Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-1)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
Date
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-2)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
*Operating Time Check(T1):
T1: Delay Time for the first control pulse LIMITS msec = ± 250
∆Us=2%× Un T2=0 Un=100 v Us = 1.00× Un
OPERATING TIME sec EXPECTED TIME sec
APPLIED APPLIED INV .diff.
SET TIME OPERATI (V) AT (V) AT INVERSE INVERSE
DEFINITE DEFINITE limits ms
T1 sec ON B.W 2% B.W 4% B.W 2% B.W 4% B.W 2% B.W 4%
RAISE 97 95 10.03 7.84 8.47 10 7.85 8.61 -10-140
10 SEC
LOWER 103 105 10.08 6.79 8.34 10 6.6 8.4 190 &-60
RAISE 97 95 20.02 15.83 16.78 20 15.69 16.82 140 &-40
20 SEC
LOWER 103 105 20.08 13.44 16.6 20 13.19 16.82 250 &-220
INV.TIME CAL: T1/2^(B-1) B=Ud/∆Us
1.5 s 1.78 s
Date
Design by : Eng'r: Muhammad Eshiba
E-mail: eng_eshiba2010@yahoo.com
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-3)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
HINT:
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-4)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
MEASURED VALUES
SETTING %In EXPECTED CURRENT
PICK UP RESET
1 In 1 AMP 0.991 A 0.98 A
1.5 In 1.5 AMP 1.507 A 1.503 A
2 In 2 AMP 2.017 A 2.011 A
Notes:
#selection over current Blocking
I> SGF2/3=1 I> IN use
SGF2/3=0 I> not use O/P relay
SGF2/2=0 Active
Hint:
Ursv= reduce set voltage value Setting Range (0-9%)Un
Can be used for load shedding or simple line drop compansation purposes .
the RSV can be activating by injecting dc voltage to binary input at X1 (13-14)
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-5)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
RAISE LOWER
SET COMPANSATION REG CAL .∆U
OPERATE EXPECTED OPERATE EXPECTED
Angle between v&I at 0 dgree & CAL ∆Us =(U2-U1)/(U1+U2)*100 & REG=(U1+U2)/2 & Up= Us+UR
RAISE LOWER
SET COMPANSATION
UR REG CAL .∆U
OPERATE EXPECTED OPERATE EXPECTED
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-6)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
Angle between v&I at 90 dgree & CAL ∆Us =(u2-u1)/(u1+u2)*100 & REG=(U1+U2)/2 & Up= Us+Ux
RAISE LOWER
SET COMPANSATION REG CAL .∆U
UX OPERATE EXPECTED OPERATE EXPECTED
Notes:
Ur% = : resistive line -drop compansating factor
0………..25% Un
RAISE LOWER
SET COMPANSATION
REG CAL .∆U
UX OPERATE EXPECTED OPERATE EXPECTED
Date
Design by : Eng'r: Muhammad Eshiba
E-mail: eng_eshiba2010@yahoo.com
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-7)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
USING:
Minimum circulating current principle
Selection of parallel operation principle
When SGF1/2 =0 Minimizing circulating current USED OR Master/Slave
When SGF1/2 =1 Negative Reactance USED
CASE (1)
TRAFO NO. (1) , TRAFO NO. (2) IN PARALLEL OPERATION & TRAFO(3) SINGLE
Digit No. AVR Of TRAFO (1) Mes. AVR Of TRAFO (2) Mes. AVR Of TRAFO (3) Mes.
1 2 5 5 2 5 5 5 5 2
2 0.3 kA 0.3 KA 0.3 kA
3 0.6 A 0.5 A 0.5 A
4 -40 30 30
5 0.3 kA 0.3 KA 0.3 KA
6 0 Amp 0 Amp 0.6 A
7 0 0 -40
HINT
By register( 3) inside of it supmenu are enabled when communication ok
from (1-7) digits
Red digit NO (1): status information
0= no communication 3= waiting for establishment of parallel operation
1= AVR blocked 4= parallel operation by NRP
2= single operation 5= parallel operation by MCC
Red digit No (2): ………..present value of In for TR# 2
Red digit No (3): ………..I1×In of TR# 2
Red digit No (4): ………..phase shift of TR# 2
Red digit No (5): ………..present value of In for TR# 3
Red digit No (6): ………..I1×In of TR# 3
Red digit No (7): ………..phase shift of TR# 3
Date
Design by : Eng'r: Muhammad Eshiba
E-mail: eng_eshiba2010@yahoo.com
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-8)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
2- PARALLEL OPERATION TEST
CASE 1): Trafo 1 phase shift variable
Trafo 2 phase shift Fixed
Trafo (2) angle Trafo (1) angle Trafo (1) angle Trafo (1) angle Action Happen
pick up reset
Ф= 0º
variable (lag) 47.9º 47º Trafo 1 make LOWER
Trafo (1) angle Trafo (2) angle Trafo (2) angle Trafo (2) angle Action Happen
pick up reset
Ф= 0º
variable (lag) 77.9º 77.1º Trafo 1 make RAISE
Ф= 0º
variable (lead) 47.3º 47º Trafo 1 make LOWER
CASE (2)
TRAFO NO. (2) , TRAFO NO. (3) IN PARALLEL OPERATION & TRAFO(1) SINGLE
Digit No. AVR Of TRAFO (1) Mes. AVR Of TRAFO (2) Mes. AVR Of TRAFO (3) Mes.
1 5 5 2 5 2 5 5 2 5
2 0.3 KA 0.3 KA 0.3 KA
3 0.5 A 0 Amp 0 Amp
4 30 0 0
5 0.3 KA 0.3 KA 0.3 KA
6 0.6 A 0.6 A 0.5 A
7 -40 -40 30
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-9)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
2- PARALLEL OPERATION TEST
CASE 1): Trafo 2 phase shift variable
Trafo 3 phase shift Fixed
Trafo (3) angle Trafo (2) angle Trafo (1) angle Trafo (1) angle Action Happen
pick up reset
Ф= 0º
variable (lag) 55.9º 55.8º Trafo 2 make LOWER
Trafo (2) angle Trafo (3) angle Trafo (2) angle Trafo (2) angle Action Happen
pick up reset
Ф= 0º
variable (lag) 47.9º 47.8º Trafo 3 make LOWER
CASE (3)
TRAFO NO. (1) , TRAFO NO. (3) IN PARALLEL OPERATION & TRAFO(2) SINGLE
Digit No. AVR Of TRAFO (1) Mes. AVR Of TRAFO (2) Mes. AVR Of TRAFO (3) Mes.
1 5 2 5 5 5 2 2 5 5
2 0.3 KA 0.3 KA 0.3 KA
3 0 Amp 0.5 A 0.5 A
4 0 30 30
5 0.3 KA 0.3 KA 0.3 KA
6 0.6 A 0.6 A 0
7 -40 -40 0
Date
a SIEMENS Company
Site Test Report for AVR SPAU 341 C3
Project NEW NEWARIAH Substation 110/13.8 kv MAKKAH (1-10)
Consumer SEC-WOA Jop# I=3199
Location WJ01 Equipment Tag N101
Trafo (3) angle Trafo (1) angle Trafo (1) angle Trafo (1) angle Action Happen
pick up reset
Ф= 0º
variable (lag) 46.8º 46.7º Trafo 1 make LOWER
Trafo (1) angle Trafo (3) angle Trafo (2) angle Trafo (2) angle Action Happen
pick up reset
Ф= 0º
variable (lag) 46.6º 46.5º Trafo 3 make Lower
9-FUNCTION TEST
2 External control binary input pulse for MANUAL selection at X1:1 check OK
3 External control binary input pulse for AUTO selection at X1:3 check OK
External control binary input signal at X1: 11 for BLOCKING AUTO/MANUAL votage regulation by
4 OK
using SGF1/3=0
5 External control binary input signal at X1: 11 for REMOT/LOCAL BLOCKING by SGF1/3=1 when OK
input energized (REMOTLY CONTROL) when input not energized (LOCALY CONTROL)
Date