Вы находитесь на странице: 1из 5

Normal inverse ("inverse") IEC

Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
0.14 1000 3 1.123201 1 0.123201 1.13635 0.2 0.22727 0.14
T= x Tp
(I/Ip) 0.02
-1

Very inverse ("short in") IEC


Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
13.5 1000 3 333.3333 1 332.3333 0.04062 0.2 0.008124 13.5
T= x Tp
(I/Ip)1 - 1

Extremely inverse ("extr inv") IEC


Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
80 1000 3 111111 1 111110 0.00072 0.2 0.000144 80
T= x Tp
(I/Ip) - 1
2

Long time inverse ("long inv") IEC


Ip (set Tp (set
I (fault pickup time T (tripping
current) value) multiplier) Time)
120 1000 3 333.3333 1 332.3333 0.36108 0.2 0.072217 120
T= x Tp
(I/Ip)1 - 1

RI-curve ("RI")

Ip (set Tp (set
pickup time
value) multiplier)
1 0.339 0.236 0.103 3 1000 0.003 0.000309 3236.246 0.2 647.2491909

RD-curve ("RD")
Inverse ANSI/IEEE
Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
8.9341 1000 3 191603.5 1 191602.5 ### 0.1797 0.1797 0.2 0.035941 8.9341
( )
t= (I/Ip)2.0938 - 1 + 0.17966 x D
Short inverse ("short in") ANSI/IEEE
Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
0.2663 1000 3 1870.344 1 1869.344 ### 0.0339 0.0341 0.2 0.006814 0.2663
( )
t= (I/Ip)1.2969 - 1 + 0.03393 x D
Long inverse ("long inv") ANSI/IEEE
Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
5.6143 1000 3 333.3333 1 332.3333 ### 2.1859 2.2028 0.2 0.440563 5.6143
(
t= (I/Ip) - 1 )
+ 2.18592 x D

Moderately inverse ("mode inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
0.0103 1000 3 1.123201 1 0.123201 ### 0.0228 0.1064 0.2 0.021281 0.0103
(
t= (I/Ip)0.02 - 1 )
+ 0.0228 x D

Very inverse ("very inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
3.922 1000 3 111111.1 1 111110.1 ### 0.0982 0.0982 0.2 0.019647 3.922
(
t= (I/Ip)2 - 1 )
+ 0.0982 x D

Extremely inverse ("extr inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
5.64 1000 3 111111.1 1 111110.1 ### 0.0243 0.0244 0.2 0.004878 5.64
(
t= (I/Ip)2 - 1 )
+ 0.02434 x D

Definite inverse ("def inv") ANSI/IEEE


Ip (set D (set
I (fault pickup time t (tripping
current) value) dialer) Time)
0.4797 1000 3 8749.798 1 8748.798 ### 0.2136 0.2136 0.2 0.042729 0.4797
( )
t= (I/Ip)1.5625 - 1 + 0.21359 x D
Squared inverse ("I-squared-t") ANSI/IEEE
Ip (set
I (fault pickup D (set time t (tripping
current) value) dialer) Time)
1000 3 111111.1 50.7 0.20 10.14 10.14 20.28 0.000183 50.7 x D + 10.14
t=
(I/Ip)2