SL 80 - 399 condensing boiler

specifications

Specification SL 80-399
CSA Input (Natural Gas or Propane) - MBH 80 - 399 DESCRIPTION SIZE
CSA Input (Natural Gas or Propane) - kW 23.4 - 117
A Flue Outlet 4 1/2" O.D. PVC/CPVC Pipe
CSA Output - MBH 77 - 382
Combustion Air
CSA Output - kW 22.6 - 112 B
Inlet
4 1/2" O.D. ABS/PVC/CPVC

Combustion Efficiency (CSA 4.9 - 2010) 95.7% C Safety Relief Valve 3/4" NPT

Minimum gas supply pressure (Natural Gas or Pro- D LCD Display


pane) - inch w.c. 5 E Water Outlet 1 1/2” NPT - M
Maximum gas supply pressure (Natural Gas or Pro- F Water Inlet 1 1/2” NPT - M
pane) - inch w.c. 14
G Knock-outs (6) 1/2”
Power use (115Vac/60Hz) @ full fire - Watts 345 (excl. pumps) H Gas Inlet 3/4” NPT - M

Weight (empty) - lbs/Kg 240 / 110 I Condensate Outlet 3/4” Flexible Hose Barb

Pressure vessel water content - USG/Litres 7 / 26 Dimensions

Maximum boiler flow rate - USgpm 45


MaxIMUM
EXHAUST Pipe Size
Minimum boiler flow rate - USgpm 20 EquivAlEnt Length
4" 150' (each side)
Maximum operating water pressure* - psig 30
90° vent elbow allow 8’ equivalent
Minimum water pressure - psig 8
90° long sweep vent elbow allow 5’ equivalent
Approved installation altitude - ASL 0 - 8,000’
45° elbow allow 3' equivalent
Ambient temperature - Low/High (°F-°C) 34°F(1°C)/122(50)
Maximum exhaust venting length
Max. relative humidity (non-condensing) 90%
Minimum water temp. 34°F / 1.1°C Distance from Combustible
Surface
Maximum water temp. (electronic hi-limit) 185°F / 85°C Surfaces
Front 1"
Maximum water temp. (mechanical hi-limit) 200°F / 93.3°C
Rear 0"
Max. ΔT - supply/return (electronic fence) 35°F
Left Side 1"
Maximum equivalent vent length – 4” CPVC or PVC 150’
Each side (Vent & Air Intake) Right Side 1"
(Natural Gas or Propane) Top 12”
Air intake options: either direct vent or indoor supply
Bottom 12"
* boilers are shipped with 30 psig pressure relief valve
Clearance from boiler cabinet
PRESSURE VESSEL HEAD

Flow rate (gpm) 20 35 30 35 40 45 MaxIMUM


INTAKE Pipe Size
EquivAlEnt Length
Head @ flow (ft wc) 1 1.5 2 3 4 6
4" 150' (each side)

Pressure Vessel Head 90° vent elbow allow 8' equivalent

Model 3/4" IPS 1" IPS 1 1/4” IPS 1 1/2" IPS 90° long sweep vent elbow allow 5’ equivalent

SL 80-399 (Natural Gas) 10 40 150 350 45° elbow allow 3’ equivalent

SL 80-399 (Propane) 30 100 400 900 Air Intake Filter Contact Factory

Maximum intake piping length


Maximum Gas Pipe Length (ft)