a) Calculo A1:

Id=

1.25
=1.25 ; KT KA=1
KTKA

=499.2 por lo tanto Id=624 A

S=( 31500m m2 )
Calculo A2:

Id=
=

1.25
=1.25
KTKA

104
192
100

=199.68
Id=249.6 A ; S= ( 3195 mm2 )
Calculo A3:

Id=
=

1.25
=1.25
KTKA

104
130=135.2 por lotanto Id =169 A
100

S=( 3150 mm2 )


Calculo A4:

Id=

TA=15KW

I
=I
KTKA

Id=I =

15000
=75.75 A
2200.9

S=( 3116 mm2 )

Calculo F11:

P=

0.746HP
; n=0.95
n

P(200HP)=157.05KW
P(75HP)=58.89KW
P(50HP)=39.26KW

cos =0.9

TA =
HP
200
75
50
TA

15000
=43.73
3 ( 220 )0.9
KW
157.05
58.89
39.26
15
270.2

In
499.2
199.68
135.2
43.73
877.81

Id ( F 11 )= I i+ 0.25(499.2)
i=1

Id ( F 11 )=877.81+124.8=1002.61 A
Id=

I
=1002.61 A
KTKA

Calcular F12:

MD=75KW

I MD =

75000
fr
3 ( 220 )0.8

cos =0.8

cos =0.95

I MD =246.03 A
Id=

I MD
=246.03 A
KTKA

S=( 31120m m2 )
Calcular F13:

MD=55KW

I MD =

55000
fr
3 ( 220 )0.95

I MD =455.8 A
Id=

I MD
=455.8 A
KTKA

S=( 31300 mm2 )


Calculo F0:

Carga
F11
F12
F13

P(KW)
270.2
100
60
430.2

Q(KVar)
91.144
75
19.72
185.864

185.864

430.2

cos real=0.9179
I n=

430200
=1229.96 A
3 ( 220 )0.9179
I d=

1229.96
=768.73 A
20.8

S=( 31500m m2 )
b)

V = 3 I n L( fase cos + X fase cos )

80 = 20(1+ (tt 0))

80= 20 (1+0.0039(60))
80 = 20 1.2358
In

A1

499.2

Seccin
transver
sal
500

mm

20

80

V /
220%

0.0601

0.0743

0.366

0.166%

0.193

0.2385

0.548

0.24%

A2

199.68

95 m m

A3

135.2

50 mm

0.387

0.4783

0.896

0.41%

A4

43.73

16 mm

1.15

1.4212

0.872

0.39%

Ahora para F11:

cos
0.95
0.95
0.95
0.9

P(KW)

Q(KVar)

In

157.05
58.89
39.26
15
270.2

51.62
19.36
12.90
7.264
91.144

499.2
199.68
135.2
43.73
877.81

91.144

270.2

cos real=0.9475

Id F 11=1002.61 A ;

S=( 31500m m2 )

20 =0.0601
80 =0.0743
I d=

1002.61
=626.63
20.8

V = 3877.810.0050.07430.9475
V =0.535
V
0.535
100 =
100=0.243 <2.5
V
220
*Cada de tensin de F0 ( 500 mm

80= 20(1+ (tt 0))

( 0.0601 ) ( 1+ 0.00393 ( 60 ) )
80 =0.074
V = 3 I n L( fase cos + X fase cos )
Dnde:
In=1299.9
L=0.003

fase =0.074
cos =0.918

X fase =0
V = 3 ( 1299.9 ) ( 0.003 ) ( 0.074 ) ( 0.918 )
V =0.458

V =

0.458100
=0.208
220
0.208 < 2.5 %Vn

c) Proteccin por sobrecarga de A1( 500 mm

Proteccin termo magntica para A1


Multiplicamos 1.25 al valor nominal para seleccionar el interruptor
termomagnetico
In*(1.25)=624 A
escogemos el valor prximo de la tabla I 800 A
El calibre de conductor a tierra es 1% AWG.

Tubera para A1 tenemos 4 conductores y

500 mm

de seccin del

conductor segn la tabla II.


La dimensin de la tubera seria

115 m m2

*Proteccin por sobrecarga para F11 ( 500 mm

de dimetro.

Proteccin termo magntica para F11


In*(1.25)=877.8*(1.25)=1095.27
Escogemos el valor 1200 de la tabla I
El calibre de conductor a tierra es 3% AWG.
Tubera para F11

500 mm2

Tenemos 4 conductores y
La dimisin ser

75 mm

segn la tabla II

de dimetro.

*Proteccin por sobrecarga para F0 ( 500 mm

In*(1.25)=(1229.9)(1.25)=1537.37
Escogemos 1600 A de la tabla I.

El calibre de conductor a tierra es 4% AWG.


Tubera para F0

500 mm2

Tenemos 7 conductores y
La dimisin ser

155 mm

de dimetro.

Proteccin contra cortocircuito para proteger A1, F11 Y F0 se instala un


fusible en F0:
Capacidad fusible cortocircuito = 1.75(F11+F12+F13)
Como:
F11=877.8 A
F12=246.03 A
F13=455.8 A
La capacidad de fusible=1.75(877.82+246.03+455.8)
=2764.38
POR LO TANTO : Elegimos un fusible de 3000 A.