OFFSHORE CABLES
NEK 606:2004

SRL Group

Offshore Cables
NEK 606:2004
Dual Compound
Halogenfree - Mud Resistant
Low Smoke
Flame Retardant
Fire Resistant
IEC 60331-21 @ 1000 Deg C and 1000 V

Type Approvals:

ABS American Bureau of Shipping


DNV
Det Norske Veritas
LRS
Lloyds Register of Shipping

DUAL COMPOUND
NEK 606:2004 Offshore Cables
The objective of CCI was to develop a cable which would perform in some
of the most inhospitable conditions imaginable.
Saline atmosphere, UV radiation, extremes of temperature, hydrocarbons,
oils, drilling fluids and muds while still maintaining the highest levels of
safety for personnel on board.

DUAL COMPOUND
CCIs sheathing materials are flame retardant, halogenfree and resistant to
drilling fluids and muds, in accordance to NEK 606:2004.

EASE OF INSTALLATION
CCIs Flexible Class 2 conductor concept (Patent N MI2003U 00349)
offers significant cost reduction on final installed cable, due to the
unique 4D bending radius, giving unequalled benefits to both Contractors
and final Clients alike, against the traditional rigid stranding.

FLAMEBAR
A complete flame barrier system utilizyng the natural high temperature
characteristics of glass combined with new technology to provide class-leading
Flame Retardant performances, which is the standard all other naval/offshore
cables should be measured.

FIRE RESISTANCE
CCIs entire range of BFOU fire resistant Power, Control and Instrumentation
cables have been approved in accordance to IEC 60331-21 but submitted
to the following test conditions:
1000 Deg C and 1000 V
These severe test conditions are the most stringent offered in the market and
supersede anything available for the naval Offshore Industry today.
This Type Approval is the most stringent and severe test requirement and
supersedes anything available for the Offshore Industry today.

HEPR INSULATION
in order to increase the insulating properties, and, as a result the current
carrying capacity of 0,6/1 kV cables and above, CCI have developed
High Modulus Ethylene Propylene Rubber (HEPR compound).
This offers superior insulation constant (Ki) and significantly improved
ageing performance at higher operating temperatures than 90 Deg C
requested by NEK 606:2004. These results can be seen below on the
ARRHENIUS GRAPH obtained by performing the Thermal Endurance
Evaluation according to IEC 60216, where Temperature Index achieved
has been Ti = 114 Deg C
(witnessed by ABS, DNV and LRS)

Reciprocal thermodynamic temperature (1000/Deg K)


2,66

2,61

2,56

2,51

2,46

2,41

2,36

2,31

2,26

2,21

2,16

160

170

180

190

2,11

100.000

20.000

by courtesy of SBM
10.000

Time (hours)

1.000

100

10
100

110 114 120

130

140

150

200

Temperature (Deg C)
ON REQUEST:

COLD BEND AND IMPACT (CSA C22.2) 40 Deg C with the


search of hydrocarbons in ever more inhospitable climates and increased
use of FPSO vessels which can find themselves operating in extremes of
temperature from one field to another, all cables manufactured by CCI can
be installed and operate at temperatures down to 40 Deg Centigrade.

Type Approvals

ABS

DNV

Lloyds Register

Reference Standards
The informations in this catalog apply to materials, constructions, and
testing of power and telecommunication shipboard and off-shore cables
according to next standards:
NEK 606:2004

Cables for offshore installation halogen-free and/or


mud resistant

IEC 60092-3

Electrical installations in ships

IEC 60092-350

Low voltage shipboard power cables.


General construction and test requirements.

IEC 60092-351

Insulating materials of shipboard power cables.

IEC 60092-352

Electrical installations in ships - Choice and installation


of cables for low voltage power systems

IEC 60092-353

Single and multicore non-radial field power cables with


extruded solid insulation for rated voltages 1 kV and 3 kV.

IEC 60092-359

Sheathing materials for shipboard power and


telecommunication cables.

IEC 60092-376:2003 Electrical installations in ships - Cables for control


instrumentation circuits 150/250 V (300 V).
IEC 60331-21

Tests for electric cables under fire conditions - Circuit integrity


Procedure and requirements - Cables of rated voltage up
to including 0,6/1kV
Enhanced to 1000 Deg C @ 1000 V

IEC 60331-31

Tests for fire resistance with mechanical shocks.


Enhanced to 1000 Deg C @ 1000 V

IEC 60332-1

Tests on electric cables under fire conditions.


Test on a single vertical insulated wire or cable.

IEC 60332-3-22

Tests on electric cables under fire conditions.


Tests for vertical flame spread of vertically-mounted
bunched wires of cables Category A

IEC 60754-1/2

Test on gases evolved during combustion of electric cables.


Part 1:1994 Determination of the halogen acid gas
Part 2:1991 Determination of the degree of acidity
during the combustion of materials taken from electric
cables by measuring pH and conductivity.

IEC 61034-2:1991 Measurement of smoke density of cables burning under


defined conditions.
CSA C22.2 N 38-95 Thermoset Insulated Wires and Cables - Wiring Products
Clause 6.4.4 Low Temperature Flexibility (-40C)
Clause 6.4.5 Low Temperature Impact
(-40C)
6

Cable designation
in accordance to NEK 606:2004
R

ethylene propylene (HEPR or EPR) insulation


halogenfree flame retardant

mica tape + HEPR or EPR insulation


fire resistant halogenfree flame retardant

thermosetting bedding compound


halogenfree flame retardant

O
U

tinned copper wire braid armour

(c)

common screen of copper / polyester tape


tinned copper drain wire over assembled pairs / triples

(i)

individual screen of copper / polyester tape


tinned copper drain wire over each pair / triple

P1/P8

power & control


0,6 / 1 kV
HALOGENFREE & MUD RESISTANT flame retardant

P2/P9

power medium voltage


3,6 / 6 kV
HALOGENFREE & MUD RESISTANT flame retardant

P3/P10

power medium voltage


6 / 10 kV
HALOGENFREE & MUD RESISTANT flame retardant

P4/P11

power medium voltage


8,7 / 15 kV
HALOGENFREE & MUD RESISTANT flame retardant

SHF2 MUD thermosetting dual compound


HALOGENFREE & MUD RESISTANT
flame retardant - (on request: low temperature - 40 Deg C)

P19/P21 power

medium voltage
12 / 20 kV
HALOGENFREE & MUD RESISTANT flame retardant

P20/P22 power

medium voltage
18 / 30 kV
HALOGENFREE & MUD RESISTANT flame retardant

S1/S5

instrumentation individual screen


250 V
HALOGENFREE & MUD RESISTANT flame retardant

S2/S6

instrumentation common screen


250 V
HALOGENFREE & MUD RESISTANT flame retardant

P5/P12

power & control


0,6 / 1 kV
HALOGENFREE & MUD RESISTANT flame retardant fire resistant

S3/S7

instrumentation individual screen


250 V
HALOGENFREE & MUD RESISTANT flame retardant fire resistant

S4/S8

instrumentation common screen


250 V
HALOGENFREE & MUD RESISTANT flame retardant fire resistant
7

Manufacturing Program
Halogenfree
RFOU P1/P8

Power & control, armoured

RFOU(i) S1/S5

Instrumentation, individual screen

RFOU(c) S2/S6

Instrumentation, common screen

RFOU P2/P9

Medium Voltage, armoured

RFOU P3/P10

Medium Voltage, armoured

RFOU P4/P11

Medium Voltage, armoured

RFOU P19/P21

Medium Voltage, armoured

RFOU P20/P22

Medium Voltage, armoured

Mud Resistant
Flame Retardant
page 11
0,6/1 kV
page 15
250 V
page 17
250 V
page 21
3,6/6 kV
page 23
6/10 kV
page 25
8,7/15 kV
page 27
12/20 kV
page 29
18/30 kV

Halogenfree Mud Resistant


Fire Resistant IEC 60331-21 @ 1000 DegC and 1000 V
BFOU P5/P12

Power & control, armoured

BFOU(i) S3/S7

Instrumentation, individual screen

BFOU(c) S4/S8

Instrumentation, common screen

page 33
0,6/1 kV
page 37
250 V
page 39
250 V

ON REQUEST: ALL CABLES LISTED ABOVE CAN BE MANUFACTURED IN


ACCORDANCE TO:
IEC 60092-3 ( Electrical installations in ships )
CSA C 22-2 N 38-95 ( Cold bend and Impact Test to
- 40 Deg C )
IEC 60331-31 ( Fire Resistance test with Mechanical
Shocks @ 1000 Deg C and 1000 V )
8

NEK 606:2004
Halogenfree
MUD resistant

Flame retardant

FLAME RETARDANT TEST


IEC 60332-3-22

10

RFOU P1/P8
Power & Control 0,6/1 kV
Halogenfree & MUD Resistant

Design and construction


Operating temperature
Nominal voltage Uo / U
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-353
90 Deg C (see page 3)
0,6/1 kV
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 INSULATION

halogenfree HEPR compound

3 BEDDING

halogenfree FLAMEBAR

4 BEDDING

halogenfree compound

5 ARMOUR

tinned copper wire braid


according to IEC 60092-352

6 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
1 core
2 cores
3 cores
4 cores
5 cores and above

off-white (grey)
off-white black
off-white black red
off-white black red blue
white & numbered

sheath colour

black

Sheath Marking
CCI RFOU P1/P8 0,6/1 kV n x s/braid mm2
NEK 606:2004 IEC 60332-3-22 meter marking year QA ref.

11

RFOU P1/P8

0,6 / 1 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING at 45 Deg C
approx
in air approx
[mm]
[A]

1
1
1
1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x
x
x
x

16
25
35
50
70
95
120
150
185
240
300

4,8
6,3
7,1
8,3
10,0
11,7
13,0
14,3
16,3
18,7
21,7

1
1,2
1,2
1,4
1,4
1,6
1,6
1,8
2,0
2,2
2,4

10,1
11,7
13,0
14,3
16,2
18,5
19,6
21,4
23,9
27,3
30,7

1,2
1,5
1,6
1,6
1,7
1,8
1,9
2,0
2,1
2,2
2,3

11,2
13,3
14,6
15,9
17,8
20,1
21,2
23,0
25,5
28,9
32,9

385
573
713
896
1.160
1.484
1.758
2.119
2.558
3.240
4.050

45
53
58
64
71
80
85
92
102
116
132

93
117
147
180
283
285
333
386
444
528
612

2
2
2
2
2
2

x
x
x
x
x
x

1.5 /4
2.5 /4
4
/6
6
/6
10 /10
16 /16

1,6
2,0
2,6
3,2
3,8
4,8

1,0
1,0
1,0
1,0
1,0
1,0

10,2
11,2
12,8
13,8
14,8
16,9

1,5
1,5
1,5
1,6
1,6
1,8

14,4
15,5
17,1
18,3
20,2
22,7

317
373
460
546
724
957

58
62
68
73
81
91

23
31
43
55
75
100

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.5 /4
2.5 /6
4
/6
6
/6
10 /10
16 /16
25 /16
35 /16
50 /25
70 /35
95 /50
120 /60
150 /70
185 /95
240/120

1,6
2,0
2,6
3,2
3,8
4,8
6,3
7,1
8,3
10,0
11,7
13,0
14,3
16,3
18,7

1,0
1,0
1,0
1,0
1,0
1,0
1,2
1,2
1,4
1,4
1,6
1,6
1,8
2,0
2,2

10,8
11,9
13,6
14,7
15,8
18,0
21,7
24,6
27,6
31,8
36,7
39,4
43,6
49,0
55,8

1,5
1,5
1,5
1,6
1,6
1,8
1,8
2,0
2,2
2,4
2,6
2,8
2,8
3,0
3,2

15,0
16,1
17,8
19,1
21,1
23,6
27,6
30,9
34,6
39,4
45,2
48,5
54,0
61,0
68,5

349
417
521
627
857
1.148
1.609
2.079
2.780
3.684
4.929
5.954
7.526
9.487
12.050

60
64
71
76
84
94
110
124
138
158
181
194
216
244
274

20
28
37
47
65
87
110
137
167
214
259
301
347
397
468

Electrical Data: see pages 42-44

12

RFOU P1/P8

0,6 / 1 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING at
approx
45 Deg C in air
[mm]
[A]

4
4
4
4
4
4
4
4
4
4
4
4

x
x
x
x
x
x
x
x
x
x
x
x

1.5 /4
2.5 /6
4
/6
6
/6
10 /10
16 /16
25 /25
35 /35
50 /50
70 /35
95 /50
120/60

1,6
2,0
2,6
3,2
3,8
4,8
6,3
7,1
8,3
10,0
11,7
13,0

1,0
1,0
1,0
1,0
1,0
1,0
1,2
1,2
1,4
1,4
1,6
1,6

11,7
12,9
14,8
16,0
17,2
19,7
23,8
27,1
30,4
35,0
40,5
43,5

1,5
1,5
1,5
1,6
1,6
1,8
1,8
2,0
2,2
2,4
2,6
2,8

15,9
17,1
19,0
20,9
22,5
25,6
29,7
33,3
37,4
42,6
49,0
52,6

397
479
616
761
1.009
1.370
1.938
2.520
3.387
4.506
6.042
7.324

64
68
76
84
90
102
119
133
150
170
196
210

20
28
37
47
65
87
110
137
167
214
259
301

7
12
19
37

x
x
x
x

1,5 /6
1,5/10
1,5/10
1,5/16

1,6
1,6
1,6
1,6

1,0
1,0
1,0
1,0

14,0
18,2
21,2
25,6

1,5
1,7
1,8
2,0

18,2
23,6
27,0
31,8

370
545
743
1.291

73
94
108
127

11
9
8
6

7
12
19
27
37

x
x
x
x
x

2.5 /6
2.5/10
2.5/10
2.5/16
2.5/16

2,0
2,0
2,0
2,0
2,0

1,0
1,0
1,0
1,0
1,0

15,3
19,9
23,5
28,4
31,9

1,5
1,7
1,8
2,0
2,2

19,9
25,5
29,3
34,6
38,6

657
1.115
1.516
2.107
2.662

80
102
117
138
154

15
13
11
9
9

Electrical Data: see pages 45-46

13

14

RFOU (i) S1/S5


Instrumentation

250 V

Halogenfree & MUD Resistant - Individual Screen

Design and construction


Nominal voltage
Operating temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-376:2003
250 V
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 INSULATION

halogenfree HEPR compound

3 INDIVIDUAL SCREEN

copper/polyester tape
+ flexible tinned copper drain wire

4 BEDDING
INNER SHEATH

halogenfree FLAMEBAR
halogenfree compound

5 ARMOUR

tinned copper wire braid


according to IEC 60092-376:2003

6 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Pair/Triple Identification
pair
triple

black light blue


light blue black brown
(pairs/triples progressively numbered)

sheath colour

grey
(blue for intrinsically safe)

Sheath Marking
CCI RFOU(i) S1/S5 250 V n x p(trp) x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking

year

QA n

15

RFOU (i) S1/S5

250 V
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM
BENDING RADIUS
approx
[mm]

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

8,1
11,9
13,8
16,5
17,5
20,9
24,1
26,0
28,8
32,7
8,5
13,0
15,1
18,8
20,1
23,6
27,2
29,4
32,6
37,5

1,3
1,4
1,5
1,6
1,7
1,9
2,0
2,1
2,2
2,4
1,3
1,5
1,6
1,7
1,8
2,0
2,1
2,2
2,4
2,6

12,0
16,0
18,0
21,5
22,8
26,6
30,3
32,3
35,4
40,3
12,3
17,2
20,2
24,2
25,7
29,8
33,6
36,0
40,1
45,5

228
408
551
689
765
1.035
1.374
1.549
1.850
2.420
248
477
684
854
954
1.322
1.710
1.935
2.433
3.127

48
64
72
86
91
107
121
129
141
161
49
69
81
97
103
119
134
144
161
182

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

8,9
13,2
15,4
18,5
19,7
23,5
27,1
29,3
32,5
37,4
9,4
14,5
16,9
21,1
22,7
27,0
30,7
33,2
37,3
42,5

1,3
1,5
1,5
1,7
1,8
1,9
2,0
2,1
2,4
2,5
1,3
1,5
1,6
1,8
1,9
2,0
2,2
2,4
2,5
2,7

12,7
17,5
20,0
23,6
25,2
29,3
33,3
35,7
39,5
45,2
13,2
18,7
22,0
26,7
28,4
33,2
37,4
40,2
45,0
50,6

258
484
658
808
902
1.207
1.610
1.815
2.216
2.934
281
557
799
1.007
1.125
1.590
2.025
2.312
2.942
3.707

51
70
80
94
101
117
133
143
158
181
53
75
88
107
114
133
149
161
180
203

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7

9,2
13,8
16,0
19,3
20,6
25,0
28,4
30,6
34,4
39,2
9,7
15,1
17,6
22,1
23,7
28,3
32,2
34,7
39,1
44,5

1,3
1,5
1,6
1,7
1,9
2,0
2,2
2,2
2,5
2,6
1,3
1,5
1,6
1,8
1,9
2,2
2,3
2,4
2,7
2,8

13,0
18,0
21,1
24,6
26,3
31,2
35,0
37,3
41,7
47,1
13,5
20,0
22,7
27,7
29,7
34,9
39,0
41,8
47,2
52,9

277
525
759
900
1.018
1.452
1.846
2.065
2.584
3.344
306
648
895
1.146
1.318
1.862
2.355
2.674
3.453
4.336

52
72
85
98
105
125
140
149
167
189
54
80
91
111
119
139
156
167
189
211

Electrical Data: see page 47

16

RFOU (c) S2/S6


Instrumentation

250 V

Halogenfree & MUD Resistant - Common Screen

Design and construction


Nominal voltage
Operating temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-376:2003
250 V
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 INSULATION

halogenfree HEPR compound

3 COMMON SCREEN

copper/polyester tape
+ flexible tinned copper drain wire

4 BEDDING
INNER SHEATH

halogenfree FLAMEBAR
halogenfree compound

5 ARMOUR

tinned copper wire braid


according to IEC 60092-376:2003

6 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
pair
triple

black light blue


light blue black brown
(pairs/triples progressively numbered)

sheath colour

grey
(blue for intrinsically safe)

Sheath Marking
CCI RFOU(c) S2/S6 250 V n x p(trp) x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking year

QA n

17

RFOU (c) S2/S6

250 V
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM
BENDING RADIUS
approx
[mm]

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

8,1
11,8
13,6
16,2
17,2
20,4
23,5
25,3
28,1
31,9
8,5
12,9
14,9
18,5
19,7
23,1
26,6
28,7
31,9
36,6

1,3
1,4
1,5
1,6
1,7
1,9
2,0
2,1
2,2
2,4
1,3
1,5
1,6
1,7
1,8
2,0
2,1
2,2
2,4
2,6

12,0
15,8
17,8
21,2
22,5
26,2
29,7
31,7
34,7
39,4
12,3
17,1
19,9
23,6
25,3
29,3
33,0
35,2
39,4
44,6

228
391
505
608
671
886
1.173
1.309
1.562
2.027
248
457
630
766
852
1.161
1.490
1.672
2.121
2.694

48
63
71
85
90
105
119
127
139
158
49
68
80
94
101
117
132
141
158
178

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

8,9
13,1
15,2
18,1
19,3
23,1
26,5
28,6
31,8
36,6
9,4
14,3
16,7
20,8
22,3
26,5
30,1
32,5
36,6
41,6

1,3
1,5
1,5
1,7
1,8
1,9
2,0
2,1
2,4
2,5
1,3
1,5
1,6
1,8
1,9
2,0
2,2
2,4
2,5
2,7

12,7
17,3
19,8
23,3
24,9
28,8
32,7
35,0
38,9
44,4
13,2
18,6
21,7
26,3
28,0
32,7
36,7
39,5
44,3
49,8

258
466
609
722
801
1.051
1.392
1.555
1.908
2.504
281
538
749
922
1.025
1.433
1.808
2.050
2.629
3.281

51
69
79
93
99
115
131
140
155
177
53
74
87
105
112
131
147
158
177
199

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7

9,2
13,6
15,8
19,0
20,2
24,5
27,8
30,0
33,8
38,4
9,7
15,0
17,4
21,8
23,3
27,8
31,5
34,1
38,3
43,6

1,3
1,5
1,6
1,7
1,9
2,0
2,2
2,2
2,5
2,6
1,3
1,5
1,6
1,8
1,9
2,2
2,3
2,4
2,7
2,8

13,0
17,9
20,9
24,3
26,0
30,7
34,4
36,6
41,0
46,3
13,5
19,8
22,5
27,3
29,3
34,4
38,4
41,2
46,5
52,0

277
507
709
814
917
1.292
1.630
1.806
2.271
2.916
306
624
838
1.052
1.207
1.692
2.118
2.412
3.111
3.874

52
72
84
97
104
123
138
147
164
185
54
79
90
109
117
137
153
165
186
208

Electrical Data: see page 47

18

NEK 606:2004
Halogenfree
Flame retardant
MUD resistant

Medium Voltage

20

RFOU P2/P9
Medium Voltage

3,6/6 kV

Halogenfree & MUD Resistant

Design and construction


Nominal voltage Uo/U
Maximum rated temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-354 IEC 60502-2


3.6/6 kV
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 SEMICONDUCTORS

halogenfree compound

3 INSULATION

halogenfree HEPR compound

4 SCREEN

tinned copper wire braid


according to IEC 60092-352

5 BEDDING

halogenfree FLAMEBAR

6 INNER SHEATH

halogenfree compound

7 ARMOUR

tinned copper wire braid

8 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
by coloured or numbered tapes

sheath colour

red

Sheath Marking
CCI RFOU P2/P9 3.6/6 kV n x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking

year

QA n

21

RFOU P2/P9

3,6 / 6 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

DIAMETER OVER
INSULATION
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING
approx
at 45 Deg C in air
[mm]
[A]

1
1
1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x
x
x

25
35
50
70
95
120
150
185
240
300

6,3
7,1
8,2
10,0
11,7
13,0
14,3
16,3
18,7
21,7

14,5
15,3
16,5
18,2
19,9
21,2
22,6
24,5
27,1
30,5

20,7
21,5
22,6
24,4
26,1
27,4
28,7
30,7
33,3
37,2

26,0
27,0
28,0
30,0
32,0
33,5
35,0
37,5
40,5
45,0

1090
1205
1375
1670
1980
2295
2600
3160
3850
4765

104
108
112
120
128
134
140
150
162
180

113
140
175
222
275
315
367
422
502
582

3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x

25 /16
35 /16
50 /25
70 /35
95 /50
120/60
150/70
185/70

6,3
7,1
8,2
10,0
11,7
13,0
14,3
16,3

14,5
15,3
16,5
18,2
19,9
21,2
22,6
24,5

40,4
42,1
45,0
48,8
53,5
57,3
60,2
64,4

47,5
49,5
53,0
57,5
63,0
67,0
70,5
77,5

2980
3355
4055
4960
6315
7510
8530
10830

190
196
212
230
252
268
282
310

106
135
160
203
246
287
330
380

Electrical Data: see page 50

22

RFOU P3/P10
Medium Voltage

6/10 kV

Halogenfree & MUD Resistant

Design and construction


Nominal voltage Uo/U
Maximum rated temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-354 IEC 60502-2


6/10 kV
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 SEMICONDUCTORS

halogenfree compound

3 INSULATION

halogenfree HEPR compound

4 SCREEN

tinned copper wire braid


according to IEC 60092-352

5 BEDDING

halogenfree FLAMEBAR

6 INNER SHEATH

halogenfree compound

7 ARMOUR

tinned copper wire braid

8 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
by coloured or numbered tapes

sheath colour

red

Sheath Marking
CCI RFOU P3/P10 6/10 kV n x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking

year

QA n

23

RFOU P3/P10

6 / 10 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

DIAMETER OVER
INSULATION
approx
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING
approx
at 45 Deg C in air
[mm]
[A]

1
1
1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x
x
x

25
35
50
70
95
120
150
185
240
300

6,3
7,1
8,2
10,0
11,7
13,0
14,3
16,3
18,7
21,7

16,3
17,1
18,3
20,0
21,7
23,0
24,4
26,3
28,7
31,7

22,5
23,3
24,4
26,2
27,9
29,2
30,5
32,5
34,9
38,4

28,2
29,0
30,3
32,1
34,0
35,6
37,4
39,6
42,2
46,0

1220
1335
1515
1800
2135
2460
2850
3340
4025
4890

113
116
121
129
136
142
150
158
169
184

113
140
175
222
275
315
367
422
502
582

3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x

25 /16
35 /16
50 /25
70 /35
95 /50
120/60
150/70
185/95

6,3
7,1
8,2
10,0
11,7
13,0
14,3
16,3

16,3
17,1
18,3
20,0
21,7
23,0
24,4
26,3

44,7
46,4
48,9
53,7
58,4
61,2
64,1
68,3

52,5
54,0
57,5
62,5
68,5
71,5
74,5
81,5

3465
3815
4505
5705
6995
8070
9075
11500

210
216
230
250
274
286
298
326

106
135
160
203
246
287
330
380

Electrical Data: see page 51

24

RFOU P4/P11
Medium Voltage

8,7/15 kV

Halogenfree & MUD Resistant

Design and construction


Nominal voltage Uo/U
Maximum rated temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-354 IEC 60502-2


8,7/15 kV
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 SEMICONDUCTORS

halogenfree compound

3 INSULATION

halogenfree HEPR compound

4 SCREEN

tinned copper wire braid


according to IEC 60092-352

5 BEDDING

halogenfree FLAMEBAR

6 INNER SHEATH

halogenfree compound

7 ARMOUR

tinned copper wire braid

8 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
by coloured or numbered tapes

sheath colour

red

Sheath Marking
CCI RFOU P4/P11 8,7/15 kV n x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking

year

QA n

25

RFOU P4/P11

8,7 / 15 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

DIAMETER OVER
INSULATION
approx
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING
approx
at 45 Deg C in air
[mm]
[A]

1
1
1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x
x
x

25
35
50
70
95
120
150
185
240
300

6,3
7,1
8,2
10,0
11,7
13,0
14,3
16,3
18,7
21,7

18,5
19,3
20,5
22,2
23,9
25,2
26,6
28,5
30,9
33,9

24,7
25,5
26,6
28,4
30,1
31,4
32,7
34,7
37,1
40,6

30,5
31,5
32,5
34,5
37,0
38,5
40,0
42,0
44,5
48,5

1385
1505
1695
1985
2415
2750
3065
3565
4265
5150

122
126
130
138
148
154
160
168
178
194

113
140
175
222
275
315
367
422
502
582

3
3
3
3
3
3
3

x
x
x
x
x
x
x

25 /16
35 /16
50 /25
70 /35
95 /50
120/60
150/70

6,3
7,1
8,2
10,0
11,7
13,0
14,2

18,5
19,3
20,5
22,2
23,9
25,2
26,6

50,5
52,2
54,7
59,5
63,1
66,0
68,9

58,5
60,5
63,5
69,0
73,5
76,5
80,0

4140
4580
5335
6400
7660
8780
9805

234
242
254
276
294
306
320

106
135
160
203
246
287
330

Electrical Data: see page 52

26

RFOU P19/P21
Medium Voltage

12/20 kV

Halogenfree & MUD Resistant

Design and construction


Nominal voltage Uo/U
Maximum rated temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-354 IEC 60502-2


12/20 kV
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 SEMICONDUCTORS

halogenfree compound

3 INSULATION

halogenfree HEPR compound

4 SCREEN

tinned copper wire braid


according to IEC 60092-352

5 BEDDING

halogenfree FLAMEBAR

6 INNER SHEATH

halogenfree compound

7 ARMOUR

tinned copper wire braid

8 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
by coloured or numbered tapes

sheath colour

red

Sheath Marking
CCI RFOU P19/P21 12/20 kV n x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking

year

QA n

27

RFOU P19/P21

12 / 20 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

DIAMETER OVER
INSULATION
approx
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING
approx
at 45 Deg C in air
[mm]
[A]

1
1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x
x

35
50
70
95
120
150
185
240
300

7,1
8,2
10,0
11,7
13,0
14,3
16,3
18,7
21,7

21,3
22,5
24,2
25,9
27,2
28,6
30,5
32,9
35,9

27,5
28,6
30,4
32,1
33,4
34,8
36,7
39,1
42,6

33,5
35,0
37,5
39,0
40,5
42,0
44,0
47,0
50,5

1675
1851
2255
2610
2928
3277
3788
4495
5395

134
140
150
156
162
168
177
188
202

140
175
222
275
315
367
422
502
582

3
3
3
3
3
3

x
x
x
x
x
x

35 /16
50 /25
70 /35
95 /50
120/60
150/70

7,1
8,2
10,0
11,7
13,0
14,4

21,3
22,5
24,2
25,9
27,2
28,6

57,5
60,0
63,8
67,5
70,3
73,2

66,0
69,5
73,5
78,0
81,5
84,5

5270
5995
7010
8285
9485
10530

264
278
294
312
326
338

135
160
203
246
287
330

Electrical Data: see page 53

28

RFOU P20/P22
Medium Voltage

18/30 kV

Halogenfree & MUD Resistant

Design and construction


Nominal voltage Uo/U
Maximum rated temperature
Flame retardancy
Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C)

IEC 60092-354 IEC 60502-2


18/30 kV
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D
CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 SEMICONDUCTORS

halogenfree compound

3 INSULATION

halogenfree HEPR compound

4 SCREEN

tinned copper wire braid


according to IEC 60092-352

5 BEDDING

halogenfree FLAMEBAR

6 INNER SHEATH

halogenfree compound

7 ARMOUR

tinned copper wire braid

8 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
by coloured or numbered tapes

sheath colour

red

Sheath Marking
CCI RFOU P20/P22 18/30 kV n x s mm2
NEK 606:2004 IEC 60332-3-22 meter marking

year

QA n

29

RFOU P20/P22

18 / 30 kV
CONSTRUCTION

CONDUCTOR
DIAMETR
approx
[mm]

DIAMETER OVER
INSULATION
approx
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

approx
[kg / km]

50
70
95
120
150
185
240
300

8,2
10,0
11,7
13,0
14,3
16,3
18,7
21,7

27,5
29,2
30,9
32,2
33,6
35,5
37,9
40,9

33,6
35,4
37,1
38,4
39,8
41,7
44,5
48,0

41,0
43,0
44,5
46,0
47,5
49,5
52,5
56,5

2430
2760
3135
3470
3830
4360
5150
6105

164
172
178
184
190
198
210
226

175
222
275
315
367
422
502
582

3 x 50 /25
3 x 70 /35
3 x 95 /50

8,2
10,0
11,7

27,5
29,2
30,9

70,8
74,6
78,3

81,0
85,0
89,5

7600
8710
10075

324
340
358

160
203
246

[mm 2 ]

1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x

Electrical Data: see page 54

30

WEIGHT

MINIMUM BENDING
CURRENT
RADIUS
RATING
approx
at 45 Deg C in air
[mm]
[A]

NEK 606:2004
Halogenfree
Flame retardant
MUD resistant

Fire resistant
IEC 60331-21 @ 1000 Deg C and 1000 V
on request:

IEC 60331-31 @ 1000 Deg C and 1000 V


with mechanical shocks

FIRE RESISTANT TESTS

IEC 60331-21@1000 Deg C - 1000 V

IEC 60331-31@1000 Deg C - 1000 V with mechanical shocks

32

BFOU P5/P12
Power & Control 0,6/1 kV
Halogenfree & MUD Resistant

Design and construction


Operating temperature
Nominal voltage Uo / U
Flame retardancy
Fire resistance

IEC 60092-353
90 Deg C (see page 3)
0,6/1 kV
IEC 60332-1 IEC 60332-3-22
IEC 60331-21 @ 1000 Deg C and 1000 V
on request:
IEC 60331-31 @ 1000 Deg C and 1000 V
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D

Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C) CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 INSULATION

glass braid over mica tape +


halogenfree HEPR compound

3 BEDDING

halogenfree FLAMEBAR

4 INNER SHEATH

halogenfree compound

5 ARMOUR

tinned copper wire braid


according to IEC 60092-352

6 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
1 core
2 cores
3 cores
4 cores
5 cores and above

off-white (grey)
off-white black
off-white black red
off-white black red blue
white & numbered

sheath colour

black

Sheath Marking
CCI BFOU P5/P12 0,6/1 kV n x s/braid mm2 NEK 606:2004
IEC 60331-21@ 1000 Deg C meter marking
year QA ref.
FIRE RESISTANT

33

BFOU P5/P12

0,6 / 1 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING at 45 Deg C
approx
in air approx
[mm]
[A]

1
1
1
1
1
1
1
1
1
1
1

x
x
x
x
x
x
x
x
x
x
x

16
25
35
50
70
95
120
150
185
240
300

4,8
6,3
7,1
8,3
10,0
11,7
13,0
14,3
16,3
18,7
21,7

1,0
1,2
1,2
1,4
1,4
1,6
1,6
1,8
2,0
2,2
2,4

10,8
12,4
13,5
14,9
17,0
18,6
20,0
21,9
24,0
27,1
29,8

1,2
1,5
1,6
1,6
1,7
1,8
1,9
2,0
2,1
2,2
2,3

15,0
17,2
18,5
20,3
22,6
24,4
26,0
28,1
30,4
33,7
36,6

437
597
730
927
1.187
1.487
1.773
2.139
2.563
3.232
3.921

60
69
74
81
90
98
104
112
122
135
146

93
117
147
180
283
285
333
386
444
528
612

2
2
2
2
2
2

x
x
x
x
x
x

1.5 /4
2.5 /4
4
/6
6
/6
10 /10
16 /16

1,6
2,0
2,6
3,2
3,8
4,8

1,0
1,0
1,0
1,0
1,0
1,0

11,2
12,3
13,9
14,9
16,3
18,5

1,5
1,5
1,5
1,6
1,6
1,8

15,5
16,5
18,1
19,3
21,6
24,3

353
411
501
589
794
1.037

62
66
72
77
86
97

23
31
43
55
75
100

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.5 /4
2.5 /6
4
/6
6
/6
10 /10
16 /16
25 /16
35 /16
50 /25
70 /35
95 /50
120 /60
150 /70
185 /95
240/120

1,6
2,0
2,6
3,2
3,8
4,8
6,3
7,1
8,3
10,0
11,7
13,0
14,3
16,3
18,7

1,0
1,0
1,0
1,0
1,0
1,0
1,2
1,2
1,4
1,4
1,6
1,6
1,8
2,0
2,2

11,9
13,0
14,7
15,8
17,3
19,7
23,4
25,8
29,0
33,5
36,8
40,3
44,7
49,2
55,5

1,5
1,5
1,5
1,6
1,6
1,8
1,8
2,0
2,2
2,4
2,6
2,8
2,8
3,0
3,2

16,1
17,2
19,0
20,7
22,6
25,5
29,2
32,0
36,0
41,1
45,3
49,5
55,1
61,2
68,2

389
458
565
685
930
1.236
1.706
2.149
2.872
3.816
4.940
6.039
7.641
9.517
11.999

64
69
76
83
90
102
117
128
144
164
181
198
220
245
273

20
28
37
47
65
87
110
137
167
214
259
301
347
397
468

Electrical Data: see pages 42-44

34

BFOU P5/P12

0,6 / 1 kV
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM BENDING
CURRENT
RADIUS
RATING at
approx
45 Deg C in air
[mm]
[A]

4
4
4
4
4
4
4
4
4
4
4
4

x
x
x
x
x
x
x
x
x
x
x
x

1.5 /4
2.5 /6
4
/6
6
/6
10 /10
16 /16
25 /25
35 /35
50 /50
70 /35
95 /50
120/60

1,6
2,0
2,6
3,2
3,8
4,8
6,3
7,1
8,3
10,0
11,7
13,0

1,0
1,0
1,0
1,0
1,0
1,0
1,2
1,2
1,4
1,4
1,6
1,6

12,9
14,1
16,1
17,3
18,9
21,6
25,7
28,3
31,9
37,0
40,7
44,5

1,5
1,5
1,5
1,6
1,6
1,8
1,8
2,0
2,2
2,4
2,6
2,8

17,1
18,4
20,7
22,1
24,3
27,5
31,5
34,6
38,9
44,6
49,2
53,7

442
526
680
814
1.092
1.469
2.045
2.596
3.489
4.653
6.054
7.415

68
74
83
88
97
110
126
138
156
178
197
215

20
28
37
47
65
87
110
137
167
214
259
301

7
12
19
27
37

x
x
x
x
x

1,5 /6
1,5/10
1,5/10
1,5/16
1,5/16

1,6
1,6
1,6
1,6
1,6

1,0
1,0
1,0
1,0
1,0

15,5
20,3
23,8
28,7
32,4

1,5
1,7
1,8
2,0
2,2

20,2
25,9
29,6
34,9
39,0

606
1.028
1.356
1.885
2.357

81
104
118
140
156

11
9
8
7
6

7
12
19
27
37

x
x
x
x
x

2.5 /6
2.5/10
2.5/10
2.5/16
2.5/16

2,0
2,0
2,0
2,0
2,0

1,0
1,0
1,0
1,0
1,0

16,8
22,1
26,1
31,5
35,5

1,5
1,7
1,8
2,0
2,2

21,4
27,7
31,9
37,8
42,2

720
1.236
1.670
2.332
2.935

86
111
128
151
169

15
13
11
9
9

Electrical Data: see pages 45-46

35

36

BFOU (i) S3/S7


Instrumentation

250 V

Halogenfree & MUD Resistant - Individual Screen


Fire Resistant

Design and construction


Nominal voltage
Operating temperature
Flame retardancy
Fire resistance

IEC 60092-376:2003
250 V
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60331-21 @ 1000 Deg C and 1000 V
on request:
IEC 60331-31 @ 1000 Deg C and 1000 V
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D

Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C) CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 INSULATION

glass braid over mica tape +


halogenfree HEPR compound

3 INDIVIDUAL SCREEN

copper/polyester tape
+ flexible tinned copper drain wire

4 BEDDING
INNER SHEATH

halogenfree FLAMEBAR
halogenfree compound

5 ARMOUR

tinned copper wire braid


according to IEC 60092-352

6 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Pair/Triple Identification
pair
triple

black light blue


light blue black brown
(pairs/triples progressively numbered)

sheath colour

grey
(blue for intrinsically safe)

Sheath Marking
CCI BFOU(i) S3/S7 250 V n x p(trp) x s mm2 NEK 606:2004
IEC 60331-21@ 1000 Deg C meter marking
year QA n
FIRE RESISTANT

37

BFOU (i) S3/S7

250 V
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM
BENDING RADIUS
approx
[mm]

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

9,1
13,7
15,9
19,1
20,3
24,3
28,1
30,3
33,6
38,3
9,6
15,0
17,4
21,9
23,5
27,6
31,8
34,4
38,2
44,0

1,3
1,4
1,5
1,6
1,7
1,9
2,0
2,1
2,2
2,4
1,3
1,5
1,6
1,7
1,8
2,0
2,1
2,2
2,4
2,6

13,0
17,7
20,5
24,2
25,7
30,1
34,3
36,7
40,3
45,9
13,5
19,6
22,5
27,2
29,0
33,8
38,2
41,0
45,8
52,0

259
479
655
773
860
1.165
1.550
1.740
2.075
2.716
281
574
795
963
1.075
1.491
1.933
2.178
2.743
3.522

52
71
82
97
103
120
137
147
161
184
54
78
90
109
116
135
153
164
183
208

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

11,0
16,1
18,6
22,4
23,8
28,3
32,7
35,2
39,0
45,2
11,5
17,5
20,6
25,6
27,3
32,6
36,9
39,8
45,1
51,1

1,3
1,5
1,5
1,7
1,8
1,9
2,0
2,1
2,4
2,5
1,3
1,5
1,6
1,8
1,9
2,0
2,2
2,4
2,5
2,7

13,7
19,6
22,1
26,4
28,0
32,7
37,3
40,0
44,4
50,8
14,3
21,1
24,4
29,8
31,7
37,2
41,9
45,2
50,7
57,1

291
573
756
898
1.000
1.340
1.789
2.008
2.452
3.250
315
659
918
1.121
1.255
1.770
2.256
2.570
3.272
4.116

55
78
88
106
112
131
149
160
178
203
57
84
97
119
127
149
168
181
203
229

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7

10,2
15,5
18,1
21,9
23,4
28,4
32,3
35,0
39,3
44,8
10,8
17,1
20,0
25,2
27,0
32,3
36,7
39,7
44,7
51,0

1,3
1,5
1,6
1,7
1,9
2,0
2,2
2,2
2,5
2,6
1,3
1,5
1,6
1,8
1,9
2,2
2,3
2,4
2,7
2,8

14,1
20,2
23,1
27,2
29,1
34,6
39,0
41,6
46,5
52,8
14,6
21,9
25,1
30,7
33,0
38,9
43,6
46,8
52,8
59,4

310
616
861
987
1.117
1.593
2.030
2.261
2.830
3.660
341
742
1.015
1.262
1.450
2.044
2.590
2.932
3.786
4.751

56
81
92
109
116
139
156
166
186
211
59
88
100
123
132
156
174
187
211
237

Electrical Data: see page 47

38

BFOU (c) S4/S8


Instrumentation

250 V

Halogenfree & MUD Resistant - Common Screen


Fire Resistant

Design and construction


Nominal voltage
Operating temperature
Flame retardancy
Fire resistance

IEC 60092-376:2003
250 V
90 Deg C (see page 3)
IEC 60332-1 IEC 60332-3-22
IEC 60331-21 @ 1000 Deg C and 1000 V
on request:
IEC 60331-31 @ 1000 Deg C and 1000 V
IEC 60754-1 IEC 60754-2
IEC 61034-2
NEK 606:2004 IEC 61892-4 Annex D

Corrosivity
Smoke density
MUD resistance
on request:
Cold bend and Impact test (40 Deg C) CSA C22.2 No 38-95

Construction Data
1 CONDUCTOR

tinned flexible compacted copper


IEC 60228 Class 2

2 INSULATION

glass braid over mica tape +


halogenfree HEPR compound

3 COMMON SCREEN

copper/polyester tape
+ flexible tinned copper drain wire

4 BEDDING
INNER SHEATH

halogenfree FLAMEBAR
halogenfree compound

5 ARMOUR

tinned copper wire braid


according to IEC 60092-352

6 OUTER SHEATH

SHF2 MUD thermoset dual compound


halogenfree & MUD resistant

Core Identification
pair
triple

black light blue


light blue black brown
(pairs/triples progressively numbered)

sheath colour

grey
(blue for intrinsically safe)

Sheath Marking
CCI BFOU(c) S4/S8 250 V n x p(trp) x s mm2 NEK 606:2004
IEC 60331-21@ 1000 Deg C meter marking
year QA n
FIRE RESISTANT

39

BFOU (c) S4/S8

250 V
CONSTRUCTION
[mm 2 ]

CONDUCTOR
DIAMETR
approx
[mm]

INSULATION
THICKNESS
nominal
[mm]

UNDER ARMOUR
DIAMETER
approx
[mm]

OUTER SHEATH
THICKNESS
approx
[mm]

OVERALL
DIAMETER
approx
[mm]

WEIGHT
approx
[kg / km]

MINIMUM
BENDING RADIUS
approx
[mm]

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75
0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

9,1
13,5
15,7
18,8
20,0
23,9
27,5
29,6
33,0
37,5
9,6
14,8
17,2
21,5
23,1
27,0
31,2
33,7
37,5
43,1

1,3
1,4
1,5
1,6
1,7
1,9
2,0
2,1
2,2
2,4
1,3
1,5
1,6
1,7
1,8
2,0
2,1
2,2
2,4
2,6

13,0
17,5
20,3
23,9
25,3
29,6
33,7
36,1
39,6
45,1
13,5
19,0
22,3
26,9
28,6
33,2
37,6
40,4
45,0
51,1

259
463
611
695
768
1.020
1.353
1.502
1.790
2.324
281
542
744
879
979
1.337
1.716
1.941
2.432
3.100

52
70
81
96
101
118
135
144
158
180
54
76
89
107
114
133
150
162
180
204

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4

0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6

9,9
14,8
17,3
20,7
22,1
26,5
30,5
33,0
36,7
42,2
10,5
16,3
19,0
23,9
25,6
30,5
34,8
37,6
42,2
48,1

1,3
1,5
1,5
1,7
1,8
1,9
2,0
2,1
2,4
2,5
1,3
1,5
1,6
1,8
1,9
2,0
2,2
2,4
2,5
2,7

13,7
19,1
21,9
26,1
27,7
32,2
36,8
39,4
43,7
50,0
14,3
20,9
24,1
29,4
31,3
36,7
41,4
44,6
49,9
56,2

291
542
706
814
900
1.185
1.574
1.748
2.145
2.827
315
641
867
1.039
1.159
1.615
2.064
2.336
2.967
3.688

55
76
88
104
111
129
147
158
175
200
57
84
97
118
125
147
166
178
200
225

1
2
4
7
8
12
16
19
24
32
1
2
4
7
8
12
16
19
24
32

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7

10,2
15,4
17,9
21,6
23,0
28,0
31,8
34,4
38,6
44,0
10,8
16,9
19,7
24,8
26,6
31,7
36,2
39,1
43,9
50,1

1,3
1,5
1,6
1,7
1,9
2,0
2,2
2,2
2,5
2,6
1,3
1,5
1,6
1,8
1,9
2,2
2,3
2,4
2,7
2,8

14,1
20,0
22,9
26,9
28,8
34,2
38,4
41,0
45,9
51,9
14,6
21,8
24,9
30,4
32,6
38,4
43,0
46,2
52,1
58,5

310
599
810
904
1.018
1.440
1.815
2.027
2.525
3.231
341
722
960
1.173
1.345
1.875
2.379
2.678
3.443
4.285

56
80
91
108
115
137
154
164
183
208
59
87
99
121
131
154
172
185
208
234

Electrical Data: see page 47

40

Electrical Data

RFOU P1/P8 - BFOU P5/P12

1 core

0,6 / 1 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

1 x 1,5 12,2

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20

IMPEDANCE
[ /km ]

50 Hz

60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
[A]
[ kA ]

15,57

0,131

0,157

0,184

417

12,20

12,20

15,57

15,57

20

0,21

1 x 2,5

7,56

9,65

0,123

0,148

0,228

391

7,56

7,56

9,65

9,65

27

0,35

1x4

4,70

5,99

0,114

0,137

0,271

364

4,70

4,70

5,99

5,99

37

0,58

1x6

3,11

3,97

0,105

0,126

0,324

335

3,11

3,11

3,97

3,97

48

0,87

1 x 10

1,84

2,35

0,103

0,124

0,375

330

1,84

1,84

2,35

2,35

68

1,46

1 x 16

1,16

1,48

0,098

0,117

0,453

311

1,16

1,17

1,48

1,49

93

2,33

1 x 25

0,734

0,937

0,093

0,112

0,451

298

0,739

0,742

0,942

0,944

120

3,65

1 x 35

0,529

0,675

0,092

0,110

0,519

293

0,537

0,540

0,681

0,684

145

5,11

1 x 50

0,391

0,499

0,090

0,108

0,548

286

0,401

0,406

0,507

0,511

180

7,30

1 x 70

0,270

0,344

0,088

0,105

0,595

278

0,284

0,290

0,355

0,360

232

10,20

1 x 95

0,195

0,249

0,085

0,102

0,718

270

0,213

0,220

0,263

0,269

285

13,90

1 x 120

0,154

0,196

0,084

0,101

0,738

269

0,175

0,184

0,213

0,220

332

17,50

1 x 150

0,126

0,161

0,088

0,105

0,683

278

0,154

0,164

0,183

0,192

385

21,90

1 x 185

0,100

0,128

0,085

0,102

0,689

269

0,131

0,143

0,154

0,164

445

27,00

1 x 240

0,0762 0,0972

0,083

0,099

0,719

262

0,113

0,125

0,128

0,139

530

35,00

1 x 300

0,0607 0,0775

0,084

0,101

0,884

269

0,102

0,118

0,114

0,127

610

43,80

42

RFOU P1/P8 - BFOU P5/P12

2 cores

0,6 / 1 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

2 x 1,5 12,2

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20
50 Hz

15,57

0,101

0,121

0,151

321

12,2

IMPEDANCE
[ /km ]
60 Hz

12,2

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING in air
1 sec.
60 Hz @ 45C [ A ]
[ kA ]

15,57

15,57

23

0,21

2 x 2,5

7,56

9,65

0,094

0,113

0,182

300

7,56

7,56

9,65

9,65

31

0,35

2x4

4,70

5,99

0,089

0,107

0,205

283

4,70

4,70

5,99

5,99

43

0,58

2x6

3,11

3,97

0,084

0,101

0,231

268

3,11

3,11

3,97

3,97

55

0,87

2 x 10

1,84

2,35

0,081

0,097

0,254

257

1,84

1,84

2,35

2,35

77

1,46

2 x 16

1,16

1,48

0,077

0,092

0,285

245

1,16

1,16

1,48

1,48

102

2,33

2 x 25

0,734

0,937

0,077

0,092

0,294

242

0,738

0,740

0,940

0,942

130

3,65

2 x 35

0,529

0,675

0,076

0,091

0,308

238

0,534

0,537

0,679

0,681

160

5,11

2 x 50

0,391

0,499

0,074

0,089

0,317

235

0,399

0,401

0,506

0,507

195

7,30

2 x 70

0,270

0,344

0,073

0,087

0,332

232

0,280

0,284

0,352

0,355

230

10,20

2 x 95

0,195

0,249

0,071

0,085

0,357

226

0,208

0,213

0,259

0,263

272

13,90

43

RFOU P1/P8 - BFOU P5/P12

3 cores

0,6 / 1 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

3 x 1,5 12,2

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20
50 Hz

15,57

0,103

0,124

0,152

329

12,2

IMPEDANCE
[ /km ]
60 Hz

12,2

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING in air
1 sec.
60 Hz @ 45C [ A ]
[ kA ]

15,57

15,57

20

0,21

3 x 2,5

7,56

9,65

0,096

0,115

0,177

305

7,56

7,56

9,65

9,65

29

0,35

3x4

4,70

5,99

0,091

0,109

0,195

289

4,70

4,70

5,99

5,99

37

0,58

3x6

3,11

3,97

0,085

0,102

0,234

271

3,11

3,11

3,97

3,97

48

0,87

3 x 10

1,84

2,35

0,080

0,096

0,258

255

1,84

1,84

2,35

2,35

65

1,46

3 x 16

1,16

1,48

0,078

0,0934

0,291

248

1,16

1,16

1,48

1,48

87

2,33

3 x 25

0,734

0,937

0,076

0,0914

0,304

242

0,738

0,740

0,940

0,941

110

3,65

3 x 35

0,529

0,675

0,073

0,0876

0,318

232

0,534

0,536

0,679

0,680

136

5,11

3 x 50

0,391

0,499

0,072

0,0864

0,329

229

0,398

0,400

0,504

0,506

167

7,30

3 x 70

0,270

0,344

0,071

0,0852

0,341

226

0,279

0,283

0,351

0,354

215

10,20

3 x 95

0,195

0,249

0,070

0,0844

0,349

225

0,207

0,212

0,259

0,263

258

13,90

3 x 120

0,154

0,196

0,070

0,0836

0,370

222

0,160

0,175

0,208

0,213

300

17,50

3 x 150

0,126

0,161

0,069

0,0831

0,390

221

0,144

0,151

0,175

0,181

350

21,90

3 x 185

0,100

0,128

0,069

0,0828

0,394

220

0,121

0,130

0,145

0,153

395

27,00

3 x 240

0,0762 0,0972

0,068

0,0822

0,406

218

0,102

0,112

0,119

0,127

467

35,00

3 x 300

0,0607 0,0775

0,068

0,0816

0,414

216

0,091

0,102

0,103

0,113

553

43,80

44

RFOU P1/P8 - BFOU P5/P12

4 cores

0,6 / 1 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

4 x 1,5 12,2

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20
50 Hz

15,57

0,110

0,132

0,146

350

12,2

IMPEDANCE
[ /km ]
60 Hz

12,2

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING in air
1 sec.
60 Hz @ 45C [ A ]
[ kA ]

15,57

15,57

20

0,21

4 x 2,5

7,56

9,65

0,103

0,123

0,172

325

7,56

7,56

9,65

9,65

29

0,35

4x4

4,70

5,99

0,097

0,116

0,190

308

4,70

4,70

5,99

5,99

37

0,58

4x6

3,11

3,97

0,091

0,109

0,229

289

3,11

3,11

3,97

3,97

48

0,87

4 x 10

1,84

2,35

0,086

0,103

0,254

273

1,84

1,84

2,35

2,35

65

1,46

4 x 16

1,16

1,48

0,083

0,100

0,287

265

1,16

1,16

1,48

1,48

87

2,33

4 x 25

0,734

0,937

0,082

0,098

0,299

259

0,739

0,741

0,941

0,942

110

3,65

4 x 35

0,529

0,675

0,078

0,094

0,312

248

0,535

0,537

0,679

0,682

136

5,11

4 x 50

0,391

0,499

0,077

0,092

0,324

245

0,399

0,402

0,505

0,507

167

7,30

4 x 70

0,270

0,344

0,076

0,091

0,337

242

0,280

0,285

0,352

0,356

215

10,20

4 x 95

0,195

0,249

0,076

0,091

0,346

241

0,209

0,215

0,260

0,265

258

13,90

4 x 120

0,154

0,196

0,075

0,090

0,368

238

0,171

0,178

0,210

0,216

300

17,50

4 x 150

0,126

0,161

0,074

0,089

0,387

237

0,146

0,154

0, 177

0,184

350

21,90

4 x 185

0,100

0,128

0,074

0,089

0,392

236

0,124

0,134

0,148

0,156

395

27,00

4 x 240

0,0762 0,0972

0,074

0,089

0,403

235

0,106

0,117

0,122

0,132

467

35,00

45

RFOU P1/P8 - BFOU P5/P12

multicores

0,6 / 1 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20
50 Hz

IMPEDANCE
[ /km ]
60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
[A]
[ kA ]

5 x 1,5

12,2

15,57

0,118

0,142

0,203

377

12,2

12,2

15,57

15,57

12

0,21

7 x 1,5

12,2

15,57

0,126

0,151

0,157

400

12,2

12,2

15,57

15,57

11

0,21

10 x 1,5

12,2

15,57

0,139

0,167

0,113

444

12,2

12,2

15,57

15,57

10

0,21

12 x 1,5

12,2

15,57

0,145

0,174

0,102

461

12,2

12,2

15,57

15,57

0,21

14 x 1,5

12,2

15,57

0,149

0,179

0,096

474

12,2

12,2

15,57

15,57

0,21

16 x 1,5

12,2

15,57

0,153

0,184

0,090

488

12,2

12,2

15,57

15,57

0,21

19 x 1,5

12,2

15,57

0,157

0,188

0,085

499

12,2

12,2

15,57

15,57

0,21

24 x 1,5

12,2

15,57

0,163

0,196

0,078

524

12,2

12,2

15,57

15,57

0,21

27 x 1,5

12,2

15,57

0,168

0,201

0,075

534

12,2

12,2

15,57

15,57

0,21

30 x 1,5

12,2

15,57

0,171

0,205

0,072

545

12,2

12,2

15,57

15,57

0,21

37 x 1,5

12,2

15,57

0,177

0,212

0,068

562

12,2

12,2

15,57

15,57

0,21

5 x 2,5

7,56

9,65

0,115

0,138

0,206

366

7,56

7,56

9,65

9,65

17

0,36

7 x 2,5

7,56

9,65

0,120

0,144

0,172

382

7,56

7,56

9,65

9,65

15

0,36

12 x 2,5

7,56

9,65

0,139

0,167

0,107

443

7,56

7,56

9,65

9,65

12

0,36

19 x 2,5

7,56

9,65

0,151

0,181

0,090

480

7,56

7,56

9,65

9,65

11

0,36

27 x 2,5

7,56

9,65

0,159

0,195

0,084

517

7,56

7,56

9,65

9,65

0,36

37 x 2,5

7,56

9,65

0,171

0,205

0,071

543

7,56

7,56

9,65

9,65

0,36

46

RFOU (i) S1/S5 - RFOU (c) S2/S6


BFOU (i) S3/S7 - BFOU (c) S4/S8

INSTRUMENTATION CABLES

250 V
FORMATION
[ n x mm2 ]

pair

triple

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
approx
at 1 kHz
nominal
[ Farad/km ] [ Henry/km ]

IMPEDANCE
[ /km ]
20
90
50 Hz & 60 Hz

L / R ratio
at 1 kHz
[H/Ohm] max
at 20C

2 x 0,75

26,3

33,18

0,243

0,291

0,090

680

26,3

33,18

20

2x1

19,3

24,50

0,180

0,216

0,100

640

19,3

24,50

25

2 x 1,50

12,9

16,34

0,155

0,186

0,110

630

12,9

16,34

35

3 x 0,75

26,3

33,18

0,128

0,154

0,090

680

26,3

33,18

20

3x1

19,3

24,50

0,093

0,111

0,100

640

19,3

24,50

25

3 x 1,50

12,9

16,341

0,78

0,093

0,110

630

12,9

16,34

35

47

48

Electrical Data
Medium voltage

49

RFOU P2/P9

3,6 / 6 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20

IMPEDANCE
[ /km ]

50 Hz

60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
in air [ A ]
[ kA ]

1 x 25

0,734

0,937

0,139

0,167

0,29

445

0,747

0,754

0,948

0,953

113

3,65

1 x 35

0,529

0,675

0,132

0,158

0,32

421

0,546

0,553

0,688

0,694

140

5,11

1 x 50

0,391

0,499

0,126

0,151

0,34

401

0,411

0,420

0,515

0,512

175

7,30

1 x 70

0,270

0,344

0,120

0,144

0,39

374

0,297

0,308

0,365

0,374

222

10,20

1 x 95

0,195

0,249

0,114

0,137

0,45

367

0,228

0,241

0,276

0,286

275

13,90

1 x 120

0,154

0,196

0,110

0,132

0,49

351

0,192

0,206

0,227

0,239

315

17,50

1 x 150

0,126

0,161

0,107

0,128

0,55

343

0,169

0,184

0,196

0,210

367

21,90

1 x 185

0,100

0,128

0,103

0,124

0,60

333

0,147

0,164

0,168

0,182

422

27,00

1 x 240

0,0762 0,0972

0,101

0,121

0,65

324

0,130

0,147

0,143

0,159

502

35,00

1 x 300

0,0607 0,0774

0,100

0,120

0,72

315

0,118

0,135

0,127

0,144

582

43,80

3 x 25

0,734

0,937

0,111

0,133

0,23

353

0,745

0,750

0,946

0,950

106

3,65

3 x 35

0,529

0,675

0,105

0,126

0,25

335

0,543

0,549

0,686

0,691

135

5,11

3 x 50

0,391

0,499

0,101

0,121

0,28

321

0,408

0,415

0,512

0,518

160

7,30

3 x 70

0,270

0,344

0,095

0,114

0,31

301

0,291

0,300

0,361

0,368

203

10,20

3 x 95

0,195

0,249

0,092

0,110

0,35

292

0,221

0,232

0,270

0,279

246

13,90

3 x 120

0,154

0,196

0,087

0,107

0,39

283

0,188

0,197

0,221

0,231

287

17,50

3 x 150

0,126

0,161

0,084

0,104

0,42

276

0,160

0,173

0,188

0,200

330

21,90

3 x 185

0,100

0,128

0,082

0,101

0,46

268

0,139

0,152

0,160

0,172

380

27,00

50

RFOU P3/P10

6 / 10 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20

IMPEDANCE
[ /km ]

50 Hz

60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
in air [ A ]
[ kA ]

1 x 25

0,734

0,937

0,143

0,171

0,23

454

0,747

0,754

0,948

0,953

113

3,65

1 x 35

0,529

0,675

0,135

0,162

0,25

429

0,546

0,553

0,688

0,694

140

5,11

1 x 50

0,391

0,499

0,128

0,154

0,28

409

0,411

0,420

0,515

0,512

175

7,30

1 x 70

0,270

0,344

0,123

0,147

0,31

389

0,297

0,308

0,365

0,374

222

10,20

1 x 95

0,195

0,249

0,118

0,141

0,35

374

0,228

0,241

0,276

0,286

275

13,90

1 x 120

0,154

0,196

0,114

0,137

0,39

364

0,192

0,206

0,227

0,239

315

17,50

1 x 150

0,126

0,161

0,112

0,134

0,42

356

0,169

0,184

0,196

0,210

367

21,90

1 x 185

0,100

0,128

0,108

0,130

0,46

345

0,147

0,164

0,168

0,182

422

27,00

1 x 240

0,0762 0,0972 0,105

0,126

0,51

335

0,130

0,147

0,143

0,159

502

35,00

1 x 300

0,0607 0,0774 0,101

0,121

0,56

320

0,118

0,135

0,127

0,144

582

43,80

3 x 25

0,734

0,937

0,128

0,154

0,23

408

0,745

0,750

0,946

0,950

106

3,65

3 x 35

0,529

0,675

0,122

0,146

0,25

387

0,543

0,549

0,686

0,691

135

5,11

3 x 50

0,391

0,499

0,116

0,139

0,28

369

0,408

0,415

0,512

0,518

160

7,30

3 x 70

0,270

0,344

0,108

0,130

0,31

345

0,291

0,300

0,361

0,368

203

10,20

3 x 95

0,195

0,249

0,105

0,126

0,35

333

0,221

0,232

0,270

0,279

246

13,90

3 x 120

0,154

0,196

0,102

0,122

0,39

323

0,188

0,197

0,221

0,231

287

17,50

3 x 150

0,126

0,161

0,098

0,118

0,42

312

0,160

0,173

0,188

0,200

330

21,90

3 x 185

0,100

0,128

0,096

0,115

0,46

304

0,139

0,152

0,160

0,172

380

27,00

51

RFOU P4/P11

8,7 / 15 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20

IMPEDANCE
[ /km ]

50 Hz

60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
in air [ A ]
[ kA ]

1 x 25

0,734

0,937

0,151

0,181

0,19

479

0,749

0,756

0,940

0,954

113

3,65

1 x 35

0,529

0,675

0,143

0,171

0,21

453

0,548

0,556

0,690

0,696

140

5,11

1 x 50

0,391

0,499

0,136

0,163

0,23

432

0,414

0,424

0,517

0,525

175

7,30

1 x 70

0,270

0,344

0,127

0,152

0,26

402

0,298

0,310

0,367

0,376

222

10,20

1 x 95

0,195

0,249

0,122

0,146

0,29

387

0,230

0,244

0,277

0,289

275

13,90

1 x 120

0,154

0,196

0,120

0,144

0,31

382

0,195

0,211

0,230

0,243

315

17,50

1 x 150

0,126

0,161

0,116

0,139

0,34

368

0,171

0,188

0,198

0,213

367

21,90

1 x 185

0,100

0,128

0,113

0,136

0,37

362

0,151

0,169

0,171

0,187

422

27,00

1 x 240

0,0762 0,0972 0,108

0,130

0,42

345

0,132

0,151

0,145

0,162

502

35,00

1 x 300

0,0607 0,0774 0,090

0,126

0,44

335

0,109

0,140

0,119

0,148

582

43,80

3 x 25

0,734

0,937

0,135

0,162

0,19

431

0,746

0,752

0,947

0,951

106

3,65

3 x 35

0,529

0,675

0,128

0,154

0,21

408

0,544

0,551

0,687

0,692

135

5,11

3 x 50

0,391

0,499

0,123

0,147

0,23

390

0,410

0,418

0,514

0,520

160

7,30

3 x 70

0,270

0,344

0,115

0,138

0,26

365

0,294

0,303

0,363

0,371

203

10,20

3 x 95

0,195

0,249

0,110

0,132

0,29

351

0,224

0,236

0,272

0,282

246

13,90

3 x 120

0,154

0,196

0,107

0,128

0,31

339

0,188

0,200

0,223

0,234

287

17,50

3 x 150

0,126

0,161

0,103

0,124

0,34

328

0,163

0,177

0,191

0,203

330

21,90

52

RFOU P19/P21

12 / 20 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20

IMPEDANCE
[ /km ]

50 Hz

60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
in air [ A ]
[ kA ]

1 x 50

0,391

0,499

0,145

0,174

0,20

461

0,417

0,428

0,520

0,528

175

7,30

1 x 70

0,270

0,344

0,136

0,163

0,22

434

0,302

0,315

0,370

0,381

222

10,20

1 x 95

0,195

0,249

0,130

0,156

0,25

414

0,234

0,250

0,281

0,294

275

13,90

1 x 120 0,154

0,196

0,127

0,152

0,27

403

0,200

0,216

0,234

0,248

315

17,50

1 x 150 0,126

0,161

0,124

0,149

0,29

394

0,177

0,195

0,203

0,219

367

21,90

1 x 185 0,100

0,128

0,122

0,146

0,31

387

0,158

0,177

0,177

0,194

422

27,00

1 x 240 0,0762 0,0972

0,113

0,136

0,35

362

0,136

0,156

0,149

0,167

502

35,00

1 x 300 0,0607 0,0774

0,110

0,133

0,38

353

0,127

0,146

0,135

0,154

582

43,80

3 x 50

0,391

0,499

0,119

0,143

0,20

380

0,409

0,416

0,513

0,519

160

7,30

3 x 70

0,270

0,344

0,113

0,136

0,22

361

0,293

0,302

0,362

0,370

203

10,20

3 x 95

0,195

0,249

0,109

0,131

0,25

348

0,223

0,235

0,272

0,281

246

13,90

3 x 120 0,154

0,196

0,106

0,127

0,27

336

0,187

0,200

0,223

0,234

287

17,50

3 x 150 0,126

0,161

0,103

0,123

0,29

325

0,163

0,172

0,191

0,203

330

21,90

53

RFOU P20/P22

18 / 30 kV
FORMATION
[ n x mm ]
2

CONDUCTOR
RESISTANCE
[ /km ]
20C
90C

REACTANCE
[ /km ]
50 Hz
60 Hz

CAPACITANCE INDUCTANCE
[ Farad/km ] [ Henry/km ]

20

IMPEDANCE
[ /km ]

50 Hz

60 Hz

50 Hz

MAXIMUM
SHORT
CURRENT
CIRCUIT RATING
90
RATING @ 45C
1 sec.
60 Hz
in air [ A ]
[ kA ]

1 x 50

0,391

0,499

0,148

0,178

0,17

473

0,418

0,430

0,520

0,530

175

7,30

1 x 70

0,270

0,344

0,139

0,167

0,19

442

0,304

0,317

0,371

0,382

222

10,20

1 x 95

0,195

0,249

0,134

0,161

0,22

426

0,237

0,253

0,283

0,297

275

13,90

1 x 120

0,154

0,196

0,128

0,153

0,25

406

0,200

0,217

0,234

0,249

315

17,50

1 x 150

0,126

0,161

0,125

0,150

0,27

398

0,178

0,196

0,204

0,220

367

21,90

1 x 185

0,100

0,128

0,120

0,144

0,29

384

0,156

0,175

0,175

0,192

422

27,00

1 x 240

0,0762 0,0972 0,116

0,139

0,31

369

0,139

0,159

0,151

0,170

502

35,00

1 x 300

0,0607 0,0774 0,111

0,133

0,33

354

0,127

0,146

135

0,154

582

43,80

3 x 50

0,391

0,499

0,139

0,167

0,17

444

0,415

0,425

518

0,526

160

7,30

3 x 70

0,270

0,344

0,130

0,156

0,19

414

0,300

0,312

368

0,378

203

10,20

3 x 95

0,195

0,249

0,125

0,150

0,22

399

0,232

0,246

279

0,291

246

13,90

3 x 120

0,154

0,196

0,121

0,145

0,25

384

0,196

0,212

230

0,244

287

17,50

3 x 150

0,126

0,161

0,117

0,140

0,27

372

0,172

0,188

199

0,213

330

21,90

54

Generals

56

General informations
Some parameters affecting operational characteristics of the cables
mentioned in this catalog

CONDUCTOR RESISTANCE
It Is the most important parameter of the conductor sizing.
It is related to:

conductor resistivity
[ / mm 2/m]
l
conductor length
[km]
A
cross area
[mm 2]
t
temperature
[C]
f
frequency
[Hz]
For low frequencies, conductor resistance is equal to DC condition.

R=l/A

[]

Temperature influence is calculated as:

Rt = R20 (234,5 + t) / 254,5


where:
Rt
conductor resistance
R20 conductor resistance at 20C
t
conductor temperature
Conductor resistance increases with frequency.

[]

[]
[]
[C]

INSULATION RESISTANCE
Its a peculiar characteristic of the insulation material.
An higher value of insulation resistance means larger insulating capacity
of the insulation.
The "insulation resistance constant Ki" is calculated from the measured
insulation resistance by the following formula:

Ki = l R 10-11 / (log10D / d)
where:
R
measured insulation resistance
l
length if the cable
D
outer diameter of the insulation
d
inner diameter of the insulation

[M km]

[]
[m]
[mm]
[mm]
57

SHORT CIRCUIT RATING


The theoretical temperature that arises in XLPE conductors during a short
circuit using a basis of 250C.
The short circuit current for copper conductors is usually given for 1 sec.
For other durations the current may be calculated by the following formula:

lt =

[A]

It = short circuit for t sec. (Amp.)


I = short circuit for 1 sec. (Amp.)
T = short circuit duration (sec.)

INTERFERENCES
Are defined as all the noises influencing the signal transmission.
They are produced internally the cable (i.e. cross talk) and externally (i.e.
power equipments or HF generators).
Both can be reduced by using suitable screenings.

CURRENT DETERMINATION according to power and voltage


In case of three-phase systems, determination of the current Intensity related
to power and voltage can be easily calculated by using:

I = 722 kW / V

I = 578 kVA / V

where
I = current intensity
V = rated voltage
kW = power(cos = 0.8)
kVA = power
HP = horse power

[A]
[V]
[kW]
[kVA]
[HP]

VOLTAGE DROP (up to 1 kV)


V = K I L / 1000 [V]
I
L
K

58

rated current
electric line length
see following table

[A]
[m]

I = 531 HP / V

REACTANCE
In a cable operating in a.c. it is related mainly to axial distance between
conductors.
For 2 - 3 - 4 conductors the reactance per phase could be calculated as:

X=2
f
L
l
L

fLI

[]

frequency
[Hz]
Induction
[H/m]
core length
[m]
Induction Is calculates as follows:

L = 0,2 [(ln 2a / d) + 0.25] 10-6


a
d

distance between cores


core diameter

IMPEDANCE

Z
R
X

[H/m]

[mm]
[mm]

Z = (R2 + X2)

[]

impedance in ohm per phase


resistant @ operating temperature per phase
reactance per phase

[]
[]

MUTUAL CAPACITANCE
Low mutual capacitance causes small distorsion of the signal.
Digital signal transmissions are sensible to this features. Is affected by:
- type of conductor construction (increasing of conductor size means larger
capacitance)
- insulation thickness (inversely proportional)

ATTENUATION
It is defined as the decreasing, in signal amplitude, over the total length of
the cable. Its value increases with the frequency increasing.
Minimizing the attenuation means long distance transmission without
amplification and no distortions.

59

VOLTAGE DROP
nominal

K
2 cores

3 cores

3 cores (three-foil format.)

size
[mm2 ]2

cos =1

cos = 0.8

cos =1

cos = 0.8

cos =1

cos = 0.8

1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

45.0
30.2
18.2
11.4
7.56
4.55
2.87
1.81
1.31
0.967
0.669
0.484
0.383
0.314
0.251
0.193
0.156

36.1
24.3
14.7
9.21
6.16
3.73
2.39
1.55
1.14
0.866
0.624
0.476
0.394
0.341
0.289
0.245
0.215

39.0
26.1
15.7
9.85
6.54
3.94
2.48
1.57
1.13
0.838
0.579
0.419
0.332
0.272
0.217
0.167
0.135

31.3
21.0
12.7
7.98
5.34
3.24
2.07
1.34
0.988
0.750
0.541
0.412
0.342
0.295
0.250
0.212
0.186

38.3
25.7
15.4
9.65
6.42
3.87
2.44
1.54
1.11
0.820
0.568
0.410
0.325
0.265
0.213
0.163
0.132

30.8
20.7
12.5
7.87
5.28
3.22
2.07
1.34
0.993
0.760
0.555
0.428
0.358
0.308
0.265
0.224
0.198

PULLING TENSION DURING INSTALLATION


The cable pulling tension during installation can be estimated of the
following formula:
p = 50 N x total cross section of conductors in the armoured cables
p = 25 N x total cross section of conductors in the unarmoured cables
Additional tension will be supplied from the braid and insulation and
sheathing compound

US / METRIC CROSS SECTION CONVERSION TABLE


Metric

Standard
metric
AWG (U.S.) cross-section cross-section
(mm2 )
(mm2 )

20
18
16
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0

60

0.519
0.823
1.31
2.08
3.31
5.26
8.37
13.30
21.15
33.62
42.41
53.49
67.23
85.01
107.2

0.75
1
1.5
2.5
4
6
10
16
25
35
50
70
70
95
120

Metric

Standard
metric
MCM (U.S.) cross-section cross-section
(mm2 )
(mm2 )

250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1250

126.7
152.0
177.3
202.7
228.0
253.4
278.7
304.0
329.4
354.7
380.0
405.4
430.7
456.0
481.4
506.7
633.4

150
150
185
185
240
300
300
300
300
400
400
400
400
500
500
500
630

61

NOTES

NOTES

CCI - NEK 606:2004 Offshore Cables - REV 04 07-08


All data mentioned in the catalogue may be subject to continuous revision and improved at any time

SRL Group

Head office: Strada Provinciale, n. 117


20010 BERNATE TICINO (MILANO) - ITALY
Phone +39.02.97.25.58.17 a.r. - Fax +39.02.97.25.57.54
www.ccicables.com
e-mail: cci@ccicables.com

Вам также может понравиться