Академический Документы
Профессиональный Документы
Культура Документы
EST's Engineer Guide to the NYC Building Code Fire Alarm Requirements
1
A – Assembly
B – Business 2
E- Education (K–12)
F - Factory 3
H-5 – Hazardous 4
I – Institutional
5 9
M- Mercantile R-2 Apartments
14
R-1 Hotel
R-2 Student Apts. 6 (not Student Apartments/Dorms)
Atriums 7
Aerosol Storage
Lumber Mills
Underground Buildings
Covered Malls > 50,000 sq. ft.
System Type Temporal 3 Fire Alarm system or Voice Sprinkler and Smoke Detection
Evacuation (see red section below for voice evac) Add One-Way voice if > 125 ft tall.
Pull Stations:
At the main panel No Yes (NFPA 72 6.8.5.1.2)
At all Egress Exits on every floor Yes (907.3.1) No
Mounted within 5 feet from door Yes (907.3.1) N/A
Distance to Next Nearest Station < 200 ft (NFPA72 5.12.8) N/A
Mounting Height 42 to 48 Inches AFF (907.3.2) 42 to 48 Inches AFF (907.3.2)
Must be Painted Red Must be Red (907.3.3) Must be Red (907.3.3)
Pull Stations Can Be Eliminated I-3 Prison – (907.2.6.2) N/A
Instructions (code card) at station No No
White Strip for Central Station No No
Smoke Detectors:
Equip Rooms (Elect, Mech, & Similar) Yes - All (907.2) If over 75 Sq. ft. (907.2.9)
In Elevator Lobbies Yes (appendix K 2.27.3.2.1) Yes (907.2.9)
At Top of Elevator Shaft Yes if Sprinklered or Hatch (NFPA72 6.15.3.6) Yes (appendix K 2.27.3.2 (d), 907.2.9)
In Elevator Mechanical Room Yes (907.2) Yes (907.2.9)
Waiting Areas/spaces open to Corridor I Occupancies (407.2, 407.6, 907.2.6) N/A
10 20
In Corridors R-1, R-2 Dorm , and I-2 ccupancies No
At Top of Stair Shaft for Hatch Yes Yes
Above Smoke Doors with Door Holders Yes Yes
12
Housing, Day Rms, Common Spaces I-3 Occupancies No
Partial Detection if Un-sprinklered B and M Occupancies 17 No
R-2 with Student Apartments10 10
In Student Use Rooms R-2 with Student Apartments
In Sleeping Rooms8 Yes in R-1 Hotels and R-2 Dorm Occupancies No (see smoke alarm section below)
11
In Spaces Open to Corridors I-2 Nursing Homes, Detox No
Entrance to Stairwell for Pressurization If > 75 ft tall and no Smokeproof enclosure 15 If > 75 ft tall and no Smokeproof enclosure 15
Above FACP if its in Unoccupied Area Yes Yes
For Smoke Dampers See MC607.3.2.1 See MC607.3.2.1
Sleeping Room Smoke Alarms:
Each Sleep Room, Egress, & Level Yes in I-1, R2, R3 (907.2.10.1.1). Yes (907.2.10.1.1)
<15 feet from Sleeping Room Door Yes in I-1, R2, R3 (907.2.10.1.1) Yes (907.2.10.1.1)
Must Be Interconnected (activate in tandem) Yes in I-1 R2, R3 (907.2.10.3) Yes (907.2.10.3)
Use Smoke Detector in Sleeping Room Yes in R-1 Hotels and R-2 Dorm Occupancies Optional
Heat Detectors:
In Boiler Rooms Yes Yes
At Top of Elevator shaft Include it if a Sprinklered Shaft Include it if a Sprinklered Shaft
In Elevator Mechanical room No (it’s un-sprinklered – 3006.5) No (it’s un-sprinklered 3006.5)
Stages Yes if Proscenium Curtain (410.3) N/A
Duct Detectors:
> 2,000 cfm On AHU Return Yes (606.2.1) Yes (606.2.1)
> 2,000 cfm On AHU Supply Yes (606.2.4) Yes (606.2.4)
Each Return if > 1 story & > 15,000 cfm Yes (if AHU covers > 1 floor -- see 606.2.3) Yes (if AHU covers > 1 floor -- see 606.2.3)
On Return if Common/Supply Return Yes if > 2,000 cfm (see 606.2.2) Yes if > 2,000 cfm (see 606.2.2))
On Return of R-1 Over 5,000 cfm Yes (see 907.2.12.1) NA
Within 5 ft of the Smoke Damper See MC607 See MC607
Notes:
1 - Assembly (907.2.1): A fire alarm system is required if the occupant load is greater than 300 or is a cabaret with
an occupant load > 75. A-1 with an occupant load > 300 or any other A occupancy with > 1,000 requires one
way voice evacuation (see 907.2.1 for details – exception for “E” education occupancies). FDNY does not want
total evacuation in large (>1000) assembly spaces.– contact EST for a suggested sequence.
2 – Business (907.2.2): A fire alarm system is required if the occupant load is 500 or more or more than 100 people
above or below the lowest level of exit discharge (907.2.2). High Rise B buildings over 75 ft. tall or more than
100,000 sq. ft require voice evacuation and fire fighters telephone (907.2.2.1 and 907.2.12). See note 13.
3 - Factory (907.2.4): A Fire Alarm system is required if >2 stories in height and have an occupant load of more
than 100 or if 25 people or more are above or below the lowest level of exit.
4 – H-5 Hazardous (907.2.5): A manual and automatic fire alarm system is required in H-5 occupancies and in
occupancies used for the manufacture of organic coatings. In addition automatic smoke detection system is
required for highly toxic gases, organic peroxides and oxidizers and shall be connected to a central station.
5 – Mercantile (907.2.7): A fire alarm system is required if the Fire area exceeds 12,000 square feet, Fire area is
located more than three stories above grade, combined fire areas on all floors including mezzanines exceeds 24,000
square feet, or Fire area in a below-grade story exceeds 1,500 square feet. Unsprinklered M occupancies require
partial smoke detection (see note 17 for details).
Note: Please read the appropriate section of the code for details. In some cases exceptions are not all included. Also,
as with any code, many items are subject to interpretation.