Bus-Bar Protection Schemes

 Bus-Bar Protection Schemes.


• 500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme.
    

   - Differential Protection For each section of bus-bar.


   - SF6 Pressure low Trip.                                 
 
• 66 and 33 KV. Bus-Bar Protection Scheme.
    

   - Differential Protection For each section of bus-bar or Arc protection or


Micro switch protection.
-         SF6 Pressure low Trip.
 
•     22 and 11 KV BUS-Bar Protection Scheme.
   - Arc protection or Micro switches protection.
 
•     500, 400, 275, and 220 KV BB section & BB couplers protection scheme.
       - I.D.M.T Non Directional O/C & E/F Relay.
       - C.B Fail to Trip.
       - SF6 Pressure Trip.
       - Inter Trip (through pilot cable).
 
•     132 KV BB section & BB couplers protection scheme.
       - I.D.M.T Non Directional O/C & E/F Relay.
       - C.B Fail to Trip.
 
•     33 KV BB section & BB couplers protection scheme.
        - I.D.M.T Non Directional O/C & E/F Relay.
 
•     11 KV BB section & BB couplers protection scheme.
        - I.D.M.T Non Directional O/C & E/F Relay.
 
Shunt Reactor Protection Scheme.
275 &132 KV. Shunt Reactor Protection Scheme.
•     I.D.M.T Non Direction O/C & E/F relay.
•     Inter Trip (through pilot cable – SHR connected through cable C.B. “for 132
kV only”).
•     Buchhols Trip.
•     Oil Temperature Trip.
•     Winding Temperature Trip.
•     Cable oil pressure Low Trip. (For cable tails)
•     SF6 pressure Low Trip.
•     C.B Fail to trip. (For 132 KV. C.B only).
 33 KV. Shunt Reactor Protection Scheme for both connected 
to 33 KV Bus-Bar or to tertiary of 300 MVA Transformer.

•      I.D.M.T Non Direction O/C & E/F relay.


•      Buchhols Trip.

•      Oil Temperature Trip.

•      Winding Temperature Trip.