Вы находитесь на странице: 1из 2

SAT REPORT FOUR WAY PANELS ABB 22kV/415V substation

CLIENT

M/s MUSANADA

SHS09-07

S/S

CONSULTANT

M/s MOTT
MACDONALD / PB
POWER

CONTRACTOR
DATE

ARC JV CSCEC
15/02/2015

PROJECT NAME: DEVELOPMENT OF SOUTH SHAMKA INFRASTRUCTURE LOT-3


BUS BAR CONTACT RESISTANCE:
All CBs and Isolator are in closed position
Phase

Injected Current

R TO R
Y TO Y

100A

B TO B

Measured Contact Resistance()


J01-J04

J01-J02

J02-J03

J03-J04

276

298

356

326

321

235

314

317

264

255

268

288

TEST EQUIPMENT DETAILS:


Sl. No

Description
LOW RESISTANCE

01

METER

Make

Model

Serial No

Calibration Due

MEGGER

DLRO 200

101013729

23/02/2016

HV TEST FOR BUSBAR:

COMPANY

Tested By

Witnessed By

Witnessed By

Witnessed By

Approved By

SPACEAGE

CSCEC JV ARC

MOTT MACDONALD

PB POWER

ADDC

NAME
SIGNATURE
DATE
Rev #4

Page 47 of 48

SAT REPORT FOUR WAY PANELS ABB 22kV/415V substation


CLIENT

M/s MUSANADA

SHS09-07

S/S

M/s MOTT
MACDONALD / PB
POWER

CONSULTANT

CONTRACTOR
DATE

ARC JV CSCEC
15/02/2015

PROJECT NAME: DEVELOPMENT OF SOUTH SHAMKA INFRASTRUCTURE LOT-3

INSULATION RESISTANCE TEST OF 22KV SWICHGEAR


Phase

Applied Megger Voltage


for 1Min

Before HV Test
()

After HV Test
()

Remarks

R : Y+B+E

5000 V

609 G

523 G

OK

Y : R+B+E

5000 V

636 G

426 G

OK

B : R+Y+E

5000 V

566 G

356 G

OK

A.C HIGH VOLTAGE TEST: (TIME DURATION: 1MIN)


Phase

Applied Voltage (kV)

Leakage Current (mA)

Remarks

R : Y+B+E

40

7.0

OK

Y : R+B+E

40

7.2

OK

B : R+Y+E

40

6.9

OK

TEST EQUIPMENT DETAILS:


Sl. No

Description

Make

Model

Serial No

Calibration Due

01

INSULATION TESTER

MEGGER

MIT 520

20039

27/09/2015

02

HV TEST

HV

PFT 1003 CMF

168

24/02/2016

COMPANY

Tested By

Witnessed By

Witnessed By

Witnessed By

Approved By

SPACEAGE

CSCEC JV ARC

MOTT MACDONALD

PB POWER

ADDC

NAME
SIGNATURE
DATE
Rev #4

Page 48 of 48