Вы находитесь на странице: 1из 1

TECHNICAL BULLETIN no: TB1091

T2550 v2.2 to v4.0


MOD_DO_UIO
2000
T2550
We have recently discovered an issue with T2550 that can cause de-synchronisation of redundant
processors if using the MOD_DO_UIO block in the strategy. This issue is potentially present in all 26/2700
versions of T2550 software from v2.2 to v4.0.
3000
Simplex processor applications are not effected by this issue.
MINI8®
The MOD_DO_UIO is the Digital Output Module Block that allows connection of up to eight logic Controller
signals in the T2550 to eight digital output channels in a single block and provides
Auto/Manual/Track control, and inversion in a single block. Graphic
Recorders
Symptoms
Where redundant processor T2550 databases are using the MOD_DO_UIO block there may be
Paper
difficulties in synchronising or the processors appear to synchronise and then immediately Recorders
desynchronise due to a redundancy check sum error.
Power
Engineering Solution Products
There no issues with the MOD_UIO and the DO_UIO blocks.
It is recommended to replace MOD_DO_UIO with MOD_UIO and individual DO_UIO block as T Series
necessary. Where data base size prevents this option a permanent solution is in development
Eycon™
testing.
Visual
Permanent Solution Supervisor
A permanent solution for this problem has been developed and this version is currently
undergoing independent test. This fix will be released in T2550 version 4.1.
Eurotherm
Suite
T2550 version 4.1 is currently due for release at the End of March
LINtools
Review
If you have any problems concerning the above technical information,
please contact Terry Minns, terry.minns@eurotherm.com

Eurotherm Limited
General Enquiries:
Tel. +44 (0)1903 268500
Email: info@eurotherm.co.uk
www.eurotherm.co.uk

Author: Terry Minns Approved: Dave Cozens

Ref: TB1091.doc - Page 1 of 1 - 26/03/08

Registered Office Portland House, Bressenden Place, London SW1E 5BF Registered in England No 853008