Академический Документы
Профессиональный Документы
Культура Документы
GEK 28156k
Revised, June 2012
GE Energy
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to
be met in connection with installation, operation or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser's purposes the matter should be referred to General Electric
Company. These instructions contain proprietary information of General Electric Company, and are furnished to its customer solely
to assist that customer in the installation, testing, operation, and/or maintenance of the equipment described. This document shall
not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of General
Electric Company.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
The following notices will be found throughout this publication. It is important that the
significance of each is thoroughly understood by those using this document. The definitions are
as follows:
NOTE
Highlights an essential element of a procedure to assure correctness.
CAUTION
Indicates a potentially hazardous situation, which, if not avoided, could result in minor
or moderate injury or equipment damage.
WARNING
INDICATES A POTENTIALLY HAZARDOUS SITUATION, WHICH, IF
NOT AVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY
***DANGER***
INDICATES AN IMMINENTLY HAZARDOUS SITUATION,
WHICH, IF NOT AVOIDED WILL RESULT IN DEATH OR
SERIOUS INJURY.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
TABLE OF CONTENTS
I.
II.
III.
IV.
V.
GENERAL .................................................................................................................................................. 4
GAS TURBINE........................................................................................................................................... 4
A. Factory Preservation for Shipment ........................................................................................................ 4
B. Gas Turbine Storage ............................................................................................................................ 11
C. Gas Turbine Long Term Storage ......................................................................................................... 12
D. Instruction for Long Term Storage of Rotor Upon Receipt at Destination.......................................... 17
CONTROL EQUIPMENT ...................................................................................................................... 18
A. Factory Preparation for Shipment ........................................................................................................ 18
B. Storage and Transportation .................................................................................................................. 19
OFF BASE ACCESSORY MODULES.................................................................................................. 20
A. External Water Cooling Skid Module.................................................................................................. 20
B. Off Base Atomizing Air Skid .............................................................................................................. 22
C. Liquid Fuel Skids................................................................................................................................. 23
D. Fuel Gas Module (MLI 0991) and Fuel Gas Compartment (MLI A160) Preservation ....................... 24
E. Water Injection Skid Preservation (as applicable) ............................................................................... 25
LOAD GEAR ............................................................................................................................................ 26
A. Factory Preparation for Shipment ........................................................................................................ 26
B. Storage ................................................................................................................................................. 26
LIST OF FIGURES
Figure 1. Example of a Borescope fogging tool..................................................................................................... 6
Figure 2. Dehumidifier Port Patch ....................................................................................................................... 10
Figure 3. Emitter Pads VCI-309........................................................................................................................... 10
Figure 4. MilCorr VpCI Shrink Film ................................................................................................................... 11
Figure 5. Closed Loop Humidity Control See drawing 372A4635 for CFM values............................................ 14
LIST OF TABLES
Table 1. Required amounts of VpCI 337GE for Internal Fogging......................................................................... 5
Table 2. Preservation Part Numbers....................................................................................................................... 9
Table 3. Tarp Drawing Numbers.......................................................................................................................... 12
Table 4. Dehumidification system components, 372A4635 ................................................................................ 15
LIST OF CHECKLISTS
Checklist 1. Pre-Storage....................................................................................................................................... 27
Checklist 2. Bi-Weekly Storage Inspection ......................................................................................................... 28
Checklist 3. 1-Year Storage Inspection................................................................................................................ 29
Checklist 4. Final Visual Inspection .................................................................................................................... 30
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
I. GENERAL
These instructions have been issued to recommend minimum protection and preservation for storage of
heavy-duty gas turbines and their accessory equipment. Both short term and long-term storage are
described. Information for short-term storage relates to periods up to 1 year. Long-term storage
information refers to periods of storage in excess of 1 year. Storage period begins when equipment ships
from the factory to an onsite or off-site storage location. This document supersedes GEK 111645.
These instructions cannot anticipate all of the environmental conditions and other variables to which a
customer may have to expose his equipment for one reason or another. It is essential therefore that
reasonable judgment be used and additional protective measures taken where necessary and appropriate.
For shipment of materials direct from vendor, the vendors will provide required factory protection and
include special site instructions with the shipment if notified that long-term storage is required.
This information is furnished to serve as a guide in giving proper protection under a given situation.
Protection of this type of equipment can be complex and subject to so many variables that each owner
should determine his plan of protection. This documents content will not create any liability whatsoever
on the part of the General Electric Company or it employees whether in warranty, alleged negligence or
otherwise. The General Electric Company may be consulted for any special shipping or storage concerns
applicable to a specific unit. In addition to information provided refer to maintenance and System
Description section of the Service Manual.
II. GAS TURBINE
A. Factory Preservation for Shipment
This section describes the preservation requirements performed in the General Electric
Manufacturing facility prior to shipment. When executing the requirements listed below, the factory
should ensure the following steps are taken to protect equipment that can be damaged by shock or
vibration during shipment:
Parts that are required to be removed from an assembly shall be identified properly for
replacement
Articles with moving parts or projecting parts are blocked, braced, or tied down. If possible
they should be disassembled and separately packaged.
ACCESSORY BASE
The oil tank and associated base oil and water piping, valves are to remain wetted after factory test. If
internals of accessory base are 100% painted, then no fogging will be required. Prior to storage and
shipment, the lube oil tank is filled and turbine base oil channels fogged using Engineer approved
turbine oil w/corrosive reducing additives. This turbine oil is a vapor space inhibiting oil with an anti
rust compound. This corrosion inhibitor fills the vapor space to form a rust preventative barrier on all
exposed metal surfaces. After fogging the oil tank, open flanges and pipe flanges on the accessory
base are covered with metal or plastic flange covers bolted to the flanges and then sealed properly
with gasket material or other sealing material to prevent corrosion inhibitor from escaping. All other
open flanges or pipes are sealed with plugs to avoid contaminants from entering.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
All doors, access doors and panels are secured to the frame. Milcor material and a desiccant capsule
are placed into all electrical junction boxes. Desiccant capsules are devices designed to provide
corrosion protection in enclosed non-ventilated areas up to 5 cubic feet. Vapor phase corrosion
inhibitor technology emits a protective coating on all metal surfaces.
TURBINE INTERIOR
The compressor section of the turbine is fogged using VpCI-337GE anti-corrosive material or
approved acceptable substitute. VpCI 337GE is a vapor phase corrosion inhibitor. To determine the
required amount reference Table 1. Fogging is performed by spraying the VpCI material into the
compressor using a borescope fogging tool (Figure 1) using pressurized shop air. The fogging tool
will be inserted thru existing Borescope holes on either side of the casing; the best practice is to
choose a set of borescope holes in the compressor section that are closest to the inlet, and a set
towards the exhaust end. The direction of the spray should be done to help coat both upstream and
downstream at each Borescope hole. The fogging agent fills the entire internal compressor area and
attaches to any exposed bare metal surfaces by creating a chemical bond that forms an anticorrosion
barrier.
Table 1. Required amounts of VpCI 337GE for Internal Fogging
Frame
0.73 (2.76)
0.37 (1.40)
0.66 (2.50)
1.04 (3.94)
0.52 (1.97)
0.94 (3.56)
1.24 (4.69)
0.62 (2.35)
1.13 (4.28)
0.80 (3.03)
0.40 (1.51)
0.60 (2.27)
0.37 (1.40)
0.19 (0.72)
0.37 (1.40)
1.16 (4.39)
0.58 (2.20)
0.88 (3.33)
1.40 (5.30)
0.70 (2.65)
1.05 (3.97)
1.16 (4.39)
0.58 (2.20)
0.88 (3.33)
1.40 (5.30)
TBD
TBD
0.70 (2.65)
TBD
TBD
1.05 (3.97)
TBD
TBD
9E
6FA (scale from 7FA)
LMS Booster
7FA
9FA (scale from 7FA)
7FB (same as 7FA)
9FB (same as 9FA)
7H
9H
Suggested
Requirement
2.7 - 3 qts
(2.5 - 2.8 liters)
3.75 - 4.25 qts
(3.5 - 4 liters)
4 - 5 quarts
(4.25 - 4.75 liters)
2.5 - 3 quarts
(2.25 - 3 liters)
1 - 1.5 quarts
(1.0 - 1.4 liters)
3.5 - 4.5 quarts
(3.3 - 4.4 liters)
4.0 - 5.5 quarts
(4.0 - 5.3 liters)
3.5 - 4.5 quarts
(3.3 - 4.4 liters)
4.0 - 5.5 quarts
(4.0 - 5.3 liters)
TBD
TBD
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
CAUTION
All emitter pads must be removed prior to unit operation.
EXHAUST EXTERIOR
Prior to sealing the exhaust end of the gas turbine, a pre-determined amount of VCI-309 emitter pads
are hung in a circular pattern around the exhaust flange. The VCI-309 emitter pads (Figure 2) emit
chemical vapors that are attracted to bare metal and bond with metal to form a corrosion resistant
barrier. The exhaust end is then covered with MilCorr VpCI shrink film, which is sized to fit the
exhaust, and secured in place via a heat shrink method or tied in place. The MilCorr VpCI shrink film
is a vapor phase corrosion inhibitor with UV light protection. Reference Figure 3 for the required
MilCorr dimensions.
For the E Class turbines, the exhaust plenum is covered with either rectangular corrugated plastic or
metal cover.
INLET EXTERIOR
Prior to sealing the inlet end of the gas turbine, a pre-determined amount of VCI-309 emitter pads are
hung in a circular pattern around the inlet flange. The VCI-309 emitter pads (Figure 2) emit chemical
vapors that are attracted to bare metal and bond with metal to form a corrosion resistant barrier. The
inlet end is then covered with MilCorr VpCI shrink film, which is sized to fit the inlet, and secured in
place via a heat shrink method or tied in place. The MilCorr VpCI shrink film is a vapor phase
corrosion inhibitor with UV light protection. Reference Figure 3 for the required MilCorr
dimensions.
For the F Class turbines, bearings located inside of the inlet plenum are covered with a corrugated
plastic cover, which is attached to the rotor-blocking device MLI 0103 prior to installation of the
MilCorr shrink film. After the MilCorr shrink film is installed, a circular corrugated plastic cover is
applied on top of the MilCorr.
For E class turbines, the inlet plenum is covered with Milcorr shrink fill, and then a rectangular
corrugated plastic cover is installed over top or a wooden crate is constructed around entire inlet.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
TURBINE EXTERIOR
All exposed external, non-machined surfaces shall be covered by one of the following surface
protection methods: paint or engineering approved turbine oil w/corrosive reducing additives. Tectyl
506 is applied to all exposed machined surfaces. Following application of the surface protection
method, the turbine is enclosed by a large tarp. The tarp is cinched and shrunk around the turbine
ensuring the inlet and exhaust ends are sealed. This tarp is to remain on the turbine during storage and
transit.
For the 9E turbines, the exhaust plenum will not be cover with this tarp because the plenum is already
covered metallic cover.
For on-base enclosures, enclosure doors, access doors and panels are secured to the frame. Milcorr
material and a desiccant capsule are placed into all electrical junction boxes. Desiccant capsules are
devices designed to provide corrosion protection in enclosed non-ventilated areas up to 5 cubic feet.
Vapor phase corrosion inhibitor technology emits a protective coating on all metal surfaces.
NOTE
Assure that all parts are dry prior to storage.
CONNECTION COVERS
All gas turbine connections, including extraction and secondary flow ports, pressure monitoring
parts, bearing lube oil feed and drain openings and etc. shall be covered to protect the gas turbine
from contamination. Flange covers may be metal or plastic construction. They shall be secured to the
gas turbine in such a way as to ensure that they do not fall out during shipment.
Steel covers shall be painted on both sides and made of stainless steel.
All covers shall be painted or made of colored plastic to indicate that they are temporary
flange covers.
For connection identifiers on the drawing that lists flange covers, refer to MLI 0329 view
drawing for detailed locations.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
MISCELLANEOUS
Turbine base machined parts are covered with 1 coat of Tectyl 506. Shock indicators (258A4714P001
and P002) shall be mounted as per drawing 255A4682 if required by contract or justified. One of
each shock indicator shall be mounted on the face of the speed ring and one each on the forward
face-off the combustion ring. Shock indicators have an adhesive back. To install, remove the tape
liner and press the unit onto a clean flat surface.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
Ordering
Drawing
P001
P002
P003
P004
P005
P006
P007
P025
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
P008
P009
P010
P011
P012
P013
P014
P015
P016
P017
P018
P019
P026
P027
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
P020
P021
P022
P023
P024
P028
P029
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
100T2452
Blu-Guard Cover
7E Turbine Flanged Cover
7E Accessory Base Flanged Cover
9E Turbine Flanged Cover
9E Accessory Base Flanged Cover
7FA.03/.04 Turbine Quonset Cover
7FB Turbine Quonset Cover
9FA Turbine Quonset Cover
7FA.05 Turbine Quonset Cover
Blu-Guard Accessories
Truion Patch
Mesh Bag VCI-309
9FA Exhaust Circular Bonnet
7FA.03/.04 Exhaust Circular Bonnet
7FB Exhaust Circular Bonnet
9FA Inlet Semi-Circular Bonnet
7FA.03/.04 Inlet Semi-Circular Bonnet
7FB Inlet Semi-Circular Bonnet
7E Inlet - Bonnet w/ropes
7E Exhaust - Bonnet w/ropes
LMS Exhaust Circular Bonnet
LMS Inlet Semi-Circular Bonnet
7FA.05 Exhaust Circular Bonnet
7FA.05 Inlet Semi-Circular Bonnet
Miscellaneous
Polyken 360-17 Printed Waterproof Repair Tape 4 Wide
Polyken 360-17 Printed Waterproof Repair Tape 2 Wide
Milcorr (Roll)
Blu-Guard (30ft Roll) (VpCI-126)
Shock Indicator Viewing Box
Dehumidifier Port 4 Patch
Dehumidifier Port 6 Patch
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
10
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
3. Check for visible surface rust. All rusty areas must be reported to the Power Answer Center.
4. The unit will be inspected, following a formal documented inspection checklist (Refer 1 Year
Storage Inspection Checklist). This inspection will include outer surfaces as well as borescoping
of the gas turbine internals. All functional and cosmetic rust must be reported through the Power
Answer Center immediately. Cosmetic rust is defined by any rust that does not affect the heat
rate output, life or serviceability of the gas turbine. The bearings will be inspected with a
borescope through a pipe plug in the sealed drain line during the annual inspection. Any rust
found within the bearing area, will be reported through the Power Answer Center immediately.
Once the inspection is complete, new engineered approved turbine oil w/corrosive reducing
additives will be added into each of the bearings.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
11
GEK 28156k
5. If the tarp is damaged anytime during storage, the recommendation is to replace the tarp. Heat
guns are required to shrink the tarp. Shrinkfast Model #998. 200,000 BTUs or equivalent are
recommended. New rope may be required if the old rope cannot be used to tie down the bottom
tarp. Comparable rope can be purchased at any local hardware store. In lieu of the above
shrink-wrap, one can use the alternative vinyl coated nylon tarp (Drawing 255B9506P001). If the
gas turbine is stored inside and the tarp is in working condition, the tarp can be repaired by
sewing or taping any hole. It is also acceptable to remove the shrink-wrap until the unit is ready
to be shipped to site for internal storage only. See Table 3 for list of drawing numbers per frame
size.
332B7317P016
332B7318P004
357B1925P001
116E2885P005
332B7318P002
332B7338P002
332B7318P003
332B7338P004
332B7318P004
MS-7FA
MS-9FA
6. Upon the completion of the storage term, a full inspection of the unit will be completed, and all
findings reported thru the Power Answer Center. This inspection will include the outer surfaces,
as well as borescoping of the gas turbine internals. All functional and cosmetic rust must be
reported at this time. Cosmetic rust is defined by any rust that does not affect the heat rate
output, life or serviceability of the gas turbine. Rust removal recommendations will be obtained
from engineering, that come thru the Power Answer Center. The condition of the unit must be
documented on the formal inspection checklist. Refer to Final Visual Inspection Checklist
C. Gas Turbine Long Term Storage
Long-term storage is defined as duration in excess of 1 year. All reference points in Gas Turbine
storage should follow one of the following options:
12
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
Option A:
Before the unit is stored, the unit will be inspected, and all deficiencies reported through the Power
Answer Center.
The turbine shall be stored inside a building.
Restore back to factory preservation for shipment (Section A) by replenishing or repairing any
original factory preservation. Examples are Milcorr Shrink Film, Emitter Pads or fogging.
Option B:
Before the unit is stored, the unit will be inspected, and all deficiencies reported through the Power
Answer Center.
If electric is available, hook up air dryer to turbine to provide a humidity controlled air circulated
loop. This closed loop air circulation will go through the turbine where circulated air maintained at
low humidity and above the dew point temperature. The airflow will circulate from gas turbine inlet
to exhaust. The air will be filtered, dehumidified and electrically heated (if required) (Refer to Figure
4). If the dehumidified system decreases the temperature of the circulated air, a heater must be
provided to maintain the internal air temperature within10 degrees of ambient.
The relative humidity of the closed loop system must be kept lower than 30% at all times the unit is
in storage. Each unit will have a dedicated dehumidifier. The flow rate will be in the range of
150-300 cfm. The tarp should be tightened around the unit since the tarp is open at the bottom. The
inlet and exhaust should be sealed in order to minimize the amount of outside air leakage
contaminating the closed loop system. The quality of the dehumidified air will be sacrificed if
leakage occurs in the closed loop system.
The bearings will be preserved by using engineer approved turbine oil w/corrosive reducing additives
upon the start of the storage term; the site will verify the approved turbine oil is stocked in the
bearing area.
The temperature and humidity of the air will be monitored and recorded at least twice a week as well
as the condition of the air filters. Ripped or dirty filters are to be replaced immediately. These
procedures are covered in the Bi-Weekly Storage Inspection checklist.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
13
GEK 28156k
14
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
Description
Dehumidifier 60 hertz
6 Diameter x 25 Flexaust reinforced flexible duct
10 gage wire
Dehumidifier 50 hertz
10 x 6 Duct Reducer
6 x 4 Duct Reducer
6 Diameter x 100 Flexaust reinforced flexible duct
Dehumidifier Requirements
P001
PROCESS
CFM
175 min
LENGTH
(inch)
29 max
WIDTH
(inch)
28
HEIGHT
(inch)
22 max
RATED
VOLTAGE
240/1/60
P004
178 min
29 max
28
22 max
240/1/50
FCL
(Amp)
27.8
max
27.8
max
WEIGHT
(lb)
150 max
150 max
The dehumidification unit shall be run in a continuous mode during the following periods:
While in storage.
When installed on its pedestal in the power plant until such time as it is no longer practical to
do so. This decision shall be coordinated with the site Project Manager.
Supply and return hoses from the dehumidifier to the turbine inlet and exhaust are in place
with no leaks.
Visual assurance that all shrink-wrap, covers and tarps are still securely in place.
Ensures that the tarp is free of moisture and the drain is free of obstructions.
Preparation for Shipment for Rotor only to be Stored Long Term
Each operator is responsible for all dimensions he/she generates while performing this operation.
7. Maintain workstation in a neat and orderly manner.
8. Out-of-cycle fixtures, gages or masters cannot be used or kept at the workstation.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
15
GEK 28156k
9. Always match the part number and serial number to the part number and serial number on the
router. Re-mark if the marking is removed.
10. Refer any questions to your supervisor or engineer.
11. Record data per Q.C. Card and obtain Q.C. Verification as required.
12. With the rotor still in the balancing machine, clean the entire rotor with GE approved solvent
(EG. NAPHTHA or equivalent). Remove rusty spots on the rotor surfaces, if any, using
Scotchbrite. Use shop compressed air to dry all parts.
NOTE
Avoid handling parts with bare hands; salt and moisture from hands will promote
corrosion.
13. Using a pressurized spray can apply a heavy coat of VCI-379 (or equivalent) corrosion
preventive coating (5 parts water to 1 part of VCI-379) to the entire rotor, except buckets,
journals, thrust collar and seals, until the entire rotor is wet on all surfaces.
NOTE
Cover the floor to catch drippings. Keep the spraying pressure low to minimize
chemical mist.
14. Allow VCI-379 (or equivalent) coating to dry in air for at least 60 minutes.
15. Wrapping of rotor:
a. Wrap compressor rotor blades with ocean or bubble wrap while slowly turning the rotor.
b. Use VCI stretch film to wrap around the rotor with 50% overlapping while slowly turning the
rotor.
NOTE
Do not wrap the journals and onward until the end of the shaft.
c. Place a pre-determined amount of VCI-609 powder (or equivalent) into enclosure while
wrapping of VCI stretch film is in progress. The VCI-609 will slowly evaporate to cover
inaccessible surface and extra protection on top on VCI-379 protective layer. Calculation of
required VCI-609 powder: 130 GMS per m3 of space area.
d. Apply a thick coat of TECTYL 506 (or equivalent) on journals, thrust collar, seal surfaces
and end coupling. Allow TECTYL coating to dry in air. Tape the Bentley burnished areas
with PVC tape. Wrap journals and thrust face with layers of grease tape. Apply TECTYL
506 (or equivalent) on each layer of tape.
e. For wrapping the journals use a heavy coat of Tectyl 506, then layer with a layer of wax
cloth, layer of fiber board and finally with a layer of PVC tape. Then follow with a second
layer of cloth, fiberboard and tape.
16
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
f. Remove rotor from balancing machine. Remove the drive plate, clean and spray Tectyl 506
(or equivalent) on the rotor end face and wrap with oil base grease tape and follow with
layers of shrink-wrap film.
g. Remove rotor from stand or load into shipping crate.
16. Inspect the shipping skid for any damage.
17. Ensure that the inner face of the wooden walls is covered with a layer of plastic sheet. Replace
plastic sheet if necessary.
18. Lay vacuum bag in box. Use PP005/Pet-Alu-HDPE; grade MIL PRF 1 31 J Class 1.
19. Calculate appropriate amount of desiccant for volume of bag. Insert into bag prior to sealing.
Insert humidity indicator at a location that can be seen through viewing window in crate.
20. Rotor placed in vacuum bag, and purged with nitrogen. Seal top of bag with hand sealer. Leave
aperture large enough for vacuum sealer. Vacuum seal.
21. Pack rotor in the shipping skid and secure in place.
22. Cover the top covers of shipping skid.
23. Cover any opening on the sidewall of the shipping skid.
24. Rotor ready to ship.
D. Instruction for Long Term Storage of Rotor Upon Receipt at Destination
1. Inspect the shipping skid and shipping crate for any damage. If shipping crate is damaged, it
must be replaced prior to long-term storage.
2. Before rotor is stored, all deficiencies will be corrected and all findings reported through power
answer center (PAC).
3. Rotor must be stored in an ambient temperature range not exceeding 22F (-30C) and 158F
(70C). Where ambient temperatures exceed this range, space heaters or air conditioners must be
provided by the customer to keep the temperature within these specified limits. Relative
humidity must be kept < 30%. Humidifier with flow rate of 150-300 CFM is required through
container.
4. Humidity indicator to be checked and level to be recorded bi-weekly. Humidity levels > 30% on
indicator to be reported through power answer center (PAC). The temperature and humidity of
the air will be monitored and recorded at least twice a week as well as the condition of the air
filters. Ripped or dirty air filters are to be replaced immediately.
5. Upon the completion of the storage term, a full inspection of the rotor will be completed and all
findings must be reported through the Power Answer Center (PAC). Rust removal
recommendations shall be obtained from an engineering disposition through the PAC. The
factory prep to ship will be reapplied.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
17
GEK 28156k
18
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
19
GEK 28156k
4. Batteries
Refer to Battery Vendor Publications in the gas turbine Service Manual for complete
information. A copy of The Battery Instructions is included in the Accessories Package
shipped with each battery. The battery charger cabinet should contain a copy of the battery
charger instructions.
Read the Receiving section, the Storage section, and the Initial charge section: General Vendors
Instructions before accepting and/or handling the battery.
With 77F or lower storage temperature, a lead-calcium battery must receive boost or initial
charge within six months of the date the battery was manufactured. Higher than 77F storage
temperature will accelerate internal self-discharge of a battery by a factor of two (and therefore
decrease the time between manufacture and initial charge by a factor of 0.5) for each 15F
degrees above 77F storage temperature.
IV.
20
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
c. Check pressure of nitrogen in tube bundle and pump skid (if applicable) weekly. Recharge
with nitrogen to 5 psig as required.
d. Rotate fan, pump and motor shafts and verify proper lubrication of the bearings monthly.
3. Long Term Storage
In addition to the short term storage recommendations,
a. Check all painted surfaces for rust every six months after the unit is put into storage. All
rusted areas must be cleaned and touched up (painted) immediately. If storage is outdoors,
apply one coat of finish (enamel) paint to all primed surfaces. If storage is indoors, it is
recommended that the temperature be maintained between +50F and +160F, and relative
humidity held below 35%.
b. Inspect shafts for adequate preservative every twelve months and add a heavy film of
Valvoline TECTYL 894 (or equivalent) as necessary.
c. For oil to air units, add 5 gallons of engineer approved turbine oil w/corrosive reducing
additives to each header when the unit is put into storage.
d. For the water to air unit in lieu of section IV .A.3.c, above, apply a nitrogen purge to the coil
section as follows:
1)
2)
Blow warm (l00F minimum) air through the unit. The unit is sufficiently dry when a
mirror held in the exhaust air stream does not fog.
3)
Seal the inlet and outlet nozzles with gasketed steel plates. The inlet plate has a tire
valve installed in it, and the outlet plate a .5 inch or .75 inch NPT coupling.
4)
Admit nitrogen via the tire valve. When a match flame held at the outlet is extinguished
(due to the nitrogen concentration of the exhaust air), plug the coupling.
5)
Continue to admit nitrogen until the internal pressure is 5 to 6 psig. Pressure may be
checked with a tire gauge or pressure gauge if installed. Cap the tire valve.
6)
Check nozzle cover joints, tire valve, and outlet coupling plug for leakage.
7)
e. Uncouple the motors and energize them for at least one hour each month. An alternative is to
remove the motors and store them in a controlled environment. For V-belt drive, remove the
belts and sheaves and store in a controlled environment.
f. Rotate the fans a few revolutions every month and assure that the bearings are packed with
grease.
g. Protect top of tube bundle, if exposed, from damage by covering with plywood.
h. Protect pump skid, ship loose structural and piping spool pieces, instrumentation and other
site installed items from corrosion and damage by waterproof packaging, storage in a climate
controlled environment or other such means.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
21
GEK 28156k
22
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
23
GEK 28156k
D. Fuel Gas Module (MLI 0991) and Fuel Gas Compartment (MLI A160) Preservation
1. Factory Preparation for Shipment
a. Loose parts shall be clearly identified and braced to prevent movement during shipping. If
any Strainers, valves or pipe spools are shipped loose, they shall be capped at both ends with
a desiccant pouch attached to the inner surface of one of the blind flanges.
b. Open flanges and pipes shall be sealed with metal shipping covers or blind flanges.
c. Tube connections shall be sealed using a metal tube cap.
d. Gas and air pipes shall be purged with nitrogen and a 5-psig blanket established.
e. Ventilation louvers or dampers shall be internally covered with a sheet-metal panel.
f. VCI paper or desiccant shall be placed inside all junction boxes, panels, and sealed
containers.
g. All enclosure doors and panels shall be securely latched for shipment. A steel shipping brace
shall be installed across each door to prevent it from springing open during shipment.
h. Sheet-metal covers shall be installed over all openings in the roof.
2. Short Term Storage
a. Inspect all primed, painted and galvanized surfaces for oxidation at monthly intervals. Clean
and re-paint as necessary.
b. Inspect pipe caps and flanges for tightness and damage. Replace as necessary. (Note: If a
visible air gap exists between the pipe cover and the pipe, purge the gas piping with nitrogen
and re-establish the seal.
c. Lubricate and rotate fans monthly (if provided).
d. Inspect the desiccant bags monthly to determine if they need replacement.
e. Check the nitrogen pressure blanket monthly to make sure the pressure is above 5 PSIG.
f. Doors shall be kept closed.
3. Long Term Storage
a. Perform Short Term storage checks at monthly intervals.
b. Apply a finish coat to all factory-primed surfaces.
c. Replace either VCI paper or desiccant capsules at least once every six months. If humidity
heaters are provided by GE (customer option) they shall be energized and run during the
storage period using the thermostat provided with them to control their operation. If no
humidity heaters are provided, then the customer may locate a temporary humidity heater
24
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
inside each compartment and run it during the storage period to aid in the preservation of the
equipment.
E. Water Injection Skid Preservation (as applicable)
1. Factory Preparation for Shipment
a. Completely drain water from all skid piping, etc.
b. Thoroughly flush system with 1:1 Propylene Glycol/Demineralized Water Solution. Ensure
that flowmeter(s), filter housing, pump casing and all low points are completely flushed with
this solution. Completely drain as much of this solution as possible from the system.
c. Install steel shipping covers on all flanged openings. Install threaded plugs in all threaded
openings.
d. Apply film of suitable corrosion preventative compound to exposed pump/gearbox/motor
drive shafts.
e. Remove vertical pump motors and package separately for shipment in accordance with motor
manufacturers instructions.
f. VCI paper and desiccant capsules placed in all electrical enclosures and junction boxes.
g. Remove inlet/outlet ventilation hoods and secure them inside the skid enclosure for shipment.
h. Final check and touch-up of all painted surfaces immediately prior to shipment of skid.
i. Seal all openings; install shipping channels to secure all doors closed.
2. Short Term Storage
a. Energize compartment space heaters if provided. If pump motors are installed, energize
motor space heaters if provided.
b. Re-inspect painted surfaces and touch-up as necessary.
c. Reapply corrosion preventative to shafts as necessary, recheck at two monthly intervals.
d. Fill water injection pump gearbox to normal level with specified oil. Manually rotate
pump/motor/gearbox at least five revolutions, check bearing lubrication, repeat at intervals of
six weeks.
e. Operate the cooling fan for approximately one minute at intervals of six weeks.
3. Long Term Storage
In addition to the Short Term storage procedures:
a. If the skid is stored outdoors, all factory primed surfaces must be finish painted.
b. Check and repaint as necessary.
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
25
GEK 28156k
Spray the load gear interior with a mist using one quart of warm (greater than 80F)
engineer approved turbine oil w/corrosive reducing additives.
Seal any openings to the air and access holes immediately after spraying.
If the inspection cover is opened during storage; then after casing has been closed up (except for
minimum access hole), repeat steps 2 and 3, above.
1. Regarding oils equivalent, rust resistance tests must be conducted.
2. Application (spraying) of oil may be accomplished with Sure Shot Sprayer Model A with 302C
Nozzle (extra fine). Sure Shot Sprayer is a product of Milwaukee Sprayer Company, Inc., 5635
West Douglas Avenue, Milwaukee, Wisconsin 53218, toll free phone number: 1-800-558-7035.
This sprayer also comes with CO2 Adapter No. 450, which makes it portable for field use. Three
CO2 cartridges are required to spray one quart of oil.
26
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
Pre-Storage
Serial Number
NOTE
Any discrepancies found during this check must be reported immediately through
the PAC.
Table 1
Check all units for:
Checked by:
(Initials)
Comments
Date:
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
27
GEK 28156k
/
/
/
/
%
F
Good / Poor
%
F
Comments:
Performed by:
28
Date:
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
Checked by:
(Initials)
Comments
Date:
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
29
GEK 28156k
Checked by:
(Initials)
Comments
30
Date:
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
GEK 28156k
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.
31
GEK 28156k
GE Energy
General Electric Company
www.ge-energy.com
32
2012 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part,
without prior permission of the copyright owner.