Device Type Glossary

4009A4

Multipoint: 4 NACs Common


This device type is used when connecting a basic
4009 NAC Extender Panel as a point on an IDNet.

4009A8

Multipoint 8 NACs Common


This device type is used when connecting a 4009 NAC Extender
Panel (expanded to control 8 NAC Circuits) on an IDNet.

ADRPUL

Addressable Pull Station


This device type is used when adding an Addressable Pull Station
to an IDNet.

ANAMON

Analog Monitor ZAM


This device type is used when adding an analog device
(such as VESDA) to an IDNet.

CANPUL

Canadian 2-Stage Pull Station


This device type is used when adding a Canadian 2-Stage
Pull Station to an IDNet.

COMBO

Multipoint: Common, Normal Base

CPHOTO

Caged TrueAlarm Photo


This device type is used when connecting to a Caged Photo Sensor
(used in gyms and prisons)

.
CRPHOTO

Caged True Alarm Photo w/ Relay


This device type is used when connecting a Caged Photo Sensor
with a Relay Base to an IDNet (used in gyms and prisons).
A separate 24 VDC is needed for the relay which is not part of the
base.

CSPHOTO

Caged True Alarm Photo w/ Sounder


This device type is used when connecting a Caged Photo Sensor
with a Sounder Base to an IDNet (used in gyms and prisons).
A separate 24 VDC is needed for the sounder.

CTPHOTO

Caged True Alarm Single Station Photo


This device type is used when connecting a Caged Photo Sensor
with a sounder base to an IDNet (used in gyms and prisons).
A separate 24 VDC is needed for the sounder. Single station
operation has the sounder activate when the Photo Sensor
activates.

FRIAM

Multipoint FRIAM Common

HEAT

TrueAlarm Heat
This device type is used when connecting a TrueAlarm Heat
Sensor to an IDNet.

IAM

IAM Monitor
This device type is used when connecting an individual
conventional device to an IDNet. (used if a 200 degree fixed-temp
detector required).

ICOMBO

Multipoint: Common, Isolator Base

IDNETISO

IDNet Isolator
This device type is used when adding an Isolator card to the IDNet.
It is a mounted I a 4-inch square box and is part of the IDNet circuit.

IHEATHeat w/ Isolator Base


This device type is used when adding a Heat Sensor with an
Isolator base to an IDNet.
IION

Ion Sensor w/ Isolator Base


This device type is used when adding an Ionization Sensor with an
Isolator base to an IDNet.

IOHEAT

Rate of Rise Heat w/Isolator Base


This device type is used when adding a Heat Sensor with an
Isolator base where the application calls for Rate-of-Rise detection.

ION

TrueAlarm Ion
This device type is used when adding an Ionization Sensor to an
IDNet.

IPHOTO

Photo w/ Isolator Base


This device type is used when adding a Photo Sensor with an
Isolator base to an IDNet.

ISO

Isolator
This device type is used when adding a 4-loop Isolator card
(must be physically located next to a MAPNET card).

KACPULL

KAC Pull Station

MAZAM

1 Zone Class A Monitor ZAM IDNet


This device type is used when adding a Class A Zone Adapter
Module to an IDNet. A ZAM takes a conventional zone and makes
it a point on an addressable system. A ZAM requires a separate
24 VDC.

MBZAM

1 Zone Class B Monitor ZAM IDNet


This device type is used when adding a Class B Zone Adapter
Module to an IDNet. A ZAM takes a conventional zone and makes it
a point on an addressable system. A ZAM requires a separate
24 VDC.

MLPTIO

Multipoint: MLPTIO Common

OHEAT

True Alarm Heat w/ ROR


This device type is used when adding a Heat Sensor where the
application calls for Rate-of-Rise detection.

PHOTO

TrueAlarm Photo
This device type is used when adding a Photo Sensor to an IDNet.

POWERISO Power Isolator


This device type is used when adding a Power Isolator to an IDNet.
Adding power isolators to the power circuit allows the circuit to
isolate a 24 VDC short and not take down the entire power circuit.
R4009A4

Multipoint: 4 NACs Common w/ Repeater


This device type is used when connecting a basic 4009 NAC
extender panel with a repeater card as a point on an IDNet.
A repeater card re-amplifies the IDNet communications allowing the
IDNet distance to be extended another 4000 ft. It does not allow
more addressable devices.

R4009A8

Multipoint 8 NACs Common w/ Repeater


(Expanded to control 8 NAC circuits) on an IDNet
This device type is used when connecting a 4009 NAC
extender panel (expanded to control 8 NACs) with a repeater card
as a point on an IDNet. A repeater card re-amplifies the IDNet
communications allowing the IDNet distance to be extended
another 4000 ft. It does not allow more addressable devices.

RCOMBO

Multipoint: Common, Relay Base

RELEASE

Suppression Release Device

RHEAT

TrueAlarm Heat w/ Relay


This device type is used when adding a Heat Sensor with a Relay
Base. A separate 24 VDC is needed for the relay which is not part
of the base.

RIAM

Relay IAM
This device type is used when adding a Relay IAM to an IDNet.
A separate 24 VDC is NOT needed for this module which mounts in
a 4 square box.

RION

TrueAlarm Ion w/ Relay


This device type is used when adding an Ionization Sensor with a
Relay Base to an IDNet. A separate 24 VDC is needed for the relay
which is not part of the base.

ROHEAT

TrueAlarm Heat w/ ROR w/ Relay


This device type is used when application calls for a Heat Sensor
with Rate of Rise and a Relay Base. A separate 24 VDC is needed
for the relay which is not part of the base.

RPHOTO

TrueAlarm Photo w/ Relay


This device type is used when adding a Photo sensor with a Relay
base. A separate 24vdc is needed for the relay which is not part of
the base.

SCOMBO

Multipoint: Common, Sounder

SECIAM

Security IAM
This device type is used when connecting an individual
conventional Security device to an IDNet.

SHEAT

TrueAlarm Heat w/Sounder


This device type is used when adding a Heat Sensor with a
Sounder base. A separate 24 VDC is needed for the sounder.

SION

TrueAlarm Ion w/ Sounder


This device type is used when adding an Ionization Sensor with a
Sounder base to an IDNet. A separate 24 VDC is needed for the
sounder.

SOHEAT

TrueAlarm Heat w/ ROR w/Sounder


This device type is used when the application calls for a Heat
sensor with rate of rise and a Sounder base. A separate 24 VDC is
needed for the sounder.

SPHOTO

TrueAlarm Photo w/ Sounder


This device type is used when the application calls for a Photo
Sensor with a Sounder base. A separate 24 VDC is needed for the
sounder.

TION

TrueAlarm Single Station Ion


This device type is used when the application calls for an Ionization
Sensor with a sounder base which is to operate as a single station.
A separate 24 VDC is needed for the sounder. Single station
operation has the sounder activate when the Photo Sensor
activates.

TPHOTO

TrueAlarm Single Station Photo


This device type is used when the application calls for a Photo
Sensor with a Sounder Base which is to operate as a Single Station
Device. A separate 24 VDC is needed for the sounder. Single
station operation has the sounder activate when the Photo Sensor
activates.

TRIAM

Multipoint: TRIAM Common

UHEAT

Utility TrueAlarm Heat


This device type is used when the application calls for a Heat
Sensor that does not alarm. One application would be a meat
packing plant that would like to turn on a backup AC system if the
temperature reaches 40 degrees.

UNUSED

Unused
This device type is used when the IDNet point is not used
(a spare point).

XIPHOTO

.2% Photo w/ Isolator Base


This device type is used when adding an Extra Sensitive Photo
Sensor with an Isolator Base to an IDNet.

XPHOTO

Extra-Sensitive TrAlm Photo


This device type is used when adding an Extra Sensitive Photo
sensor to an IDNet.

XRPHOTO

Extra-Sensitive TrAlm Photo w/Relay


This device type is used when adding an Extra Sensitive Photo
sensor with a Relay base. A separate 24vdc is needed for the relay
which is not part of the base.

XSPHOTO

Extra-Sensitive TrAlm Photo w/ Sounder


This device type is used when the application calls for an Extra
Sensitive Photo sensor with a Sounder base. A separate 24 VDC is
needed for the sounder.

XTPHOTO

Extra-Sensitive TrAlm sgl-station Photo


This device type is used when the application calls for an Extra
Sensitive Photo sensor with a sounder base is to work as a Single
Station Device. A separate 24 VDC is needed for the sounder.
Single station operation has the sounder activate when the Photo
Sensor activates.