TRANSFORMER SPECIFICATION REFERENCE

IS 2026 [PART I, II & IV]-1977 & [PART III] -1981

TYPE SOCR FORM 3NYC

HV 9000 TYPE OF COOLING ONAN


kVA
IMPEDANCE VOLTAGE
LV 9000 9.12 %
(9.0 MVA BASE RATED TAP)
HV 66000 CONNECTION SYMBOLS YNd1
VOLT
(AT NO-LOAD)
LV 11000 MASS OF CORE & WINDING kg 9800

HV 78.8 MASS OF OIL kg 4500


AMPERE
LV 473 TOTAL MASS kg 20000

NO. OF PHASES 3 MASS OF HEAVIEST PACKAGE kg 16500

FREQUENCY 50 Hz UNTANKING MASS kg 9300

DIAGRAM DRG. NO. TK 204580 UNTANKING HEIGHT mm 4350

MAKER’S SER. NO. 110088-1 VOLUME OF OIL L 5060

YEAR OF MANUFACTURE 1990

GUARANTEED MAXIMUM TEMPERATURE RISE OF OIL - 45°C, WINDING - 55°C

IMPULSE TEST POWER FREQUENCY TEST VECTOR DIAGRAM


WINDING
VOLTAGE kV peak VOLTAGE kV rms
HV LV

HV LINE 350 140

HV NEUTRAL 95 38

LV 75 28

HV OFF-CIRCUIT TAP CHANGER


TAP SELECTOR CONNECTION 1N
1NS1 1NS2
1.2 1.1
1U 2U
HV LINE TERMINALS 2.1
2.2
POSITION CONNECTION 7 6
5 4
3
2VS2 2VS1
VOLT % VOLT AMPERE 1.2 1.1
1V 2V
2.1
2.2
1 4-5 107.5 70950 73.3 7 6
5 4
3

1.2 1.1 2W
1W
2 4-6 105.0 69300 75.1 3
2.1 2.2
7 6
5 4

3 3-6 102.5 67650 76.9


4 3-7 100.0 66000 78.8

BUSHING CURRENT TRANSFORMERS CONFORMING TO IS 2705: [PARTS I ~ IV] - 1981

MINIMUM
MAXIMUM
KNEE MAXIMUM
SEC. WINDING
SECONDARY ACCURACY POINT MAGNETIZING
CIRCUIT RATIO VA A.L.P RESISTANCE
TERMINALS CLASS VOLTAGE CURRENT AT Vk °
AT 75 C
Vk [ mA ]
[ OHMS ]
[ VOLTS ]
HV
1NS1-1NS2 100/1 30 10P 10 250 600 1.0
NEUTRAL
LV LINE 2VS1-2VS2 473/2 − 3.0 − − − −