Bus-Main-P1 Bus Bar: 3phase 11kV, 1200A
CB-P1-1 Indoor VCB switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with one isolator switch.
CB-P1-2 Indoor VCB switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with one isolator switch.
CB-P1-3 Indoor VCB switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with one isolator switch.
HVMU1 High Voltage Measuring Unit (11kV): A; V; W; Wh; P.F.; and f with all CTs & VTs
HVMU2 High Voltage Measuring Unit (11kV): A; V; W; Wh; P.F.; and f with all CTs & VTs
R Over Load Relay (11kV) : to be set in the range (45-70)A
Earth Bus Bar Eart Busbar: 600A
Substation-P1
Descriptions Unit Qty.
Off Line Cable Box, 11kV, 630A 1
3-1/C, 11kV,120mm2, Cu m 50
3-1/C, 11kV,70mm2, Cu m 50
3-1/C, 11kV,70mm2, Cu m 50
9-1/C, 0.4kV,400mm2, Cu m 50
9-1/C, 0.4kV,400mm2, Cu m 50
6-1/C, 0.4kV,185mm2, Cu m 5
6-1/C, 0.4kV,185mm2, Cu m 5
6-1/C, 0.4kV,185mm2, Cu m 5
6-1/C, 0.4kV,185mm2, Cu m 30
6-1/C, 0.4kV,185mm2, Cu m 30
6-1/C, 0.4kV,185mm2, Cu m 30
3-1/C, 0.4kV,70mm2,Cu m 5
3-1/C, 0.4kV,70mm2,Cu m 5
3-1/C, 0.4kV,150mm2,Cu m 20
Off Load Bus Coupler Switch 0.4kV, 1500A 1
of 1
Bus Bars: 3phase, 11kV, 1200A Set
Indoor VCB switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with one isolator switch. 1
Indoor VCB switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with one isolator switch. 1
Indoor VCB switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with one isolator switch. 1
High Voltage Measuring Unit (11kV): A; V; W; Wh; P.F.; and f with all CTs & VTs Set
High Voltage Measuring Unit (11kV): A; V; W; Wh; P.F.; and f with all CTs & VTs Set
Over Load Relay (11kV) : to be set in the range (45-70)A 1
Eart Busbar: 600A 1
Power Transformer 11/0.4kV; 1.6MVA withThermal indicator, Buchholz relay and Differential relay with
the necessary current transformers and accessories. 1
Power Transformer 11/0.4kV; 1.6MVA withThermal indicator, Buchholz relay and Differential relay with
the necessary current transformers and accessories. 1
of 4
Bus Bars: 3phase, 0.4Kv, 1200A Set
Indoor Air Circuit Breaker ( 0.4kV,1500A,100 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV,1500A,100 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV, 800A,100 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV, 800A,100 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV, 800A,100 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV, 160A, 70 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV, 160A, 70 kA ) [2]. 1
Indoor Air Circuit Breaker ( 0.4kV, 400A, 70 kA ) [2]. 1
Low Voltage Measuring Unit (0.4kV): A; V; W; Wh; P.F.; and f with all CTs & VTs Set
Soild State Tripe Relay: to be programmed at PLC with all CTs 3
Eart Busbar: 600A
Soft-Starter 1
Soft-Starter 1
Soft-Starter 1
Variable Capacitor Bank to control PF set at 0.92 lag. 1
Variable Capacitor Bank to control PF set at 0.92 lag. 1
Low Voltage Panel for Pump Station P1 Services. 1
Low Voltage Motor, 315kW, 0.4kV, 1500rpm 1
Low Voltage Motor, 315kW, 0.4kV, 1500rpm 1
Low Voltage Motor, 315kW, 0.4kV, 1500rpm 1
Item No. ID
1 OLCB
2 Cable-P1-1
3 Cable-P1-2
4 Cable-P1-3
5 Cable-P1-4
6 Cable-P1-5
7 Cable-P1-6
8 Cable-P1-9
9 Cable-P1-10
10 Cable-P1-12
11 Cable-P1-13
12 Cable-P1-14
13 Cable-P1-7
14 Cable-P1-11
15 Cable-P1-8
16 Bus Coupler-P1-1
17 Main Panel ( 11kV ): consists of
Bus-Main-P1
CB-P1-1
CB-P1-2
CB-P1-3
HVMU1
HVMU2
R
Earth Bus Bar
18 T-P1-1

19 T-P1-2
20 Main Panel ( 0.4kV ): consists of
Bus-Main-P1
CB-P1-4
CB-P1-5
CB-P1-6
CB-P1-9
CB-P1-10
CB-P1-7
CB-P1-11
CB-P1-8
LVMU
SST
Earth Bus Bar
21 P1-1-SS
22 P1-2-SS
23 P1-3-SS
24 CAP-P1-1, CAP-P1-2
25 CAP-P1-2
26 LUMP-P1
27 P1-1
28 P1-2
29 P1-3
30
31