500 mw 210 mw 110 mw


  Actual %age %age Actual %age %age Actual %age %age
load kw gener APC load kw gener APC load kw gener APC
ation ation ation
BFP 0 0 0 5380 2.69 33.63 2793 2.94 24.5
CEP 1903 0.40 5.7 534 0.267 3.34 364 0.38 3.19
CW Pump 4754 0.99 14.1 1329 0.66 8.31 1197 1.26 10.5
ID Fans 6289 1.31 18.7 2523 1.26 15.77 1622 1.71 14.23
P A Fans 2845 0.59 8.5 1360 0.68 8.50 1648 1.73 14.46
F D Fans 1368 0.29 4.1 800 0.4 5.00 243 0.26 2.13
Mills 2776 0.58 8.3 1157 0.579 7.23 789 0.83 6.92
C T Fans 1083 0.23 3.2 630 0.315 3.94 456 0.48 4
Air compressors 385.5 0.08 1.1 249 0.125 1.56 228 0.24 2
A/C Plant 175 0.04 0.5 150 0.075 0.94 105 0.11 0.92
CHP 591 0.12 1.8 272 0.136 1.70 275 0.29 2.41
Ash handling plant 455 0.09 1.4 266 0.133 1.66 290 0.31 2.54
Lighting 266 0.06 0.8 160 0.08 1.00 100 0.11 0.88
Others 10709 2.23 31.9 1190 0.595 7.44 1290 1.36 11.32
Total auxiliaries 33600 7.00 100.0 16000 8 100.00 11400 12 100
consumption -kw
Generation - kw 480000 100   200000 100   95000 100  