Вы находитесь на странице: 1из 1

ETAP

Project:

14.0.0C

Contract:
Engineer:
Filename:

CRCC_TEMP~

Page:

Date:

06-23-2016

Revision:

Base

Location:

Cable Ampacity Report (IEEE 399)

General

Library

Physical

ID

Cable1

Size (AWG/kcmil)

750

Jacket type:

Tag #

Source

ICEA

Jacket thickness (mil)

From Bus

N/A
Bus1

Insulation

Rubber

Sheath type

To Bus

Bus2

kV

15.0

Sheath thickness (mil)

No./Cable

3/C

% Class

100

Armor type

No. Cond/Phase

Installation

Non-Mag.

Armor thickness (mil)

Length (m)

7500.000

Conduit Type

AL

Armor/Sheath Grounding
Shield Grounding

Installation

None
None
None

Open

Layout

Standard

IEEE 399

Rows

Type

U/G Buried

Column

Tray Layout and #


Cable Layout
Spacing

Allowable Ampacity - Current Carrying Capacity


Base
Operating

Ambient Temperature
20
35

Conductor Temperature
90
90

RHO
90
90

Ampacity / Capacity Result


Operating
0.00

* The calculated depth is smaller than the cable diameter. The cable diameter will be treated as the depth for derating calculation.

Base
538.00

Derated
386.28

Allowable Ampacity / Capacity


386.28 (A) Derated

Вам также может понравиться