Вы находитесь на странице: 1из 23

Design Guide for Fire Services

Installations
Construction II for 2006/07
Design Guides for
Fire Services Installations 1. Fire Services Provision.

2. Fire Services System Design.

3. Recommended Design Practice.


8 February 2007

1 2

1. Fire Services Provision 1. Fire Services Provision

1.1 Audio/Visual Advisory System 1.2 Automatic Actuating Devices


• Required for any floor area exceeding 2,000 m2 • Automatically actuated fire door/shutter/curtain
with transient occupants. Indication signs of to be provided at locations for the purpose of
the system are not required to show on the fire compartmentation or gas flooding systems.
general building plans. Submit detailed design Fire shutter to be operated by smoke detectors
to FSD separately as early as possible. c/w manual controls on both sides except fire
shutter located in carpark areas which to be
operated by heat detector c/w manual control.
Automatic actuating devices not to be
connected to building fire alarm and direct
telephone link.

3 4

1. Fire Services Provision 1. Fire Services Provision

1.3 Automatic Fixed Installations Other Than 1.4 Automatic Fixed Installations Using Water
Water • Automatic sprinkler system designed to LH/
• Provision of automatic gas flooding system to OH(I/II/III/IIIS)/ HH to be provided for all
be avoided except for essential usage with no areas including staircases, common corridor
other alternative. Consider to use CO2 system and toilets but exclude boiler/battery/cold
for un-occupied area before using FM200 storage (Group I minor)/consumer electrical
(heptafluoropropane). equipment/mechanical plant/lift motor/fuel oil
tank/fuel pump rooms/D.G. store. Alarm signal
to be transmitted to F.S. Communication
Centre via direct telephone link.

5 6

1
1. Fire Services Provision 1. Fire Services Provision

1.4 Automatic Fixed Installations Using Water 1.4 Automatic Fixed Installations Using Water
• Water supply to sprinkler tank to be • Provide sprinkler for above ground oil/gas
single/double end feed as confirmed by WSD. boiler room and underground gas boiler room.
Sprinkler system for curtain wall building of • Provide automatic water drencher system in
six storeys and above shall be one grade in accordance with "FOC Rules for the
excess of that normally required for the Installation of External Drenchers (4th
accepted risk category. This can be dispensed Edition)" and/or "Codes of National Fire
with if project architect confirms the building is Protection Association for Water Spray Fixed
constructed in accordance with FRC code 1996. System for Fire Protection (Standard 15)".

7 8

1. Fire Services Provision 1. Fire Services Provision

1.4 Automatic Fixed Installations Using Water 1.4 Automatic Fixed Installations Using Water
• Water to be supplied at 10 l/min per m2 of • Water tank volume to be agreed with FSD for
surface area of opening to be protected. building block with 3 or more refuge floors.
Independent water tank is required for each • Automatic water spray system to be provided in
building block with 30 minutes of water storage. accordance with "Codes of National Fire
• External drencher system operated by heat Protection Association for Water Spray Fixed
detector or sprinkler c/w manual control for System for Fire Protection (Standard 15)".
protection of external wall opening to be
provided for refuge floor. Calculation to be
based on refuge floor with larger external wall
opening.
9 10

1. Fire Services Provision 1. Fire Services Provision


1.4 Automatic Fixed Installations Using Water
1.6 Emergency Lighting
• Water to be supplied at the rate of application as
per NFPA Standard 15 para. 4.4 for the surface • To be provided throughout the entire building
and for all exit signs and routes leading to
area to be protected. 30 minutes of water
ground level and backed up by emergency
storage is required. Locate water tank and
generator and/or secondary battery.
pump room on ground or basement level where
space is available. • Central battery emergency lighting system to
be provided for cinema/theatre and other
1.5 Emergency Generator
specified premises used for entertainment.
• To be provided to supply standby electricity to
all fire service installations and fireman's lift as • Emergency lighting in building not equipped
with emergency generator to be provided with
required in the Code of Practice. Locate the
secondary battery.
engine exhaust flue satisfying EPD's
requirements. 11 12

2
1. Fire Services Provision 1. Fire Services Provision
1.6 Emergency Lighting 1.7 Exit Sign and Directional Sign
• Emergency lighting to be activated within 5 • Sufficient exit and directional sign of self
seconds for all bowling alleys, commercial contained battery type to be provided at
buildings, hotel buildings and institutional locations to ensure that all exit routes from the
buildings. Battery type emergency lighting is floors are clearly indicated as required by the
required to fulfil this requirement. Where configuration of staircases serving the building.
emergency generator is provided, emergency • Battery backup is required for exit sign and
lighting shall also be backed up by the directional sign in bowling alleys, commercial
emergency generator. Allow provisions for buildings, hotel buildings and institutional
ease of monthly discharge test for 1 minute and buildings to meet with the 5-second activation
weekly voltage/ hydrometer tests for central requirement.
battery system.
13 14

1. Fire Services Provision 1. Fire Services Provision


1.8 Fire Alarm System
• Manually operated fire alarm system 1.8 Fire Alarm System
comprising manual breakglass and alarm bell to • According to the Design Manual - Barrier Free
be provided at each hosereel location. The Access 1997, visual fire alarm is required in all
system to be linked to the automatic fire alarm areas accessible by the public for buildings
system and FS Communication Centre via intended to be used by the public. Refer to
direct telephone link. FSD Circular Letter No. 4/2001 (Part 1) on
• Visual fire alarm system to be provided for area extent of application. FSD allows the use of
intended to be accessible to public and the emergency generator or electricity before the
alarm signal shall form part of the fire alarm main switch as the secondary supply source for
system in accordance with FSD Circular visual fire alarm system.
Letters 4/2001 (Part 1) and Clause 9.7 of BS
5839: Part 1: 1988. 15 16

1. Fire Services Provision 1. Fire Services Provision

1.8 Fire Alarm System 1.9 Fire Control Centre


• Additional alarm bells may be required at • To be provided for high rise buildings (over 30
locations other than those adjacent to hosereels m) and special premises (e.g. hotel, industrial
in order to comply with the requirements on building, aircraft maintenance, etc.). However,
sound level stipulated in BS 5839: Part 1. it is strongly recommended to be provided for
• In large buildings and in special premises complex building even it is of low rise. To be
supervised by trained staff, alarm zoning located on street level readily accessible to
provided for phased evacuation to be indicated FSD personnel.
on the drawings for FSD approval.

17 18

3
1. Fire Services Provision 1. Fire Services Provision

1.10 Fire Detection System


1.10 Fire Detection System
• Automatic fire alarm and detection system in
accordance with “Rules of the Loss Prevention • Smoke detection system to be provided for the
Council for automatic fire detection and alarm entire floor of the building excluding toilets,
systems for the protection of property” (LPC bathrooms and staircases which are covered by
Rules) and BS5839: Part 1: 2002 to be sprinkler system, if any part of that floor is
provided for areas not protected by automatic used for sleeping accommodation. Alarm signal
sprinkler system. to be transmitted to F.S. Communication
Centre via direct telephone link.
• Heat detection system to be provided for boiler/
battery/consumer electrical
equipment/mechanical plant/lift motor/fuel oil
tank/fuel pump rooms/D.G. store. 19 20

1. Fire Services Provision 1. Fire Services Provision


1.11 Gas Detection System 1.13 Pressurization of Staircase
• Required for flammable or toxic gas storage • Not to be provided for staircase where there is
and/or emission including SF6 type transformer natural venting of staircases or aggregate area
room, cold storage (Group II), mechanical plant of openable windows of all floors exceed
room, road tunnel and petro-chemical 6.25% of the floor area calculated on a floor by
complex . floor basis.
1.12 Portable Hand Operated Approved Provision to be avoided wherever practical by
Appliances satisfying the conditions specified in the Code
• Required for all non-sprinkler protected areas of Practice. To be confirmed by the Project
like boiler/battery/cold storage/consumer Architect with calculation shown on building
electrical equipment/mechanical plant/lift plans. Design to be submitted by RPE(BS or
motor/fuel tank rooms/D.G. store, etc. Mech) or equivalent.
21 22

1. Fire Services Provision 1. Fire Services Provision


1.14 Smoke Extraction System
• Not to be provided for building with no fire 1. 14 Smoke Extraction System
compartment to exceed 7,000 m3; or the • To be provided for atrium if the compartment
aggregate area of openable window of the of atrium exceeds 28000m3 or if any other level
compartment exceeding 7,000 m3 to exceed forming that compartment exceeds 7000m3..
6.25% of the floor area of that compartment.; • Hot smoke test may be required for smoke
or the design fire load not exceed 1,135 MJ/m2. extraction system in atrium and complex
• Provision to be avoided wherever practicable building. FSD should be consulted at an early
by satisfying the conditions specified in the stage to confirm whether the test is required or
Code of Practice. To be confirmed by the not.
Project Architect with calculation shown on
building plans.
23 24

4
1. Fire Services Provision 1. Fire Services Provision

1. 14 Smoke Extraction System 1.15 Ventilation/Air-conditioning Control System


• If smoke extraction system is designed by using • To be provided to stop mechanically induced
fire engineering approach, the methodology air movement within a designated fire
should be approved by FSD. Design to be compartment. FSD's requirements to be
submitted by RPE(BS or Mech) or equivalent. complied with. Refer to Codes of Practice for
the type of mechanical ventilation systems
which are exempted from VAC provision.
• Refer B.S.B. Circular No. 3 of 2003 for
examples of VAC tripping method.

25 26

1. Fire Services Provision 1. Fire Services Provision

1.16 Dangerous Goods Stores/Fuel Oil Tank


Room 1.17 Others
• Details for the storage/use of dangerous goods • For buildings with life safety risk, all linings
as defined in Chapter 295 of the Laws of Hong for acoustic, and thermal insulation purposes in
Kong to be submitted to the Fire Services ductings, and concealed locations shall be of
Department. Class 1 or 2 Rate of Surface Spread of Flame as
per British Standard 476 : Part 7 or its
• FSD has different requirements for different international equivalent, or be brought up to
types of dangerous goods. Fire damper for that standard by use of an approved fire
door louvre is required to be actuated by retardant product.
detector. Electrical apparatus to be suitable for
the classified hazardous zone.
27 28

1. Fire Services Provision 1. Fire Services Provision

1.17 Others 1.17 Others


• For buildings with life safety risk, all linings • Protection for hospital lifts which are designed
for acoustic, thermal insulation and decorative for evacuation purpose shall satisfy every
purposes within protected means of escape condition for a Fireman’s lift with the
shall be of Class 1 or 2 Rate of Surface Spread exception of the internal floor area of car, and
of Flame as per British Standard 476 : Part 7 or the minimum rated load factors.
its international equivalent, or be brought up to
that standard by use of an approved fire
retardant product.

29 30

5
2. Fire Services System Design. 2. Fire Services System Design.
2.1 Hydrant and Hose Reel System
2.1 Hydrant and Hose Reel System „ The minimum effective quantity of water
„ Hydrant outlet not less than 800mm nor more required to be available, having regard to the
than 1200mm above finished floor level (f.f.l.) floor area factor of the largest floor is as follows,
with design water pressure between 400kPa - „ Floor Area (gross) Water Storage Required
„ Not exceeding 230m2 9 m3
700 kPa. „ Over 230m2 but not exceeding 460m2 18 m3
„ Hose reel will normally cover area with 30 „ Over 460m2 but not exceeding 920m2 27 m3
Over 920m2 36 m3
meters radius and capable of projecting a jet not „

less than 6 meters in length. „ Locate the water storage tank at the top of the
building so that the system is fed by gravity as
far as possible.
31 32

2. Fire Services System Design. 2. Fire Services System Design.


2.1 Hydrant and Hose Reel System 2.1 Hydrant and Hose Reel System
„ Fixed fire pumps capable to provide adequate „ Fixed fire pump shall be duplicated for duty and

flow for three hydrant outlets (each with a flow standby use. Should the duty pump electrically
of 450L/min at a running pressure of not less or mechanically fail to operate within 15s the
than 350kPa) operating simultaneously with an standby pump shall be energized to become the
aggregate flow of not less than 1350 L/min for duty pump.
industrial buildings or two hydrant outlets (each „ Jockey pump shall be set to operate at 95% of
with a flow of 450L/min at a running pressure of the required system pressure and stop when the
not less than 350kPa) operating simultaneously system pressure is restored to 100% level. The
with an aggregate flow of not less than 900 jockey pump shall stop when the fire pump is
L/min for other buildings put into operation.
33 34

2. Fire Services System Design. 2. Fire Services System Design.

2.1 Hydrant and Hose Reel System 2.1 Hydrant and Hose Reel System
„ Hose reel pipe riser shall be not less than 50mm
„ Intermediate booster pumps shall be provided in
all buildings where the height between the in diameter as specified in BS 5306: Part 1 (only
topmost hydrant and the lowest Fire Services 40mm riser is required in para. 5.14 of the
Inlet is in excess of 60m to maintain the flow FSCOP)
and pressure in the rising main system. „ Attenuation for alarm bell concealed in hose reel

„ Twin hydrant outlet shall be fitted with


cabinet shall be checked to ensure sound can be
independent handwheel. clearly heard when the cabinet door is in close
position.

35 36

6
2. Fire Services System Design. 2. Fire Services System Design.
2.1 Hydrant and Hose Reel System 2.1 Hydrant and Hose Reel System
„ When no flow condition of duty pump is „ Fixed fire pump room shall not houses potable/

simulated by closing the stop valve at the duty flushing pump installation.
pump discharge, the fixed fire pump shall „ Auto air relief valve shall be provided at the top
change over to standby pump. of FH riser.
„ Gate valve of hose reel shall be installed not „ HR cabinet door shall not obstruct MOE when
deeper than 500mm from front of cabinet. in open position.
„ Height of HR nozzle shall not be installed
higher than 1,350mm.

37 38

2. Fire Services System Design. 2. Fire Services System Design.

2.1 Hydrant and Hose Reel System 2.1 Hydrant and Hose Reel System
„ Pump ‘start/stop’ control button or indicators „ Fixed fire pump shall not be stopped other than
and alarm buzzer for intermediate booster pump manually reset at local control panel.
shall be provided at FS inlet. „ FS inlet shall be provided with independent non-
„ Pump running, faulty and power on indicators return valve and each FH riser be provided with
shall be provided in central FS panel. independent FS inlet
„ Priming tank shall be provided for fixed fire
pump with negative suction head

39 40

2. Fire Services System Design. 2. Fire Services System Design.


2.2 Automatic Sprinkler System
2.2 Automatic Sprinkler System
„ To control the fire for subsequent
extinguishment by the fire brigade but often the „ To deal mainly with solid-fuel fires, but can

sprinklers will have accomplished serve also to hold a flammable-liquid fire in


extinguishment prior to their arrival. check and to extinguish some oil fires (e.g.
transformer oil fires) by deluge sprinklers purely
„ In accordance with the Loss Prevention Council
using water; to effectively extinguish it, suitable
Rules (LPC Rules) for Automatic Sprinkler
foam concentrate to be added to the water.
Installations (with suitable modification
pertinent to Hong Kong which incorporate
BS5306: Part 2 : 1990 ) or other standards
acceptable to the Director of Fire Services. 41 42

7
2. Fire Services System Design. 2. Fire Services System Design.
2.2 Automatic Sprinkler System 2.2 Automatic Sprinkler System
‰ Hazard Group Height between H/L Sprinkler Capacity of the water tank (m3)
„ The effective water capacity is the amount of ‰ LH 15 9
LH 30 10
water that can be used effectively inside a tank
‰

‰ LH 45 11
without having the least sign of occurrence of a ‰

‰
OH Group I
OH Group I
15
30
55
70
vortex that could draw air into the water being ‰ OH Group I 45 80
OH Group II 15 105
conveyed to the pump. Thus, a certain portion of ‰

‰ OH Group II 30 125
internal volume of the tank cannot be included ‰

‰
OH Group II
OH Group III
45
15
140
135
in the effective capacity calculation. ‰ OH Group III 30 160
‰ OH Group III 45 185
‰ OH Group IIIS 15 160

43 44

2. Fire Services System Design. 2. Fire Services System Design.


2.2 Automatic Sprinkler System 2.2 Automatic Sprinkler System
„ If city water supply to the sprinkler tank is of „ The hazard classification dictate the minimum
double-end-feed, (from 2 mid-level reservoirs), amount of water which must be provided at the
capacity can be reduced as follow, fire in the form of spray and this is normally
expressed as the `design density’. The expected
‰

‰
Hazard Group Min. cap. of the water tank with in-fill (m3) Cap.of the water tank (m3)
LH 2.5 30
max. area of the sprinkler system which will be
‰ OH Group I 25 60 activated by the fire is also dictated and this
OH Group II 50 60
`assumed maximum area of operation’ is
‰

‰ OH Group III 75 60
‰ OH Group IIIS 100 90
expressed in square meters. Design densities and
assumed max. area of operation are,
45 46

2. Fire Services System Design. 2. Fire Services System Design.


2.2 Automatic Sprinkler System
„ Colour code to distinguish sprinklers of different nominal
2.2 Automatic Sprinkler System temperature ratings:-
Hazard Classification Min. design density(mm m/min) Assumed max.
area of operation (m2) „ Fusible Link type (℃) Colour
‰ 68 to 74 Un-coloured
„ Light 2.25 84
‰ 93 to 100 White
„ Ordinary (Group I) 5 72 ‰ 141 Blue
„ Ordinary (Group II) 5 144 ‰ 182 Yellow
„ Ordinary (Group III) 5 216 ‰ 227 Red
„ Ordinary (Group III Special) 5 360 „ Quartzoid Bulb type (℃) Colour of Bulb
„ High 7.5-30 260-375 ‰ 57 Orange
‰ 68 Red
‰ 79 Yellow
‰ 93 Green
‰ 141 Blue
‰ 182 Mauve
‰ 204 to 260 Black

47 48

8
2. Fire Services System Design. 2. Fire Services System Design.
2.2 Automatic Sprinkler System
2.2 Automatic Sprinkler System
„ The deflector plate of the sprinkler head must be
„ The response time index (RTI) is a measure of
mounted parallel to the surface to which it is
sprinkler thermal sensitivity and sprinklers are
fixed.
graded according to the sensitivity range into
which they fall. The three response classes are : „ All shafts must have one head installed at the

standard response (RTI between 80 and 200); top of the shafts. If the shaft is built from
special response (RTI between 50 and 80) and combustible material, additional heads should be
quick response (RTI below 50). Recessed, installed at alternate floors. If the shaft is built of
concealed and horizontal sidewall sprinklers are non-combustible material, heads should be
not classified and are referred to as `unrated’. located as required. In the case of combustible
stairs, sprinklers should be installed to protect
49 both the underside and the top of the staircase. 50

2. Fire Services System Design. 2. Fire Services System Design.

2.2 Automatic Sprinkler System 2.2 Automatic Sprinkler System


„ Suspended ceilings exceed 800 mm deep to be „ Dry pipe system is used where the system
protected by sprinklers as well as the room pipework may be subjected to freezing
space below. temperatures such as in cold stores, fur vaults
„ The number of sprinklers controlled by one set etc. or where the temperature is maintained
of valve shall not exceed 500 in case of light above 70oC as in drying ovens etc..
hazard and 1000 in case of other hazard. „ The installation is pressurized with air within the
pressure range recommended by the alarm valve
manufacturer and not exceed 400 kPa.
51 52

2. Fire Services System Design. 2. Fire Services System Design.


2.2 Automatic Sprinkler System
2.2 Automatic Sprinkler System
„ Pre-action system is also a type of dry pipe
„ A drop of the pressure to a predetermined value
installation. There are two types of pre-action
opens the installation dry alarm valve and
installation. Type 1 is used to prevent a
primes the installation. Each installation is
premature discharge of water from pipework or
served by an independent air supply system. In
sprinklers that have suffered mechanical damage;
cold room, the installation is fitted with upright
and Type 2 is used to facilitate an early
sprinklers and automatic means are fitted to
discharge of water from a dry pipe installation
automatically shut down the air circulation fans
by opening the installation main control valve,
of cooling system when the sprinkler system
thus filling the installation control pipework
operates.
with water, upon operation of a fire detection
53 system. 54

9
2. Fire Services System Design. 2. Fire Services System Design.
2.2 Automatic Sprinkler System
2.2 Automatic Sprinkler System „ The number of dry sprinklers will not exceed
„ For Type 1 system, the water is normally flow 500 and 1000 per installation for light hazard
into the pre-action pipework when the sprinkler and ordinary/high hazard installation
is opened and the fire detection system is respectively.
operated. For Type 2 system, the water fill the „ Audio and visual warning of pump power failure
pre-action system pipework upon operation of a shall be provided at control panel.
fire detection system before the sprinkler is
„ Thermal overload cut-off is not necessary for
operated. Type 2 system will normally be used
sprinkler pump and sprinkler pump protection
for pre-action system.
shall be protected by HRC fuse.
55 56

2. Fire Services System Design. 2. Fire Services System Design.

2.2 Automatic Sprinkler System 2.2 Automatic Sprinkler System


„ Sprinkler shall be provided underneath the „ Length of sprinkler suction pipe from tank shall
platform of the chute inside refuse collection be less than 30m.
room. Sprinkler head provided at top of refuse „ Sprinkler provision for open cell ceiling shall be
chute shall be of 57°C. supported with calculations of ceiling free area.
„ Duplicate ‘pump power supply’ indicators for „ Sprinkler shall be provided underneath
each phase of building shall be provided. ventilation duct with width greater than 800mm,
or 1000mm if over 150mm from wall.

57 58

2. Fire Services System Design. 2. Fire Services System Design.


2.3 Gaseous Extinguishing System
2.3 Gaseous Extinguishing System
„ Gaseous extinguishants are effective medium for
„ Carbon dioxide, halon 1301 (BTM) and halon
the extinction of flammable liquid fires and fires
1211 (BCF) were the common gases used for
in the presence of electrical hazards. Gaseous
non water-based automatic fire suppression
systems are usually used for hazards which are
system in the past. However, halons have been
located inside buildings, or around which
prohibited form importing into Hong Kong for
protective screens can be erected. They are
local consumption since Jan 94.
suitable for most combustible material except
those which contain their own oxygen supply, or „ There are two basic alternatives to replace

chemicals that react with the gas. halons.


59 60

10
2. Fire Services System Design. 2. Fire Services System Design.
2.3 Gaseous Extinguishing System 2.3 Gaseous Extinguishing System
„ The halocarbon agents extinguish fire by „ The unit cost of the gas for the chemical agent is
reaction with the combustion process and by much higher than for the inert gas agent but the
cooling the atmosphere in the enclosure. They quantity required is far less. This means that
are clean , environmentally acceptable and may halocarbon option may be more suitable where
be regarded as `chemical gas’. storage is restricted.
„ The inert gas agents are permanent gas blends „ Surveyor report for gas cylinder shall be
based on nitrogen which extinguish fire by submitted to FSD for approval.
reducing the oxygen content of the atmosphere „ Mechanical emergency manual release shall be
from 21% to below 15%. provided.
61 62

2. Fire Services System Design. 2. Fire Services System Design.

2.3 Gaseous Extinguishing System 2.3 Gaseous Extinguishing System


„ Inert gas agents are stored in gaseous rather than „ Designed and installed in accordance with either
liquid form, the frictional losses in the pipework BS 5306 Part 4 or NFPA 12
will be very small thus the storage bottles for „ Only be used in normally unoccupied areas
inert gas agents can be positioned some distance where egress of personnel can be accomplished
away from the risk. in thirty (30) seconds.
„ Clean agents including FM200, NAFS-III, „ Carbon dioxide obtained by converting dry ice
Inergen and CEA-410 systems are considered as to liquid will not be acceptable.
acceptable halon alternative.
63 64

2. Fire Services System Design. 2. Fire Services System Design.


2.3 Gaseous Extinguishing System 2.3 Gaseous Extinguishing System
„ Carbon dioxide is stored in rechargeable „ Carbon dioxide total flooding systems is
cylinders to hold it in liquid form at ambient designed to discharge CO2 into the entire
temperature. There are two types of storage enclosed space in order to produce a
system, the high pressure system and the low concentration sufficient to extinguish a fire
pressure system. For high pressure system, anywhere within the space.
carbon dioxide is pressurized to a corresponding „ The design concentration (34% for surface fire
nominal pressure of 5860 kPa at 21°C. The and 50% for deep seated fire) to be achieved
normal filling density would not be in excess of within 1 minute and 7 minutes for surface fire
68%. and deep-seated fire respectively.
65 66

11
2. Fire Services System Design. 2. Fire Services System Design.
2.4 Manual and Automatic Fire Alarm System
2.3 Gaseous Extinguishing System
„ Manual alarm system consist of breakglass units
„ Carbon dioxide system is actuated when fire is and alarm sounders connected to a control panel,
detected by smoke or heat detectors. Sufficient only operated and the alarm raised when
detectors is installed to give duplicate coverage activated by an individual having detected a fire
of the whole of the protected area and connected incident.
in cross-zones.
„ Automatic systems consist of smoke and heat
detectors, in addition to those in manual alarm
system to raise the alarm whether or not
personnel are present at the time, thus giving
67
early warning of a fire incident. 68

2. Fire Services System Design. 2. Fire Services System Design.

2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
„ Automatic fire detection and alarm (AFA) „ Fire alarm systems may be installed in buildings
system provides warning of fire danger and to satisfy one, or both, of two principal
permits counter-action to be taken usually objectives, i.e. protection of life and protection
before the danger has reached serious proportion. of property. The objectives may differ in time or
„ AFA system shall be designed and installed in place. Because of the great variety of
accordance with the specifications given in the applications for system, BS5839 fire alarm
BS5839: Part 1: 2002 and FSD Circular 1/2002 systems are divided into a number of different
Categories.

69 70

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
„ Category M System - manual alarm system 2.4 Manual and Automatic Fire Alarm System
„ Category L System - automatic alarm system stage to enable all occupants, other than possibly
intended for protection of life. It is subdivided those in the room of fire origin, to escape safely,
into before the escape routes are impassible.
L1 - systems installed throughout all areas of the L2 - with L3 coverage plus the objective of
building, thus offer the earliest possible warning affording early warning of fire in specified areas
of fire to achieve the longest available time for of high fire hazard level
escape L4 -systems installed within those parts of the
L3 - systems installed only in defined parts of escape routes comprising circulation areas
the building thus giving a warning of fire at an
early 71 72

12
2. Fire Services System Design. 2. Fire Services System Design.

2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
L5 - systems in which the protected area and the P1 - systems installed throughout all areas of the
location of detector is designed to satisfy a building, thus offer the earliest possible warning
specify fire safety objective. Often the design is of fire so as to minimize the time between
based on a fire risk assessment or form parts of a ignition and the arrival of fire fighters
fire engineering solution. P2 - systems installed only in defined parts of
Category P Systems - automatic alarm system the building to provide early warning of fire in
intended for protection of property. It is areas of high fire hazard level.
subdivided into
73 74

2. Fire Services System Design. 2. Fire Services System Design.

2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
„ BS5839 does not recommend which Category of „ Manual fire alarm systems are often sufficient to
systems need to be installed in any given satisfy legislation in workplaces in which no one
premises. However, an informative annex sleeps. Automatic fire detection system is
(Annex A) is attached with the standard to usually required by legislation to supplement the
provide information on the Categories of manual system in premises in which people
systems that are typically installed in various sleep. AFA might also be necessary to satisfy
types of premises. legislation under the following circumstances,

75 76

2. Fire Services System Design. 2. Fire Services System Design.

2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
- AFA forms part of a fire engineering solution „ Fire detectors are designed to detect one or more

- AFA detection is needed to operate fire of the four characteristics of fire, namely, heat,
protection system such as door closing facilities smoke, combustion gas (such as carbon
or smoke control system monoxide) and infra-red or ultraviolet radiation.
- the low level of occupancy of a building may „ Heat detectors may take the form of either point

create potential risk to occupants before they are type detectors or line type detectors. The
aware of the fire detection system may be designed to respond
when a fixed temperature is reached.
77 78

13
2. Fire Services System Design. 2. Fire Services System Design.
2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
„ Smoke detectors detect smoke either by means „ Flame detectors detect the infra-red and/or

of reduction in current flows between electrodes ultraviolet radiation that is emitted by flame.
(ionization chamber type) or the scattering of „ In selection of the type of fire detectors, we
light results from the presence of smoke (optical should consider the speed of response required,
smoke type) or the obscuration of the light the need to minimize false alarms and the nature
between the light source and the receiver of the fire hazard.
(optical beam type). „ Heat detectors are less sensitive and not suitable
„ Combustion gas detectors respond to the gases for the protection of areas where warning of the
produced by a fire such as carbon monoxide. presence of smoke is required.
79 80

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System
„ However, they have the greatest immunity to
„ Optical beam smoke detectors is economical and
false alarms.
effective for the protection of large, open plan
„ Optical smoke detectors are sensitive optically
spaces with relatively high ceilings, particularly
dense smoke but less sensitive to small particles. if access to point smoke detectors for
They are well suited for use in escape routes maintenance.
because they detect visible smoke and might
„ In general, smoke detectors give faster response
operate before the escape route becomes
to most fire than heat detectors, but are more
impassible.
likely to give false alarms.
81 82

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System - escape routes in Cat. L system
„ As recommended in BS5839, heat detectors may - areas in which the production of smoke could
be used in any area other than the following, present a threat to occupants’ escape before it is
- Cat. P system in which a small fire has the likely to be detected by people or heat detection
potential to cause unacceptable damage „ Smoke detectors may be used in any area other
(products of combustion may be corrosive and than the following,
cause considerable damage without burning the - the principal fire hazard is the presence of
contents of the affected area. flammable liquids or gases that produce little
smoke
83 84

14
2. Fire Services System Design. 2. Fire Services System Design.
2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System
- areas in which high potential for false alarms
(e.g. generator room) „ The limits of ceiling height for installation of
detectors (general) are as follows,
- Cat. L systems, smoke detectors installed
within corridors and stairways that form part of Heat detectors (Class A1) - 9.0m
the means of escape should be of optical type, Heat detectors (Other Classes) - 7.5m
unless the use of optical detectors would Point Smoke Detectors - 10.5m
significantly increase the rate of false alarm Optical Beam Smoke Detectors - 25.0m
„ Use optical smoke detectors for smouldering fire

85 86

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System
„ The greatest concentration of smoke and heat
„ The limits of ceiling height for installation of will generally occur at the highest parts of
detectors (Cat P System and 5 min. fire services enclosed areas and therefore detectors should
attendance) are as follows, normally be sited at these locations. Heat
Heat detectors (Class A1) - 13.5m detectors should be sited so that the heat
Heat detectors (Other Classes) - 12.0m sensitive element is not less than 25mm nor
Point Smoke Detectors - 15.0m more than 150mm below the ceiling or roof. If a
protected space has a pitched roof, smoke
Optical Beam Smoke Detectors - 40.0m
detector should be installed in each apex.
87 88

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System „ In system that incorporate more than 40
„ The spacing for detectors under flat ceilings is automatic fire detectors, it is not `acceptable’
7.5m if the nearest detector is a smoke detector (i.e. the user should instigate an in-depth
(i.e. area coverage of 100 sq.m) and 5.3m if the investigation by specialist) if in any rolling
nearest detector is a heat detector (i.e. area period of 12 months, either
coverage of 50 sq.m). - the average rate of false alarm exceeds one
„ In BS5839, a comprehensive guidelines for false alarm per 20 detectors per annum or
different Category of system and various - more than two false alarms are initiated by any
application had been stated. single manual call point or detector location
89 90

15
2. Fire Services System Design. 2. Fire Services System Design.
2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
„ The standby battery capacity for Fire Services
„ The capacity of battery shall maintain the fire
Panel should be determined by consultation with alarm and control system in alarm condition for
the battery manufacturer and should take into 30 minutes and maintain the system at normal
account the standby load, the alarm load, any condition for not less than 24 hours (or 18 hours
required de-rating to take account of the higher if emergency generator is installed).The battery
current drawn in the alarm condition and a de- shall maintain the automatic power failure alarm
rating factor to take account of battery ageing for 72 hour duration for sprinkler control
during the anticipating life of the battery. system(consider to use two battery system).

91 92

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System
„ The minimum capacity of valve regulated lead
acid batteries should be calculated in accordance
with the following formula: T1 = total battery standby period in hours;
C min = 1.25 (T1 I1 + D I 2/2) I1 = total battery standby load in amperes;
where I2 = total battery alarm load in amperes;
C min = minimum capacity of the battery D = a de-rating factor.
when new at the 20 h discharge rate and at When C min/20 is equal to or greater than I2, it
20°C in ampere-hours; can be assumed than D = 1.

93 94

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
„ When C min/20 is less than I2, the value of D „ For total floor areas >300m2, zoning of detectors
should either be based on battery manufacture’s shall not cover area more than one floor level
data or should be 1.75. except for stairway.
„ In practice, C min is unlikely to correspond „ The floor area of single zone should not exceed
exactly to an available battery capacity and 2000m2, other than in the case of a zone
therefore the next highest available capacity size comprising mainly a single, open plan area not
should be used. exceed 10000m2.
„ Battery capacity calculation shall be „ For non addressable system, the floor area of
documented. single zone should not exceed 2000m2.
95 96

16
2. Fire Services System Design. 2. Fire Services System Design.
2.4 Manual and Automatic Fire Alarm System
„ The search distance (the distance that has to be 2.4 Manual and Automatic Fire Alarm System
traveled by anyone responding to a fire alarm „ The detector and annunciator panel shall be of
signal after entry to the zone in order for the FSD approved type.
location of fire to be determined visually) shall
„ Breakglass unit shall not cover more than one
not exceed 60m
floor level
„ Sensing element of smoke detector shall be
„ Smoke detector shall be provided to entire floor
installed between 25mm to 60mm from soffit of
with sleeping risk (heat detector may be used in
ceiling.
kitchen).
„ Sensing element of heat detector shall be
installed between 25mm to 150mm from soffit
of ceiling. 97 98

2. Fire Services System Design. 2. Fire Services System Design.

2.4 Manual and Automatic Fire Alarm System 2.4 Manual and Automatic Fire Alarm System
„ Detector shall be provided to area not covered „ Detector shall be provided to ceiling void with
by sprinkler, e.g. MDF room, pump room, etc. depth greater than 80mm and void containing
„ Electrical earthing shall be provided to safety combustible irrespective of its depth. (except for
barrier in intrinsically-safe detector installation. LV power cable in metal conduit/trunking)
„ Detector shall be provided to void with beam „ AFA shall be provided to basement area (except

depth greater than 10% of ceiling height. car parking area and safe deposit vault) and
„ Detector shall not be positioned more than 1.5m
intermediate pump enclosure.
from open area or void.
99 100

2. Fire Services System Design. 2. Fire Services System Design.


2.4 Manual and Automatic Fire Alarm System
2.4 Manual and Automatic Fire Alarm System
„ Detectors not to be mounted within 500mm of
any walls, partitions or obstructions to flow of „ Where structural beams or ductwork or lighting

smoke and hot gases with depth over 250mm. fittings less 250mm depth that create obstacles
to the flow of smoke, detectors should not be
„ Ceiling obstructions such as beams deeper than
mounted closer to the obstruction than twice the
10% of the overall ceiling height should be
depth of the obstruction
treated as wall
„ Where an area contains partitions or racks that
reach within 300mm of the ceiling, the partitions
should be treated as wall
101 102

17
2. Fire Services System Design. 2. Fire Services System Design.
2.5 Audio and Visual Alarm System 2.5 Audio and Visual Alarm System
„ A system of records/ signals either verbal, „ Supplied and installed to all areas and places

graphic or musical or direct transmission over a controlled and classified under Places of Public
Public Address System to advise staff and other Entertainment Ordinance, Cap 172 and to other
occupants of emergency condition and the areas as required in FSD Requirements and
action to be followed. It supplement exit signs Circular Letters. In special occupancy premises
and fire alarm warning devices and when e.g. hospitals, cinemas, an agreed sound signal
operated in the event of a fire, provides audio / may be broadcast to give early warning to staff
visual indication of safe direction of egress from of emergency condition which may or may not
the area. necessitate action by them at that time.
103 104

2. Fire Services System Design. 2. Fire Services System Design.


2.5 Audio and Visual Alarm System 2.5 Audio and Visual Alarm System
„ The floor is evacuated by operating the lights on „ For sounders to be used in premises such as
that floor in flashing mode and the evacuation hotels, boarding houses, etc. where it is required
routes are indicated by low-level Directional to wake sleeping persons, the sound level should
Signs. be 75 dBA minimum at the bedhead.
„ Under BS5839, the fire alarm bell is required „ The frequency produced by fire alarm sounders
produce a minimum sound level of either should lie in the range of 500Hz to 1000Hz. The
65dBA or 5dBA above any background noise sounders should be provided near the control
likely to persist for a period longer than 30 and indicating equipment to draw attention to
seconds, whichever is greater, at any accessible the indications of fire.
point in the building. 105 106

2. Fire Services System Design. 2. Fire Services System Design.

2.5 Audio and Visual Alarm System 2.5 Audio and Visual Alarm System
„ The level of sound provided should not be so „ For the attenuation of sound in air, we may use
high (say for example 120 dBA) as to cause the inverse square law as the rule of thumb in
permanent damage to hearing. estimation, i.e. Lp – Lp’ = ∆ Lp = 20 log (d / do)
„ To estimate the fire alarm level within the same where Lp is the sound level of the bell at the
room/area e.g. in the public area, we need only distance of do =1m, and Lp’ is the sound level
to consider the attenuation of sound due to after the attenuation of distance d. We can take
distance effect. 65 dBA as the minimum criterion, or use 5-15
dBA above the ambient sound level as the
criterion when the background noise level is
107 high. 108

18
2. Fire Services System Design. 2. Fire Services System Design.
2.5 Audio and Visual Alarm System 2.5 Audio and Visual Alarm System
„ If the fire alarm bell is located in a separate „ When the door of the room is opened, the sound
room/area, the sound level generated by the fire passing through the door will be dominant.
alarm bell will be attenuated by the furnishings Attenuation through the wall is therefore not be
in the room where it is situated and by the considered. Only the attenuation due to entry
wall/door through which the sound passes. and due to furnishings in the next room will be
„ After the average sound level is calculated for considered. Additional paths such as air ducts,
the room where the fire alarm bell is situated, etc. for the noise to travel to the next room will
the sound level in the next room can be reduce the attenuation and should also be
estimated by calculating the attenuation due to considered.
door/obstacle. 109 110

2. Fire Services System Design. 2. Fire Services System Design.

2.5 Audio and Visual Alarm System 2.5 Audio and Visual Alarm System
„ Strobe light on its own which is required to be „ The visual alarm system shall be of flashing

installed in conjunction with fire alarm systems light operating at 24V DC providing a minimum
inside buildings does not required specific of 75 candela (cd) light output. The system shall
approval from FSD. Only beacon lamp comply with Section 6-4 of NFPA 72 : National
integrated with sounder or intrinsically safe Fire Alarm Code or BS 5839. In NFPA 72,
beacon lamp is required to be of approved type. Clause 6-4.2.2, the light source shall not exceed
Also, traditional red colour for flashing light is 1000 candela (cd) (effective intensity). The
for achieving a better fire alarm alert effect. intensity of light varies from 15 cd to 185 cd
depending on the size of the room and the
111
number of visual alarm unit. 112

2. Fire Services System Design. 2. Fire Services System Design.


2.5 Audio and Visual Alarm System 2.5 Audio and Visual Alarm System
„ For area with sleeping risk, in order to offset the „ If more than two flashing units are installed in a
obscuration effect of smoke near the ceiling, a room, they shall flash in synchronization or be
value of 177cd would be required when the spaced at more than 16.76m apart i.e. requiring a
notification appliance is located within 24 higher light intensity level. For sleeping area
inches of the ceiling, and a value of 110cd having no linear dimension greater than 4.87m,
would be used when the distance is greater than the intensity of the unit shall be 110cd if the
24 inches. For flashing unit, the light pulse shall distance from ceiling to top of the lens is greater
not exceed two flashes per second not be less than or equal to 0.61m and 177cd if the distance
than one flash every second. The pulse duration if less than 0.61m.
shall be less than 0.2 second. 113 114

19
2. Fire Services System Design. 2. Fire Services System Design.
2.6 Emergency Lighting System
„ Emergency lighting shall be of battery operated
2.6 Emergency Lighting System
type for building not provided with generator to „ Provided within 2m from each exit door; near

fulfill the 15 second requirement after power intersections of corridors, near each staircase so
changeover. that each flight of stairs receives direct light;
„ Exit sign shall be provided to the common area
near each change in direction; near any change
in high rise domestic building. in floor level; near fire fighting equipment and
fire alarm call point.
„ Emergency lighting shall be provided
throughout the entire building and for all exit
signs and routes in accordance with FSD
Requirements Circular Letters and FSDCOP. 115 116

2. Fire Services System Design. 2. Fire Services System Design.


2.6 Emergency Lighting System
2.6 Emergency Lighting System
„ The minimum illumination provided at floor
„ At least two emergency lighting in any one
level shall be 0.2 lux anywhere along the centre
line of the defined escape route and 0.1 lux over installation to cater for the case of the failure of
a central band 1 meter wide. any one lamp.
„ All emergency lighting fitting shall be of non-
„ The average luminance for undefined escape
routes should be not less than 1 lux. For flammable type (resistance to flame and ignition)
staircase, the illumination should not less than 2 complying with BS EN 60598-2-22.
lux. The lux values should be measured at the „ If the central battery emergency lighting system

mid-point between any two emergency lighting is used, there is a greater flexibility in the choice
fittings. of lighting fitting.
117 118

2. Fire Services System Design. 2. Fire Services System Design.


2.6 Emergency Lighting System
2.6 Emergency Lighting System
„ - the whole battery/emergency lighting system
„ Recommended to provide a separate lighting
including lighting fitting can be separated from
system for the battery/emergency lighting
the electrical contract and therefore it can be
because:
installed/maintained by a registered fire service
„ - the power of the lighting is smaller. It can be contractor as required by Fire Services
solely designed to meet with the fire service Department.
requirements during power interruption without
„ - with smaller power requirement of battery
taking into account of the requirements during
lighting, the capacity of central battery system
other period of normal use.
can be made even smaller and thus the cost is
119
reduced. 120

20
2. Fire Services System Design. 2. Fire Services System Design.
2.6 Emergency Lighting System
2.6 Emergency Lighting System
„ If higher illumination level is required during
„ May select a separate system of energy efficient power interruption for other client’s
down lights of small size using 5W-25W lamps requirements, it can be met by providing
to meet with the illumination requirements in emergency power supply to the lighting
BS5266. The battery-connected lighting can be designed for normal use. They should be
of non-maintained type and be activated only separated from the battery connected emergency
during power interruption. For areas without lighting system where possible.
ceiling, fluorescent light fitting or other lamps of
„ Exit signs should be positioned between 2m and
suitable types can be used.
2.5m above FFL according to BS5266
121 122

2. Fire Services System Design. 2. Fire Services System Design.


2.6 Emergency Lighting System 2.6 Emergency Lighting System
„ The capacity of the battery for emergency
„ EN60598-2.22 required the life span of dry
lighting required is 2 hours while international battery for battery lighting to be 4 years; i.e. the
standard normally required the battery to be battery shall be replaced in 4 years
tested for 1 hour or 3 hours.
„ Battery charger shall provide the rated charge
„ FSD has clarified that Clause 2.9 (ii) of COP
performance specified by the battery
apply to Central Battery System only and for manufacturer to charge the batteries within 24
self-contained emergency luminaires, the hours over the rated ambient temperature
maintenance should follow Clause 12 of
BS5266-1:1999
123 124

2. Fire Services System Design. 3. Recommended Design Practice

2.6 Emergency Lighting System „ Though FSD submission is not mandatory for
„ If electronic ballast is used for emergency works carried out by ArchSD, we are committed
lighting, care shall be taken to ensure that the to have the same design standard.
electronic ballast can withstand the transient „ Sprinkler pipework shall be installed to falls so
high voltage build up during the changeover that air can be vented. The water can also flow
from battery to normal power supply to the low points and be drained off for
„ FSD allows the use of radioactive self-luminous maintenance or when other considerations
exit/directional sign. Remind the building owner demand.
to obtain licence from the Hong Kong Radiation „ Use Ni-MH battery or products having
Board. equivalent functions in FS system
125 126

21
3. Recommended Design Practice 3. Recommended Design Practice
„ As halocarbon gases are heavier than air, for
halocarbon gases systems, provide openings in
„ Recycling system shall be provided to restrict
the room at low level to allow heavy gases to
water damage after a fire is extinguished; to
leak out of the protected area.
avoid closure of the main installation stop valve
if modifications are made to the installation „ High Pressure Carbon dioxide system is
pipework or if sprinkler heads are to be replaced; normally used.
to prevent water damage caused by accidental „ Clean agent used is normally FM200 except in
mechanical damage of the installation pipework areas with high ceiling height or with low
or sprinklers. temperature or with limitation in storage spaces
for the clean agent that makes the use of FM200
unsuitable.
127 128

3. Recommended Design Practice 3. Recommended Design Practice


„ Even in building with comprehensive fire
detection, the provision of manual call points „ At the design stage of every system, there
will still normally be of great value, people in should be formal consideration of the potential
the vicinity of a fire will normally be aware of for false alarms, with a view to confirming that
the fire, and able to raise the alarm by use of a design is such that the frequency of false alarms
manual call point, before it is detected is likely to be acceptable
automatically. „ Any relevant design information regarding false
„ Heat detectors that operate only when the rate of alarms should be recorded and documented in
rise of temperature is abnormal, but not when a accordance with the recommendations of Clause
fixed temperature is reached do not comply with 40 of BS5839
BSEN54-4 and ought not to be use.
129 130

3. Recommended Design Practice 3. Recommended Design Practice

„ Audio/visual warning indicator for emergency


generator ‘on/failure’ shall be provided at local „ Tripping of ventilating fan shall be by smoke
panel and FS control panel. detection device with manual override switch
„ Cooling and exhaust duct for generator passing provided at FS control panel.
through compartment shall be provided with fire „ FSD’s approval of Automatic Actuating Device
damper. design is required for closing time of horizontal
„ Annunciation panel to be located on street level fire shutter not exceeding 60 seconds. FSD will
readily accessible to FSD personnel, or in Fire inspect the actuating device and the operation of
Control Centre where provided. the fire door/shutter/curtain.

131 132

22
3. Recommended Design Practice 4. Recommended Design Practice

„ Use pre-action or pre-action recycling sprinkler „ Locate water tank and pump room on ground or
system for computer room where possible. basement level where space is available. Only
Limit the volume of D.G. Store within 44 m3. one sprinkler inlet is required for each zone.
„ Ceiling mounted gas fire extinguisher to be used Provide duplicate alarm valve for all buildings
to protect D.G. store and other areas requiring except no life safety risk. Supply water tank to
gas flooding system with volume smaller than be refilled to its full capacity within 6 hours by
44 m3. automatic means or by a transfer pump powered
„ Check and ensure the transformer provided by by essential power supply.
Supply Company is non-flammable type.

133 134

4. Recommended Design Practice 4. Recommended Design Practice

„ Sprinklers installed in heated rooms including


kitchen/cooking area/autoclave room to have a „ Two stages fuel capacity alarm/control to be
temperature rating of 93oC. Fast response provided to alert management/to shut down
sprinkler system to be provided in basement other essential load when the fuel storage for
with sprinkler flow switch connected to the generator is reduced to that required to maintain
general fire alarm. a minimum 6-hour continuous operation for fire
„ Provide one FS inlet for each hydrant riser and a service installation. FSD’s approval required for
common header not higher than 30m above one generator set serving more than one block.
ground level to link up all risers.

135 136

4. Recommended Design Practice


„ Include the provision of Exit sign and
directional sign under the fire service
installation contract for single responsibility and
better co-ordination. They shall be connected to
both main and emergency power supply. If the
building is not equipped with an emergency
generator, exit sign and directional sign shall be
THE END
backed up by secondary battery.
„ For new projects, centrally supplied emergency
lighting system should be considered with
priority.
137 138

23

Вам также может понравиться