIL AS


HIGH AS POSSIBLE

36"X14"

24"X10"

8"
3.- 28" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 22" X 10" EXHAUST DUCT
DOWN TO 1ST FLOOR.

MOVEABLE PARTITION

24"X8"

CEILING HEIGHT
8"

TYP.

FC-6

7.5

7
6.8

FC-5

15"X10"

18"X14"

4.- 28" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 22" X 10" SUPPLY DUCT DOWN
TO 1ST FLOOR.
5.- DUCT FOR FUTURE EXHAUST FOR FIRST FLOOR EAST SHELL SPACE. SIZED FOR
APPROXIMATELY 1150 CFM.
6.- DUCT FOR FUTURE SUPPLY FOR FIRST FLOOR EAST SHELL SPACE. SIZED FOR
APPROXIMATELY 1210 CFM.

OVERHEAD
PROJECTOR

SOUTH WING A-SECTION DETAIL

TYPICAL

SCALE: 1/8"=1'-0"
PROJ
SCREEN

123A

20"X12"

14"X10"

8.2

TYPICAL

14"X10"

SCOPE OF WORK

UP

22"X15"

122

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

111 CFM
FC-6

FC-7

8"
203 CFM
60 CFM

8"
WHITEBOARD

6"
24"X8"
SW4

24"X8"

10"X8"

C-1-6
122A
WHITEBOARD

14"X10"

UP

8"

FC-6

FC-4
185 CFM
8"

10"X14"

120 CFM

ROOM SCHEDULE
NO.

NAME

VA NO.

24"X8"
122B

14"X10"

122D

VA NAME
1

101

VESTIBULE

100CW

VESTIBULE

102

WAITING

102CW

WAITING

102A

RECEPTION

102CW

102B

REGISTER

133EW

118

CONFERENCE #4

132EW

CONFERENCE

120

MEN

104CW

MEN

120A

JAN

103CW

HAC CLOSET

121

WOMEN

105CW

WOMEN

122

CYBER CAFE

106CW

CAFE

122A

VENDING

107CW

VENDING

122B

EMPLOYEE DINING

108CW

DINING

122D

CONFERENCE 3

109CW

CONFERENCE

122G

CANTEEN

123

CONFERENCE 1

111CW

CONFERENCE

123A

CONFERENCE 2

110CW

CONFERENCE

125

COMM RM

112CW

COMMUNICATIONS

125A

ELECT RM

100WW

ELECTRICAL

143

ENROLLMENT

113CW

144

PBS/STAFF

114CW

FC-5

C-1-5

IC

DS
410 Connector

556-4098

LEVEL 1
HVAC DUCT PLAN

HVAC DUCT PLAN LEVEL 1


SCALE: 1/8"=1'-0"
NORTH

M201
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

UP

DN

SW2

8.2
8

thinkchamplin.com
7.5

C-1-4

C-2-4
7
F.E.

231

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

6.8

3
231A

4
C-2-2
UP

DN

6.1

SW3

Q
8

DAYTON VAMC

PLAN NOTES
1.- 46" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 36" X 14" EXHAUST DUCT
DOWN TO 1ST FLOOR.

DN
UP

2.- 48" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 36" X 14" SUPPLY DUCT DOWN
TO 1ST FLOOR.

3.- 28" X 20" EXHAUST DUCT UP TO FLOOR ABOVE. 28" X 14" EXHAUST DUCT
DOWN TO 1ST FLOOR.

STAIR-2

4.- 28" X 18 SUPPLY DUCT UP TO FLOOR ABOVE. 28" X 14" SUPPLY DUCT DOWN
TO 1ST FLOOR.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

5.- DUCT FOR FUTURE EXHAUST FOR SECOND FLOOR EAST SHELL SPACE. SIZED
FOR APPROXIMATELY 1150 CFM.
6.- DUCT FOR FUTURE SUPPLY FOR SECOND FLOOR EAST SHELL SPACE. SIZED
FOR APPROXIMATELY 1210 CFM.
7.- DUCT FOR FUTURE EXHAUST FOR SECOND FLOOR SOUTH SHELL SPACE. SIZED
FOR APPROXIMATELY 1250 CFM.
8.- DUCT FOR FUTURE SUPPLY FOR SECOND FLOOR SOUTH SHELL SPACE. SIZED
FOR APPROXIMATELY 1350 CFM.
3

SW4
UP

DN

IC

DS

556-4098

LEVEL 2
HVAC DUCT PLAN

ROOM SCHEDULE
NO.

NAME

VA NO.

VA NAME

231

COMM RM

200CW

COMMUNICATIONS

231A

ELECTR

200WW

ELECTRICAL

HVAC DUCT PLAN LEVEL 2


SCALE: 1/8"=1'-0"
NORTH

M202
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

FC-4

348

48"X10"

FC-7

18"X8"

30"X10"
3

FC-1

50 CFM 301A
FC-4

130 CFM
8"

FC-1

FC-1

FC-1

FC-1

FC-1

304

FC-1

14"X6"
24"X8"

302

303

302B

302A

303A

307
308

FC-6

304A

305A

305

24"X8"
6"

55 CFM
6"

30"X10"

DN

8"X8"
10"x8"

30"X10"

8"x6"

FC-1

12"x10"

14"x10"

3
6"

14"X12"

6"
80 CFM

301 30"X10"

FC-6

FC-1

SW2
C-3-4

50 CFM

8"
6"

12"X8"

FC-8

22"X6"

6"

90 CFM

FC-8

6"

90 CFM

FC-8

48"X10"

48"X10"

8"x6"
313

140 CFM

7.5

48"X10"

C-3-4

317

14"X12"

310

316

331A

3
331

90 CFM

18"X8"

18"X8"

18"X8"

48"X10"

10"X8"

14"x10"
7

314

315

FC-8

18"X8"

318A E2

45

FC-1

DN

12"x8"

D
U

14"X20"

FC-1

FC-2

312

6.1

E2
345

SW3

thinkchamplin.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

FC-3
3

C-3-1

6.8

313A

24"X10"

UP

8.2

309

306

311

318

12"X14"
12"

A
M203

20"X14"

630 CFM
328

14"X12"
FC-5

319

30"X10"

327

20"x10"

12"x8"

15"x10"

E2
380

DAYTON VAMC

GENERAL NOTES
4
A.- CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING AND CONDUIT AS
NECESSARY TO ALLOW FOR INSTALLATION OF NEW DUCTWORK.

C-3-5
DN

PLAN NOTES

4
8.2

1.- 60" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 46" X 14" EXHAUST DUCT
DOWN TO 2ND FLOOR.

MOUNT FAN COIL AS


HIGH AS POSSIBLE

2.- 62" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 48" X 14" SUPPLY DUCT DOWN
TO 2ND FLOOR.

7.5

3.- PROVIDE BALANCE DAMPER IN DUCT EXTENSION FOR FINAL BALANCE.


CEILING HEIGHT

14"X20"

4.- DUCT FOR FUTURE EXHAUST FOR THIRD FLOOR SOUTH SHELL SPACE. SIZED
FOR APPROXIMATELY 700 CFM.

14"X12"
FC-5

5.- DUCT FOR FUTURE SUPPLY FOR THIRD FLOOR SOUTH SHELL SPACE. SIZED FOR
APPROXIMATELY 730 CFM.

6.8

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

6.- 28" X 20" EXHAUST DUCT UP TO FLOOR ABOVE. 28" X 20" EXHAUST DUCT
DOWN TO 2ND FLOOR.
3

SOUTH WING A-SECTION DETAIL

7.- 28" X 20 SUPPLY DUCT UP TO FLOOR ABOVE. 28" X 18" SUPPLY DUCT DOWN
TO 2ND FLOOR.

SCALE: 1/8"=1'-0"

ROOM SCHEDULE
NO.

NAME

VA NO.

VA NAME

DN

301

WAITING

300EW

PATIENT BUSINESS
SERVICES

301A

BREAK ROOM

301EW

BREAK ROOM

302

PRIVACY OFFICER

302EW

OFFICE

302A

TUMOR REGISTRY

303EW

OFFICE

302B

CODING SUPERVISOR

304EW

OFFICE

303

TRAINER

305EW

OFFICE

303A

COMPUTER
COORDINATOR

306EW

OFFICE

304

RELEASE TECHS

308EW

OPEN OFFICE

304A

RELEASE SUPERVISOR 307EW

OFFICE

305

STORAGE

309EW

STORAGE

310EW

OFFICE
ELECTRICAL

305A
306

ELECTR

311EW

307

SCANNING STAGING

313EW

308

PBS CHIEF

314EW

OFFICE

309

ADMINISTRATIVE
ASSISTANT

315EW

OFFICE

310

ASSISTANT

316EW

OFFICE

311

CHIEF OF HIMS

317EW

OFFICE

312

SCANING TECHS

318EW

OPEN OFFICE

313

WORK ROOM

312 EW

OFFICE

313A

CORRIDOR

CHIEF

IC

DS

556-4098

314

319EW

OFFICE

315

320EW

OFFICE

316

FEE BASIS TECHS

317

CODING TECHS

321EW

OFFICE

317A

RECEPTION

322EW

RECEPTION

318

MEN

301CW

MEN

318A

JANITOR

300CW

HAC CLOSET

319

WOMEN

302CW

WOMEN

327

STORAGE

303CW

STORAGE

328

STORAGE

304CW

STORAGE

331

COMM RM

300WW

COMMUNICATIONS

331A

ELECTRICAL

301WW

ELECTRICAL

348

CONFERENCE

305CW

CONFERENCE

LEVEL 3
HVAC DUCT PLAN

HVAC DUCT PLAN LEVEL 3


SCALE: 1/8"=1'-0"
NORTH

M203
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

L-5
42" 1

D
M204

C
M204

L-2
48" 1

18"x18"

20"x22"

8.2

EXH OUT
DOAS-X
OA

SA
9

28"x20"

EXH IN
OA
DOAS-2 4 5
SA
EXH OUT

EXH IN

28"x20"

7.5
3

L-6
48" 1

7
6.8

28"x20"
6

28"x20"

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

18"x18"

2 8

thinkchamplin.com

28"x20"

2 8

7
L-1
30"x60"

62"x14"

60"x14"

L-4
42" 1

A
T

DAYTON VAMC

3
D

EXIST. SPR. LINE (TYP.)

L-5
42"

30"x25"

30"x25"

30"x25"

10

30"x25"

DOAS-1

30"x25"

SOUTH WING A-SECTION DETAIL


SCALE: 1/8"=1'-0"

SA

EXH IN

3.-COORDINATE ALL DUCTWORK INSTALLATION IN ATTIC AND PENTHOUSE WITH


EXISTING SPRINKLER PIPING.
A
M204
EXIST. SPR. LINE (TYP.)

L-6
48"

DOAS-1
4 5

10

30"x25"

30"x25"

SOUTH WING B-SECTION DETAIL

OA

EXH OUT

DOAS-1

30"x25"

4.-AIR HANDLER MUST BE DISASSEMBLED AS NECESSARY TO TRANSPORT UNIT TO


ATTIC SPACE, THEN RE-ASSEMBLED IN ATTIC SPACE. CONTRACTOR SHALL
INCLUDE IN HIS PRICE ALL LABOR AND MATERIALS AS NECESSARY TO
DISASSEMBLE, TRANSPORT, AND RE-ASSEMBLE UNIT IN ATTIC. AIR HANDLER
MANUFACTURER'S REPRESENTATIVE SHALL SUPERVISE, APPROVE, OR
PERFORM (AT THE DESCRETION OF UNIT MANUFACTURER) ALL
DISASSEMBLING AND RE-ASSEMBLING OF UNIT.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

5.-RUN 1-1/2" AC CONDENSATE DRAIN PIPING FROM AIR HANDLER TO NEAREST


FLOOR DRAIN.
6.-INSTALL ALL DUCTWORK IN ATTIC AND PENTOUSE WITH TOP OF DUCT AT MIN.
24" BELOW ALL SPRINKLER HEADS.

SCALE: 1/8"=1'-0"
7.-INSTALL DRAIN IN BOTTOM OF LOUVER PLENUM AND RUN 1" INSULATED
DRAIN PIPE TO NEAREST FLOOR DRAIN.

8.- COORDINATE CLOSELY WITH REFRIGERANT PIPING, SO THAT BOTH


DUCTWORK AND REFRIGERANT PIPING HAVE ACCESS TO THE CHASE BELOW
ON THE THIRD FLOOR.

B
M204
3

9.- FOOTPRINT FOR FUTURE UNIT TO SERVE ALL ADDITIONAL FLOORS. SHOWN
FOR REFERENCE ONLY (NOT INCLUDED IN CONTRACT).

10

1.-LOUVER SIZE SHOWN IS FOR BIDDING PURPOSES ONLY. CONTRACTOR TO


FIELD-VERIFY EXISTING OPENING SIZE AND SIZE NEW LOUVER TO MATCH
EXISTING OPENING SIZE.
2.-PROVIDE FIRE DAMPERS AT ALL DUCT ATTIC FLOOR PENETRATIONS.

4
D

PLAN NOTES

6
L-4
42"
28"x20"

10.- PROVIDE AND INSTALL NEW LOUVERS IN THESE LOCATIONS TO MATCH


EXISTING LOUVERS INSTALLED ON EAST WING. LOUVERS ARE SHOWN WITH
FLOW PARAMETERS FOR GUIDELINES, NOTHING WILL BE CONNECTED TO
LOUVERS IN ATTIC SPACE. PROVIDE INSULATED BLANK-OFF PLATES ON ATTIC
SIDE OF LOUVERS FOR FUTURE CONNECTION TO DOAS-X.

28"x20"

DOAS-2

EAST WING C-SECTION DETAIL


SCALE: 1/8"=1'-0"

1
L-3
48" 1
28"x20"

IC
28"x20"
DOAS-2

EAST WING D-SECTION DETAIL


SCALE: 1/8"=1'-0"

DS

556-4098

LEVEL 4
HVAC DUCT PLAN

HVAC DUCT PLAN LEVEL 4


NORTH

SCALE: 1/8"=1'-0"

M204
02-21-2011

1/8" = 1'-0"

DN

M.1

8.3

UP

H.9

UP

DN

041

DN

FC-1
1-1/4"
11

041

1"
11
9

4
001

CUH-1
18
1"

C-B-1

T
1
SW2

2
040B

040A

UP

8.2
8

15

PRV-4

19

18

PRV-3

1"

18
1-1/4"

2"

thinkchamplin.com
7.5

15 PSI

C-B-4

C-B-7

C-B-6

12
7

PRV-2

15 PSI

13

PRV-1 12

26

DN

3"
CP-1

C-B-2

V
17

27

14
AH-1

6.8

28

26
29
C

RS RD
RS RD RL
RL
RL RHGBP
RS

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

RS RHGBP

RL

UP

SW3

1-1/4"

6.1

21

16

028

20
1"
2-1/2"

11

1-1/2"
C-B-8

UP

22

23

24

25

PIPING PLANS GENERAL NOTES


RL RD
RS
RS RD
RL

SW1B

A. SLOPE ALL COOLING COIL CONDENSATE DRAIN PIPING AT MIN. 1/10 SLOPE IN
DIRECTION OF FLOW

RL RHGBP
RS RHGBP RS
RL

B. ALL VRV SYSTEM REFRIGERANT PIPING TEES ARE TO BE REFNET JOINTS. REFNET
JOINTS TO BE MIN. 40" FROM EACH OTHER.
10
6

C. SEE PIPING SCHEMATICS ON SHEETS M503 AND M504, FOR VRV SYSTEM
REFRIGERANT PIPE SIZES. SIZES SHOWN ARE FOR BIDDING PURPOSES ONLY.
VRV SYSTEM MANUFACTURER IS RESPONSIBLE FOR PIPE SIZING OF INSTALLED
PIPE.
D. ALL COOLING COIL CONDENSATE DRAIN PIPING TO HAVE 45 WYE ELBOWS. 90
ELBOWS ARE NOT PERMITTED. PROVIDE CLEANOUTS AT ALL VERTICAL RISERS
AND HORZONTAL CHANGES IN DIRECTION.

7
SW1

E. FURNISH AND INSTALL WALL-MOUNTED THERMOSTATS FOR ALL FAN COIL


UNITS.
F. COOLING COIL CONDENSATE DRAIN RUN-OUTS TO FAN COIL UNITS SHALL BE
MIN. 1".

4
UP

G.- REFER TO SCHEDULES ON SHEET M501.

PLAN NOTES
1.-REMOTE MOUNTED THERMOSTAT FOR VRV FAN COIL UNIT.
2.-1" COOLING COIL CONDENSATE DRAIN LINE UP THRU SLAB TO FAN COIL UNIT
ON FLOOR ABOVE.
3.-DROP REFRIGERANT PIPING DOWN INSIDE FURRED WALL AND CONNECT TO
FAN COIL UNIT (FROM INSIDE WALL). COORDINATE PIPING WITH OTHER
PIPING IN CHASE.
4.-BRANCH SELECTOR BOX MANUFACTURED BY VRV SYSTEM MANUFACTURER.
5.-EXISTING 3" FLOOR DRAIN IN MECHANICAL ROOM. ROUTE CONDENSATE
DRAIN LINES DOWN WALL AND NEAR DRAIN.
6.-REFRIGERANT LINES TO CONDENSING UNIT 1. SEE M301 FOR FURTHER
INFORMATION.
7.-REFRIGERANT LINES TO CONDENSING UNIT 2. SEE M301 FOR FURTHER
INFORMATION.
8.-REFRIGERANT LINES TO CONDENSING UNIT 3. SEE M301 FOR FURTHER
INFORMATION.
9.-REFRIGERANT LINES TO CONDENSING UNIT 4. SEE M301 FOR FURTHER
INFORMATION.
10.-REFRIGERANT LINES TO CONDENSING UNIT 5. SEE M301 FOR FURTHER
INFORMATION.

C-B-5

C-B-4

DAYTON VAMC

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

11.-COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.


COORDINATE PIPING WITH OTHER PIPING IN CHASE. SEE PIPING
CONTINUATION ON PLUMBING SHEET P200.
12.-NEW PRV STATION. SEE DETAIL 12 ON SHEET M502.
13.-CONNECT TO EXISTING 3" HIGH PRESSURE STEAM LINE. PROVIDE NEW 2-1/2"
TAP ON EXISTING MAIN STEAM HEADER. PROVIDE A LINE SIZE GATE VALVE
DOWNSTREAM TAP. COORDINATE DOWNTIME OF MAIN STEAM SYSTEM
WITH VA FACILITIES STAFF PRIOR TO EXECUTING WORK. PROVIDE A
MINIMUM OF A WEEK LEAD TIME PRIOR TO STEAM SYSTEM SHUTDOWN.

14.-STEAM AND CONDENSATE PIPING TO AHU-1. SEE M200 FOR MORE


INFORMATION.
15.-CONNECT NEW 3" LOW PRESSURE RETURN INTO EXISTING LOW PRESSURE
RETURN LINE IN CRAWL SPACE.
16.-2" VENT FROM CONDENSATE PUMP. TERMINATE AT 24" ABOVE BUILDING
CONNECTOR ROOF LINE WITH 90 ELBOW DOWN. FASTEN PIPING TO
EXTERIOR OF THE BUILDING.
17.-CONNECT TO NEW HOT WATER HEATER.
18.-PIPING SHALL BE RUN BELOW BASEMENT SLAB AND INTO
SUB-BASEMENT/CRAWL SPACE.

19.-NEW PRV STATION. SEE DETAIL 12 ON SHEET M502. PRV STATION TO BE


RECONNECTED TO EXISTING LOW PRESSURE STEAM SYSTEM LOCAL TO THE
MECHANICAL ROOM SPACE.

20.-VENT FROM PRESSURE REDUCING STATIONS. TERMINATE AT 24" ABOVE


BUILDING CONNECTOR ROOF LINE WITH 90 ELBOW DOWN. FASTEN PIPING
TO EXTERIOR OF THE BUILDING.
21.-REFRIGERANT LINES TO CONDENSING UNIT 6. SEE M301 FOR FURTHER
INFORMATION.
22.-STEAM AND CONDENSATE LINES UP TO LEVEL 4 SERVING DOAS-1 UNIT, SEE
DRAWING M304 FOR DETAILS. CONDENSATE LINE UP TO LEVEL 1 FAN COIL
UNITS, SEE M301 CODED NOTE 9 FOR DETAILS.

23.-REFRIGERANT LINES TO CONDENSING UNIT 5 / DOAS-1 UNIT. SEE DRAWINGS


M301 AND M304 FOR FURTHER INFORMATION.
24.-REFRIGERANT LINES TO CONDENSING UNIT 1/LEVEL 3 FAN COIL UNITS. SEE
DRAWINGS M301 AND M303 FOR FURTHER INFORMATION.

IC

25.-REFRIGERANT LINES TO CONDENSING UNIT 2/LEVEL 1 FAN COIL UNITS. SEE


DRAWING M301 FOR FURTHER INFORMATION.
26.-STEAM AND CONDENSATE LINES UP TO LEVEL 4 SERVING DOAS-2 UNIT, SEE
DRAWING M304 FOR DETAILS.
DN

27.-REFRIGERANT LINES TO CONDENSING UNIT 3/LEVEL 3 FAN COIL UNITS. SEE


DRAWINGS M301 AND M303 FOR FURTHER INFORMATION.

NAME

VA NO.

VA NAME

001

UNOCCUPIED

028

STORAGE

001CW

STORAGE

040A

ELECT RM

000WW

ELECTRICAL

040B

COMM RM

001WW

COMMUNICATIONS

041

ENTRY

000CW

VESTIBULE

556-4098

28.-REFRIGERANT LINES TO CONDENSING UNIT 4/LEVEL 3 FAN COIL UNITS. SEE


DRAWINGS M301 AND M303 FOR FURTHER INFORMATION.

ROOM SCHEDULE
NO.

DS

29.-REFRIGERANT LINES TO CONDENSING UNIT 6 / DOAS-2 UNIT. SEE DRAWINGS


M301 AND M304 FOR FURTHER INFORMATION.

BASEMENT
HVAC PIPING PLAN

HVAC PIPING PLAN BASEMENT


SCALE: 1/8"=1'-0"
NORTH

M300
02-21-2011

1/8" = 1'-0"

M.1

8.3

DN

Prntr

Camera
FC-2

H.9

CUH-2

1-1/4"
1"

101

101
144

DN

4 10
6

Copy

TV

T
T

DN

Files

(TYP.) 3
T
102102

6
10 4

C-1-1
C-1-1
FC-4

FC-1

Brochures

UP

143
143

SW2

8.2

FC-4

8
102A

NOT IN SCOPE

102A
C-1-3

7.5

RL

C-1-2C-1-2

thinkchamplin.com

1"

RS RD

125

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

6.8

102B
102B
WHITEBOARD

125A

13

DN

118

120A
118

1"

120A

UP

1-1/4"
6

10'-0"

D
7

13

10 9

120

RS RHGBP
WHITEBOARD

RL

9
11
12
RL RD
RS

10'-0"

1"

RL RD
RS

12

12

(TYP.) 3

RS

FC-5

12
T

121
5

RL RHGBP

305 Connector

RL RHGBP
RS

12

120

10'-0"

1"

5
SW3

6.1

CU-6
CU-5
1
1

121

FC-8

2 CU-4

DAYTON VAMC

CU-3

RS
RL RHGBP

OVERHEAD
PROJECTOR

C-1-48

1
CU-1

RS RS
RDRL

C-1-4
PROJ
SCREEN

123

FC-7
8

RL

11
122G

DN

CU-2
1

10'-0"

RS RD

PLAN NOTES

RL RD

DN

2.-COVER WEATHER-EXPOSED PIPING WITH ALUMINUM JACKET. MOUNT PIPING


ON EQUIPMENT SUPPORTS LOCATED AT 5'-0" O.C. AND AT CHANGES IN
DIRECTION. SEE DETAIL 16 ON SHEET M502 FOR EQUIPMENT SUPPORT
DESIGN.

MOVEABLE PARTITION

3.-REMOTE MOUNTED THERMOSTAT FOR VRV FAN COIL UNIT.

D
TYP.

122

FC-6

1.-MOUNT CONDENSING UNIT ON OUTDOOR EQUIPMENT PAD - SEE DETAIL 17


ON M502. PAD TO EXTEND 4" FROM EDGE OF UNIT/UNITS ON ALL SIDES.

12
TYPICAL

4.-1" COOLING COIL CONDENSATE DRAIN LINE FROM FC UNIT DOWN THRU
FLOOR. SEE FLOOR PLAN BELOW FOR CONTINUATION.

12

UP

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

SCOPE OF WORK

5.-1" COOLING COIL CONDENSATE DRAIN LINE DOWN TO MOP SINK BELOW.

8.2
8

7.5

OVERHEAD
PROJECTOR
TYPICAL

7.-REFRIGERANT PIPING DOWN TO CONDENSING UNIT 2. ALL FAN COILS ON THIS


LEVEL SHALL BE SERVED BY THIS CONDENSING UNIT. COORDINATE LOCATION
WITH CHASE OR WALLS ON FLOORS ABOVE AND BELOW.

123A

PROJ
SCREEN

8.-BRANCH SELECTOR BOX MANUFACTURED BY VRV SYSTEM MANUFACTURER.

1"

9.-COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.


COORDINATE PIPING WITH OTHER PIPING IN CHASE.
FC-6

10.-SEE BASEMENT PIPING PLAN FOR CONTINUATION.

FC-7

6.8

6.- DROP REFRIGERANT PIPING DOWN INSIDE FURRED WALL AND CONNECT TO
FAN COIL UNIT (FROM INSIDE WALL). COORDINATE PIPING WITH OTHER
PIPING IN CHASE.

11.-REGRADE AS NECESSARY. FURNISH AND INSTALL 6 INCH GRAVEL BED


CONFORMING TO AASHTO IN THIS AREA.

T
T

WHITEBOARD

12.- FOOTPRINT FOR FUTURE UNITS TO SERVE ALL ADDITIONAL FLOORS. SHOWN
FOR REFERENCE ONLY (NOT INCLUDED IN CONTRACT).

13.- STEAM, CONDENSATE AND REFRIGERANT PIPING UP AND DOWN THRU


CHASE. SEE ADDITIONAL BASEMENT, SECOND, THIRD, AND ATTIC LEVEL
PIPING DRAWINGS FOR FURTHER INFORMATION. COORDINATE WITH
DUCTWORK IN CHASE.

C-1-6
C-1-6

SW4

1" 122A

WHITEBOARD

UP

T
2

FC-4

10'-0"

FC-6

3
T (TYP.)

122B

1"

ROOM SCHEDULE
NO.

NAME

VA NO.

122D

VA NAME
1

101

VESTIBULE

100CW

VESTIBULE

102

WAITING

102CW

WAITING

102A

RECEPTION

102CW

102B

REGISTER

133EW

118

CONFERENCE #4

132EW

CONFERENCE

120

MEN

104CW

MEN

120A

JAN

103CW

HAC CLOSET

121

WOMEN

105CW

WOMEN

122

CYBER CAFE

106CW

CAFE

122A

VENDING

107CW

VENDING

122B

EMPLOYEE DINING

108CW

DINING

122D

CONFERENCE 3

109CW

CONFERENCE

122G

CANTEEN

123

CONFERENCE 1

111CW

CONFERENCE

123A

CONFERENCE 2

110CW

CONFERENCE

125

COMM RM

112CW

COMMUNICATIONS

125A

ELECT RM

100WW

ELECTRICAL

143

ENROLLMENT

113CW

144

PBS/STAFF

114CW

FC-5

C-1-5
C-1-5

IC

DS
410 Connector

556-4098

LEVEL 1
HVAC PIPING PLAN

HVAC PIPING PLAN LEVEL 1


SCALE: 1/8"=1'-0"
NORTH

M301
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

1-1/4"
3

2
2

1"
3

2
9

1"

1"

1"

1"

1"
1"

UP

DN

2
1
SW2

8.2
8

thinkchamplin.com
7.5

C-1-4

C-2-4
7
F.E.

231

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

6.8

231A

1
C-2-2
UP

1"

DN

SW3

6.1

2
3

1"

1-1/4"
2

1"

1-1/4"

DAYTON VAMC

PLAN NOTES
1.- MOUNT PIPING AS HIGH AS POSSIBLE.

DN
UP

2.- COOLING COIL CONDENSATE DRAIN UP TO FLOOR ABOVE. COORDINATE


EXACT LOCATION WITH EQUIPMENT THAT DRAIN CONNECTS TO ON FLOOR
ABOVE OR WALL OR CHASE THAT DRAIN IS CONCEALED IN ON FLOOR ABOVE.

3.- COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.
COORDINATE PIPING WITH OTHER PIPING IN CHASE.

STAIR-2

4.- STEAM, CONDENSATE AND REFRIGERANT PIPING UP AND DOWN THRU CHASE.
SEE ADDITIONAL BASEMENT, THIRD, AND ATTIC LEVEL PIPING DRAWINGS FOR
FURTHER INFORMATION.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

SW4
UP

DN

IC

DS

556-4098

LEVEL 2
HVAC PIPING PLAN

ROOM SCHEDULE
NO.

NAME

VA NO.

VA NAME

231

COMM RM

200CW

COMMUNICATIONS

231A

ELECTR

200WW

ELECTRICAL

HVAC PIPING PLAN LEVEL 2


SCALE: 1/8"=1'-0"
NORTH

M302
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

FC-4
3

348

348

T
6

FC-7

301A

6
4

4
6

FC-1
8

FC-1

301A

1"
3
T

FC-1

FC-1

T 3

302

T
1"

8
3

301

302B

302A

8
T

303A

303

8
T

FC-6

303

302B

302A

305

8
3
T

307

305A

305A

305

3
8
3

DN

304

1"
T

FC-1

SW2

C-3-4

3
FC-8

FC-8

4
68.2

309

306

8
FC-8

308

FC-6

304A
304A

303A

8
3

FC-1

304

FC-1

FC-4
302

FC-1

FC-1

313
7.5

313

11

RS RD
317

RS RD

1"
331A

1"

317

RL

C-3-4

RL

1"

12
331

C-3-4

316 316

RS RD

1"

3
RL

310

6.8

313A

FC-3

15 PSI

UP

1"

10

318A 1"

DN

3
312

FC-8
8

1"

315

6
314

315

318A

314

FC-1

FC-1

FC-2

312

311

6.1

1"

SW3

10

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

1"

C-3-1
C-3-1

thinkchamplin.com

318

8
U

T
3

7
328
328

FC-5

319

327 327

DAYTON VAMC

C-3-5
DN

PIPING PLANS GENERAL NOTES

4
8.2

A. SLOPE ALL COOLING COIL CONDENSATE DRAIN PIPING AT MIN. 1/10 SLOPE IN
DIRECTION OF FLOW

B. ALL VRV SYSTEM REFRIGERANT PIPING TEES ARE TO BE REFNET JOINTS. REFNET
JOINTS TO BE MIN. 40" FROM EACH OTHER.

7.5

C. SEE PIPING SCHEMATICS ON SHEETS M503 AND M504 FOR VRV SYSTEM
REFRIGERANT PIPE SIZES. SIZES SHOWN ARE FOR BIDDING PURPOSES ONLY.
VRV SYSTEM MANUFACTURER IS RESPONSIBLE FOR PIPE SIZING OF INSTALLED
PIPE.

D. ALL COOLING COIL CONDENSATE DRAIN PIPING TO HAVE 45 WYE ELBOWS. 90


ELBOWS ARE NOT PERMITTED. PROVIDE CLEANOUTS AT ALL VERTICAL RISERS
AND HORIZONTAL CHANGES IN DIRECTION.

6.8

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

E. FURNISH AND INSTALL WALL-MOUNTED THERMOSTATS FOR ALL FAN COIL


UNITS.

F. COOLING COIL CONDENSATE DRAIN RUN-OUTS TO FAN COIL UNITS SHALL BE


MIN. 1".
G.- REFER TO SCHEDULES ON SHEET M501.

PLAN NOTES

ROOM SCHEDULE
NO.

NAME

VA NO.

VA NAME

DN

1.- COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.
COORDINATE PIPING WITH OTHER PIPING IN CHASE.

301

WAITING

300EW

PATIENT BUSINESS
SERVICES

301A

BREAK ROOM

301EW

BREAK ROOM

302

PRIVACY OFFICER

302EW

OFFICE

302A

TUMOR REGISTRY

303EW

OFFICE

302B

CODING SUPERVISOR

304EW

OFFICE

303

TRAINER

305EW

OFFICE

303A

COMPUTER
COORDINATOR

306EW

OFFICE

304

RELEASE TECHS

308EW

OPEN OFFICE

304A

RELEASE SUPERVISOR 307EW

OFFICE

305

STORAGE

309EW

STORAGE

7.-REFRIGERANT LINES TO CONDENSING UNIT 1/LEVEL 3 (CENTER) FAN COIL


UNITS. SEE DRAWING M301 FOR FURTHER INFORMATION.

310EW

OFFICE

8.- BRANCH SELECTOR BOX MANUFACTURED BY VRV SYSTEM MANUFACTURER.

ELECTRICAL

305A

2.- REFRIGERANT PIPING UP TO ATTIC ABOVE. COORDINATE PIPING, DUCTWORK


AND HOLE PENETRATIONS IN SAME AREA.
3.- REMOTE MOUNTED THERMOSTAT FOR VRV FAN COIL UNIT.
4.- 1" COOLING COIL CONDENSATE DRAIN LINE FROM FC UNIT DOWN THRU
FLOOR. SEE FLOOR PLAN BELOW FOR CONTINUATION.
5.- 1" COOLING COIL CONDENSATE DRAIN LINE DOWN TO MOP SINK BELOW.
6.- DROP REFRIGERANT PIPING DOWN INSIDE FURRED WALL AND CONNECT TO
FAN COIL UNIT (FROM INSIDE WALL). COORDINATE PIPING WITH OTHER
PIPING IN CHASE.

306

ELECTR

311EW

307

SCANNING STAGING

313EW

308

PBS CHIEF

314EW

OFFICE

309

ADMINISTRATIVE
ASSISTANT

315EW

OFFICE

10.- COOLING COIL CONDENSATE DRAIN LINE FROM DOAS UNITS ABOVE. ROUTE
PIPING TO HOUSEKEEPING CLOSET MOP SINK.

310

ASSISTANT

316EW

OFFICE

311

CHIEF OF HIMS

317EW

OFFICE

11.-REFRIGERANT LINES TO CONDENSING UNIT 3/LEVEL 3 (NORTH EAST) FAN


COIL UNITS. SEE DRAWING M301 FOR FURTHER INFORMATION.

312

SCANING TECHS

318EW

OPEN OFFICE

313

WORK ROOM

312 EW

OFFICE

313A

CORRIDOR

CHIEF

9.- STEAM, CONDENSATE AND REFRIGERANT PIPING UP AND DOWN THRU CHASE.
SEE ADDITIONAL BASEMENT, FIRST, SECOND AND ATTIC LEVEL PIPING
DRAWINGS FOR FURTHER INFORMATION..

IC

DS

12.-REFRIGERANT LINES TO CONDENSING UNIT 4/LEVEL 3 (SOUTH EAST) FAN COIL


UNITS. SEE DRAWING M301 FOR FURTHER INFORMATION.

556-4098

314

319EW

OFFICE

315

320EW

OFFICE

316

FEE BASIS TECHS

317

CODING TECHS

321EW

OFFICE

317A

RECEPTION

322EW

RECEPTION

318

MEN

301CW

MEN

318A

JANITOR

300CW

HAC CLOSET

319

WOMEN

302CW

WOMEN

327

STORAGE

303CW

STORAGE

328

STORAGE

304CW

STORAGE

331

COMM RM

300WW

COMMUNICATIONS

331A

ELECTRICAL

301WW

ELECTRICAL

348

CONFERENCE

305CW

CONFERENCE

LEVEL 3
HVAC PIPING PLAN

HVAC PIPING PLAN LEVEL 3


SCALE: 1/8"=1'-0"
NORTH

M303
02-21-2011

1/8" = 1'-0"

M.1

8.3

H.9

8.2
8
5
AH-X

7.5

DOAS-2

thinkchamplin.com

7
6.8

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

1-1/4"
2"
1-1/4"
3 4

15 PSI

15 PSI

DAYTON VAMC

5
2-1/2"
1-1/2"

3 4

PLAN NOTES
1.-RUN 1-1/2" COOLING COIL CONDENSATE DRAIN PIPING FROM AIR HANDLER
HOUSEKEEPING CLOSET ON FLOOR BELOW. ROUTE DRAIN TO MOP SINK
LOCATED WITHIN THIS HOUSEKEEPING CLOSET.
2.-REFRIGERANT PIPING DOWN THRU ATTIC FLOOR. COORDINATE LOCATION
WITH WALL OR CHASE ON FLOOR BELOW.

3.-COORDINATE INSTALLATION AND LOCATIONS OF ALL NEW PIPING WITH


EXISTING SPRINKLER PIPING IN ATTIC.
4.-REFRIGERANT PIPING TO BE SIZED BY AIR HANDLING UNIT/CONDENSING UNIT
MANUFACTURER.
AH-X

DOAS-1

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

5.-MOUNT AIR HANDLER ON 4" BASE RAILS. PROVIDE VIBRATION ISOLATION PER
SPECIFICATION SECTION 23 05 41.

1-1/4"
1

IC

DS

556-4098

LEVEL 4
HVAC PIPING PLAN

HVAC PIPING PLAN LEVEL 4


SCALE: 1/8"=1'-0"
NORTH

M304
02-21-2011

1/8" = 1'-0"

HVAC LEGEND

(ALL MAY NOT APPLY)

HVAC LEGEND

(ALL MAY NOT APPLY)

PRESSURE GAUGE WITH SHUTOFF COCK SNUBBER


REQUIRED FOR STEAM SERVICE
THERMOMETER

HVAC LEGEND

(ALL MAY NOT APPLY)

REFRIGERATION MONITORING SYSTEM ALARM DEVICE

SPACE TEMPERATURE SENSOR - MOUNTING HEIGHT 48"

SPACE HUMIDISTAT

THERMOSTATIC AIR VENT

SPACE MOTION SENSOR

MANUAL AIR VENT WITH SHUTOFF COCK

THERMOSTAT ELECTRIC - MOUNTING HEIGHT 48"

AUTOMATIC AIR VENT WITH SHUTOFF COCK, VENT TO DRAIN

CPD

PUMPED CONDENSATE

THERMOSTAT PNEUMATIC - MOUNTING HEIGHT 48"

WATER TEMPERATURE SENSOR

(CR)E

EXISTING CONDENSER WATER RETURN

CARBON MONOXIDE SENSOR


VARIABLE SPEED PUMPING DIFFENTIAL PRESSURE SENSOR

D
(C)E
C
(CPD)E

DRAIN PIPE
EXISTING STEAM CONDENSATE (GRAVITY RETURN)

EXISTING PUMPED CONDENSATE

CS

CONDENSER WATER SUPPLY

CR

CONDENSER WATER RETURN

SPACE PRESSURE SENSOR

(P-1)E

EXISTING EQUIPMENT TAG

METER

(CS)E

EXISTING CONDENSER WATER SUPPLY

NEW EQUIPMENT REFERENCE SYMBOL

FLEXIBLE CONNECTOR

CWR

CHILLED WATER RETURN

NOTE SYMBOL

UNION

CONNECT TO EXISTING SYMBOL


105

CO

CO

STRAINER WITH BLOW DOWN

ROOM NUMBER
APPROXIMATE ELEVATION FROM FLOOR TO
BOTTOM OF DUCT, PIPE OR EQUIPCHMENT ITEM

9'-6"
A
M1-1

SHUTOFF/ISOLATION VALVE
COMBINATION BALANCING/SHUTOFF VALVE

SECTION "A" DESIGNATION, SHOWN ON SHEET H1

21
H33

CHECK VALVE

DETAIL REFERENCE SYMBOL, DETAIL "A" SHOWN ON SHEET H1

E1-22"x22"
1200
R1-22"x22"
1200

CLEAN OUT

CEILING MOUNTED AIR DEVICE, E1- AIR DEVICE DESIGNATION.


REFER TO SCHEDULE. 22"x22" NECK SIZE, 1,200 REQUIRED CFM.
DUCT SIZE SAME AS NECK SIZE UNLESS INDICATED OTHERWISE.
CEILING MOUNTED AIR DEVICE, R1- AIR DEVICE DESIGNATION.
REFER TO SCHEDULE. 22"x22" NECK SIZE, 1,200 REQUIRED CFM.
DUCT SIZE SAME AS NECK SIZE UNLESS INDICATED OTHERWISE.

WALL OR DUCT MOUNTED AIR DEVICE, S1 AIR DEVICE


DESIGNATION. REFER TO SCHEDULE. 10"x6" NECK SIZE,
200-REQUIRED CFM, 7'-6" MOUNTING HEIGHT FROM FLOOR TO
BOTTOM OF AIR DEVICE. BRANCH DUCT SIZE SAME AS NECK SIZE
UNLESS INDICATED OTHERWISE.
MANUAL BALANCING VOLUME DAMPER WITH LOCKING DEVICE

DEMOLITION OF DUCTWORK, PIPING, EQUIPMENT ETC.


R

DUCT RISE IN DIRECTION OF AIR FLOW 45 OFFSET

DUCT DROP IN DIRECTION OF AIR FLOW 45 OFFSET

B
E

EXISTING FIRE DAMPER

SMOKE DAMPER

S B
E E
S B
M
M

VACUUM BREAKER

PIPE ANCHOR
PIPE GUIDE
PIPE EXPANSION JOINT
P

DUCT TEMPERATURE SENSOR


DUCT HUMIDITY SENSOR

VALVE IN RISER

MOTOR OPERATED DAMPER (PARALLEL)

EXISTING HOT WATER SUPPLY


HOT WATER SUPPLY
EXISTING MAKE UP WATER
MAKE UP WATER
REFRIGERANT LIQUID
REFRIGERANT HOT GAS BYPASS LINE

REFRIGERANT SUCTION

PIPE TEE DOWN

MOTOR OPERATED DAMPER (OPPOSED)

HOT WATER RETURN

RS

PIPE TEE UP

EXST. COMBINATION SMOKE/FIRE DAMPER AND CONFIG. TYPE

EXISTING HOT WATER RETURN

NEEDLE VALVE

PIPE RISE

COMBINATION SMOKE/FIRE DAMPER AND CONFIGURATION TYPE

RHGBP

STEAM SUPPLY (VALUE INDICATES PRESSURE)

REFRIGERANT DISCHARGE

PIPE DROP

EXISTING SMOKE DAMPER

RL

PRESSURE DIFFERENTIAL SWITCH WITH SHUTOFF COCK

B.- ALL WORK SHALL BE INSTALLED ACCORDING TO THE LATEST LOCAL, STATE
AND NATIONAL CODES. ALL DUCTWORK SHALL BE INSTALLED ACCORDING TO
THE LATEST ASHRAE RECOMMENDATIONS AND SMACNA INSTALLATION
MANUALS.

U.- INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES
AND OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

C.- CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE


DIAGRAMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
D.- PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO
PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.
E.- PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO
AND WITHIN 50 FEET OF ISOLATED EQUIPMENT THROUGHOUT MECHANICAL
EQUIPMENT ROOMS.

V.-PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMS


MOUNTED GREATER THAN 7'-0" ABOVE FLOOR LEVEL; CHAIN SHALL EXTEND TO
7'-0" ABOVE FLOOR LEVEL.
W.-UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF
EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS (100 FEET OR MORE) TO
PERMIT DISASSEMBLY FOR ALTERATIONS AND REPAIRS.
X.-ALL PIPING WORK AND DUCTWORK SHALL BE COORDINATED WITH ALL
TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS AROUND OBSTRUCTIONS
SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

F.- COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH


ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON
OTHER CONTRACT DOCUMENT DRAWINGS.

Y.-CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS,


VOLUME DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT
DRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL
NOT BE INTERPRETED AS THE EXTEND OF THE REQUIREMENTS FOR THESE ITEMS.

G.- MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS,


CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN
MECHANICAL ROOMS.

Z.-ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL


CLEAR DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR
DUCT LINING THICKNESS.

H.- CAULK SPACE BETWEEN SLEEVES, DUCTS AND PIPES WHERE DUCTS AND PIPES
PASS THROUGH WALLS. CAULKING TO BE AIRTIGHT.

AA.- PROVIDE 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING


VANES UNLESS OTHERWISE INDICATED. PROVIDE ACCESS DOORS UPSTREAM OF
ALL ELBOWS WITH TURNING VANES.

EXISTING HIGH PRESSURE RETURN

RD

PIPE CAP

FIRE DAMPER AND CONFIGURATION TYPE

MEDIUM PRESSURE RETURN

CIRCUIT SETTER

VENTURI FLOW METER


AIR TRANSFER ASSEMBLY

HWS

MUW

ECCENTRIC PIPE REDUCER

AIR TURNING VANES

(HWS)E

BALL VALVE

CONCENTRIC PIPE REDUCER

FLEXIBLE DUCT CONNECTION

HWR

(MUW)E

PIPE FLANGE

DOUBLE WALL DUCT WITH 1" INSULATION PERFORATED LINER

(HWR)E

FILL VALVE

FLOW SWITCH
VB

LINED DUCTWORK

EXISTING MEDIUM PRESSURE RETURN

EXISTING STEAM SUPPLY (VALUE INDICATES PRESSURE)

FLOW CONTROL VALVE


FS

LOW PRESSURE RETURN

(15)E

AUTOMATIC FLOW CONTROL VALVE WITH SHUTOFF

EXISTING LOW PRESSURE RETURN

3/4" NPT PETES PLUG

15

T.- UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE


OF STRUCTURE OR SLAB, WITH SPACE FOR INSULATION WHERE REQUIRED IN
THE SPECIFICATIONS.

EXISTING CHILLED WATER SUPPLY

HIGH PRESSURE RETURN

PLUG VALVE

NEW WORK

CHILLED WATER SUPPLY

HPR

BUTTERFLY VALVE

EXISTING TO REMAIN

(MPR)E

EXISTING CHILLED WATER RETURN

TRIPLE DUTY VALVE

PRESSURE RELIEF VALVE WITH INDICATED SETTING

1" DOOR UNDER CUT

U/C

LPR

(HPR)E

GLOBE VALVE
S1-10"x6"
200-7'-6"

(LPR)E

TWO WAY CONTROL VALVE

SOLENOID VALVE

30

(CWS)E

MPR

OS&Y VALVE
S

CWS

THREE WAY CONTROL VALVE

PRESSURE REDUCING VALVE

2-WAY SUPPLY DIFFUSER

(CWR)E

A.- PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR
REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS
INDICATED ON THE DRAWINGS AND AS SPECIFIED.

STEAM CONDENSATE (GRAVITY RETURN)

H-1

HVAC GENERAL NOTES

I.- ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR


PIPING INSULATION IS APPLIED.
J.- COORDINATE OPENINGS THROUGH OUTSIDE WALLS, LINTELS FOR LOUVERS
WITH STRUCTURAL AND ARCHITECTURAL REQUIREMENTS.
K.- COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS'
CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING
TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTONS TO FURNISHED
EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING
DIMENSIONS BEFORE FABRICATION.
L.- MINIMUM CONCRETE PAD THICKNESS SHALL BE 4 INCHES FOR INTERIOR
EQUIPMENT, 6 INCHES FOR EXTERIOR EQUIPMENT. PAD SHALL EXTEND BEYOND
THE EQUIPMENT A MINIMUM OF 4 INCHES ON EACH SIDE, WITH BEVELED
EDGES.
M.- PROVIDE INSULATED SUBBASES ON ALL THERMOSTATS/TEMPERATURE
SENSORS LOCATED ON EXTERIOR WALLS.
N.- INLET DUCTWORK TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK SIZE
UNLESS NOTED OTHERWISE. INLET DUCTWORK TO AIR TERMINAL BOXES SHALL
BE SAME SIZE AS BOX INLET UNLESS NOTED OTHERWISE.
O.- ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION
AND AS SHOWN IN DETAILS FOR PIPING, DUCTWORK AND EQUIPMENT (UNLESS
NOTED OTHERWISE) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
P.- ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL
STEEL SHALL BE COORDINATED WITH STRUCTURAL REQUIREMENTS. ALL
ATTACHMENTS TO STEEL BAR JOISTS, TRUSSES OR JOIST GIRDERS SHALL BE AT
PANEL POINTS. PROVIDE BEAM CLAMPS MEETING MSS STANDARDS. WELDING
TO STRUCTURAL MEMBERS SHALL NOT BE PERMITTED. THE USE OF C-CLAMPS
SHALL NOT BE PERMITTED.
Q.- LOCATION AND SIZED OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED.
R.- ALL OPENINGS IN FIRE RATED WALLS DUE TO DUCTWORK, PIPING, CONDUIT,
ETC., SHALL BE FIRE STOPPED. SEE SPECIFICATIONS FOR REQUIREMENTS. FIRE
RATED WALL TO HAVE FIRE DAMPERS IN ALL DUCT PENETRATIONS.
S.- ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR
HANDLING UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH
P-TRAP, AND PIPED TO NEAREST DRAIN. PROVIDE CONDENSATE TRAP AS
REQUIRED.

BB.- COORDINATE DIFFUSER, REGISTER AND GRILLE LOCATIONS WITH


ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING AND OTHER CEILING
ITEMS AND MAKE MINOR DUCT MODIFICATIONS TO SUIT.
CC.- PROVIDE MINIMUM 4" FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
(SUPPLY, RETURN AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS
AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE
CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE
EQUIPMENT UNLESS OTHERWISE INDICATED.
DD.- UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE
UNDERSIDE OF STRUCTURE, WITH SPACE FOR INSULATION WHERE REQUIRED IN
THE SPECIFICATIONS.

thinkchamplin.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

EE.- RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 7 FEET AND SHALL NOT BE USED
FOR 90 DEGREE BENDS.
FF.- PROVIDE ACCESS DO0RS IN DUCTWORK FOR ACCESS TO ALL SMOKE
DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, COILS AND
OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR
INSPECTION.
GG.- SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL
CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
MOUNTING THE SMOKE DETECTOR IN THE DUCTWORK AS SHOWN ON THE
DRAWINGS AND IN ACCORDANCE WITH MANUFACTURER'S PRINTED
INSTRUCTIONS.
HH.- CONTRACTOR TO PROVIDE FIRE STOPPING AT ALL RATED HORIZONTAL AND
VERTICAL ASSEMBLIES. CONTRACTOR SHALL NOT LEAVE OPENINGS UNPROTECTED
DURING THE CONSTRUCTION PERIOD EXCEPT FOR SHORT DURATIONS WHILE ITEMS ARE
BEING INSTALLED THROUGH OPENINGS
II.- ALL 12"x12" DIFFUSERS ARE TO BE INSTALLED IN CENTER OF CEILING TILE.
JJ.-ALL EXISTING HVAC EQUIPMENT, PIPING, AND DUCTWORK NOT SHOWN ON
DRAWINGS IS TO BE REMOVED AS NECESSARY FOR COMLETION OF NEW WORK
(CONTRACTOR SHALL INCLUDE THIS COST IN BASE BID PRICE).
KK.-ALL EXISTING EQUIPMENT, PIPING,...ECT. THAT IS ABOVE CEILING THAT CONFLICTS
WITH NEW DUCTWORK AND PIPING LAYOUT IS TO BE RELOCATED AS NECESSARY TO
ALLOW FOR NEW LAYOUT INSTALLATION (CONTRACTOR SHALL INCLUDE THIS COST IN
BASE BID PRICE).

DAYTON VAMC

LL.-FURNISH AND INSTALL ISOLATION VALVES AND PIPE CAPS IN PIPING AS REQUIRED
FOR PHASING OF ALL WORK.

F&T TRAP
BUCKET TRAP
PITCH DOWN

DUCT HUMIDITY HIGH LIMIT SENSOR


DUCT AIR FLOW SENSOR
DUCT STATIC PRESSURE SENSOR
MEDIUM PRESSURE CONICAL LOW LOSS DUCT TEE
LOW PRESSURE BELL MOUTH WITH LOCKING QUADRANT DAMPER
SUPPLY AND OR OUTSIDE AIR DUCT DROP
RETURN, EXHAUST AND OR RELIEF AIR DROP

DIRECTION OF FLOW
PRE ENGINEERED EXPANSION LOOP. SEE SPECIFICATIONS

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

SUPPLY AND OR OUTSIDE AIR RISE


RETURN, EXHAUST AND OR RELIEF AIR RISE
SINGLE LINE DUCT TRANSITION
VRV SYSTEM BRANCH SELECTOR BOX

IC

DS

556-4098

HVAC
LEGEND AND INDEX

M500
02-21-2011

NONE

FIRE DAMPER NOTES

CONDENSING UNITS

GENERAL NOTES DETAILS SHOW INSTALL. OF FIRE DAMPER IN WALL. FIRE DAMPER
IN FLOOR SIMILAR. INSTALL. OF FIRE DAMPERS SHALL CONFORM TO NFPA 90A,
SMACNA AND MFR'S INSTRUCTIONS. ALL FIRE DAMPERS TO BE DYNAMIC.

- DISCONNECT BY ELECTRICAL CONTRACTOR


- R-410A REFRIGERANT

DETAIL NOTES
1.- FIRE DAMPER SHALL BE FOLDED BLADE TYPE, EXCEPT AS NOTED. VERTICAL
MOUNT; GRAVITY DROP, HORIZONTAL MOUNT; SPRING LOADED TO CLOSE.
TYPE "A" - BLADES STORED IN AIR STREAM.
TYPE "B" - BLADES STORED OUT OF THE AIR STREAM.
TYPE "C" - HIGH VELOCITY TYPE, BLADES STORED OUT OF THE AIR STREAM,
RECTANGULAR, ROUND OR OVAL CONNECTION.

TAG

2.- DUCT/SLEEVE CONNECTION, BREAK AWAY TYPE.

CU-3

3.- SHEET METAL SLEEVE, 16 GAUGE MIN. SAME MATERIAL AS DUCT EXCEPT
GALVANIZED FOR FIBER GLASS DUCTBOARD.

CU-4

4.- DUCT ACCESS PANEL. REFER TO SPECIFICATIONS.

CU-5

5.- RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MIN. OVERLAP OF
WALL OPENING. BOLT OR TACK WELD TO WALL SLEEVE AS PER SMACNA.

CU-6

6.- 10 GAUGE WALL SLEEVE WITH 1/2" WIDE LEG AT ALL SIDES ON OPPOSITE SIDE
OF DUCT CONNECTION TO OVERLAP WALL OPENING.

REQ'D ACCESS.
1. - COMPRESSOR TO BE MOUNTED ON RUBBER IN SHEAR ISOLATORS.
2. - UNIT IS HEAT RECOVERY CONDENSING UNIT WITH INVERTER. INCLUDE R410A REFRIGERANT, HEATING OPERATION TO 0 F,
VFD CONTROLLED OUTDOOR FAN MOTOR, CONTINUOUS HEATING DURING DEFROST, MANIFOLDING KIT
3. - SINGLE POINT POWER CONNECTION.
4. - CONDENSING UNIT IS A COMBINATION OF TWO CONDENSING UNITS. EACH INDIVIDUAL CONDENSING UNIT REQUIRES AN
ELECTRICAL FEED, WIRE PER MANUFACTUERS INSTRUCTIONS.
5. - INCLUDE; HOT GAS BYPASS LINE, FIELD OUTLET CONNECTION, 4 SCROLL COMPRESSORS, 4-STEP CAPACITY CONTROL,
BUILT-IN HAIL PROTECTION, PHASE FAILURE, GROUND FAULT PROTECTION, R410A REFRIGERANT.
6. - INSTALL UNIT ON VIBRATION ISOLATION PADS (MIN. 1/4" DEFLECTION) FURNISHED BY UNIT MANUFACTURER.

CU-1
CU-2

7.- HIGH VELOCITY DUCT COUPLING

FIRE DAMPER - TYPE B

SERVICE
SOUTH WING
THIRD FLOOR
SOUTH WING
FIRST FLOOR
EAST WING
THIRD FLOOR
EAST WING
THIRD FLOOR
SOUTH WING
DOAS-1
EAST WING
DOAS-2

- HEATING CAPACITY BASED ON INDOOR CONDITIONS OF 70.0F DB AND OUTDOOR CONDITIONS OF 0.0F DB / 0.0F WB
- COOLING CAPACITY BASED ON INDOOR CONDITIONS OF 80.0F DB / 67.0F WB AND OUTDOOR CONDITIONS OF 95.0F DB

CAPACITY (BTU/Hr)
REFRIG. LINE SIZES
ELECTRICAL DATA
NO. OF
REFRIG.
DISCH. SUCTION BAL. TUBE COOLING HEATING VOLTS PHASE MCA MOCP SUCT.TEMP CIRCUITS

LIQUID

TAG

DESCRIPTION

MODULE SIZE

SUPPLY

12"x12"

SQUARE - PLAQUE

1,2,4,6

S2

SUPPLY

24"x24"

SQUARE - PLAQUE

1,2,4,6

S3

SUPPLY

AS NOTED

SUPPLY GRILLE

1,2,4,6

S4

SUPPLY

16"

SUPPLY GRILLE

R1

RETURN

24"x24"

LOUVERED FILTER GRILLE

1,3

R2

RETURN

24"x12"

LOUVERED FILTER GRILLE

1,3

R3

RETURN

24"x12"

LOUVERED RETURN GRILLE

1,3

R4

RETURN

AS NOTED

LOUVERED RETURN GRILLE

1,3

E1

EXHAUST

24"x12"

EGGCRATE RETURN GRILLE

1,3

E2

EXHAUST

12"x12"

EGGCRATE RETURN GRILLE

1,3

E3

EXHAUST

AS NOTED

EGGCRATE RETURN GRILLE

MFR. TO SIZE

192,000

216,000

208

MFR. TO SIZE

120,000

135,000

208

MFR. TO SIZE

430,000

208

160

175

43.0

3,5,6

MFR. TO SIZE

275,000

208

125

175

43.0

3,5,6

45
60
60
60
40
50

TAG

REQ'D
ACCESS

FC-7
FC-8

280/210

12.0

13.5

1/4

1/2

208

79

15

ALL

490/380

18.0

20.0

1/4

1/2

208

105

15

ALL

560/420

24.0

27.0

3/8

5/8

208

108

15

ALL

636/530

18.0

20.0

1/4

1/2

208

214

15

ALL

688/565

24.0

27.0

3/8

5/8

208

230

15

ALL

883/706

30.0

34.0

3/8

5/8

208

300

15

ALL

1130/812

36.0

40.0

3/8

5/8

208

375

15

ALL

AREA SERVED

SOUTH WING

EAST WING

1377/989

48.0

54.0

3/8

5/8

208

460

15

ALL

UNIT CONFIG.

HORIZ.

HORIZ.

MFG.

MODEL

CUSTOM AIR HANDLING UNITS

UNIT NUMBER

SUPPLY FAN

TAG

4
(IF DOOR ABOVE IS
NOT ACCESSIBLE,
INSTALL DOOR
DUCT
BELOW)

SCALE: NONE

DUCT CONSTRUCTION/SEALING
SMACNA
SEAL CL
SP CONST

DUCT SYSTEM

NOTES

MEDIUM VELOCITY SUPPLY

+3"

LOW VELOCITY SUPPLY

+1"

RETURN / RELIEF

-1"

GENERAL EXHAUST

-0.5"

OUTSIDE AIR

-0.5"

SIZE
W

F.A.
CFM P.D.
IN SQ.FT.

INTAKE

4"

30"

60"

3400 0.06

6.25

ALL

L-2

INTAKE

4"

48"

3400 0.10

4.81

ALL

L-3

EXHAUST

4"

48"

6600 0.25

6.28

ALL

L-4

INTAKE

4"

42"

2200 0.05

4.81

ALL

L-5

INTAKE

4"

42"

2200 0.05

4.81

ALL

6.28

ALL

3.5

ALL

L-6

EXHAUST

4"

48"

4200 0.12

L-7

INTAKE

4"

42"

24"

1500 0.04

NOTES (APPLIES TO ALL LOUVERS)


1.- LOUVER SIZES SHOWN ARE FOR BIDDING PURPOSES ONLY. CONTRACTOR
SHALL FIELD-VERIFY EXISTING OPENING SIZES AND SIZE LOUVERS TO FIT IN
EXISTING OPENINGS.
2.- CONTRACTOR SHALL PROVIDE INSULATED SHEETMETAL PLENUM BEHIND
ALL LOUVERS.
3.- PROVIDE 1-1/4" DRAIN PIPING FROM ALL INTAKE LOUVERS. ROUTE TO
NEAREST FLOOR DRAIN.
4.- COLOR OF LOUVER SELECTED BY THE ARCHITECT.
5.- COORDINATE LOCATION AND SIZE WITH ARCHITECT AND OTHER
CONTRACTORS.

AREA SERVED

UNIT CONFIG.

HORIZ.

CFM - FUTURE

6,700

4,400

CFM

1500

CFM - CURRENT

5,270

790

TOTAL SP./EXT. SP. IN. W.G.

1.89/1.00

TOTAL SP./EXT. SP. IN. W.G.

5.3/2.0

5.39/2.0

WHEEL DIA.

9.50

WHEEL DIA.

20 INCH

16 INCH

WHEEL TYPE

AF CENT.

WHEEL TYPE

AF-PLENUM

AF-PLENUM

MOTOR H.P.

1.5

MOTOR H.P.

10

7.5

CFM - FUTURE

5,500

3,500

FACE AREA

2.48 SF

CFM - CURRENT

3,300

640

CAP'Y - MBH

83.70

2.82/1.75

3.03/1.75

ENT. AIR TEMP.

63

WHEEL DIA.

20 INCH

16 INCH

LVG. AIR TEMP.

114

WHEEL TYPE

AF-PLENUM

AF-PLENUM

1500

0.26

215

146

88.57

428

280

ENT. AIR TEMP.


DB/WB
LVG. AIR TEMP.
DB/WB
CFM
MAX. AIR P.D. IN. W.C.
ROWS

81/71

81/70

CFM
MAX. AIR P.D. IN. W.C.
LB/HR
STEAM
PRESSURE - PSI
DESCRIPTION

IFB COIL

52/51

52/51

TYPE - FINAL

MERV 8 - 2"

6,700

4,400

5.6

0.98

0.94

0.18/0.59
PLEATED
PANEL

FACE AREA S.F.


P.D. IN. W.C.
CLEAN/DIRTY
DESCRIPTION

REFRIGERANT

R410A

R410A

100

FACE AREA

1,2

CAP'Y - MBH

495

347

ENT. AIR TEMP.

30

36

LVG. AIR TEMP.

113

109

CFM
MAX. AIR P.D. IN. W.C.
LB/HR
STEAM
PRESSURE - PSI
DESCRIPTION

6,700

4,400

637

361

IFB COIL

IFB COIL

6700

4400

5270

790

0.6

41.0

41.1

90/73

93/74

81/71

82/71

5500

3500

3300

640

68

70

30

31

75

75

84

86

MERV 8

MERV 8

0.27/1.0
PLEATED
PANEL

0.22/1.0
PLEATED
PANEL

TOTAL SP./EXT. SP. IN. W.G.

CUH-1

ELECT. CABINET UNIT HEATER

VESTIBULE

250

17

25

208

CUH-2

ELECT. CABINET UNIT HEATER

VESTIBULE

250

17

25

208

SENSIBLE CL'G
MBH

REQ'D ACCESS
1. DUCT COLLAR FOR INLINE AIRFLOW (UNIT TO BE MOUNTED HORIZONTALLY,
BOTTOM IN/TOP OUT CONFIGURATION) , WALL-MOUNTED THERMOSTAT.
PROVIDE VIBRATION ISOLATION PER SPEC SECTION 23 05 41.
2.FRONT INLET/TOP OUTLET CONFIGURATION. BUILT-IN THERMOSTAT.

CONDENSATE RECEIVER PUMP


TAG

DESCRIPTION

GPM

CP-1 CONDENSATE RETURN

PSI

18

20

RPM
3500

SIZE(IN)
1"

INLET
SIZE
2"

ELECTRICAL DATA
VOLTAGE PHASE
HP

CAP(GAL)
25

(2) 1/3

120

REQ'D
ACCESS

1,2,3,4,5

NOTES
1. PUMP SHALL BE DUPLEX.

STEAM PRESSURE REDUCING VALVE AND RELIEF VALVE

NOTES

L-1

REQ'D
ACCESS

AH-1
CONNECTOR
CORRIDOR

STEAM PRESSURE REDUCING VALVE

TAG

INLET PRESSURE OUTLET PRESS.


(PSI)
(PSI)

RELIEF VALVE

CAP'Y
lb/hr

VALVE
SIZE (IN)

REQUIRED
CV

MFR

MODEL

REQ'D
ACCESS

VALVE
SIZE (IN)

RELIEF PRESSURE
SETTING (PSI)

CAP'Y
lb/hr

PRV-1

125

60

3410

1-1/2

14.28

SPENCE

1,2,3

PRV-2

60

15

3410

26.70

SPENCE

1,2,3

25

3941

PRV-3

125

60

1609

6.74

SPENCE

1,2

PRV-4

60

15

1609

1-1/2

12.60

SPENCE

1,2

25

1856

REQ'D ACCESS
1. INCLUDE EXTERNAL STEAM PILOT CAPABLE OF +/- 1% ACCURACY.
2. NOISE LEVEL TO BE MAX. 85 DB.
3. ADDITIONAL LOAD OF 523 LBS/HR ADDED TO THIS PRV STATION TO PICK UP THE LOAD OF A FUTURE DOAS-3 UNIT FOR THE WEST WING.

OA CFM
(FUTURE)
OA CFM
(CURRENT)
WINTER EA
DB
WINTER LA
DB
SUMMER EA
DB/WB
SUMMER LA
DB/WB
EA CFM
(FUTURE)
EA CFM
(CURRENT)
WINTER EA
DB
WINTER LA
DB
SUMMER EA
DB
SUMMER LA
DB
SUPPLY AIR
TYPE - PRE
FACE AREA S.F.
P.D. IN. W.C.
CLEAN/DIRTY
DESCRIPTION

DOAS-1

DOAS-2

OUTSIDE AIR - CFM


(MIN.)
REQ'D ACCESS.

REQ'D ACCESS.
1.INSTALL UNIT ON SPRING ISOLATION
FURNISHED BY UNIT MFR.
2.POWER IS TO BE 208/3/60

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

PLAN VIEW

- PERFORMANCE SHALL BE EQUAL OR SUPERIOR TO SCHEDULED VALUES.

UNIT NUMBER

MOTOR H.P.

REQ'D ACCESS
5. PROVIDE VIBRATION ISOLATION AS
1. INLET BASKET STRAINER
RECOMMENDED BY UNIT
2. DISCHARGE PRESSURE GAUGE
3. MECHANICAL ALTERNATOR (FLOW SWITCH INSIDE RECEIVER) MANUFACTURER.
4. PUMP SUCTION ISOLATION VALVES

LOUVERS
DP

ELEC SERVICE
AMP VOLT PHASE

COOLING COIL

HEATING
MBH KW (MIN) KW (MAX)

CFM

RE-HEAT COIL

SERVICE

PLATE HEAT EXCHANGER

DESCRIPTION

- THREE (3) PHASE COIL LOADS SHALL BE DIVIDED EVENLY ACROSS EACH PHASE
- ELEC SERVICE TO THREE (3) PHASE UNITS TO BE THREE (3) WIRE UNLESS NOTED

FILTER

TYPE "B" 1

- VERIFY/COORDINATE CABINET DIMENSIONS MOUNTING AND RECESS REQUIREMENTS


WITH ARCHITECTURAL DWGS PRIOR TO ORDERING

NOTES:
1. 15 PSI STEAM IS SUPPLIED
TO CONTROL VALVE. SIZE
STEAM CONTROL VALVE
FOR 10 PSI PRESSURE
DROP.
2. IFB=INTEGRAL FACE AND
BYPASS COIL

2
4

ELEVATION VIEW

SCALE: NONE

DAYTON VAMC

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

FILTER

FIRE RATED
FLOOR

SUPPLY AIR
TYPE - FINAL
FACE AREA S.F.
P.D. IN. W.C.
CLEAN/DIRTY
DESCRIPTION

MERV 14

MERV 14

0.5/1.0

0.44/1.0

CARTRIDGE

CARTRIDGE

FILTER

EXHAUST FAN

ELECTRIC HEATING UNITS

MODULAR AIR HANDLING UNITS

- PERFORMANCE SHALL BE EQUAL OR SUPERIOR TO SCHEDULED VALUES.

REQ'D ACCESS.
1. ALL TEMPERATURE SENSORS AND FC CONTROLS SHALL BE PROVIDED BY THE UNIT MANUFACTURER.
2. DIRECT EXPANSION COIL PACKAGE WITH FACTORY MOUNTED THERMAL EXPANSION VALVE AND EQUALIZING TUBE.
3. R-I-S VIBRATION ISOLATORS.
4. PROVIDE (1) SOLENOID VALVE KIT PER DX FAN COIL.
5. UL LISTED
6. PROVIDE FACTORY MOUNTED CONDENSATE PUMP FOR FC-4 THRU 8 ONLY.
7. WASHABLE FILTER

SCALE: NONE

FIRE DAMPER - TYPE B (AT FLOOR)

SEE DWGS FOR


ASSOC. CU
SEE DWGS FOR
ASSOC. CU
SEE DWGS FOR
ASSOC. CU
SEE DWGS FOR
ASSOC. CU
SEE DWGS FOR
ASSOC. CU
SEE DWGS FOR
ASSOC. CU
SEE DWGS FOR
ASSOC. CU
SEE DWGS FOR
ASSOC. CU

OUTSIDE AIR

FLOOR MOUNTED
CONSOLE UNIT
FLOOR MOUNTED
CONSOLE UNIT
FLOOR MOUNTED
CONSOLE UNIT
DUCTED
CONCEALED UNIT
DUCTED
CONCEALED UNIT
DUCTED
CONCEALED UNIT
DUCTED
CONCEALED UNIT
DUCTED
CONCEALED UNIT

SUPPLY FAN

FC-4

FC-6

SERVICE

ELECTRICAL DATA
VOLT PHASE WATT MOCP

HEATING COIL

FC-3

FC-5

TAG

REFRIG. LINE SIZES


LIQUID
GAS

FILTER

FC-1

DUCT EXTENSION
3" MIN. TOP OF DAMPER

CAPACITY (MBH)
COOLING
HEATING

CFM

EXHAUST AIR

DUCT

FC-2

TYPE "B" 1

SERVED BY

thinkchamplin.com

TYPE

REQ'D ACCY:
1. OPPOSED BLADE DAMPER
2. 12"x12" TRIM RING, RAPID MOUNT
3. DAMPER TO BE ACCESSIBLE FROM FACE OF GRILLE.

- HEATING CAPACITY BASED ON INDOOR CONDITIONS OF 70.0F DB AND OUTDOOR CONDITIONS OF 0F DB / 0F WB


- COOLING CAPACITY BASED ON INDOOR CONDITIONS OF 80.0F DB / 67.0F WB AND OUTDOOR CONDITIONS OF 95.0F DB

FIRE RATED WALL


OR PARTITION

COMPONENTS
1 INLET OPENING (LxW):16 x 36
2 PANEL FILTER
3 IFB STEAM COIL
4 FAN
5 OUTLET
6 ACCESS SECTION
UNIT WEIGHT 986 LBS

VRV FAN COIL UNITS - MASTER SCHEDULE

REQ'D
ACCY

S1

270,000

TYPE

1,2,6

240,000

208

BY ARCH.

208

108,000

MOUNTING TYPE CONSTRUCTION TYPE


FINISH
LAY-IN SURFACE
ALUM.
STEEL
E.C.L.
O.W.B.E.

MFR. TO SIZE

96,000

19

OWBE - OFF WHITE BAKED ENAMEL FINISH ECL - ETCHED CLEAR LACQUER FINISH

REQ'D
ACCESS.

43.8
41.3
41.3
41.3
28.8
44.2

MFR. TO SIZE

AH-1 DETAIL

AIR DISTRIBUTION DEVICES

EXHAUST AIR
TYPE - PRE
FACE AREA S.F.
P.D. IN. W.C.
CLEAN/DIRTY
DESCRIPTION

MERV 8

MERV 8

0.21/1.0
PLEATED
PANEL

0.21/1.0
PLEATED
PANEL

IC

OUTSIDE AIR - CFM


(MIN.)
REQ'D ACCESS.

6,800

4,400

1,2

1,3

REQ'D ACCESS.
NOTES:
1.INSTALL UNIT ON SPRING ISOLATION
1. 15 PSI STEAM IS SUPPLIED
FURNISHED BY UNIT MFR.
TO CONTROL VALVE. SIZE
STEAM CONTROL VALVE
2.POWER IS TO BE 208/3/60, MCA 25.1, MOP 35.0
FOR 10 PSI PRESSURE
3.POWER IS TO BE 208/3/60, MCA 21.4, MOP 30.0.
DROP.
2. IFB=INTEGRAL FACE AND
BYPASS COIL

DS

556-4098

HVAC
SCHEDULES

M501
02-21-2011

NONE

1
2

TO DX FAN COIL
4

TO OUTDOOR CONDENSOR

SHUT OFF BALL VALVE WITH


INTEGRAL REFRIGERANT
MAINTENANCE PORTS. TYP.
4 BRANCH SELECTOR

5
1

6
1
6

R>=W
STANDARD
RADIUS
ELBOW

SUCTION LINE

7 DISCHARGE LINE

SCALE: NONE

HIGH PRESSURE STEAM DRIP

1
SHORT RADIUS
ELBOW WITH
ONE VANE

H
2

HPR

LOW PRESSURE STEAM SUPPLY

SEDIMENT POCKET

F&T TRAP AND STRAINER

STRAINER

LOW PRESSURE CONDENSATE


RETURN.

SUPPLY AIR TRUNK REFER TO PLANS FOR SIZE


BELLMOUTH FITTING
WITH MANUAL DAMPER

AUTOMATIC CONTROL VALVE

VACUUM BREAKER
END OF MAIN DRIP

ECCENTRIC REDUCER

1 2

RL

PIPE THREADED INTO


ELBOW (SAME SIZE AS
ELBOW)

8
RHGBP

RHGBP
RS

RS

COIL #2

RL

RL

RHGBP

RHGBP
RS

thinkchamplin.com

RS

AIR HANDLER

CONDENSING UNIT

TYP. DOAS-1 AND 2

EXPANSION VALVE

SIGHT GLASS

NOTES

SOLENOID VALVE

1. VERTICAL COIL TYPE DOMESTIC WATER


HEATER IS SHOWN.

1.

EQUALIZING LINE

FILTER/DRYER

2. SEE PLUMBING DRAWINGS FOR PIPING


CONNECTIONS.

2.
3.

HOT GAS BYPASS VALVE

3. INSTALL ALL PIPING PER WATER HEATER


MANUFACTURERS RECOMMENDATIONS.

4.

HOT GAS BYPASS SOLENOID VALVE

ELEVATION

FLEXIBLE CONNECTOR
3/4" [20mm] DRAIN TO
FLOOR DRAIN OR OPEN
SIGHT DRAIN (NOTE 4)

UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS
NOT BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD
CONTAINED IN ANSI B31.1. POWER PIPING CODE, APPENDIX II.
VENT PIPE SHALL TERMINATE AT EXTERIOR OF BUILDING WITH 90 ELBOW DOWN.
DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS
WHICH PERSONNEL MAY OCCUPY.
DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

TYP. CU-5 AND 6

24" MAX.
[610mm]

FLOOR

NOTES:

RL

OPEN DRAIN (NOTE 3)

TRAP OR ORIFICED UNION


FITTING FURNISHED BY
MANUFACTURER OF DOMESTIC
WATER HEATER, SEE PLUMBING
DWGS.

10

COIL #1

[76mm]

7 LENGTH FROM INVERT OF


MAIN TO DRIP PIPE, 1 1/2 x
MAIN PIPE DIA., 8"
MINIMUM

AUX SIDE CONNECTOR (INTRODUCES HOT GAS INTO


DISTRIBUTER

SCALE POCKET

DOAS-1,2/CU-5,6 DX COIL PIPING SCHEMATIC

SCALE: NONE

SCALE: NONE

DRIP PAN ELBOW


(SECTIONAL VIEW)

CONNECTION TO
PRESSURE VESSEL OR PIPE

DIELECTRIC FITTING

3
6 COLLECTING POCKET AND
DIRT LEG SAME SIZE AS MAIN

SCALE: NONE

VENT PIPE TO BUILDING


EXTERIOR. (NOTES 1, 2)

SAFETY VALVE

DHWR

5 SHUTOFF VALVE

CEILING PANEL

SUPPLY AIR
DIFFUSER

SAFETY VALVE DETAIL

GRAVITY STEAM CONDENSATE


RETURN

4 STRAINER
7

RETURN / EXHAUST GRILLE

DCW

2 "Y" STRAINER

HOSE CLAMP (TYP. 2 PL)

SQUARE TO ROUND
ADAPTOR

CEILING

STEAM SUPPLY
LPS

FLOAT & THERMOSTATIC


TRAP ASSEMBLY

VOLUME DAMPER (IF


DAMPER NOT PROVIDED
IN AIR DEVICE - SEE
PLANS)

TRANSITION
AS REQUIRED

SCALE: NONE

DOMESTIC WATER HEATER


1800 LB/HR @15 PSI STEAM

3 F&T TRAP

SMOOTH RADIUS
ROUND ELBOW

FLEX DUCT (5'-0" MAX)


EXTERNALLY INSULATED
HOSE CLAMPS (TYP)

1 LOW PRESSURE STEAM MAIN


(15-30 PSI)

45 TEE

FLEX. DUCT (4'-0" MAX)


EXTERNALLY INSULATED

SCALE: NONE

LOW PRESSURE STEAM DRIP

RETURN / EXHAUST
AIR TRUNK DUCT (REF.
PLAN FOR SIZE)

EXTERNAL
INSULATION

FLEX TO BE
SAG FREE

RETURN/EXHAUST CONNECTION

EXTERNALLY INSULATED DUCTWORK

PROVIDE UNION UNLESS


SAFETY VALVE HAS
FLANGED OUTLET

5 BLOW DOWN

H= 10"

SHORT RADIUS
ELBOW WITH
TWO VANES

CONTROL VALVE BY
MANUFACTURER OF DOMESTIC
WATER HEATER,

3 THERMO-DYNAMIC
STEAM TRAP
4 STRAINER

120

STEAM CONNECTIONS TO DOMESTIC WATER HEATER

1 SHUT-OFF VALVE
2 CHECK VALVE
HPR

CEILING DIFFUSER

EMD

R>=1/6W

R>=1/3W

NOTE:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE
SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES.
VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS
RECOMMENDED BY SMACNA.
SCALE: NONE

VB

5 LIQUID LINE

DOAS-1,2, AH-1 STEAM HEAT COIL

DUCTWORK RADIUS ELBOWS

[25mm]

VRF FAN COIL BRANCH SELECTOR

NOTE:
1. THIS DETAIL IS TO BE USED FOR BIDDING PURPOSES ONLY.
SIZING OF REFRIGERATION SYSTEM PIPING/EQUIPMENT SHALL
BE THE RESPONSIBILITY OF THE AH/CU MANUFACTUER.
(CONTRACTOR SHALL INCLUDE IN HIS PRICE ALL ITEMS AS
REQUIRED BY AH/CU MANUFACTURER.)
2. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF
REFRIGERATION SYSTEM LAYOUT DONE BY AIR HANDLING
UNIT/CONDENSING MANUFACTURER.
3. CONTRACTOR IS TO FURNISH AND INSTALL ALL
REFRIGERATION SPECIALTIES AND ITEMS AS REQUIRED BY
AH/CU MANUFACTURER.

SCALE: NONE

TO LPR MAIN
ALONG WALL

SAFETY RELIEF VALVE @ 25 PSI

VENT TO OUTDOORS
1"

2"

3"
125 PSI
HPS

TAPER PIPE
REDUCER

PRV-1

20" MIN.

P
40" MIN.

PRV-2

40" MIN.

4"
15 PSI LPS

80" MIN.
TO FIRST TURN

2-1/2"
60 PSI MPS

NOTE:
1. FURNISH AND INSTALL ALL PRV
ASSOCIATED TUBING AND PER
MANUFACTURER'S
RECOMMENDATIONS.

FULL SIZE DIRT LEG & 3/4"


STEAM MAIN DRIP
ASSEMBLY

SCALE: NONE

FROM DOM. HW
HEATERS

3/16"

1/2" x 8" x 8" PLATE W/ (2) 3/4" x


8" AB
GRAVEL

1"
P

(2 ) #5 CONTINUOUS

NOTE: ADJUST SIZES OF SUPPORTS


SHOWN ABOVE AS REQUIRED TO
ADEQUATLEY SUPPORT PIPING.

2"

SCALE: NONE

14

TAPER PIPE
REDUCER

40" MIN.

PRV-3

20" MIN.

FURNISH AND INSTALL OUTDOOR


CONCRETE EQUIPMENT PAD FOR ALL
OUTDOOR EQUIPMENT

SCALE: NONE

DOAS-2 DETAIL

PRV-4

40" MIN.

NOTE:
1. FURNISH AND INSTALL ALL PRV
ASSOCIATED TUBING AND PER
MANUFACTURER'S
RECOMMENDATIONS.

PIPE DETAIL FOR VENT LINES

263"
2

10
13

95"

12

COMPONENTS
1 INLET
(LxW):20 x 42
2 PANEL FILTER
3 CARTRIDGE FILTER
4 HEAT EXCHANGER
5 DX COIL
6 IFB STEAM COIL
7 FAN
8 OUTLET
(LxW):20 1/8 x 36
9 INLET
(LxW):16 x 42
10 PANEL FILTER
11 FAN
12 OUTLET
(LxW):20 1/8 x 36
13 CONTROL PANEL

10

COMPONENTS
1 INLET
(LxW):15 x 36
2 PANEL FILTER
3 CARTRIDGE FILTER
4 HEAT EXCHANGER
5 DX COIL
6 IFB STEAM COIL
7 FAN
8 OUTLET
(LxW):21 5/8 x 24
9 INLET
(LxW):14 x 36
10 PANEL FILTER
11 FAN
12 OUTLET
(LxW):21 5/8 x 24
13 CONTROL PANEL

13

77"

UNIT WEIGHT 10,500 LBS

12

20

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

SADDLE SUPPORT
ANCHOR TO
EXISTING WALL

WALL LINE
PIPE SLEEVE
3/4" THICK
INSULATION

UNIT WEIGHT 8,100 LBS


CLEARANCES:
ACCCESS DOORS - 26 in

CLEARANCES:
ACCCESS DOORS - 26 in

2"
15 PSI LPS

80" MIN.
TO FIRST TURN

FULL SIZE DIRT LEG & 3/4"


STEAM MAIN DRIP
ASSEMBLY

15

282"

DAYTON VAMC

1-1/2"
60 PSI MPS

SCALE: NONE

PIPE SAFETY VALVE


DISCHARGE TO
EXTERRIOR OF BUILDING
AND TERMINATE WITH
90 EL DOWN.

SAFETY RELIEF VALVE @ 25 PSI


P

1'-0"

EXTERIOR

9" LONG NIPPLE SCREWED


INTO DRIP PAN ELBOW &
INSERTED INTO RISER PIPE.
SEE SAFETY VALVE DETAIL

BY-PASS PIPE
WITH GLOBE
VALVE
CONTROL TUBING
WITH NEEDLE
VALVE

12" SONO-TUBE FORM 30" BELOW


GRADE

18

DRIP PAN ELBOW


3"
125 PSI HPS

CP-1

ROUTE TO
FLOOR DRAIN

DOAS-1 DETAIL

GRADE

4" SCHEDULE 40 STEEL PIPE

1"

2"
2"

CLEVIS HANGERS

PRV-3 AND PRV-4 STEAM PRESS. REDUCING STATION


PRESSURE
GAUGE WITH
COCK AND
SIPHON LOOP

#5 @ 12' EW

#4 W / 1'-8" LEGS
@ 2'-0"

MC6x12.0 CHANNEL

DRIP PAN ELBOW


P

1/2" x 5-1/2" x 5-1/2" PLATE

3/16"

17

OUTDOOR EQUIPMENT PAD

EQ EQ
1'-0"

PIPE SAFETY VALVE


DISCHARGE TO
EXTERRIOR OF BUILDING
AND TERMINATE WITH
90 EL DOWN.

16

2'-6" MIN

9" LONG NIPPLE SCREWED


INTO DRIP PAN ELBOW &
INSERTED INTO RISER PIPE.
SEE SAFETY VALVE DETAIL

BY-PASS PIPE
WITH GLOBE
VALVE
CONTROL TUBING
WITH NEEDLE
VALVE

REFRIGERANT PIPING SUPPORT

13

PR

PRESSURE
GAUGE WITH
COCK AND
SIPHON LOOP

CONDENSATE PUMP DETAIL

12

24" MIN.

PRV-1 AND PRV-2 STEAM PRESS. REDUCING STATION

PIPE

PIPE JACKET &


INSULATION
11

11

PLAN VIEW

POLYSULFIDE SEALANT

PLAN VIEW

12

12

59"

65"

SCALE: NONE

11

6"

6"

IC

ELEVATION VIEW
SCALE: NONE

11

DS

ELEVATION VIEW
SCALE: NONE

556-4098

HVAC
DETAILS

M502
02-21-2011

NONE

CU-1

CU-2
REYQ240PYDNR
REMQ120PYDNR

115.0ft [6]
3/8"x7/8"x3/4"

7.0ft [3]
3/8"x5/8"x1/2"

REMQ120PYDNR

4.0ft [2]
3/8"x5/8"
1/2"x1 1/8"x3/4"

KHRP25A33T

BHFP26P90U
BS-14

1/2"x1 1/8"x3/4"
3/4"

FC-5
50.0ft [4]
5/8"x1 3/8"x1 1/8" *

30.0ft [4]
3/8"x7/8"x3/4"

3.0ft
3/8"x5/8"x1/2"

24.0ft [3]
1/4"x1/2" *

75.0ft [1]
3/8"x5/8"x1/2"

18.0ft [2]
1/4"x1/2" *

KHRP25M73TU

KHRP25A33T
BS-1
BSVQ36PVJU
BS-15

FC-4
35.0ft [4]
5/8"x1 1/8"x1 1/8"

5.0ft
3/8"x7/8"x3/4"

FC-1
FXLQ12MVJU

3.0ft
3/8"x5/8"x1/2"

12.0ft [4]
3/8"x5/8"

3.0ft [4]
5/8"x1 1/8"x1 1/8"
KHRP25M73TU

2.0ft [2]
3/8"x5/8"x1/2"

6.0ft [3]
3/8"x5/8"

to centralized controller

KHRP25M73TU

CU-2

KHRP25A33T
BS-2
BSVQ36PVJU
BS-16

FC-6
11.0ft
5/8"x1 1/8"x1 1/8"

17.0ft
3/8"x3/4"x5/8"

FC-5
FXMQ24PVJU

2.0ft
3/8"x5/8"x1/2"

8.0ft [2]
3/8"x5/8"

3.0ft
3/8"x5/8"x1/2"

REYQ240PYDNR
OUT F1/F2

6.0ft [4]
3/8"x5/8"

IN F1/F2

thinkchamplin.com

REMQ120PYDNR
Q1/Q2

KHRP25M73TU

L1, L2, L3

BS-3
BSVQ60PVJU
BS-17

FC-8
FXMQ48PVJU

REMQ120PYDNR
Q1/Q2

FC-7
10.0ft
5/8"x1 1/8"x1 1/8"

16.0ft [2]
3/8"x5/8"x1/2"

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

21A 3ph

KHRP25A22T

C22.0ft [4]
1/4"x1/2" *

2.0ft [1]
3/8"x5/8"x1/2"

L1, L2, L3

12.0ft [2]
3/8"x5/8"

21A 3ph

KHRP25M73TU

L1, L2

0.1A 1ph

BS-1
BS-4
BSVQ36PVJU
BS-18

FC-7
FXMQ36PVJU

FC-4
24.0ft
5/8"x1 1/8"x1 1/8"

4.0ft [1]
3/8"x5/8"x1/2"

BSVQ36PVJU
OUT F1/F2

8.0ft [2]
3/8"x5/8"

FC-1

IN F1/F2

F1/F2

BS-5
BSVQ36PVJU

FC-6
FXMQ30PVJU

OUT F1/F2

FC-5

IN F1/F2
L1, L2

OUT F1/F2

14.0ft [4]
1/2"x1 1/8"x3/4"

20A 3ph

2.0ft [1]
3/8"x5/8"x1/2"

12.0ft [2]
3/8"x5/8"

F1/F2

OUT F1/F2

FC-7

IN F1/F2

F1/F2

L1, L2

0.1A 1ph

BS-14

OUT F1/F2

FC-5

IN F1/F2
L1, L2

F1/F2

BS-15

OUT F1/F2

FC-4

IN F1/F2
L1, L2

F1/F2

L1, L2

F1/F2

L1, L2

FC-4
FXMQ24PVJU

L1, L2

4.0ft [1]
3/8"x5/8"x1/2"

3.0ft [4]
3/8"x5/8"

OUT F1/F2

BS-9
BSVQ36PVJU
14.0ft [5]
3/8"x5/8"x1/2"

2.3A 1ph

F1/F2
0.1A 1ph

BS-18

FC-6
FXMQ30PVJU

FC-4

IN F1/F2

IN F1/F2

OUT F1/F2

6.0ft [4]
3/8"x5/8"

P1/P2

F1/F2

BS-10
BSVQ36PVJU
30.0ft [2]
3/8"x3/4"x5/8"

35.0ft [3]
3/8"x5/8"x1/2"

FC-5
FXMQ24PVJU

FC-5

F1/F2

FC-6

L1, L2

F1/F2

2.0ft [1]
3/8"x5/8"x1/2"

FC-5

IN F1/F2
L1, L2

F1/F2

BRC1E71

2.3A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-43

OUT F1/F2

1.8A 1ph

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

BRC1E71

FXMQ24PVJU

FC-4

BSVQ36PVJU

12.0ft [3]
1/4"x1/2" *

BRC1E71

P1/P2

L1, L2

0.1A 1ph

BS-10

FC-4
FXMQ18PVJU

2.9A 1ph

FXMQ30PVJU

BSVQ36PVJU

BS-43
BSVQ36PVJU

BRC1E71

P1/P2

L1, L2

0.1A 1ph

IN F1/F2

OUT F1/F2

2.3A 1ph

FXMQ24PVJU
IN F1/F2

OUT F1/F2

5.0ft
1/4"x1/2" *

1.6A 1ph

40.0ft [4]
3/8"x5/8"x1/2"

BRC1E71

P1/P2

L1, L2

0.1A 1ph

BSVQ36PVJU

BRC1E71

L1, L2

F1/F2

BS-9

2.9A 1ph

2.3A 1ph

FXMQ36PVJU

BSVQ36PVJU

KHRP25A22T

OUT F1/F2

FC-7

BS-8

BRC1E71

L1, L2

DAYTON VAMC
BRC1E71

P1/P2

L1, L2

0.1A 1ph

BSVQ36PVJU

KHRP25A22T

BRC1E71

P1/P2

F1/F2

BS-7

1.6A 1ph

P1/P2

L1, L2

FC-6

IN F1/F2

8.0ft
3/8"x3/4"x5/8"

2.9A 1ph

FXMQ30PVJU
BS-8
BSVQ36PVJU

BRC1E71

P1/P2

F1/F2

6.0ft [3]
3/8"x5/8"

L1, L2
FC-7

IN F1/F2

IN F1/F2

KHRP25A33T

1.8A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-17

OUT F1/F2

2.0ft [1]
3/8"x5/8"x1/2"

BRC1E71

FXMQ30PVJU

L1, L2
FC-6

IN F1/F2

BRC1E71

L1, L2

0.1A 1ph

BS-16

OUT F1/F2

11A 1ph

P1/P2

L1, L2

0.1A 1ph

10.0ft
3/8"x7/8"x3/4"

FC-6

BSVQ36PVJU
OUT F1/F2

3.4A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-5
FC-7
FXMQ36PVJU

BRC1E71

FXMQ36PVJU

L1, L2
BS-7
BSVQ36PVJU

1.8A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-4

KHRP25M72TU

BRC1E71

FXMQ48PVJU

BSVQ36PVJU

IN F1/F2
L1, L2, L3

FC-8

L1, L2

FC-6
FXMQ30PVJU

P1/P2

L1, L2

0.1A 1ph

IN F1/F2

CU-1

OUT F1/F2

F1/F2

BSVQ60PVJU

to centralized controller

0.5A 1ph

FXMQ24PVJU

BS-3

8.0ft [2]
3/8"x5/8"

L1, L2

0.1A 1ph

BS-2
BSVQ36PVJU

REFRIGERANT PIPING SCHEMATIC - CU-1 - THIRD FLOOR CENTER CORE UNITS

BRC1E71

FXLQ12MVJU

L1, L2

KHRP25M73TU

28A 1ph

P1/P2

1.8A 1ph

P1/P2

BRC1E71

FXMQ18PVJU
IN F1/F2

F1/F2

L1, L2

1.6A 1ph

KHRP25A22T

L1, L2

0.1A 1ph

BS-11

WIRING SCHEMATIC - CU-1 - THIRD FLOOR CENTER CORE UNITS

BS-11
BSVQ36PVJU

FC-4
FXMQ18PVJU

BSVQ36PVJU
OUT F1/F2

8.0ft
3/8"x5/8"x1/2"

8.0ft [1]
3/8"x5/8"x1/2"

FC-4

L1, L2

F1/F2

FC-1

BSVQ36PVJU
bacnet gateway
BS-12
BSVQ36PVJU

L1, L2

12.0ft [2]
3/8"x5/8"x1/2"

FC-1
FXLQ12MVJU

OUT F1/F2

I-TOUCH (WITH WEB


& PPD OPTIONS)

BS-13
BSVQ36PVJU

CU-2

F1/F2

OUT F1/F2

IN F1/F2
L1, L2

F1/F2

FC-2
FXLQ18MVJU

P1/P2

L1, L2

0.1A 1ph
FC-2

BSVQ36PVJU
OUT F1/F2

1.6A 1ph

BRC1E71

FXLQ12MVJU

BS-13

17.0ft [2]
1/4"x1/2" *

L1, L2

0.1A 1ph

BS-12

KHRP25A22T

BRC1E71

FXMQ18PVJU
IN F1/F2

25.0ft [2]
1/4"x1/2" *

P1/P2

0.5A 1ph

P1/P2

BRC1E71

FXLQ18MVJU
IN F1/F2

F1/F2

L1, L2

0.6A 1ph

WIRING SCHEMATIC - CU-2 - BASEMENT AND FIRST FLOOR UNITS

REFRIGERANT PIPING SCHEMATIC - CU-2 - BASEMENT AND FIRST FLOOR UNITS

L1, L2
CU-1

OUT F1/F2
CU-3

VARIABLE REFRIGERANT VOLUME SYSTEM INSTALLATION NOTES


COUT F1/F2

1.
CU-4

2.

OUT F1/F2

3.

CENTRALIZED CONTROL WIRING SCHEMATIC

ENTIRE VRV SYSTEM INCLUDING FAN COIL UNITS, BRANCH


SELECTOR BOXES, CONDENSING UNITS AND ALL CONTROLS
SHALL BE MANUFACTURED BY ONE MANUFACTURER.
FOR CLARIFICATION PURPOSES ALL REFRIGERATION VALVES
AND SPECIALTIES ARE NOT SHOWN ON THE ABOVE SCHEMATIC.
CONTRACTOR IS TO FURNISH AND INSTALL ALL VALVES,
REFRIGERATION SPECIALTIES AND ACCESSORIES AS REQUIRED
BY VRV SYSTEM MANUFACTURER AND PROJECT
SPECIFACATIONS.
PIPING LAYOUT MAY VARY FROM MANUFACTURER TO
MANUFACTURER. CONTRACTOR SHALL INSTALL PER
MANUFACTURER RECOMMENDATIONS AND ALL
REQUIREMENTS SHALL BE INCLUDED IN CONTRACTORS BID
PRICE.

IC

DS

556-4098

HVAC
SCHEMATICS

M503
02-21-2011

NONE

CU-3
CU-4

3/8"x7/8"x3/4"
BHFP26P90U
120.0ft [8]
5/8"x1 1/8"x1 1/8"

3/8"x7/8"x3/4"

210.0ft [12]
5/8"x1 1/8"x3/4" *

6.0ft
3/8"x5/8"x1/2"

20.0ft [3]
1/4"x1/2" *

KHRP25M72TU

3/4"
21.0ft
3/8"x5/8"x1/2"

to centralized controller

23.0ft [4]
1/4"x1/2" *

BS-39

FC-1

CU-3

KHRP25M73TU

REYQ192PAYD
BS-19

FC-1

10.0ft
1/2"x1 1/8"x3/4"

IN F1/F2

OUT F1/F2

10.0ft
3/8"x5/8"x1/2"

16.0ft [2]
1/4"x1/2" *

KHRP25M72TU
5.0ft
5/8"x1 1/8"x1 1/8"

21.0ft
3/8"x5/8"x1/2"

23.0ft [4]
1/4"x1/2" *

Q1/Q2

L1, L2, L3
BS-40

20A 3ph

KHRP25M73TU

BS-20

FC-1

Q1/Q2

13.0ft
1/2"x1 1/8"x3/4"

L1, L2, L3

FC-1

6.0ft [2]
3/8"x5/8"x1/2"

5.0ft [3]
3/8"x5/8"

thinkchamplin.com

KHRP25M72TU

20A 3ph
10.0ft
5/8"x1 1/8"x1 1/8"

6.0ft
3/8"x5/8"x1/2"

10.0ft [2]
3/8"x5/8"

BS-41

424 East Fourth Street


Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

FC-8

KHRP25M73TU

L1, L2
BS-21

0.1A 1ph

BS-19

FC-8

FC-1

16A 1ph

P1/P2

30.0ft
3/8"x7/8"x3/4"

BRC1E71

15.0ft [2]
3/8"x5/8"x1/2"

13.0ft [4]
1/4"x1/2" *

KHRP25A33T
8.0ft [4]
5/8"x1 1/8"x1 1/8"

22.0ft
3/8"x5/8"x1/2"

OUT F1/F2

26.0ft [2]
1/4"x1/2" *

L1, L2

KHRP25M73TU

F1/F2

22.0ft
3/8"x5/8"x1/2"

FC-1

OUT F1/F2

0.5A 1ph
BS-42

FC-1

IN F1/F2
L1, L2

19.0ft [2]
1/4"x1/2" *

L1, L2

0.1A 1ph

BS-20

BS-22

10.0ft
5/8"x1 1/8"x1 1/8"

IN F1/F2

F1/F2

L1, L2

0.1A 1ph

BS-21

P1/P2

FC-8

FC-2

BRC1E71
15.0ft [1]
3/8"x3/4"x5/8"

0.5A 1ph

P1/P2

4.0ft [2]
3/8"x5/8"x1/2"

20.0ft [4]
3/8"x5/8"

KHRP25A22T

BRC1E71
BS-35

FC-3

KHRP25M73TU

OUT F1/F2
BS-23

IN F1/F2
L1, L2

FC_1

F1/F2
0.1A 1ph

BS-22
6.0ft
1/2"x1 1/8"x3/4"

22.0ft
3/8"x5/8"x1/2"

25.0ft [4]
1/4"x1/2" *

OUT F1/F2

L1, L2

FC-1

IN F1/F2

F1/F2

3.4A 1ph

P1/P2

L1, L2

13.0ft
3/8"x5/8"x1/2"

4.0ft
3/8"x5/8"x1/2"

12.0ft [2]
1/4"x1/2" *

KHRP25A22T

BRC1E71

0.5A 1ph

BS-36

FC-1

KHRP25M72TU

L1, L2

0.1A 1ph

BS-23
BS-24

FC_1

P1/P2

BRC1E71

4.0ft
3/8"x5/8"x1/2"

FC-1

5.0ft
3/8"x5/8"x1/2"

16.0ft [2]
1/4"x1/2" *

DAYTON VAMC

KHRP25A22T

OUT F1/F2
46.0ft [2]
3/8"x5/8"

L1, L2

22.0ft
3/8"x5/8"x1/2"

F1/F2

OUT F1/F2

FC-1

IN F1/F2

F1/F2

IN F1/F2
L1, L2

11.0ft
3/8"x5/8"x1/2"

9.0ft [2]
3/8"x5/8"

F1/F2

FC-1

21.0ft [2]
3/8"x5/8"x1/2"

0.5A 1ph

P1/P2

OUT F1/F2

FC-1

IN F1/F2
L1, L2

KHRP25A33T

L1, L2

0.1A 1ph

BS-26

FC-1

F1/F2

16.0ft [2]
1/4"x1/2" *

BRC1E71

FC-6

FC-1

3.4A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-27
BS-27

BS-37

BRC1E71

BS-38

KHRP25A33T

10.0ft
3/8"x7/8"x3/4"

0.5A 1ph

P1/P2

L1, L2

FC-8

19.0ft [2]
1/4"x1/2" *

BS-26

L1, L2

0.1A 1ph

BS-24

FC-8

27.0ft
3/8"x7/8"x3/4"

IN F1/F2

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

BRC1E71

REFRIGERANT PIPING SCHEMATIC - CU-4 - THIRD FLOOR EAST UNITS

0.5A 1ph

P1/P2

BRC1E71

FC-6

OUT F1/F2

IN F1/F2

F1/F2

62.0ft [4]
3/8"x5/8"

L1, L2

FC-8

2.3A 1ph

P1/P2

BRC1E71

to centralized controller
IN F1/F2

F1/F2

L1, L2

3.4A 1ph
CU-4

FC-8

OUT F1/F2

IN F1/F2
L1, L2, L3

REFRIGERANT PIPING SCHEMATIC - CU-3 - THIRD FLOOR EAST UNITS

WIRING SCHEMATIC - CU-3 - THIRD FLOOR EAST UNITS

21A 3ph

L1, L2

0.1A 1ph

BS-39

OUT F1/F2

FC-1

IN F1/F2
L1, L2

F1/F2

OUT F1/F2

FC-1

IN F1/F2
L1, L2

F1/F2

FC-8

IN F1/F2
L1, L2

F1/F2

OUT F1/F2

FC-2

IN F1/F2
L1, L2

F1/F2

OUT F1/F2

FC-3

IN F1/F2
L1, L2

F1/F2

FC-1

0.5A 1ph

BRC1E71

3.4A 1ph

BRC1E71

0.6A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-36

BRC1E71

P1/P2

L1, L2

0.1A 1ph

BS-35

0.5A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-42

BRC1E71

P1/P2

L1, L2

0.1A 1ph

BS-41

OUT F1/F2

L1, L2

0.1A 1ph

BS-40

7.9A 1ph

P1/P2

BRC1E71

0.6A 1ph

P1/P2

BRC1E71

VARIABLE REFRIGERANT VOLUME SYSTEM INSTALLATION NOTES


1.
2.

3.

ENTIRE VRV SYSTEM INCLUDING FAN COIL UNITS, BRANCH


SELECTOR BOXES, CONDENSING UNITS AND ALL CONTROLS
SHALL BE MANUFACTURED BY ONE MANUFACTURER.
FOR CLARIFICATION PURPOSES ALL REFRIGERATION VALVES
AND SPECIALTIES ARE NOT SHOWN ON THE ABOVE SCHEMATIC.
CONTRACTOR IS TO FURNISH AND INSTALL ALL VALVES,
REFRIGERATION SPECIALTIES AND ACCESSORIES AS REQUIRED
BY VRV SYSTEM MANUFACTURER AND PROJECT
SPECIFACATIONS.
PIPING LAYOUT MAY VARY FROM MANUFACTURER TO
MANUFACTURER. CONTRACTOR SHALL INSTALL PER
MANUFACTURER RECOMMENDATIONS AND ALL
REQUIREMENTS SHALL BE INCLUDED IN CONTRACTORS BID
PRICE.

IC
OUT F1/F2

IN F1/F2
L1, L2

F1/F2
0.1A 1ph

BS-37

OUT F1/F2

FC-1

IN F1/F2
L1, L2

F1/F2

FC-1

IN F1/F2

F1/F2

0.5A 1ph

P1/P2

L1, L2

0.1A 1ph

BS-38

OUT F1/F2

L1, L2

BRC1E71

0.5A 1ph

556-4098

P1/P2

L1, L2

DS

BRC1E71

0.5A 1ph

HVAC
SCHEMATICS
WIRING SCHEMATIC - CU-4 - THIRD FLOOR EAST UNITS

M504
02-21-2011

NONE

DP-1

DA-1

DP-2

EHXT

EF-C
EF-S

EAT

DP-3

SD-1

EF

OUTSIDE
AIR
HX

EXHAUST
AIR

CCT FB-D LL-T

LHXT
C

EXHAUST
AIR

HE-1

SF

ST
C

DISCHARGE
AIR

LAT

SF-C
SF-S
VA-1

DA-2

DAT

NO

OUTSIDE WALL

DOAS-1 & 2 CONTROLS SCHEMATIC DIAGRAM

OAT
(STM)

WEATHER SHIELD

(COND)

CONDENSING UNIT
DX1-C R-X
DX2-C R-X

thinkchamplin.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081

DOAS-1 & 2 CONTROLLER POINTS


TYPE:
AI - ANALOG INPUT
AO - ANALOG OUTPUT
DI - DIGITAL INPUT
DO - DIGITAL OUTPUT
PI - PULSED INPUT

TAG

TYPE

DA-1

DO

DA-2
DP-1

DO
DI

DP-2

DI

DP-3

DI

DX1-C

DO

DX2-C

DO

EF-C

DO

EF-S

DI

HE-1

AI

LL-T

DI

SD-1

DI

SF-C

DO

SF-S

DI

OAT

AI

EHXT

AI

CCT

AI

DAT

AI

EAT

AI

LAT

AI

LHXT

AI

VA-1

AO

FEATURES:
D - DISPLAYED ON WORKSTATION GRAPHICS
M - MODIFIED/OVERRIDDEN FROM WORKSTATION GRAPHICS
A - ALARMS AT WORKSTATION
L - LOGGED/TRENDED AT WORKSTATION
S - TIME SCHEDULED AT WORKSTATION
G - GLOBALLY SHARED TO ALL CONTROLLERS

DESCRIPTION
OUTSIDE
DAMPER CONTROL
EXHAUST
DAMPER CONTROL
PRE-FILTER DIFF.
PRESSURE
FINAL-FILTER DIFF.
PRESSURE
PANEL-FILTER DIFF.
PRESSURE
DX COOLING
STAGE 1 COMMAND
DX COOLING
STAGE 2 COMMAND
FAN START/STOP
COMMAND
FAN STATUS
DISCHARGE AIR
HUMIDITY SENSOR
LOW TEMPERATURE
LIMIT SENSOR
SMOKE DETECTOR
STATUS
FAN START/STOP
COMMAND
FAN STATUS
OUTSIDE AIR
TEMPERATURE
HEAT EXCHANGER ENT
TEMPERATURE
COOLING COIL
TEMPERATURE
DISCHARGE AIR
TEMPERATURE
EXHAUST AIR TEMP
ENTERING UNIT
EXHAUST AIR TEMP
LEAVING UNIT
HEAT EXCHANGER LVG
TEMPERATURE
HEATING
VALVE CONTROL

DOAS-1 & 2 OPERATION

QTY

FEATURES
A L
S

1
1

X
X

X
-

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS (PART 2)

SAFETIES - ALL CONTROLS SHALL INCORPORATE THE FOLLOWING HARDWIRED


SAFETIES. THE FOLLOWING SAFETIES SHALL BE PROVEN TO BE OPERATIONAL
UPON FINAL CHECKOUT. LOW TEMPERATURE LIMIT "FREEZESTAT" SHALL STOP
THE AIR HANDLING UNIT FAN IF A TEMPERATURE BELOW 38 DEG F. IS DETECTED.
SMOKE DETECTORS SHALL STOP THE AIR HANDLING UNIT FAN WHEN SMOKE IS
DECTECTED.

HEAT RECOVERY CONTROL - HEAT RECOVERY IS FIXED PLATE TYPE WITH NO


MOVABLE PART OR CONTROLS.

NOTES

DOAS-1 & 2 OPERATION

MODE CONTROL - THE AIR HANDLING UNIT SHALL BE CAPABLE OF OPERATING IN


THE FOLLOWING MODES: OCCUPIED, AND UNOCCUPIED MODES. THE UNIT
SHALL BE AUTOMATICALLY INTIATED THROUGH TIME-OF-DAY SCHEDULES
(APPLICATION PROGRAMS).

DISCHARGE AIR CONTROL - DURING THE OCCUPIED MODE THE UNIT SHALL
MAINTAIN DISCHARGE AIR SETPOINT. THE HEATING AND COOLING CONTROLS
SHALL BE MODULATED IN SEQUENCE TO MAINTAIN A DISCHARGE AIR
TEMPERATURE BETWEEN 68 AND 75 DRY BULB (ADJUSTABLE).
DEHUMIDIFACATION CONTROL - DURING THE OCCUPIED CYCLE, A SUPPLY AIR
HUMIDITY SENSOR SHALL ENERGIZE THE COOLING SYSTEM AND REHEAT COIL TO
MAINTAIN MAXIMUM 60 PERCENT RELATIVE HUMIDITY (ADJUSTABLE).

OCCUPIED MODE - THE SUPPLY AND EXHAUST FANS SHALL BE INDEXED TO START.
THE TEMPERATURE CONTROLS SHALL FUNCTION AS SPECIFIED BELOW DURING
THE OCCUPIED OPERATION.
UNOCCUPIED - THE AIR HANDLING UNIT SHALL BE DE-ENERGIZED. SEE BELOW FOR
DESCRIPTION OF DE-ENERGIZING AIR HANDLER.

VARIABLE REFRIGERANT FLOW -SYSTEM


SEQUENCE OF OPERATIONS

FAN CONTROL - WHENEVER THE UNIT IS INDEXED TO START, THE FOLLOWING


SEQUENCE SHALL BE EXECUTED: THE DDC SYSTEM SHALL ENABLE THE ELECTRIC
RELAY. THIS RELAY SHALL OPEN THE OUTSIDE AND EXHAUST DAMPERS. UPON
CONFIRMATION OF THE OUTSIDE AIR DAMPER BEING FULLY OPEN, AS
INDICATED BY ELECTRIC END SWITCH, THE SUPPLY AND EXHAUST FANS SHALL BE
STARTED. ONCE THE FAN STATUS HAS BEEN PROVEN, THE DISCHARGE AIR
CONTROL SHALL BE ENABLED. WHENEVER THE UNIT IS DE-ENERGIZED, DUE TO
EITHER A SCHEDULED SHUTDOWN OR A SAFETY TRIP, THE FOLLOWING
SEQUENCE SHALL BE EXECUTED: THE SUPPLY AND EXHAUST FANS SHALL STOP.
THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL FULLY CLOSE. THE DX
COOLING SHALL BE DISABLED. THE REHEAT COIL VALVE SHALL REMAIN UNDER
CONTROL. IF THE LOW TEMPERATURE LIMIT SAFETY "FREEZESTAT" HAS
TRIPPED, THE HEATING COIL VALVE SHALL FULLY OPEN TO THE COIL. IF EITHER
FAN IS ENABLED BY THE MANUAL SWITCH AT THE DRIVE, THE ASSOCIATED
DAMPERS SHALL OPEN TO ALLOW FAN OPERATION.
REHEAT CONTROL IF THE OUTSIDE AIR TEMPERATURE IS AT OR ABOVE 40 DEG F. THE FOLLOWING
SHALL OCCUR: THE FACE AND BYPASS DAMPER SHALL BE POSITIONED TO
ALLOW FULL AIR FLOW THROUGH THE FACE OF THE STEAM COIL. THE
DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED THROUGH THE
MODULATION OF THE STEAM OR DX COOLING IN SEQUENCE.
IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40 DEG F. THE FOLLOWING SHALL
OCCUR: THE STEAM VALVE SHALL BE OPEN TO PROVIDE FULL STEAM FLOW
THROUGH THE STEAM COIL. THE DISCHARGE AIR TEMPERATURE SHALL BE
MAINTAINED THROUGH THE MODULATION OF THE FACE AND BYPASS DAMPERS
TO MAINTAIN SETPOINT.

THE VARIABLE REFRIGERANT FLOW (VRF) SYSTEM SHALL CONSIST OF AN


OUTDOOR CONDENSING UNIT WITH VARIABLE SPEED COMPRESSOR(S) AND
MULTIPLE INDOOR FAN COILS. VRF CONTROL SYSTEM SHALL BE BY THE SAME
MANUFACTURER AS VRF SYSTEM. THE SYSTEM SHALL BE CONTROLLED ON AN
OCCUPIED/UNOCCUPIED TIME SCHEDULE AS DEFINED AT THE OPERATOR
WORKSTATION. THE VRF SYSTEM SHALL HAVE CENTRALIZED CONTROLLERS. THE
BUILDING AUTOMATION SYSTEM SHALL INTERFACE TO THE VRF SYSTEM
CONTROLLER TO ADJUST SETPOINTS, OCCUPY ZONES, AND MONITOR THE
SYSTEM.

DAYTON VAMC

THE VRF CONDENSING UNIT SHALL MODULATE TO MATCH THE LOAD OF THE
CONNECTED INDOOR UNITS.
OCCUPIED MODE
THE INDIVIDUAL FAN COILS SHALL CYCLE THE FAN UPON A CALL FOR
COOLING OR HEATING. THE FAN COIL SHALL OPERATE AT REDUCED LOAD
AND VARY THE REFRIGERANT FLOW TO FULL COOLING OR HEATING UNTIL THE
SPACE IS AT THE OCCUPIED COOLING OR HEATING SETPOINT. FAN COIL
UNIT
CONTROLLER SHALL COMMUNICATE WITH THE BRANCH SELECTOR BOX TO
CONTROL THE MODE OF OPERATION (HEATING OR COOLING).
UNOCCUPIED MODE
THE FAN AND DX COOLING COIL SHALL BE CYCLED TO MAINTAIN AN
INCREASED UNOCCUPIED SPACE TEMPERATURE SETPOINT.

RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256

IN, HEATING MODE, THE FAN AND DX COIL SHALL BE CYCLED TO MAINTAIN
DECREASED UNOCCUPIED SPACE TEMPERATURE SETPOINT.
THE UNIT SHALL BE CONTROLLED ON ITS OWN OCCUPIED/UNOCCUPIED TIME
SCHEDULE AS DEFINED AT THE OPERATOR WORKSTATION.

SYSTEM POINTS:
TYPE
DESCRIPTION
AI
SPACE TEMPRATURE
AD
SPACE OCCUPIED SETPOINT
AD
SPACE UNOCCUPIED SETPOINT
DO
OCCUPIED COMMAND
AO
VRF CONDENSING UNIT COMMAND
AI
VRF SYSTEM LOAD %
DI
VRF CONDENSING UNIT STATUS
DI
FAN COIL FAULT
DI
VRF CONDENSING UNIT FAULT

QUANTITY
1 (PER FAN COIL)
1 (PER FAN COIL)
1 (PER FAN COIL)
1 (PER FAN COIL)
1 (PER COND. UNIT)
1 (PER COND. UNIT)
1 (PER COND. UNIT)
1 (PER FAN COIL)
1 (PER COND. UNIT)

RETURN
AIR

AHU-1 OPERATION
OAD-C
OAD-ES

SEQUENCE OF OPERATIONS

LL-T

TE-1
SF

ST

OUTSIDE
AIR

DISCHARGE AIR
TO ASSOCIATED SPACES

C
R-X
VA-1

SF-C

(STM)

SF-S
TE-2

NO

(COND)

SAFETIES - ALL CONTROLS SHALL INCORPORATE THE FOLLOWING HARDWIRED


SAFETIES. THE FOLLOWING SAFETIES SHALL BE PROVEN TO BE OPERATIONAL
UPON FINAL CHECKOUT. LOW TEMPERATURE LIMIT "FREEZESTAT" SHALL STOP
THE AIR HANDLING UNIT FAN IF A TEMPERATURE BELOW 38 DEG F. IS DETECTED.
SMOKE DETECTORS SHALL STOP THE AIR HANDLING UNIT FAN WHEN SMOKE IS
DECTECTED.
MODE CONTROL - THE AIR HANDLING UNIT SHALL BE CAPABLE OF OPERATING IN
THE FOLLOWING MODES: OCCUPIED, AND UNOCCUPIED MODES. THE UNIT
SHALL BE AUTOMATICALLY INTIATED THROUGH TIME-OF-DAY SCHEDULES
(APPLICATION PROGRAMS).
OCCUPIED MODE - THE SUPPLY SHALL BE INDEXED TO START. THE TEMPERATURE
CONTROLS SHALL FUNCTION AS SPECIFIED BELOW DURING THE OCCUPIED
OPERATION.

AH-1 CONTROLLER POINTS


TYPE:
AI - ANALOG INPUT
AO - ANALOG OUTPUT
DI - DIGITAL INPUT
DO - DIGITAL OUTPUT
PI - PULSED INPUT

FEATURES:
D - DISPLAYED ON WORKSTATION GRAPHICS
M - MODIFIED/OVERRIDDEN FROM WORKSTATION GRAPHICS
A - ALARMS AT WORKSTATION
L - LOGGED/TRENDED AT WORKSTATION
S - TIME SCHEDULED AT WORKSTATION
G - GLOBALLY SHARED TO ALL CONTROLLERS

TAG

TYPE

DESCRIPTION

QTY

SF-C

DO

SF-S

DI

TE-1

AI

TE-2

AI

VA-1

AO

LL-T

DI

OAD-C

DO

OAD-ES

DI

FAN START/STOP
COMMAND
SUPPLY FAN
STATUS
DISCHARGE AIR
TEMPERATURE
SPACE
TEMPERATURE
HEATING
VALVE CONTROL
LOW TEMPERATURE
LIMIT SENSOR
OUTSIDE AIR DAMPER
COMMAND
OUTSIDE AIR DAMPER
END SWITCH STATUS

FEATURES
A L
S

NOTES

UNOCCUPIED - THE AIR HANDLING UNIT SHALL BE DE-ENERGIZED. SEE BELOW FOR
DESCRIPTION OF DE-ENERGIZING AIR HANDLER.
FAN CONTROL - WHENEVER THE UNIT IS INDEXED TO START, THE FOLLOWING
SEQUENCE SHALL BE EXECUTED: THE DDC SYSTEM SHALL ENABLE THE ELECTRIC
RELAY. THIS RELAY SHALL OPEN THE OUTSIDE AIR DAMPER. UPON
CONFIRMATION OF THE OUTSIDE AIR DAMPER BEING FULLY OPEN, AS
INDICATED BY ELECTRIC END SWITCH, THE SUPPLY FAN SHALL BE STARTED.
ONCE THE FAN STATUS HAS BEEN PROVEN, THE ROOM TEMPERATURE CONTROL
SHALL BE ENABLED. WHENEVER THE UNIT IS DE-ENERGIZED, DUE TO EITHER A
SCHEDULED SHUTDOWN OR A SAFETY TRIP, THE FOLLOWING SEQUENCE SHALL
BE EXECUTED: THE SUPPLY FAN SHALL STOP. THE OUTSIDE AIR DAMPER SHALL
FULLY CLOSE. THE REHEAT COIL VALVE SHALL REMAIN UNDER CONTROL. IF THE
LOW TEMPERATURE LIMIT SAFETY "FREEZESTAT" HAS TRIPPED, THE HEATING
COIL VALVE SHALL FULLY OPEN TO THE COIL. IF EITHER FAN IS ENABLED BY THE
MANUAL SWITCH AT THE DRIVE, THE ASSOCIATED DAMPERS SHALL OPEN TO
ALLOW FAN OPERATION.
REHEAT CONTROL IF THE OUTSIDE AIR TEMPERATURE IS AT OR ABOVE 40 DEG F. THE FOLLOWING
SHALL OCCUR: THE FACE AND BYPASS DAMPER SHALL BE POSITIONED TO
ALLOW FULL AIR FLOW THROUGH THE FACE OF THE STEAM COIL. THE ROOM
AIR TEMPERATURE SHALL BE MAINTAINED THROUGH THE MODULATION OF THE
STEAM IN SEQUENCE.
IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40 DEG F. THE FOLLOWING SHALL
OCCUR: THE STEAM VALVE SHALL BE OPEN TO PROVIDE FULL STEAM FLOW
THROUGH THE STEAM COIL. THE ROOM AIR TEMPERATURE SHALL BE
MAINTAINED THROUGH THE MODULATION OF THE FACE AND BYPASS DAMPERS
TO MAINTAIN SETPOINT.
ROOM TEMPERATURE CONTROL - DURING THE OCCUPIED MODE THE UNIT SHALL
MAINTAIN ROOM TEMPERATURE SETPOINT CONTROLLED BY THERMOSTAT
LOCATED IN THE SPACE. THE HEATING CONTROLS SHALL BE MODULATED IN
SEQUENCE TO MAINTAIN ROOM SETPOINT (ADJUSTED). SETPOINT IS TO BE
ADJUSTABLE THROUGH CENTRAL DDC SYSTEM.

IC

DS

556-4098

HVAC
VENTILATION
SCHEDULES AND
CONTROL
DIAGRAMS

M505
02-21-2011