Check that Transformer-1,2,3,5&6,ICT1 &ST1 / ST4 are connected to 220Kv Bus #1. Check that Sectionalizer#1,220 KV bay 12 is closed. Check that Drives load(variable load) of Platemill is not on Transformer#3. Check that Generation of Islanding units(1&6 is balanced with the connecting loads on 220KV Bus#1 Check that ICt#1 MVAR import / export is not more than 10
Check that Transformer-1,2,3,5&6,ICT1 &ST1 / ST4 are connected to 220Kv Bus #1. Check that Sectionalizer#1,220 KV bay 12 is closed. Check that Drives load(variable load) of Platemill is not on Transformer#3. Check that Generation of Islanding units(1&6 is balanced with the connecting loads on 220KV Bus#1 Check that ICt#1 MVAR import / export is not more than 10
Check that Transformer-1,2,3,5&6,ICT1 &ST1 / ST4 are connected to 220Kv Bus #1. Check that Sectionalizer#1,220 KV bay 12 is closed. Check that Drives load(variable load) of Platemill is not on Transformer#3. Check that Generation of Islanding units(1&6 is balanced with the connecting loads on 220KV Bus#1 Check that ICt#1 MVAR import / export is not more than 10
Before putting the Unit 1&6 in island mode. Check that Transformer-1,2,3,5&6,ICT1 &ST1/ST4 are connected to 220KV Bus #1. Check that Sectionalizer#1 ,220 KV bay 12 is closed. Check that Drives load(variable load) of Platemill is not on Transformer#3.
After putting the Unit 1&6 in island mode.
Check that Generation of Islanding units(1&6) is balanced with the connecting loads on 220KV Bus#1 Check that ICt#1 MVAR import/export is not more than 10 MVAR. Do's and Don'ts Do Not Couple the Bus 1&Bus 2(trafo 3 & trafo 4) in south switchgear. Do not Close the buscoupler (Bay 8 or Bay 25). Do Not open the Sectionalizer#1 ,220 KV bay 12.
After Island from grid
Inform the various utilities that now system is islanded and caution them not to switch ON/OFF any lo Do Not Couple the Bus 1&Bus 2(trafo 3 & trafo 4) in south switchgear. Do not Close the buscoupler (Bay 8 or Bay 25). Do Not open the Sectionalizer#1 ,220 KV bay 12. Do Not switch ON/OFF any feeder.